9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 www.geodesigninc.com September 12, 2019 Kittelson & Associates, Inc. 851 SW 6 th Avenue, Suite 600 Portland, OR 97204 Attention: Tony Roos Hazardous Building Materials Survey 1844 C Street Residence Forest Grove, Oregon GeoDesign Project: ForestGrov-6-02-2.1.1 INTRODUCTION This report summarizes the results of a hazardous building materials survey of the residence located at 1844 C Street in Forest Grove, Oregon (project site). The residence consists of an 892-square-foot, vacant residence with an approximately 240-square-foot addition. The hazardous building materials survey was conducted in anticipation of upcoming demolition of the residence. Acronyms and abbreviations used herein are defined at the end of this document. SCOPE OF SERVICES The hazardous building materials survey included a pre-construction ACM survey, an LBP survey, and a universal waste evaluation. The specific scope of services for the hazardous building materials survey is presented below. PRE-CONSTRUCTION ACM SURVEY The purpose of the pre-construction ACM survey was to provide an evaluation of the interior and exterior portions of the project site structure for the potential presence of asbestos in suspect materials. The pre-construction ACM survey was conducted in general accordance with ASTM E2356-14, Standard Practice for Comprehensive Building Asbestos Surveys. For this project, our scope of services was developed consistent with the requirements of a pre- construction survey in anticipation of future demolition of the project site structure. The survey, which was conducted by personnel certified under the EPA’s AHERA program (AHERA Building Inspector Certificate #169807, presented in Attachment A), included the following:

Upload: others

Post on 30-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 www.geodesigninc.com

September 12, 2019 Kittelson & Associates, Inc. 851 SW 6th Avenue, Suite 600 Portland, OR 97204 Attention: Tony Roos

Hazardous Building Materials Survey 1844 C Street Residence

Forest Grove, Oregon GeoDesign Project: ForestGrov-6-02-2.1.1

INTRODUCTION This report summarizes the results of a hazardous building materials survey of the residence located at 1844 C Street in Forest Grove, Oregon (project site). The residence consists of an 892-square-foot, vacant residence with an approximately 240-square-foot addition. The hazardous building materials survey was conducted in anticipation of upcoming demolition of the residence. Acronyms and abbreviations used herein are defined at the end of this document. SCOPE OF SERVICES The hazardous building materials survey included a pre-construction ACM survey, an LBP survey, and a universal waste evaluation. The specific scope of services for the hazardous building materials survey is presented below. PRE-CONSTRUCTION ACM SURVEY The purpose of the pre-construction ACM survey was to provide an evaluation of the interior and exterior portions of the project site structure for the potential presence of asbestos in suspect materials. The pre-construction ACM survey was conducted in general accordance with ASTM E2356-14, Standard Practice for Comprehensive Building Asbestos Surveys. For this project, our scope of services was developed consistent with the requirements of a pre-construction survey in anticipation of future demolition of the project site structure. The survey, which was conducted by personnel certified under the EPA’s AHERA program (AHERA Building Inspector Certificate #169807, presented in Attachment A), included the following:

Page 2: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

2 ForestGrov-6-02-2.1.1:091219

Conducted an initial reconnaissance of the project site structure to verify building

construction and layout, verify building mechanical components, measure building dimensions, and gather additional information to develop an appropriate sampling plan.

Reviewed available permits and online property information to verify building conditions and construction details.

Developed an ACM sampling plan based on the initial building reconnaissance and review of the floor plans.

Collected 17 samples of homogenous suspect building materials, including appropriate sample population, taking into account material quantities and location.

Submitted the samples to EMC Labs, Inc. of Phoenix, Arizona, for analysis of asbestos content by PLM/EPA Method 600/R-93-116.

Summarized the results of the pre-construction ACM survey in this report. LBP SURVEY The purpose of the LBP survey was to evaluate paint throughout the project site structure for the presence of lead at a concentration greater than 1.0 mg/cm2. The LBP survey was performed by GeoDesign personnel and included the following: Evaluated painted surfaces throughout the project site structure for the presence of LBP

using a Niton Model XLp-306A XRF detector to identify the potential presence of lead in paint.

Summarized the results and findings of the LBP survey in this report. UNIVERSAL WASTE EVALUATION The universal waste evaluation was performed to evaluate the project site structure for the presence of universal waste that may require special handling and/or disposal. The universal waste evaluation included the following: Evaluated the project site structure for the presence of universal waste, including pesticides,

batteries, potential mercury-containing equipment (including thermostats, thermometers, barometers, and mercury-containing switches), potential PCB-containing equipment, and lamps.

Summarized the results and findings of the universal waste evaluation in this report. PROJECT SITE STRUCTURE The project site structure is an approximately 892-square-foot, wood-framed residence supported by a pier foundation. The project site structure has an approximately 240-square-foot addition attached to the west side. According to Washington County Building Services, the residence was reportedly constructed in 1921 and is currently owned by the City of Forest Grove (City).

Page 3: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

3 ForestGrov-6-02-2.1.1:091219

RECORDS REVIEW GeoDesign requested available permits and building plans from City’s Building Department staff on September 3, 2019. According to City staff, the City has a certificate of occupancy dated 1971 and a demolition permit currently pending. Records pertaining to hazardous building materials were reportedly not available. PRE-CONSTRUCTION ACM SURVEY On August 29, 2019 GeoDesign personnel certified under EPA’s AHERA program performed a pre-construction ACM survey of the project site structure. The purpose of the pre-construction ACM survey was to evaluate the structure for the possible presence of ACM. EPA’s AHERA program defines ACM as materials containing asbestos at a concentration greater than 1 percent. Materials sampled from the project site structure included roofing materials, insulation materials, wall coverings with associated mastics, flooring materials with associated mastic, ceiling tile with mastic, caulks, drywall with associated joint compound, cloth wire insulation, and pipe insulation. GeoDesign submitted 17 suspect ACM samples to EMC Labs, Inc. of Phoenix, Arizona, for analysis of percent asbestos content by EPA Method 600/R-93-116. EMC Labs is accredited by the National Institute of Standards and Technology under the procedures of the National Voluntary Laboratory Accreditation Program for bulk sample analysis. The suspect ACM sampling results are presented in Table 1. Sample locations and the locations of the rooms are shown on Figure 1. The EMC Lab report and accompanying chain-of-custody documentation are presented in Attachment B. Asbestos was not detected in the 17 samples of suspect ACM analyzed. LBP SURVEY The LBP survey was conducted on August 29, 2019 by GeoDesign personnel. The LBP survey was conducted using an XRF manufactured by Niton (Model XLp-306A Spectrum Analyzer Lead Detector). Bulk paint chip samples were not collected from the project site structure during this survey. According to the Performance Characteristic Sheet for the Niton Model XLp-306A XRF detector, there are no inconclusive readings; therefore, bulk paint chip samples are not necessary. LBP is defined by EPA/HUD as paint that contains at least 1.0 mg/cm2 of lead. Therefore, XRF readings that are equal to or greater than 1.0 mg/cm2 are considered positive for LBP. A total of 17 representative painted surfaces were analyzed using the XRF and were visually assessed for general condition. The following LBP was identified at the project site: Blue exterior siding paint contains up to 4.6 mg/cm2 lead. White exterior window trim paint contains up to 4.3 mg/cm2 lead. Black door trim paint in Room 1 contains 4.6 mg/cm2 lead.

Page 4: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

4 ForestGrov-6-02-2.1.1:091219

Turquoise baseboard paint in Room 2 contains 3.5 mg/cm2 lead. White wall paint in the laundry room contains 6.1 mg/cm2 lead. UNIVERSAL WASTE EVALUATION On August 29, 2019 GeoDesign personnel conducted a universal waste evaluation at the project site, including an evaluation for the presence of pesticides, batteries, potential mercury-containing equipment (including thermostats, thermometers, barometers, and mercury-containing switches), potential PCB-containing equipment, and lamps. Pesticides, lead acid batteries, potential PCB-containing equipment, metal halide lamps, high-intensity discharge lamps, or other universal waste-qualifying lamps were not observed at the project site. GeoDesign personnel observed three potential mercury-containing switches on baseboard space heaters within the residence at the time of the universal waste evaluation. CONCLUSIONS AND RECOMMENDATIONS GeoDesign performed a hazardous building materials survey of the residence located at 1844 C Street in Forest Grove, Oregon, including a pre-construction ACM survey, an LBP survey, and a universal waste evaluation. The pre-construction ACM survey was performed in general accordance with ASTM E2356-14, Standard Practice for Comprehensive Building Asbestos Surveys. The results of the hazardous building materials survey indicated the following: Asbestos was not detected in the suspect ACM samples analyzed. The following LBP was identified at the project site:

Blue paint on the wooden exterior siding of the residence White paint on the wooden window trim of the residence Black paint on wooden door trim in Room 1 Turquoise paint on wooden baseboard in Room 2 White paint on an interior wall of the laundry room

Universal wastes observed at the project site consisted of three potential mercury-containing switches on baseboard space heaters in the residence.

Contractors and their employees should be notified of the presence of LBP at the project site and should employ lead-safe work practices when conducting renovation or demolition activities in these areas. The LBP identified during this survey does not require removal or abatement and may be disposed of with the remainder of the demolition debris at a landfill approved to accept demolition/construction debris. Metro recommends wetting LBP-painted surfaces prior to transport and disposal to reduce flaking. The potential mercury-containing switches identified as universal waste should be removed and properly disposed of prior to demolition and renovation if future use is not anticipated. These items must not be broken to qualify as universal waste and should be packaged to avoid

Page 5: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

5 ForestGrov-6-02-2.1.1:091219

breakage during transport. If the switches contain mercury, they should be disposed of as universal waste at a hazardous waste-accepting facility, such as Metro Central Hazardous Waste, located in Portland, Oregon. LIMITATIONS This Hazardous Building Materials Survey report has been prepared for use by Kittelson & Associates, Inc. and the City of Forest Grove. This report is not intended for use by others, and the information contained herein is not applicable to other sites. Reliance by other parties must be approved by GeoDesign in accordance with our standard contractual process for third-party reliance. Our interpretations of the presence and distribution of ACM is based on data from select samples analyzed from a limited sample population. Additional suspect ACM not sampled during this survey should be assumed as ACM unless additional sampling demonstrates the materials are not ACM. It is always possible that ACM could exist within concealed areas, inaccessible areas, or between sample locations. Analytical results from the laboratory should only be considered indicators of site conditions and not a guarantee of the lack of ACM at the project site. Our interpretations of the presence and distribution of LBP is based on data from readings at select locations. Additional suspect LBP not analyzed during this survey should be assumed as LBP unless additional analysis or sampling demonstrates the materials do not contain LBP. It is always possible that LBP could exist within concealed areas, inaccessible areas, or between sample locations. Results from the field investigation should only be considered indicators of site conditions and not a guarantee of the presence or absence of LBP. The conclusions presented in this report are based on the observations made during our field investigation and laboratory analytical data and are representative of the project site as it appeared at the time of the survey. If demolition or redevelopment of the project site is delayed, it may be necessary to reinspect the project site structure to assess if building materials have been modified, added, or altered. The findings of this survey should be considered as a professional opinion. Our services have been executed in accordance with the generally accepted practices at the time this report was prepared. No warranty or other conditions, express or implied, should be understood. Further conditions and limitations to this report are included in the contract between Kittelson & Associates and GeoDesign.

Page 6: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

6 ForestGrov-6-02-2.1.1:091219

We appreciate the opportunity to be of continued service to the City of Forest Grove and Kittelson & Associates, Inc. on this project. Please call if you have questions regarding this report. Sincerely, GeoDesign, Inc. Tim Hainley Environmental Staff AHERA Certificate # 169807 Colby R. Hunt, C.H.M.M. Principal TJH:CRH:kt

Attachments

One copy submitted (via email only)

Document ID: ForestGrov-6-02-2.1.1-091219-envlr-rev.docx

© 2019 GeoDesign, Inc. All rights reserved.

Page 7: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

FIGURES

Page 8: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

AS-1

AS-2

AS-3

AS-5

AS-6

AS-7

AS-8

AS-9

AS-10

AS-11

AS-13

AS-12

AS-14 AS-15

AS-4

AS-17

AS-16

#7#8

#9

#10

#11

#12

#13

#21#22 #23

#17#18

#20

#19

#16

#15

#14

EXTERIOR, ROOF, AND ATTIC

INTERIOR

ADDITION

LAUNDRY ROOM 3

KITCHEN

ROOM 1

ROOM 2

BATHROOM

ADDITION

Prin

ted B

y: a

day

| P

rint

Dat

e: 9

/10

/20

19

10

:20

:20

AM

50

3.9

68

.87

87

w

ww

.geo

des

ignin

c.co

m

Wilso

nvi

lle

OR

97

07

0

94

50

SW

Com

mer

ce C

ircl

e -

Suit

e 3

00

File

Nam

e:

J:\E

-L\F

ore

stG

rov\

Fore

stG

rov-

6\F

ore

stG

rov-

6-0

2\F

ore

stG

rov-

6-0

2-2

.1.1

\Fig

ure

s\C

AD

\Fore

stG

rov-

6-0

2-2

.1.1

-SP0

1.d

wg | L

ayout:

FIG

UR

E 1

SIT

E P

LA

N

1844 C

STREE

T R

ESID

ENC

EFO

RES

T G

RO

VE,

OR

FORES

TG

RO

V-6

-02-2

.1.1

SEPT

EMBER

2019

FIG

UR

E 1

(NOT TO SCALE)

N

LEGEND:

SUSPECT ACM SAMPLE LOCATION

XRF READING LOCATION (RED INDICATES LEADCONCENTRATIONS GREATER THAN 1.0 MG/CM2.BLUE INDICATES LEAD CONCENTRATIONS LESSTHAN 1.0 MG/CM2.)

AS-1

#5

SITE PLAN BASED ON OBSERVATIONS ANDFIELD MEASUREMENTS BY GEODESIGN STAFF

Page 9: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

9450 SW Commerce Circle - Suite 300

Wilsonville OR 97070 503.968.8787 www.geodesigninc.com

FORESTGROV-6-02-2.1.1 LBP READING PHOTOGRAPHS

SEPTEMBER 2019 1844 C STREET RESIDENCE

FOREST GROVE, OR FIGURE 2

BLUE SIDING PAINT (READING NOS. 7 AND 11) AND WHITE WINDOW TRIM PAINT (READING NOS. 8 AND 9) CONTAIN UP TO 4.6 MG/CM2 AND UP TO 4.3 MG/CM2 LEAD, RESPECTIVELY.

BLACK DOOR TRIM PAINT (READING NO. 13) CONTAINS 4.6 MG/CM2 LEAD.

Fore

stG

rov-

6-02

-2.1

.1-F

2_4-

SPH

.doc

x

Prin

t D

ate:

09/0

5/19

Page 10: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

9450 SW Commerce Circle - Suite 300

Wilsonville OR 97070 503.968.8787 www.geodesigninc.com

FORESTGROV-6-02-2.1.1 LBP READING PHOTOGRAPHS

SEPTEMBER 2019 1844 C STREET RESIDENCE

FOREST GROVE, OR FIGURE 3

TURQUOISE BASEBOARD PAINT (READING NO. 15) CONTAINS 3.5 MG/CM2 LEAD.

WHITE WALL PAINT IN THE LAUNDRY ROOM (READING NO. 20) CONTAINS 6.1 MG/CM2 LEAD.

Fore

stG

rov-

6-02

-2.1

.1-F

2_4-

SPH

.doc

x

Prin

t D

ate:

09/0

5/19

Page 11: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

9450 SW Commerce Circle - Suite 300

Wilsonville OR 97070 503.968.8787 www.geodesigninc.com

FORESTGROV-6-02-2.1.1 LBP READING PHOTOGRAPHS

SEPTEMBER 2019 1844 C STREET RESIDENCE

FOREST GROVE, OR FIGURE 4

BLUE SIDING PAINT (READING NO. 21) CONTAINS 3.2 MG/CM2 LEAD.

Fore

stG

rov-

6-02

-2.1

.1-F

2_4-

SPH

.doc

x

Prin

t D

ate:

09/0

5/19

Page 12: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

TABLES

Page 13: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

SampleI.D.

Layer Location Homogenous Material DescriptionMaterialCategory(S/T/M)

Friable(Y/N)

Asbestos(percent)

AsbestosType

ApproximateQuantity of ACM

(square feet)

AS-1 1 Attic Attic Insulation, Yellow M N ND NA NA

1 Asphalt Roofing, Black M N ND NA NA

2 Roof Felt, Black M N ND NA NA

AS-3 1 Roof Caulk, Black M N ND NA NA

1 Wood Panel Mastic, Gold M N ND NA NA

2 Backing, Light Brown M N ND NA NA

1 Ceiling Tile, White/Gray M N ND NA NA

2 Mastic, Tan M N ND NA NA

1 Wall Covering/Mastic, Off White/Tan M N ND NA NA

2 Vapor Barrier, Gray M N ND NA NA

3 Wall Paneling, White/Brown M N ND NA NA

4 Wall Covering/Mastic, White/Beige M N ND NA NA

1 Sheet Flooring, Off White/Gray M N ND NA NA

2 Mastic, Yellow M N ND NA NA

3 Sub-flooring, Beige M N ND NA NA

1 Sheet Flooring, Off White/Gray M N ND NA NA

2 Mastic, Off White M N ND NA NA

3 Sheet Flooring, Brown/Tan M N ND NA NA

4 Mastic, Yellow M N ND NA NA

1 Textured Paint, White M N ND NA NA

2 Wall Covering/Mastic, Light Blue/Yellow M N ND NA NA

3 Wall Covering, Orange/Black M N ND NA NA

4 Mastic, Dark Brown M N ND NA NA

TABLE 1

August 29, 2019Forest Grove, Oregon

1844 C Street ResidenceSummary of Suspect ACM Analytical Results1

AS-4

AS-2 Roof

Room 1

Room 3AS-5

Room 3AS-6

Bathroom

Hallway

HallwayAS-9

AS-8

AS-7

Page 1 of 2 ForestGrov-6-02-2.1.1:091219

Page 14: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

SampleI.D.

Layer Location Homogenous Material DescriptionMaterialCategory(S/T/M)

Friable(Y/N)

Asbestos(percent)

AsbestosType

ApproximateQuantity of ACM

(square feet)

TABLE 1

August 29, 2019Forest Grove, Oregon

1844 C Street ResidenceSummary of Suspect ACM Analytical Results1

1 Wall Tile, Green/Black M N ND NA NA

2 Mastic, White M N ND NA NA

1 Mastic, White M N ND NA NA

2Wall Covering/Mastic/Paint,

Beige/Brown/Light BlueM N ND NA NA

1 Drywall, White/Brown M N ND NA NA

2 Joint Compound, White M N ND NA NA

AS-13 1 Laundry Room Wire Insulation, Black/White/Beige M N ND NA NA

1 Pipe Insulation, Yellow T N ND NA NA

Pipe Insulation Wrap, Beige/Black T N ND NA NA

1 Drywall, White/Brown M N ND NA NA

2 Joint Compound, White M N ND NA NA

AS-16 1 Exterior Window Caulk, White M N ND NA NA

1 Wall Covering/Mastic, White/Beige M N ND NA NA

2 Wall Covering/Mastic, Gray/Black M N ND NA NA

3 Insulation, Yellow M N ND NA NA

Notes:

1. PLM performed by EMC Laboratories of Phoenix, Arizona.

M: miscellaneous materials

ND: Asbestos was not detected above 1 percent.

S: surfacing material

T: thermal system insulation

AS-14 Laundry Room

AS-17 Kitchen

KitchenAS-11

AS-15

AS-12

BathroomAS-10

Room 2

Room 1

Page 2 of 2 ForestGrov-6-02-2.1.1:091219

Page 15: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

Reading

Number1 Component Substrate Side Condition Color Area/Room I.D. ResultLead

Concentration

(mg/cm2)

7 Siding Wood North Cracked Blue House Exterior Positive 3.78 Window Trim Wood North Fair White House Exterior Positive 4.39 Window Trim Wood North Fair White House Exterior Positive 3.410 Entry Door Metal East Fair White House Exterior Negative 011 Siding Wood East Fair Blue House Exterior Positive 4.612 Wall Wallboard North Fair Red Room 1 Negative 013 Door Trim Wood East Intact Black Room 1 Positive 4.614 Wall Drywall North Intact White Room 2 Negative 015 Baseboard Wood West Intact Turquoise Room 2 Positive 3.516 Wall Wood South Intact White Kitchen Negative 0.0117 Floor Wood Upper Intact Blue Room 3 Negative 0.1318 Cabinet Wood East Intact Blue Room 3 Negative 0.0719 Wall Wood East Fair White Laundry Room Negative 0.0120 Wall Wood West Fair White Laundry Room Positive 6.121 Siding Wood South Fair Blue House Exterior Positive 3.222 Wall Wood South Fair Blue Lean to Exterior Negative 023 Gutter Metal Lower Fair White Southern Gutter Negative 0

Notes:

1. Missing reading numbers are due to calibration or null readings.

Shading indicates the presence of LBP (lead concentrations exceeding 1.0 mg/cm2).

Forest Grove, OregonAugust 29, 2019

TABLE 2Summary of LBP Survey Results

1844 C Street Residence

ForestGrov-6-02-2.1.1:091219

Page 16: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

ATTACHMENT A

Page 17: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson
thainley
Snapshot
Page 18: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

ATTACHMENT B

Page 19: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

AsbestosDetected

Layer Name /Sample Description

Lab ID SampleLocation

Bulk Asbestos Analysis by Polarized Light Microscopy

Non-AsbestosConstituents

Laboratory Report

0225474

NVLAP#101926-0

Client ID

Client:Address: 9450 SW COMMERCE CIRCLE, STE #300

WILSONVILLE OR 97070

GEO DESIGN, INC.

Date Received: 08/30/2019

09/04/2019Date Analyzed:

Job# / P.O. #:

EMC LABS, INC.

Collected: 08/29/2019

EPA Method: Project Name: 1844 C STREET RESIDENCE

Submitted By: TIM HAINLEYAddress: PRJ #FORESTGROV-6-02-2.1.1Collected By:

9830 S. 51st Street, Suite B109, Phoenix, AZ 85044Phone: 800-362-3373 or 480-940-5294 - Fax: (480) 893-1726

09/04/2019Date Reported:

EPA 600/R-93/116

Asbestos Type(%)

Fibrous GlassNoAttic Insulation, Yellow None Detected0225474-001 ATTIC

AS-1

98%

Carbonates 2%

Fibrous GlassNoLAYER 1Asphalt Roofing, Black

None Detected0225474-002 ROOF

AS-2

20%

CarbonatesQuartzBinder/Filler

80%

Cellulose FiberNoLAYER 2Roof Felt, Black

None Detected 60%

CarbonatesGypsumBinder/Filler

40%

Cellulose FiberNoCaulk, Black None Detected0225474-003 ROOF

AS-3

5%

CarbonatesQuartzBinder/Filler

95%

Cellulose FiberNoLAYER 1Wood Panel Mastic, Gold

None Detected0225474-004 RM 1

AS-4

1%

CarbonatesQuartzBinder/Filler

99%

Cellulose FiberNoLAYER 2Backing, Lt. Brown

None Detected 98%

CarbonatesGypsum

2%

Page 1 of 7

thainley
Typewritten Text
ForestGrov-6-02-2.1.1
thainley
Typewritten Text
1844 C Street Forest Grove, Oregon
thainley
Typewritten Text
1844 C Street Residence
Page 20: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

ACRONYMS AND ABBREVIATIONS

Page 21: Hazardous Building Materials Survey 1844 C Street Residence...Sep 12, 2019  · 9450 SW Commerce Circle, Suite 300 l Wilsonville, OR 97070 l 503.968.8787 September 12, 2019 Kittelson

ForestGrov-6-02-2.1.1:091219

ACRONYMS AND ABBREVIATIONS ACM asbestos-containing material(s) AHERA Asbestos Hazard Emergency Response Act ASTM American Society for Testing and Materials EPA U.S. Environmental Protection Agency HUD U.S. Department of Housing and Urban Development I.D. identification LBP lead-based paint mg/cm2 milligrams per square centimeter NA not applicable PCB polychlorinated biphenyl PLM polarized light microscopy XRF x-ray fluorescence