health index and on line condition monitoring elvis event marcus stenstrand
TRANSCRIPT
ELVISHealth index and On-line condition monitoring
Marcus Stenstrand @mstenstrand
SAP Work Manager Mobile
Oracle Primavera Project Portfolio &
Management
Primavera adapter
Maximo Spatial
IBM Maximo Asset Management
ESRI ArcGIS GIS
Electron CAPE Relay simulation
IPS EpisRelay Management
Siemens PSS®ODMS Grid modeling
Siemens PSS®E Grid calculation
OSIsoft PI AF & ProcessBook
Asset health
OSIsoft PI Real-time & data storage
• External measurement database • Cognos BI
SCADA
ELVIS– THE NEW PLATFORM FOR ASSET AND OPERATION MANAGEMENTIntegrated best-of-breed standard software products
ELVIS
Asset health index and condition estimation• Health indices in use for transformers & substations since 2012 • Used to identify the possible asset risk related to older substations
• Maintenance and refurbishments optimaization• Analysis can strengthen already known component weaknesses but may
also point out additional needs for further clarification
Screenshot of on-line asset health tool
Age
Which substations shall be renewed?
Poor
Good
0 years50 years
Con
ditio
n
Renew Investigate
Observe Upkeep
Substation health index
Crit
ical
ity
Power Transformer health index• Based on Dissolved Gas Analysis (DGA)
+ oil quality, tan δ, oil temperature
• DGA finger prints and a fault library are very useful in defect investigations
Transformer fault - Nurmijärvi PM1Increasing oil gas ratio was noticed and taken under observation in May 2012. Strong correlation between Low Voltage side current and oil gas ratio was detected by Condition Monitoring System and confirmed with diagnostics measurements. The early notice gave time to react and remedial actions were launched in time.
Transformer fault case Nurmijärvi PM1
SF6 leaks - saving both nature and money• Several Circuit Breaker SF6 gas leaks and detector failures has been detected at early
stage by monitoring and automatic notifications.
Benefits and future• Health indices are used for long term planning
• On-line maintenenace monitoring helps to catch faults before they cause problems for the control room
• OSIsoft PI enables us to get SCADA measurement information to the use for asset and maintenance engineers
• Next steps• Health index for protection assets• Elvis Maximo asset ID also in use in SCADA