Easy mounting and safety
Load break switches with visual breaking from 20 to 125A, 100 to 400A and 125 to 1600A, are easy to mount directly on DIN rail.
Load Break Switches20 to 1600 A
The advantages for you:
• Lorperiu scillam in eratio consectet praessi.
• Lore vullum zzrit, commy nis nos adiat la feugiam etummodo do
• Dolobor si tis accumsandre exer iril inci blamcon ulpute modolor perostis amconulla ad del ut ulputem vero odigna amcor iriliqu
• ismodiamet, sismolore dui et illumsan ent utat, si.
The advantages for you Technical data:
• Lorperiu scillam in eratio consectet praessi.
• Lore vullum zzrit, commy nis nos adiat la feugiam etummodo do
• Dolobor si tis accumsandre exer iril inci blamcon ulpute modolor perostis amconulla ad del ut ulputem vero odigna amcor iriliqu
• ismodiamet, sismolore dui et illumsan ent utat, si.
Technical data
• Easy to install
• Quick, easy and safety mounting of accessories
• Range of breaking capacities
• Lockable in off position
• Main or modular breaking
• Complies with NF EN 60 947-3
• Visual breaking
• Breaking capacity: 20-125A, 100 to 400A and 125 to 1600A
-
Modular design
Units up to 200A can be DIN-rail
mounted1
Insulated terminals
IP2 finger protection2
Lockable handles
Operational handle can be safely
locked in off position3
4
Convenient mounting
Univers kits for 125-1600A
switches5
Accessories
Auxiliary blocks and terminal
covers for all switches6
Flexible operation
All switches can be fitted with
internal or external handles
Quicktips
-
Load Break Switches with Visual Breaking20 to 125A
Description Characteristics In/A Width in z Cat. ref.
3P 4P 3P 4P
Load break switches disconnector 20A 2,6 3,5 HAB302 HAB402
visual breaking modular design
IP20 32A 2,6 3,5 HAB303 HAB403
In=Ith, AC23
40A 2,6 3,5 HAB304 HAB404
63A 2,6 3,5 HAB306 HAB406
63A 3 4,5 HAC306 HAC406
80A 3 4,5 HAC308 HAC408
100A 3 4,5 HAC310 HAC410
100A 4,5 6 HAD310 HAD410
125A 4,5 6 HAD312 HAD412
External handles for LBS 20 to 100A HZC010 HZC010
IP55
lockable with 3 padlocks for LBS 100 to 125A HZC011 HZC011
Shaft extensions 20 to 125A, 150mm HZC111 HZC111
20 to 125A, 200mm HZC112 HZC112
20 to 125A, 320mm HZC113 HZC113
Terminal shrouds 20 to 63A HZC211 HZC212
top and bottom
2 pieces / packaging 63 to 100A HZC213 HZC214
100 to 125A HZC215 HZC216
Auxiliaries contacts 1O + 1F 0,5 0,5 HZC311 HZC311
In = 10A
2F 0,5 0,5 HZC312 HZC312
HAB406
Load break switches with visual breaking, 20 to 125A
• modular design,• to mount directly on DIN rail,• lockable in OFF position.
Complies with NF EN 60 947-3.
Connection
with collar terminals copper
conductors compatible.
Connection capacity
• HAB 20 to 63A: 16 mm2 lexible or rigid cables
• HAC 60 to 100A: 35 mm2 lexible or rigid cables
• HAD 100 and 125A: 70 mm2 lexible or rigid cables
HZC113
HZC212
HZC311
3.112
-
Load Break Switches with Visible Breaking100 to 400A
Description Characteristics In/A Width in z Cat. ref. 3P 4P 3P 4P
Load break switches disconnector 100A 6,5 8 HAE310 HAE410
visible breaking modular design
IP20 125A 6,5 8 HAE312 HAE412
160A 6,5 8 HAE316 HAE416
200A 8,5 8,5 HA308 HA408
250A 11,5 HA964N
400A 19,5 HA966N
External handles for LBS 100 to 160A HZC014 HZC014
IP55
lockable with 3 padlocks for HA308, HA408, HA964N and HA966N HZC001 HZC001
Shaft extensions 200 mm, for HA308 and HA408 HZC103 HZC103
300 mm, for HA308 and HA408 HZC104 HZC104
for HAE 100 to 160A, 150mm HZC114 HZC114
for HAE 100 to 160A, 200mm HZC115 HZC115
for HAE 100 to 160A, 320mm HZC116 HZC116
Terminal shrouds 100 to 160A HZC217 HZC218
top and bottom
for HA408 HZ062
for HA964N HZ095 HZ095
for HA966N HZ096 HZ096
Collar terminals for HA308 and HA408 HZ082 HZ082
copper, 95mm2
for HA964 HZ093 HZ093
aluminium/copper, 185mm2
Auxiliaries contacts 1NC + 1NO 0,5 0,5 HZ022 HZ022
for HA308 and HA408
HAE416
HZC014
Load break switches with
visible breaking, 100 to 400A
• modular design,• to mount directly on DIN rail for
LBS up to 200A,
• lockable in OFF position.
HA964N and HA966N are with
double visible breaking
(upstream and downstream).
Mounting on plate.
Complies with NF EN 60 947-3.
Connection
• HAE: with collar terminals copper conductors compatible
• HA308, HA408, HA964N and HA966N on terminal.
Connection capacity
• HAE 100 to 160A: 70 mm2 lexible or rigid cables
• HA308, HA408: 95 mm2 end lugs,
• HA964N: 150 mm2 end lugs,• HA966N: 240 mm2 end lugs.
HZC218
HZ022
3.113
Main
Inco
mers
-
HAB402, HAB403, HAB404, HAB406, HAC408 HAE410, HAE412, HAE416
D
A C
B E EB
A C
D
Dimensions (in mm)
Technical characteristics
HAB, HAC, HAE switches
HAB302
HAB402
HAB303
HAB403
HAB304
HAB404
HAB306
HAB406
HAC306
HAC406
HAC308
HAC408
HAC310
HAC410
HAD310
HAD410
HAD312
HAD412
HAE310
HAE410
HAE312
HAE412
HAE316
HAE416
In 20 A 32 A 40 A 63 A 63 A 80 A 100 A 100 A 125A 100 A 125 A 160 A
rated insulation voltage Ui (V) 800 800 800 800 800 800 800 800 800 800 800 800
rated impulse withstand voltage Uimp (kV) 8 8 8 8 8 8 8 8 8 8 8 8
AC 22 at 400 V (A) 20 32 40 63 63 80 100 100 125 100 125 160
AC 23 at 400 V (A) 20 32 40 63 63 80 100 100 100 100 125 125
motor power AC 23A à 400 VM (kW) 9 15 18.5 30 30 37 45 45 55 45 55 75
rated short-circuit breaking capacity (kA)
in association with gG DIN fuse50 50 50 50 50 50 50 50 50 100 65 50
current rated range (A) 20 32 40 63 63 80 100 100 125 100 125 160
short-circuit making capacity Icc (A peak) 6 000 6 000 6 000 9 000 9 000 9 000 9 000 12 000 12 000 12 000 12 000 12 000
rated short-time withstand current (kA eff)
for 1s Icw2.5 2.5 2.5 2.5 3 3 3 5 5 7 7 7
mechanical endurance (nr of operations) 100 000 100 000 100 000 100 000 100 000 100 000 100 000 100 000 100 000 50 000 50 000 50 000
connection (mm²) 16 16 16 16 35 35 35 70 70 70 70 70
with visual breaking with visible breaking
HAB302, HAB303,
HAB304, HAB306HAB402, HAB403,
HAB404, HAB406
HAC306, HAC308,
HAC310
HAC406, HAC408,
HAC410
HAE410, HAE412,
HAE416
A 45 60 54 71.5 135
B 68 68 76 76 124.5
C 48,5 48.5 48,5 48.5 50.5
D 75 75 75 75 76
E 110 110 110 110 189
3.114
Load Break Switches20 to 400A
-
HA964N - HA966N
Dimensions (in mm)
HA964N HA966N
electrical characteristics
rated current 250 A 400 A
rated insulation voltage Ui (V) 800 800
rated impulse withstand voltage Uimp (kV) 8 8
AC 22A at 400 V (A) 250 400
AC 23A at 400 V (A) 250 400
rated short-circuit breaking capacity (A)
dynamic effect (peak) 11 900 15 300
thermal effect (eff. 1 s) 7 000 9 000
rated short-circuit current (kA) 80 50
with gl - gG fuses 250 A 400 A
mechanical endurance (nr of operations) 10 000 10 000
electrical connection
cage terminal (mm²) 185 -
bolt terminal (Ø mm) M 8 M 8
lugs (mm²) 150 240
Technical characteristics
HA switches
HA964N HA966N
A 201 344
B 162 214
C 85 80
E 140 135
F 145 145
G 72 132
H 130 172
J 36 66
K 18 45
L 20 20
M 268 360
3.115
Main
Inco
mers
Load Break Switches20 to 400A
-
Load Break Switches with Rotary Handle125 to 1600A
Description Characteristics In/A Cat. ref. 3P 4P
Load break switches switches with visible breaking 125A HA351 HA451
with handle
connection: 160A HA352 HA4523P 4P In 160A: 95 mm2 max. In 250A: 150 mm2 max. 200A HA353 HA453 In 400A: 240 mm2 max. ou 2 x 150 mm2 max. 250A HA354 HA454
Insulating voltage Ui: 400A HA357 HA457from 160 to 400A: 800V AC 630A: 1000V AC 630A HA358 HA458
Delivered with: 800A HA360 HA4601 lockable handle,
ixing screws and nuts, 1250A HA362 HA462tightening programming segments
1600A HA364 HA464
HA358
HZC101
Load break switches with rotary handle
Ith (40°): 125 to 1600A
Un 400 / 690V AC
For main and/or modular
breaking, to use in commercial
premises.
Characteristics:
3P and 4P switches with visible
breaking, with sudden double
breaking , positive action
opening, breaking or engage-
ment visualisation, self cleaning
silver plated copper contacts.Options:
• extended handle;• auxiliary contact.
Auxiliaries contacts 1NO + 1NC 125 to HZ023 HZ023
for HA load break switches AC1, 5A, 250V 1600A
Rotary handles for extended shaft
125 to 630A HZC002 HZC002
800 to 1600A HZC003 HZC003
Shaft extensions 63 to 630A, 200mm HZC101 HZC101
160 to 630A, 320mm HZC102 HZC102
800 to 1600A, 200mm HZC105 HZC105
800 to 1600A, 320mm HZC106 HZC106
Terminal shields for switches:top and bottom HA351, HA352 HZ033
HA451, HA452 HZ043
HA354, HA357 HZ034
HA454, HA457 HZ044
HA358 HZ035
HA458 HZ045
HA360 HZ036
HA460 HZ046
HA362, HA364 HZ037
HA462, HA464 HZ047
Terminal shrouds for switches: HA351, HA352 HZC201
HA451, HA452 HZC202
HA354, HA357 HZC203
HA454, HA457 HZC204
HA358 HZC205
HA458 HZC206
Note: Handle and shaft must
be ordered separately.
Fiberglass reinforced polyester
case, self extinguishable, resists to creepage distance and arc,
tropicalised.
Complies with EN 60 947-3.
HZ023
3.116
-
HA351, HA451, HA352, HA452, HA454, HA454, HA357, HA457, HA358, HA458 switches
Mounting Extended rotary handle
Dimensions fo switches from 125A to 630A (rotary handle)
Ref. In(A) A B B1 C D E F G H H1 J K ∅L M N O P R Rr1 S T U V W X Y Z
HA351 125A 140 135 93 120 124/354 65 50 80 50 40 120 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10
HA451 125A 170 135 93 120 124/354 65 50 80 50 40 150 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10
HA352 160A 140 135 93 120 124/354 65 50 80 50 40 120 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10
HA452 160A 170 135 93 120 124/354 65 50 80 50 40 150 65 5,5 15 75 75 36 20 20,5 25 3,5 115 22 20 9 20,5 10
HA354 250A 190 160 108 130 135/365 75 60 115 60 50 160 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15
HA454 250A 230 160 108 130 135/365 75 60 115 60 50 210 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15
HA357 400A 190 170 108 130 135/365 75 60 115 60 50 160 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15
HA457 400A 230 170 108 130 135/365 75 60 115 60 50 210 80 5,5 20 105 105 50 25 25,5 30 3,5 130 33 27 11 22,5 15
HA358 630A 230 260 170 165 167/397 110 89 115 70 75 210 140 7 30 135 135 65 45 45,5 50 5 220 37,5 37,5 13 36 20
HA458 630A 290 260 170 165 167/397 110 89 115 70 75 270 140 7 30 135 135 65 45 45,5 50 5 220 37,5 37,5 13 36 20
Transparent terminal cover
Shaft extension
Direct rotary handle Extended
rotary handle
Terminalshield
IP2 auxiliary contact
Direct rotary handleExtended rotary handle
holes
3.117
Main
Inco
mers
Load break Switches with Rotary Handle125 to 1600A
-
HA360, HA362, HA364, HA460, HA462, HA464 switches with rotary handle
Connection terminals
800A 1250-1600A
Rotary handle
Switches with rotary handle from 800A to 1600A
Ref. In(A) A B C H J N O P R S T V W Y
HA360 800 280 320 214 50 255 127,5 127,5 80 50 60,5 7 47,5 47,5 46,5
HA460 800 360 320 214 50 335 167,5 167,5 80 50 60,5 7 47,5 47,5 46,5
HA362 1250 372 288 215 66,5 347 173,5 173,5 120 90 44 8 53,5 53,5 47,5
HA462 1250 492 288 215 66,5 467 233,5 233,5 120 90 44 8 53,5 53,5 47,5
HA364 1600 372 288 215 66,5 347 173,5 173,5 120 90 44 8 53,5 53,5 47,5
HA464 1600 492 288 215 66,5 467 233,5 233,5 120 90 44 8 53,5 53,5 47,5
terminal shield
min. length with shaft extension: 262 ± 1without shaft extension:212 ± 1
3.118
Load Break Switches with Rotary Handle125 to 1600A