HIGH AIR FLOW LINEAR SLOT DIFFUSERS KLN
SERIESOVERVIEW
CHARACTERISTICSAPPLICATIONS
installation in continuos lines
OVERVIEW :The KLN series linear diffusers allow to manage high air flows with minimum pressure losses and generated noise power.They allow to fully make us of the induction principle, guaranteeing optimum comfort conditions, no noticeable air currents and temperature uniformity, even in large areas by positioning the diffusers along the perimeter of the ceiling.
The big innovation on the KLN series is the double flow deflector system: for horizontal throw 2 settings are available and fully adjustable on constrcution site.The first setting allow supply air horizontally with a big ceiling effect, while the second setting still allow horizontal air supply but for biggest air flow and low pressure loss and noise level.
CHARACTERISTICS AND OPERATION :The KLN series diffusers are constructed from an aluminium diffuser body lots and a series of deflectors, also in aluminium, for the horizontal or vertical air though. The change of direction of the air through can be easily made without removing the diffuser.
APPLICATIONS : The KLN series diffusers are ideal in application with a ceiling height between 3 and 6 meters like open space offices, commercial galleries hospital wards or hotel rooms.
VERSIONS : Standard, with or without filter holderFineline, with or without filter holderFitted, without filter holderWith panel, with or without filter holder
DIFFUSER INSTALLATION: The KLN series diffusers are installed inside special plenum boxes, by suspension using quick fix connectors. This solution allows a quick installation even at the end of work carried out on the building site. Possibilty of installation in continuos lines.
FINISH : The KLN diffusers are constructed from an aluminium body anodized or painted white RAL 9010.The deflectors cam be anodized, painted white RAL 9010 orblack painted. The KLN diffusers with panel are constructed from an aluminium body and a carbon steel panel .Special finishes for the diffuser body can be made on request.
UNSUITABLE ENVIRONMENTSThe aluminum products are not suitable for installation in environments with an atmosphere containing corrosive substances for this material and in particular containing chlorine, such as swimming pools, spas and some types of food industries.
KLN_ENG_19_00.xlsx KLN_ENG_1
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
OVERALL DIMENSIONS
Ak Efficient section for diffuser L=1 m (m²)
1 slot 2 slots 3 slots 4 slots 5 slots 6 slotsHorizontal throw high Coand� effect 0,00944 0,01888 0,02832 0,03776 0,04720 0,05664
0,09264Vertical throw 0,01500 0,03000 0,04500 0,06000 0,07500 0,09000
Horizontal throw high air flow 0,01544 0,03088 0,04632 0,06176 0,0772
KLN_ENG_19_00.xlsx KLN_ENG_2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
VERSIONS
STANDARD VERSIONPlenum P94A - plenum fixing with quick fix
FINELINE VERSIONPlenum P94B - plenum fixing with rivets
FITTED VERSIONPlenum P94B - plenum fixing with rivets
VERSION WITH PANELPlenum P94B - plenum fixing with rivets
Dimensions of the panel on request
KLN_ENG_19_00.xlsx KLN_ENG_3
Horizontal throw configuration Vertical throw configuration
for high Coandă effect The air throw penetrates directly into the roomThe throw moves along the ceiling Prevents the formation of layers of hot air whenIt guarantees the complete absence of air currents used for heating.both in heating and cooling.
Horizontal throw configuration
for high air flow
The throw moves along the ceilingIt guarantees the possibility of supply high air flow with minimal levels of pressure drop and spund power
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
AIR THROW ADJUSTMENT
CHOICE OF AIR THROW ORIENTATION :The horizontal throw represents the most common use of this type of diffuser, both for heating and cooling. The throw follows the ceiling and expands horizontally within the room. This generates a vertical recall of air present in the room, guaranteeing a perfect mixture of air without the presence of air currents within the occupied area.The vertical throw, used when heating, allows to send the hot air directly within the occupied area to hinder the formation of layers of hot air in higher parts of the room caused by the lesser density.The change of orientation of the air throw is obtained by rotating the deflector blade from an inclined position to a horizontal one, and vice versa. The blade is rotated from within the diffuser, with the use of a leaver at both extremities of the air slot.
KLN_ENG_19_00.xlsx KLN_ENG_4
L
A
B Version for installation with rivets (filter holder, fineline, fitted and with panel versions)
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
STANDARD KLN PLENUM BOXES
Nominal length of the diffuserVersion for installation with quick fix connectors (standard version without filter holder )
L ≤ 1200 mm 1201≤ L ≤ 2000 mm Holes in the counterceiling
KLN standard versionSlotsH S C connector ØD connector ØD
(mm) (mm) (mm) qty (mm) qty (mm)2 124 L+15 x 61
2 250 95 115 1 158 21 250 54 100 1 124
158 L+15 x 1043 320 138 135 1 198 2 198 L+15 x 1474 320 181 135 1 198 2 198 L+15 x 190
248 25 370 224 160 1 2486 370 267 160 1 248 L+15 x 276
2 248 L+15 x 233
KLN_ENG_19_00.xlsx KLN_ENG_5
All done
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESINSTALLATION
WITH QUICK FIX CONNECTORSSTANDARD DIFFUSER
Insert the diffuser into the plenum The diffuser will remain suspended
Open the deflectors Insert a screwdriver
Tight the screws of the quick fix connectors
KLN_ENG_19_00.xlsx KLN_ENG_6
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESREMOVE THE DIFFUSER
FIXED WITH QUICK FIX CONNECTORSSTANDARD DIFFUSER
Open the blades Insert a screwdriver
Estract the diffuser
Loose the screws Off-hook using the screwdriver
KLN_ENG_19_00.xlsx KLN_ENG_7
and tight the screws
All done
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESINSTALLATION
IN PALSTERBOARD COUNTERCEILINGSTANDARD DIFFUSER WITHOUT PLENUM
Fix the plastic elements Insert the screws
Fix the metallic bridge Insert the diffuser into the counterceiling
KLN_ENG_19_00.xlsx KLN_ENG_8
aligning them with each pipe placed on the diffuser frame
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESINSTALLATIONWITH RIVETS
FINELINE VERSION
Fix both sides with rivets Ø4,8x10
aligning them with each pipe placed on the diffuser frame
FITTED VERSION
Fix both sides with rivets Ø4,8x10
aligning them with each pipe placed on the diffuser frame
VERSION WITH PANEL
Fix both sides with rivets Ø4,8x10
KLN_ENG_19_00.xlsx KLN_ENG_9
All done
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESINSTALLATION
FILTER HOLDER VERSION WITHOUT PANEL
Open the diffuser Insert the diffuser into the plenum
Fix the diffuser to the plenum using self-drilling screws
Close the diffuser
KLN_ENG_19_00.xlsx KLN_ENG_10
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
CHANGING THE FILTER
Open the diffuser Pull the old filter in oder to extract it
insert the new filter and fix it to the magnets
Close the diffuser All done
KLN_ENG_19_00.xlsx KLN_ENG_11
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
CAUTIONS FOR VERSIONS WITH PANEL
Never apply forces of any kind on panel, this may imply panel deformation. The weight of the panel itself, of the diffuser, of the plenum box and of the air duct has to be supported by plenum box hangers and not by the panel.Always handle with care. never lift or handle the product using the panel. To lift or handle the product please hold the plenum box body.The manufacturer does not assume any responsibility in the event of uncorrect use.
KLN_ENG_19_00.xlsx KLN_ENG_12
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESONE SLOT
Vo LIMIT OF THE OCCUPIED ZONE
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
A (m) distance between diffusersVo (m/s) speed at limit of occupied area
For Hr different to 3m, use the multiplier factor KF:Vo (h) = Vo x Kf
0
0,05
0,1
0,15
0,2
0,25
0,3
0,35
0,4
0,45
0,5
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…1 Vo for Hr=3m adjusted for high Coandă effect
30m³/h
80m³/h
130m³/h
190m³/h
0
0,1
0,2
0,3
0,4
0,5
0,6
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…1 Vo for Hr=3m adjusted for high air flow
60m³/h
130m³/h
210m³/h
290m³/h
0,5
0,6
0,7
0,8
0,9
1
1,1
1,2
2,5 3 3,5 4 4,5 5 5,5
Co
rrec
tion
fact
or K
f
Hr Height of the room (m)
KLN…1 Correction factor for Hr different to 3m
KLN_ENG_19_00.xlsx KLN_ENG_13
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESONE SLOT
HORIZONTAL THROW
Correction factor for non isotermal conditions
∆T x Kf
0,92-6 0,94-4 0,96
10 1,10
0,98
Hea
tin
g
2 1,024 1,046 1,068 1,08
Co
oli
ng
-10 0,90-8
0
1
2
3
4
5
6
0 50 100 150 200 250 300 350
T (m
)
Q (m³/h)
KLN…1 Horizontal throw Vt=0,2m/s
high air f low
high Coandă ef fect
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
L (m) horizontal distance in meters from the centre of diffuserVL (m/s) maximum speed in air stream at distance LT0,2 (m) throw for an isothermal air jet with a Coand�effect for a terminal speed of Vt=0,20m/s.
0,00
0,20
0,40
0,60
0,80
1,00
1,20
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…1 Horizontal throw adjusted for high Coandă effect
30m³/h
80m³/h
130m³/h
190m³/h
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…1 Horizontal throw adjusted for high air flow
60m³/h
130m³/h
210m³/h
290m³/h
KLN_ENG_19_00.xlsx KLN_ENG_14
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESONE SLOT
VERTICAL THROW
Correction factor for non isotermal conditions
∆T x Kf
1,09-6 1,06-4 1,04
10 0,91
1,02
Hea
tin
g
2 0,984 0,966 0,948 0,93
Co
oli
ng
-10 1,11-8
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
0 50 100 150 200
T (m
)
Q (m³/h)
KLN…1 Vertical throw Vt=0,2m/s
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
H (m) vertical distance in meters from ceilingVh (m/s) maximum speed in air stream at distance HT0,2 (m) throw for an isothermal air jet for a terminal speed of Vt=0,20m/s.
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0,35
0,5 1 1,5 2 2,5 3 3,5 4 4,5
Vh
(m/s
)
H (m)
KLN…1 Vertical throw
30m³/h
80m³/h
130m³/h
190m³/h
KLN_ENG_19_00.xlsx KLN_ENG_15
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESONE SLOT
PRESSURE DROP
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
0
5
10
15
20
25
30
35
40
45
50
0 50 100 150 200 250 300 350
Δp
(Pa)
Q (m³/h)
KLN…1 Pressure drop supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
0
5
10
15
20
25
30
35
40
45
50
55
60
65
0 50 100 150 200
Δp
(Pa)
Q (m³/h)
KLN…1 Pressure drop supply
Vertical throw
0
5
10
15
20
25
30
35
40
0 50 100 150 200 250 300 350
Δp
(Pa)
Q (m³/h)
KLN…1 Pressure drop extraction without filter
high air f low
without def lectors
KLN_ENG_19_00.xlsx KLN_ENG_16
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESONE SLOT
SOUND POWER
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
0
5
10
15
20
25
30
35
40
45
50
0 50 100 150 200 250 300 350
Lw
(dB
a)
Q (m³/h)
KLN…1 Sound power supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
0
5
10
15
20
25
30
35
40
45
50
0 50 100 150 200
Lw
(dB
a)
Q (m³/h)
KLN…1 Sound power supply
Vertical throw
0
5
10
15
20
25
30
35
40
45
0 50 100 150 200 250 300 350
Lw
(dB
a)
Q (m³/h)
KLN…1 Sound power extraction without filter
high air f low
without def lectors
KLN_ENG_19_00.xlsx KLN_ENG_17
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTWO SLOTS
Vo LIMIT OF THE OCCUPIED ZONE
0,5
0,6
0,7
0,8
0,9
1
1,1
1,2
2,5 3 3,5 4 4,5 5 5,5
Co
rrec
tion
fact
or K
f
Hr Height of the room (m)
KLN…2 Correction factor for Hr different to 3m
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…2 Vo for Hr=3m adjusted for high air flow
110m³/h
250m³/h
380m³/h
520m³/h
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…2 Vo for Hr=3m adjusted for high Coandă effect
50m³/h
160m³/h
250m³/h
340m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
A (m) distance between diffusersVo (m/s) speed at limit of occupied area
For Hr different to 3m, use the multiplier factor KF:Vo (h) = Vo x Kf
KLN_ENG_19_00.xlsx KLN_ENG_18
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTWO SLOTS
HORIZONTAL THROW
Correction factor for non isotermal conditions
∆T x Kf
0,92-6 0,94-4 0,96
10 1,10
0,98
Hea
tin
g
2 1,024 1,046 1,068 1,08
Co
oli
ng
-10 0,90-8
0
1
2
3
4
5
6
7
8
0 100 200 300 400 500 600
T (m
)
Q (m³/h)
KLN…2 Horizontal throw Vt=0,2m/s
high air f low
high Coandă ef fect
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…2 Horizontal throw adjusted for high Coandă effect
50m³/h
160m³/h
250m³/h
340m³/h
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
2,00
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…2 Horizontal throw adjusted for high air flow
110m³/h
250m³/h
380m³/h
520m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
L (m) horizontal distance in meters from the centre of diffuserVL (m/s) maximum speed in air stream at distance LT0,2 (m) throw for an isothermal air jet with a Coand�effect for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_19
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTWO SLOTS
VERTICAL THROW
Correction factor for non isotermal conditions
∆T x Kf
1,09-6 1,06-4 1,04
10 0,91
1,02
Hea
tin
g
2 0,984 0,966 0,948 0,93
Co
oli
ng
-10 1,11-8
0
0,5
1
1,5
2
2,5
0 50 100 150 200 250 300 350 400
T (m
)
Q (m³/h)
KLN…2 Vertical throw Vt=0,2m/s
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0,35
0,40
0,45
0,5 1 1,5 2 2,5 3 3,5 4 4,5
Vh
(m/s
)
H (m)
KLN…2 Vertical throw
50m³/h
160m³/h
250m³/h
340m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
H (m) vertical distance in meters from ceilingVh (m/s) maximum speed in air stream at distance HT0,2 (m) throw for an isothermal air jet for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_20
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTWO SLOTS
PRESSURE DROP
0
5
10
15
20
25
30
35
0 100 200 300 400 500 600
Δp
(Pa)
Q (m³/h)
KLN…2 Pressure drop extraction without filter
high air f low
without def lectors
0
5
10
15
20
25
30
35
40
45
0 50 100 150 200 250 300 350 400
Δp
(Pa)
Q (m³/h)
KLN…2 Pressure drop supply
Vertical throw
0
5
10
15
20
25
30
35
40
0 100 200 300 400 500 600
Δp
(Pa)
Q (m³/h)
KLN…2 Pressure drop supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
KLN_ENG_19_00.xlsx KLN_ENG_21
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTWO SLOTS
SOUND POWER
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
0
5
10
15
20
25
30
35
40
45
50
0 100 200 300 400 500 600
Lw
(dB
a)
Q (m³/h)
KLN…2 Sound power supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
0
5
10
15
20
25
30
35
40
45
0 100 200 300 400 500 600
Lw
(dB
a)
Q (m³/h)
KLN…2 Sound power extraction without filter
high air f low
without def lectors
0
5
10
15
20
25
30
35
40
45
50
0 50 100 150 200 250 300 350 400
Lw
(dB
a)
Q (m³/h)
KLN…2 Sound power supply
Vertical throw
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
KLN_ENG_19_00.xlsx KLN_ENG_22
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTHREE SLOTS
Vo LIMIT OF THE OCCUPIED ZONE
0,5
0,6
0,7
0,8
0,9
1
1,1
1,2
2,5 3 3,5 4 4,5 5 5,5
Co
rrec
tion
fact
or K
f
Hr Height of the room (m)
KLN…3 Correction factor for Hr different to 3m
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…3 Vo for Hr=3m adjusted for high air flow
170m³/h
350m³/h
540m³/h
720m³/h
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…3 Vo for Hr=3m adjusted for high Coandă effect
80m³/h
230m³/h
360m³/h
480m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
A (m) distance between diffusersVo (m/s) speed at limit of occupied area
For Hr different to 3m, use the multiplier factor KF:Vo (h) = Vo x Kf
KLN_ENG_19_00.xlsx KLN_ENG_23
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTHREE SLOTS
HORIZONTAL THROW
Correction factor for non isotermal conditions
∆T x Kf
0,92-6 0,94-4 0,96
10 1,10
0,98
Hea
tin
g
2 1,024 1,046 1,068 1,08
Co
oli
ng
-10 0,90-8
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
2,00
2,20
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…3 Horizontal throw adjusted for high air flow
170m³/h
350m³/h
540m³/h
720m³/h
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…3 Horizontal throw adjusted for high Coandă effect
80m³/h
230m³/h
360m³/h
480m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
L (m) horizontal distance in meters from the centre of diffuserVL (m/s) maximum speed in air stream at distance LT0,2 (m) throw for an isothermal air jet with a Coand�effect for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_24
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTHREE SLOTS
VERTICAL THROW
Correction factor for non isotermal conditions
∆T x Kf
1,09-6 1,06-4 1,04
10 0,91
1,02
Hea
tin
g
2 0,984 0,966 0,948 0,93
Co
oli
ng
-10 1,11-8
0
0,5
1
1,5
2
2,5
0 100 200 300 400 500 600
T (m
)
Q (m³/h)
KLN…3 Vertical throw Vt=0,2m/s
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0,35
0,40
0,45
0,50
0,5 1 1,5 2 2,5 3 3,5 4 4,5
Vh
(m/s
)
H (m)
KLN…3 Vertical throw
80m³/h
230m³/h
360m³/h
480m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
H (m) vertical distance in meters from ceilingVh (m/s) maximum speed in air stream at distance HT0,2 (m) throw for an isothermal air jet for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_25
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTHREE SLOTS
PRESSURE DROP - SUPPLY
0
5
10
15
20
25
30
35
40
0 100 200 300 400 500 600
Δp
(Pa)
Q (m³/h)
KLN…3 Pressure drop supply
Vertical throw
0
5
10
15
20
25
30
35
40
0 100 200 300 400 500 600 700 800
Δp
(Pa)
Q (m³/h)
KLN…3 Pressure drop supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
KLN_ENG_19_00.xlsx KLN_ENG_26
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTHREE SLOTS
PRESSURE DROP - EXTRACTION
0
5
10
15
20
25
30
0 100 200 300 400 500 600
Δp
(Pa)
Q (m³/h)
KLN…3 Pressure drop extraction with clean filter
high air f low
without def lectors
0
5
10
15
20
25
30
0 100 200 300 400 500 600 700 800
Δp
(Pa)
Q (m³/h)
KLN…3 Pressure drop extraction without filter
high air f low
without def lectors
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
KLN_ENG_19_00.xlsx KLN_ENG_27
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTHREE SLOTS
SOUND POWER - SUPPLY
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
0
5
10
15
20
25
30
35
40
45
50
0 100 200 300 400 500 600
Lw
(dB
a)
Q (m³/h)
KLN…3 Sound power supply
Vertical throw
0
5
10
15
20
25
30
35
40
45
50
0 100 200 300 400 500 600 700 800
Lw
(dB
a)
Q (m³/h)
KLN…3 Sound power supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
KLN_ENG_19_00.xlsx KLN_ENG_28
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESTHREE SLOTS
SOUND POWER - EXTRACTION
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
0
5
10
15
20
25
30
35
40
45
0 100 200 300 400 500 600 700 800
Lw
(dB
a)
Q (m³/h)
KLN…3 Sound power extraction without filter
high air f low
without def lectors
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
0
5
10
15
20
25
30
35
40
45
50
0 100 200 300 400 500 600 700 800
Lw
(dB
a)
Q (m³/h)
KLN…3 Sound power extraction with clean filter
high air f low
without def lectors
KLN_ENG_19_00.xlsx KLN_ENG_29
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFOUR SLOTS
Vo LIMIT OF THE OCCUPIED ZONE
0,5
0,6
0,7
0,8
0,9
1
1,1
1,2
2,5 3 3,5 4 4,5 5 5,5
Co
rrec
tion
fact
or K
f
Hr Height of the room (m)
KLN…4 Correction factor for Hr different to 3m
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…4 Vo for Hr=3m adjusted for high air flow
220m³/h
450m³/h
690m³/h
920m³/h
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…4 Vo for Hr=3m adjusted for high Coandă effect
110m³/h
300m³/h
460m³/h
610m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
A (m) distance between diffusersVo (m/s) speed at limit of occupied area
For Hr different to 3m, use the multiplier factor KF:Vo (h) = Vo x Kf
KLN_ENG_19_00.xlsx KLN_ENG_30
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFOUR SLOTS
HORIZONTAL THROW
Correction factor for non isotermal conditions
∆T x Kf
0,92-6 0,94-4 0,96
10 1,10
0,98
Hea
tin
g
2 1,024 1,046 1,068 1,08
Co
oli
ng
-10 0,90-8
0
1
2
3
4
5
6
7
8
9
10
0 200 400 600 800 1000
T (m
)
Q (m³/h)
KLN…4 Horizontal throw Vt=0,2m/s
high air f low
high Coandă ef fect
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
2,00
2,20
2,40
2,60
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…4 Horizontal throw adjusted for high air flow
220m³/h
450m³/h
690m³/h
920m³/h
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
2,00
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…4 Horizontal throw adjusted for high Coandă effect
110m³/h
300m³/h
460m³/h
610m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
L (m) horizontal distance in meters from the centre of diffuserVL (m/s) maximum speed in air stream at distance LT0,2 (m) throw for an isothermal air jet with a Coand�effect for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_31
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFOUR SLOTS
VERTICAL THROW
Correction factor for non isotermal conditions
∆T x Kf
1,09-6 1,06-4 1,04
10 0,91
1,02
Hea
tin
g
2 0,984 0,966 0,948 0,93
Co
oli
ng
-10 1,11-8
0
0,5
1
1,5
2
2,5
3
0 100 200 300 400 500 600 700
T (m
)
Q (m³/h)
KLN…4 Vertical throw Vt=0,2m/s
0,00
0,10
0,20
0,30
0,40
0,50
0,60
0,5 1 1,5 2 2,5 3 3,5 4 4,5
Vh
(m/s
)
H (m)
KLN…4 Vertical throw
110m³/h
300m³/h
460m³/h
610m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
H (m) vertical distance in meters from ceilingVh (m/s) maximum speed in air stream at distance HT0,2 (m) throw for an isothermal air jet for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_32
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFOUR SLOTS
PRESSURE DROP - SUPPLY
0
5
10
15
20
25
30
35
0 100 200 300 400 500 600 700
Δp
(Pa)
Q (m³/h)
KLN…4 Pressure drop supply
Vertical throw
0
5
10
15
20
25
30
35
0 200 400 600 800 1000
Δp
(Pa)
Q (m³/h)
KLN…4 Pressure drop supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
KLN_ENG_19_00.xlsx KLN_ENG_33
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFOUR SLOTS
PRESSURE DROP - EXTRACTION
0
5
10
15
20
25
0 100 200 300 400 500 600 700
Δp
(Pa)
Q (m³/h)
KLN…4 Pressure drop extraction with clean filter
high air f low
without def lectors
0
5
10
15
20
25
0 200 400 600 800 1000
Δp
(Pa)
Q (m³/h)
KLN…4 Pressure drop extraction without filter
high air f low
without def lectors
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
KLN_ENG_19_00.xlsx KLN_ENG_34
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFOUR SLOTS
SOUND POWER - SUPPLY
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
0
5
10
15
20
25
30
35
40
45
50
0 100 200 300 400 500 600 700
Lw
(dB
a)
Q (m³/h)
KLN…4 Sound power supply
Vertical throw
0
5
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000
Lw
(dB
a)
Q (m³/h)
KLN…4 Sound power supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
KLN_ENG_19_00.xlsx KLN_ENG_35
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFOUR SLOTS
SOUND POWER - EXTRACTION
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
0
5
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000
Lw
(dB
a)
Q (m³/h)
KLN…4 Sound power extraction with clean filter
high air f low
without def lectors
0
5
10
15
20
25
30
35
40
45
0 200 400 600 800 1000
Lw
(dB
a)
Q (m³/h)
KLN…4 Sound power extraction without filter
high air f low
without def lectors
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
KLN_ENG_19_00.xlsx KLN_ENG_36
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFIVE SLOTS
Vo LIMIT OF THE OCCUPIED ZONE
0,5
0,6
0,7
0,8
0,9
1
1,1
1,2
2,5 3 3,5 4 4,5 5 5,5
Co
rrec
tion
fact
or K
f
Hr Height of the room (m)
KLN…5 Correction factor for Hr different to 3m
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
A (m) distance between diffusersVo (m/s) speed at limit of occupied area
For Hr different to 3m, use the multiplier factor KF:Vo (h) = Vo x Kf
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…5 Vo for Hr=3m adjusted for high Coandă effect
140m³/h
360m³/h
550m³/h
730m³/h
0
0,2
0,4
0,6
0,8
1
1,2
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…5 Vo for Hr=3m adjusted for high air flow
280m³/h
560m³/h
830m³/h
1110m³/h
KLN_ENG_19_00.xlsx KLN_ENG_37
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFIVE SLOTS
HORIZONTAL THROW
Correction factor for non isotermal conditions
∆T x Kf
0,92-6 0,94-4 0,96
10 1,10
0,98
Hea
tin
g
2 1,024 1,046 1,068 1,08
Co
oli
ng
-10 0,90-8
0
2
4
6
8
10
12
0 200 400 600 800 1000 1200
T (m
)
Q (m³/h)
KLN…5 Horizontal throw Vt=0,2m/s
high air f low
high Coandă ef fect
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
2,00
2,20
2,40
2,60
2,80
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…5 Horizontal throw adjusted for high air flow
280m³/h
560m³/h
830m³/h
1110m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
L (m) horizontal distance in meters from the centre of diffuserVL (m/s) maximum speed in air stream at distance LT0,2 (m) throw for an isothermal air jet with a Coand�effect for a terminal speed of Vt=0,20m/s.
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
2,00
2,20
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…5 Horizontal throw adjusted for high Coandă effect
140m³/h
360m³/h
550m³/h
730m³/h
KLN_ENG_19_00.xlsx KLN_ENG_38
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFIVE SLOTS
VERTICAL THROW
Correction factor for non isotermal conditions
∆T x Kf
1,09-6 1,06-4 1,04
10 0,91
1,02
Hea
tin
g
2 0,984 0,966 0,948 0,93
Co
oli
ng
-10 1,11-8
0
0,5
1
1,5
2
2,5
3
0 100 200 300 400 500 600 700 800
T (m
)
Q (m³/h)
KLN…5 Vertical throw Vt=0,2m/s
0,00
0,10
0,20
0,30
0,40
0,50
0,60
0,5 1 1,5 2 2,5 3 3,5 4 4,5
Vh
(m/s
)
H (m)
KLN…5 Vertical throw
140m³/h
360m³/h
550m³/h
730m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
H (m) vertical distance in meters from ceilingVh (m/s) maximum speed in air stream at distance HT0,2 (m) throw for an isothermal air jet for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_39
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFIVE SLOTS
PRESSURE DROP - SUPPLY
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
0
5
10
15
20
25
30
0 200 400 600 800 1000 1200
Δp
(Pa)
Q (m³/h)
KLN…5 Pressure drop supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
0
5
10
15
20
25
30
0 100 200 300 400 500 600 700 800
Δp
(Pa)
Q (m³/h)
KLN…5 Pressure drop supply
Vertical throw
KLN_ENG_19_00.xlsx KLN_ENG_40
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFIVE SLOTS
PRESSURE DROP - EXTRACTION
0
5
10
15
20
25
0 100 200 300 400 500 600 700 800
Δp
(Pa)
Q (m³/h)
KLN…5 Pressure drop extraction with clean filter
high air f low
without def lectors
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
0
5
10
15
20
25
0 200 400 600 800 1000 1200
Δp
(Pa)
Q (m³/h)
KLN…5 Pressure drop extraction without filter
high air f low
without def lectors
KLN_ENG_19_00.xlsx KLN_ENG_41
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFIVE SLOTS
SOUND POWER - SUPPLY
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
0
5
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000 1200
Lw
(dB
a)
Q (m³/h)
KLN…5 Sound power supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
0
5
10
15
20
25
30
35
40
45
50
0 100 200 300 400 500 600 700 800
Lw
(dB
a)
Q (m³/h)
KLN…5 Sound power supply
Vertical throw
KLN_ENG_19_00.xlsx KLN_ENG_42
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESFIVE SLOTS
SOUND POWER - EXTRACTION
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
0
5
10
15
20
25
30
35
40
45
0 200 400 600 800 1000 1200
Lw
(dB
a)
Q (m³/h)
KLN…5 Sound power extraction without filter
high air f low
without def lectors
0
5
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000 1200
Lw
(dB
a)
Q (m³/h)
KLN…5 Sound power extraction with clean filter
high air f low
without def lectors
KLN_ENG_19_00.xlsx KLN_ENG_43
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESSIX SLOTS
Vo LIMIT OF THE OCCUPIED ZONE
0,5
0,6
0,7
0,8
0,9
1
1,1
1,2
2,5 3 3,5 4 4,5 5 5,5
Co
rrec
tion
fact
or K
f
Hr Height of the room (m)
KLN…6 Correction factor for Hr different to 3m
0
0,2
0,4
0,6
0,8
1
1,2
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…6 Vo for Hr=3m adjusted for high air flow
330m³/h
650m³/h
970m³/h
1290m³/h
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0
Vo
(m/s
)
A Distance between the diffusers (m)
KLN…6 Vo for Hr=3m adjusted for high Coandă effect
160m³/h
420m³/h
640m³/h
850m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
A (m) distance between diffusersVo (m/s) speed at limit of occupied area
For Hr different to 3m, use the multiplier factor KF:Vo (h) = Vo x Kf
KLN_ENG_19_00.xlsx KLN_ENG_44
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESSIX SLOTS
HORIZONTAL THROW
Correction factor for non isotermal conditions
∆T x Kf
0,92-6 0,94-4 0,96
10 1,10
0,98
Hea
tin
g
2 1,024 1,046 1,068 1,08
Co
oli
ng
-10 0,90-8
0
2
4
6
8
10
12
0 200 400 600 800 1000 1200 1400
T (m
)
Q (m³/h)
KLN…6 Horizontal throw Vt=0,2m/s
high air f low
high Coandă ef fect
0,000,200,400,600,801,001,201,401,601,802,002,202,402,602,803,00
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…6 Horizontal throw adjusted for high air flow
330m³/h
650m³/h
970m³/h
1290m³/h
0,00
0,20
0,40
0,60
0,80
1,00
1,20
1,40
1,60
1,80
2,00
2,20
2,40
0 1 2 3 4 5 6 7 8 9
Vl (
m/s
)
L (m)
KLN…6 Horizontal throw adjusted for high Coandă effect
160m³/h
420m³/h
640m³/h
850m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
L (m) horizontal distance in meters from the centre of diffuserVL (m/s) maximum speed in air stream at distance LT0,2 (m) throw for an isothermal air jet with a Coand�effect for a terminal speed of Vt=0,20m/s.
KLN_ENG_19_00.xlsx KLN_ENG_45
-2
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESSIX SLOTS
VERTICAL THROW
Correction factor for non isotermal conditions
∆T x Kf
1,09-6 1,06-4 1,04
10 0,91
1,02
Hea
tin
g
2 0,984 0,966 0,948 0,93
Co
oli
ng
-10 1,11-8
0,00
0,10
0,20
0,30
0,40
0,50
0,60
0,70
0,5 1 1,5 2 2,5 3 3,5 4 4,5
Vh
(m/s
)
H (m)
KLN…6 Vertical throw
160m³/h
420m³/h
640m³/h
850m³/h
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
H (m) vertical distance in meters from ceilingVh (m/s) maximum speed in air stream at distance HT0,2 (m) throw for an isothermal air jet for a terminal speed of Vt=0,20m/s.
0
0,5
1
1,5
2
2,5
3
3,5
0 200 400 600 800 1000
T (m
)
Q (m³/h)
KLN…6 Vertical throw Vt=0,2m/s
KLN_ENG_19_00.xlsx KLN_ENG_46
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESSIX SLOTS
PRESSURE DROP - SUPPLY
0
5
10
15
20
25
30
0 200 400 600 800 1000
Δp
(Pa)
Q (m³/h)
KLN…6 Pressure drop supply
Vertical throw
0
5
10
15
20
25
30
0 200 400 600 800 1000 1200 1400
Δp
(Pa)
Q (m³/h)
KLN…6 Pressure drop supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
KLN_ENG_19_00.xlsx KLN_ENG_47
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESSIX SLOTS
PRESSURE DROP - EXTRACTION
0
5
10
15
20
25
0 200 400 600 800 1000
Δp
(Pa)
Q (m³/h)
KLN…6 Pressure drop extraction with clean filter
high air f low
without def lectors
0
5
10
15
20
25
0 200 400 600 800 1000 1200 1400
Δp
(Pa)
Q (m³/h)
KLN…6 Pressure drop extraction without filter
high air f low
without def lectors
Aeraulic data measured in isothermic conditions for a one meter long diffuser in accordance with the international standard:ISO 5219 1984: Air distribution and air diffusion -Laboratory. Aerodynamic testing and rating of air terminal devices.
KLN_ENG_19_00.xlsx KLN_ENG_48
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESSIX SLOTS
SOUND POWER - SUPPLY
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
0
5
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000
Lw
(dB
a)
Q (m³/h)
KLN…6 Sound power supply
Vertical throw
0
5
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000 1200 1400
Lw
(dB
a)
Q (m³/h)
KLN…6 Sound power supply
Horizontal throw adjusted for high Coandă ef fect
Horizontal throw adjusted for high air f low
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
KLN_ENG_19_00.xlsx KLN_ENG_49
L +Kf
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIESSIX SLOTS
SOUND POWER - EXTRACTION
Correction factor for different lengthsame flow rate per meter of diffuser
600 -2,2800 -1,01000 0,01200 0,81500 1,82000 3,0
0
5
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000 1200 1400
Lw
(dB
a)
Q (m³/h)
KLN…6 Sound power extraction with clean filter
high air f low
without def lectors
0
5
10
15
20
25
30
35
40
45
0 200 400 600 800 1000 1200 1400
Lw
(dB
a)
Q (m³/h)
KLN…6 Sound power extraction without filter
high air f low
without def lectors
Data measured in reverberating room in accordance with the following international standards:ISO 3741 1999: Acoustic - determination of sound power levels of noise sources using sound pressure - Precision methods for reverberation rooms
ISO 5135 1997: Acoustic - determination of sound power levels of noise from air-terminal devices ; air terminal units; dampers and valves by measurement in a reverberation room.
The data shown does not consider the attenuation given by the place of installation. This attenuation is normally included between 6 and 10dBa and is determined by the dimensions of the room, its shape and the arrangements of the furnishings within it.
KLN_ENG_19_00.xlsx KLN_ENG_50
Q = air flow (m³/h)
S = B x H / 1000000
Vf = Q / 3600 / S
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
FILTERS
Vf = frontal velocity
B = length of the filter (mm)H = height of the filter (mm)
Filter for 3 slots diffuserFiltering class G3.Polyester fiber material.Galvanized steel containment frame .Metal net on both sides.
Filter for 4 slots diffuserFiltering class G3.Polyester fiber material.Galvanized steel containment frame .Metal net on both sides.
Filter for 5 slots diffuserFiltering class G3.Polyester fiber material.Galvanized steel containment frame .Metal net on both sides.
Filter for 6 slots diffuserFiltering class G3.Polyester fiber material.Galvanized steel containment frame .Metal net on both sides.
0
2,5
5
7,5
10
12,5
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1
Δp
(Pa)
Vf (m/s)
Pressure drop
KLN_ENG_19_00.xlsx KLN_ENG_51
AR
SB (a)
SF (b)
FB (c)
RB (e)
PB (f)
PF (g)
ABRZ
(a)
(b)
(c)
(d)
(e)
(f)
Diffuser length from 300mm up to 1200mm
(g)
Diffuser length from 300mm up to 1200mm
Anodized diffuser profile
HIGH AIR FLOWLINEAR SLOT DIFFUSERS KLN
SERIES
CODES
KLN High air flow linear slot diffuser
Black deflectors
RAL 9010 diffuser profile
number of slots
Standard - with quick fix - without filterStandard - filter holderFineline - without filter
FF Fineline - filter holder (d)
Fitted - without filterPredisposed for panel - without filterPredisposed for panel - filter holder
Anodized deflectors
RAL 9010 deflectorswithout deflectors
Length
KLN A 3 SB A 0900
From 1 slot up to 6 slots Length from 300mm up to 2000mmPlenum P94A Plenum fixing with quick fix
From 3 slots up to 6 slots Length from 300mm up to 1200mmPlenum P94B Plenum fixing with screws Filter to order separately
From 1 slot up to 6 slots Length from 300mm up to 2000mmPlenum P94B Plenum fixing with rivets
From 3 slots up to 6 slots Length from 300mm up to 1200mmPlenum P94B Plenum fixing with screws Filter to order separately
From 1 slot up to 6 slots Length from 300mm up to 2000mmPlenum P94B Plenum fixing with rivets
From 3 slots up to 6 slots Size of the panel on request Panel to order separately
Filter to order separately
Plenum P94B Plenum fixing with rivets
From 3 slots up to 6 slots Size of the panel on request Panel to order separatelyPlenum P94B Plenum fixing with rivets
KLN_ENG_19_00.xlsx KLN_ENG_52
NDMF
A For installation with quick fix
HIGH AIR FLOW LINEAR SLOT DIFFUSERS KLN
SERIES
CODES - INSPECTION AND MAINTENANCE
P94 Plenum for linear diffuser KLN
Connectors in ABS with flat damper
B For installation with screws or rivets
I External insulationC Internal insulationN No insulation
number of slots
Length
Connectors in ABS without damper
FP Flat filter
Connectors in steel without damperConnectors in steel with flat damper
P94 A N 3 0900 M
As standard the plenum box is supplied separated from the diffuser
For the plenum box mounted on the diffuer use code:KLN-PLNMONT mounting of the plenum box on the diffuser
FP 15 KLN 3F 0900
15 Thickness 15mm
For linear diffuser KLN
Number of slots
Length of the diffuser
INSPECTION AND MAINTENANCE:
We recommend to check the filter condition at least every six months.Replace the filter if necessary and dispose of in accordance to local legislation separating the metal structure from the filtermedia.
KLN_ENG_19_00.xlsx KLN_ENG_53
1
2
3
4
5 Quick fix
HIGH AIR FLOW LINEAR SLOT DIFFUSERS KLN
SERIESACCESSORIESSPARE PARTS
KLN-SW2 Pair of brackets for quick fix
Coumterceiling in plasterboard12,5mm thick
Sandwich panel 20 mm thick
Bracket for quick fix
KLN diffuser
Brackets KLN-SW2 let you use the quick fix method to install the diffuser KLN with the plenum (not supplied by MP3) made on site with 20mm thick sandwich panel in plasterboard ceilings thickness 12.5mm thick.
Diffuser length up to 1500mm : order two pairs of brackets.Diffuser length more than 1500mm: order three pairs of brackets.
It is recommended to attach the brackets with the same sealant used for joining panels.
KLN_ENG_19_00.xlsx KLN_ENG_54
AR
KLN-TESTATA Standard end cap in aluminum
HIGH AIR FLOW LINEAR SLOT DIFFUSERS KLN
SERIESACCESSORIESSPARE PARTS
KLN-BAIONETTE Pair of bayonets for line mounting
KLN-QF2 Couple of Quick fix hooks
End cap per KLN
AnodizedRal 9010
4 Number of slots
KLN-TESTATA A 4
KLN_ENG_19_00.xlsx KLN_ENG_55
Pair of mounting bridges for KLN
HIGH AIR FLOW LINEAR SLOT DIFFUSERS KLN
SERIESACCESSORIESSPARE PARTS
KLN-BRIDGE Pair of mounting bridges for installationin plasterboard counterceilings without plenum
from 1 up to 2 slots one screw
from 3 up to 6 slots two screws
For diffusers with a length equal or higher to 1650 mm it is suggested to use two pairs of mounting bridges
Number of slots
KLN-BRIDGE 4
Only for installation witout plenum Only for standard version KLN … SB (no filterholder, no panel)
KLN_ENG_19_00.xlsx KLN_ENG_56
AD
AR
Corner connection for KLN
HIGH AIR FLOW LINEAR SLOT DIFFUSERS KLN
SERIESACCESSORIESSPARE PARTS
KLNCA Corner connection
Without deflectorsWith deflectors
AnodizedRal 9010
4 Number of slots
KLNC D A 4
number of B
Slots mm mm
1 501 484
A
2 458 4413 415 398
6 286 269
4 372 3555 329 312
KLN_ENG_19_00.xlsx KLN_ENG_57