High Sensitivity Smoke Detection
www.kfp.co.uk
Kelvin Miller
![Page 2: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/2.jpg)
2
What is HART High SensitivitySmoke Detection (HSSD)?
• Aspirating detection system
• Fan draws air through sampling pipework system
• Capable of detecting smoke concentration as low as 0.0025% obscuration per metre down to 1%
• Display Control Unit provides indications and controls
![Page 3: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/3.jpg)
3
HART XL Detector Unit
![Page 4: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/4.jpg)
4
Normal Pre-Alarm Alarm Fault
Tri-colour LED StatusIndicator
Hart XL Detector Unit-Option without Display Control Unit
![Page 5: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/5.jpg)
5
Laser Detector UnitMain Control Board
Fan Assembly
HART XL Detector Unit
Clip-in modular assembly, removable cable connectors
![Page 6: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/6.jpg)
6
Stages of Fire
Ob
scu
ratio
n
Time
4
Pre Alarm 2
Pre Alarm 1
100%Alarm 1
Pre Alarm 2
Alarm 2Up to 1%
43
![Page 7: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/7.jpg)
7
Kidde HSSD Performance
• Superior particle counting technology
• High immunity smoke discrimination
• Dust particle discrimination
• High immunity to unwanted alarms
• No filters
• Reliable & stable
• Automatic sensitivity & calibration checking
• Simple maintenance
![Page 8: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/8.jpg)
9
Kidde HSSD Detector Operation
Optical Sensor
Control PCB
Collimating Lens
Solid State Laser
Air Flow Sensor
Receive Optics
DetectorTest LED
![Page 9: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/9.jpg)
10
Kidde HSSD Particle Discrimination
10 micron particle size
Typical smoke particle
Upperthreshold
Lowerthreshold
10 micron particle size
Typical dust particle
Upperthreshold
Lowerthreshold
Photodiodeoutput
![Page 10: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/10.jpg)
11
HSSD Market
• Aspirating HSSD has become widely accepted as a reliable smoke detection method
• HSSD is now standard practice in Electronic Data Processing (EDP) environments, telecommunications suites and computer rooms
• HSSD has become a viable alternative to other forms of detection in areas previously not considered such as warehouses, cold stores, production areas, shopping malls and heritage buildings
• HSSD is often used when other forms of detection prove ineffective or difficult to maintain
![Page 11: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/11.jpg)
12
• Design engineers are identifying more areas where aspirating HSSD will provide the best solution to an assessed risk
• On all new projects & retrofits there is scope to include HSSD & provide the end user with an improved detection solution
• HSSD can often be installed at comparable or at lower cost than other forms of detection
HSSD Market
![Page 12: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/12.jpg)
13
Why Hart Aspirating Smoke Detection?
• Earliest detection to enable business continuity
• Extra time is required for safe evacuation
• Unnecessary suppression release must be avoided
• Smoke is difficult to detect
• Environmentally challenging areas
• Aesthetics & concealed detection are important
• Maintenance access is limited
![Page 13: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/13.jpg)
14
Earliest Detection to Enable Business Continuity
Critical processes that cannot incur any business
disruption
• Telecommunications facilities
• Computer rooms
• Banking operations
• Production facilities
• Internet Service Providers
![Page 14: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/14.jpg)
15
Extra Time is Required for Controlled Evacuation
Environments where rapid exit can be impeded
• Underground Stations
• Theatres
• Public buildings
• Airports
![Page 15: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/15.jpg)
16
Smoke is Difficult to Detect
Environments with high ceilings, high air flows or
vast open areas provide unique characteristics
• Clean rooms
• Warehouses
• Aircraft hangars
• Computer rooms
• Atria
![Page 16: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/16.jpg)
17
Unnecessary Suppression Release can be Avoided
Early warning gives time to investigate to avoid
unnecessary suppression release
• Telecommunication facilities
• EDP facilities
• Computer rooms
• Electrical sub-stations
![Page 17: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/17.jpg)
18
Environmentally Challenging Areas
Aggressive environments with high levels of
pollution or extreme temperature conditions can be
protected reliably with acceptable maintenance levels
• Cold Stores
• Production areas
• Paper mills
• Underground tunnels
• Mines
![Page 18: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/18.jpg)
19
Aesthetics are Important & Replacement Impossible
Interiors that must not be spoilt by unsightly conventional
detectors - Hart XL can be installed unobtrusively
• Cathedrals
• Stately Homes
• Museums
• Art Galleries
![Page 19: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/19.jpg)
20
Maintenance Access is Limited
Hart XL can be located at an accessible location while
the sampling pipework makes its way to the restricted area
• Warehouses
• Production machinery
• Prisons
• Restricted areas
• EMC Controlled areas
• Hospitals
![Page 20: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/20.jpg)
21
Direct connection to PC for Programming and Downloading using LaserNet Software. No programmers or interfaces are required
Programming and Diagnostics
![Page 21: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/21.jpg)
22
Programming Options
• Fixed or automatically set sensitivity
• Hart XL 0.05%/m to 1%/m obscuration
• Programmable relays
• Referencing
• Latching or non latching alarms
• Two or Four levels of Alarm
Diagnostics & Monitoring
• Download history & event log
• Full fault analysis
• Dial in & dial out via modem monitoring
• Intelligent interface module common alarm & fault relay outputs
![Page 22: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/22.jpg)
23
History Log accessed through Lasernet
![Page 23: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/23.jpg)
24
Kidde HSSD Networking Capability
With the addition of the HART Intelligent Interface Module (IIM), up to 127 standard Hart XL can be networked and displayed on a PC monitor
I. I. M.
![Page 24: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/24.jpg)
25
Servicing and Maintenance
Benefits
• Easy & quick to service & maintain
• Lower costs
• Shorter downtimes
• Reduced spares holdings
![Page 25: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/25.jpg)
26
New Updated SNIFF System Design Software
Windows compatible Easy operation and clear displays Isometric drawings from several angles
![Page 26: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/26.jpg)
27
SnifferPipe - a comprehensive range of red ABS smoke sampling pipe
Efficient & robustSmooth bore facilitates air flow to detectorLightweight and easy to installHigh resistance to chemicals & weatheringWide temperature range,-40 to +80ºC
![Page 27: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/27.jpg)
28
Conventional Detector Layout (Secondary Detection) BS6266
2.5m 5m 5m 5m 5m 2.5m
2.5m
FIRE ZONE PLAN
5m
5m
2.5m
![Page 28: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/28.jpg)
29
HSSD Layout (Secondary Detection) BS6266
Sampling pipes
FIRE ZONE PLAN
Sample Holes
2.5m
5m
5m
2.5m
2.5m 5m 5m 5m 5m 2.5m
![Page 29: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/29.jpg)
30
Distributed sampling network
![Page 30: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/30.jpg)
31
Primary Detection
Where smoke will travel when air
conditioning is operating
• Air handling units
• Duct detection
![Page 31: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/31.jpg)
32
Primary Detection
![Page 32: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/32.jpg)
33
In Cabinet sampling
![Page 33: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/33.jpg)
34
BS6266 Wire Burn Test
Wire Burn test Rig
10/0.1mm pvc wire
Burn wire for 1 minuteswith a further two minutes allowed for the detector to respond
One Metre Test
![Page 34: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/34.jpg)
35
Approvals
• LPCB - UK
• Vds - Germany
• UL and FM - USA
• Afnor - France
• Shangyen - China
![Page 35: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/35.jpg)
Beam Smoke Detection
![Page 36: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/36.jpg)
37
Guardall BM5
• 100m Linear Smoke Detector
• Optional LCD Display
• Multi-Language Support
• Event Memory
• Heat Channel
• Four Output Relays
![Page 37: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/37.jpg)
38
Beam Smoke Detection
20m
10 m
3 to 5% Ob/m
25m
1% Ob/m
![Page 38: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/38.jpg)
39
BM5 Features
• Real-time Clock
• Programmable Outputs
• Programmable Thresholds– Smoke– Heat– Smoke Pre-alarm– Heat Pre-Alarm
![Page 39: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/39.jpg)
40
BM5 Operation
• 10.5 V to 33 V Operation
• Two Line LCD Keypad
• Engineer & User PINs
• Electronic Alignment
• Fix Beam Level from Keypad
• Laser Alignment
![Page 40: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/40.jpg)
41
Approvals
• LPC Approval to BS5839
• prEN 54 Part 12 Approval in France & Germany
• Designed to UL Requirements
• 150m Non-approved Unit
![Page 41: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/41.jpg)
Linear Heat Detection
![Page 42: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/42.jpg)
43
What is Linear Heat Detection?
• Continuous heat detector in the form of a cable
- Alarmline Analogue: averaging heat detector
- Alarmline Digital: fixed temperature heat detector
![Page 43: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/43.jpg)
44
Analogue LHD Cable
• Definition:
- Multi-conductor cable containing insulators whose resistance varies proportionately to changes in temperature
- Re-settable, provided temperature does not exceed burn-off point of PVC coating
- Alarm level adjusted via controller
![Page 44: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/44.jpg)
45
Alarmline Analogue LHD Cables
• High resistance - standard applications
• Nylon extruded - chemical resistance
• Bronze braided - increased mechanical
protection over standard blue
• Stainless Steel braided over nylonextrusion - offshore applications
![Page 45: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/45.jpg)
46
LHD 4 Controller
![Page 46: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/46.jpg)
47
LHD 4 Controller
• Features
- Alarm level adjusted via moveable link
- Open circuit and closed circuit fault monitoring
- Fire and fault output to conventional fire alarm panels
- Volt-free relay option for analogue addressable fire alarm panels
- Eurocard 19” rack option
![Page 47: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/47.jpg)
48
Digital LHD Cable
• Definition:
- A cable which contains an insulator which melts at a specific temperature
- Switch output provided when the alarm temperature is reached
- Not re-settable
![Page 48: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/48.jpg)
49
Alarmline Digital LHD Cables• Polythene braid 70º C
• Nylon over sheath 70º C
• Polythene braid 90º C
• Nylon over sheath 90º C
• PVC 113º C
• PVC 180º C
• Fluoropolymer 238º C
![Page 49: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/49.jpg)
50
Alarmline LHD - Benefits
• Flexible- Mechanically- Electrically
• Durable- Wide range of casings / braiding- Operating range -65º to +200º C- Unaffected by operating environment
![Page 50: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/50.jpg)
51
Sensor Clips
Edge clip
Sensor cable
Neoprene sleeveCable tie
‘V’ Clip
Sensorcable
Neoprenesleeve
![Page 51: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/51.jpg)
52
Applications
• Heavy industry
• Warehousing
• Storage tanks
• Conveyors and escalators
• Cable trays
• Floor & ceiling voids
• Tunnels
• Car parks
![Page 52: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/52.jpg)
53
Racking
Sensor Cable
![Page 53: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/53.jpg)
54
Trays
Traywork width 600mm maximum
Sensor cable
Powercables
Sensorsupports
![Page 54: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/54.jpg)
55
Conveyor
Heat sensingcable Idle rollers
Conveyor Belt
Conveyor return
![Page 55: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/55.jpg)
56
Escalators
Sensor Pad
LHD Bronze Braided sensor cable
![Page 56: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/56.jpg)
57
International Approvals
Alarmline (Analogue) Alarmline (Digital)
UK power generation- 5117 P 11- EPA 022/215
Factory Mutual- OB 9A2.AY- OR 5A4.AY
Chinese Fire Officers- MAAL 96652
Chinese Power Generation- NSTCFEPQ (Appr) 92005
German VdS (1995)
UK power Generation- EPA 019-021- EPA 206/220
Factory Mutual- OD 6A9.AY- 300 5155- 300 3834
Chinese Fire Officers- MAAL 96652- 300 8312- 300 8933
![Page 57: High Sensitivity Smoke Detection Kelvin Miller](https://reader034.vdocuments.mx/reader034/viewer/2022051401/56649f145503460f94c294ad/html5/thumbnails/57.jpg)