guidance notes on code of practice for water-cooled air conditioning systems

22
7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 1/22  EMSD Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems (November 2011)

Upload: pedrovaladares

Post on 09-Jan-2016

218 views

Category:

Documents


0 download

DESCRIPTION

ACC

TRANSCRIPT

Page 1: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 1/22

 

EMSD

Guidance Notes on Code ofPractice for Water-cooled AirConditioning Systems

(November 2011)

Page 2: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 2/22

Page 3: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 3/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Contents

1  Guidance Notes 1

Part A

1.1 Minimum Horizontal Separation Distance for Cooling Towers 1

1.2 Cooling Tower Installation Location (Pedestrian Thoroughfare) 4

1.3 Cooling Tower Installation Location (Extended Ductwork) 6

1.4 Cooling Tower Installed on Roof and Affecting the Adjacent Buildings 8

1.5 Cooling Tower Installed on Podium Roof 10

1.6 Cooling Tower Installed at Indoor with Vertical Discharge through Roof or

Horizontal Discharge through Side Wall 14Part B

1.7 Control of Bacterial Growth 16

2011 Edition (November 2011)

Page 4: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 4/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Figures

Figure 1: Enquiries on measuring point in determining the minimum separation distance 1

Figure 2: Measuring point shall not be from the center of the cooling tower 2

Figure 3: Measuring point shall be from the nearest edge of the cooling tower exhaust / intake 2

Figure 4: Separation distance shall not be the sum of horizontal and vertical distance 2

Figure 5: Horizontal distance shall be considered separately from the vertical distance 2

Figure 6: Measuring point shall not be the directional distance as the separation distance 3

Figure 7: Measuring point shall be from the nearest edge of the cooling tower exhaust to thefaçade horizontally 3

Figure 8: Separation distance shall not be the sum of horizontal and vertical distance 3

Figure 9: Horizontal distance shall be considered separately from the vertical distance 3

Figure 10: Measuring point shall not be from the centre of the louvre 3

Figure 11: Measuring point shall be from the nearest edge of the exhaust / intake louvre 3Figure 12: Separation between the cooling tower exhaust and pedestrian thoroughfare 4

Figure 13: Provide overhead cover above the walkway 5

Figure 14: Install discharge hood to re-direct the exhaust air away from the walkway 5

Figure 15: Cooling tower installed inside building with extended ductwork for discharge from 

facade louvre 6

Figure 16: Locked window and blank-off louvre on the same facade surface within the restrictedzone 7

Figure 17: Cooling tower installed on roof surrounding by adjacent buildings 8

Figure 18: Horizontal separation requirement for cooling tower and the adjacent buildings 9

Figure 19: Cooling tower installed on podium roof 10

Figure 20: Horizontal separation requirement for cooling tower installation on podium roof 11

Figure 21: Vertical separation requirement between podium roof cooling tower and building’s airintake and operable window below podium roof 12

Figure 22: Vertical separation requirement between podium roof cooling tower and building’sexhaust air outlet below podium roof 12

Figure 23: Horizontal separation requirement between podium roof cooling tower intake and building’s exhaust air outlet on podium roof 13

Figure 24: Horizontal separation requirement between podium roof / roof cooling tower andlouvres on building façade 13

Figure 25: Cooling Tower installed in plant room with vertical discharge through roof andhorizontal intake through side wall 14

Figure 26: Separation requirement between intake lourve / exhaust outlet of indoor cooling towerand the adjacent building air opening 15

Figure 27: Flowchart for Control Strategies for the presence of Legionellae 17

Figure 28: Flow Chart for Control Strategies for the presence of heterotrophic microorganism 18

2011 Edition (November 2011)

Page 5: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 5/22

 

1

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Guidance Notes

Part A1.1 Minimum Horizontal Separation Distance for Cooling Towers

Guidance notes are given below to clarify the following section of Code of Practice for Water –

cooled Air Conditioning Systems (“CoP(WACS)”):

 Section 4.1.3, Part 1 (p.17)

Background:Enquiries on minimum separation distance for cooling tower installation are frequently received,

especially on the measuring points and measurement method. CoP (WACS) users sometimes

misinterpret the measuring points to be from the center of the cooling tower (for horizontaldistance measurement) and/or from the top or bottom of the cooling tower (for vertical distance

measurement). Furthermore, they sometimes mistakenly use the sum of horizontal and vertical

separation distance or directional distance as the separation distance to meet the CoP (WACS)

requirements.

INTAKE LOUVRE

COOLINGTOWER

EXHAUST

COOLINGTOWER

INTAKE

MIN. 7.5m COOLING

TOWERINTAKE

MIN. 7.5m

EXHAUST

AIR INTAKE/EXHAUSTS

ON BUILDING

FACADE

COOLINGTOWER

EXHAUST

MIN. 20m

MIN. 7.5m

AIR INTAKE

COOLING TOWER

EXHAUST

COOLING

TOWER

INTAKE

EXHAUST

LOUVRE

MIN. 7.5mCOOLING TOWER

EXHAUST

COOLINGTOWER

INTAKE

MIN. 7.5m

INTAKELOUVRE

COOLING

TOWER

EXHAUST

AIR INTAKE/EXHAUSTS ON

BUILDINGFACADE

MIN. 7.5m

COOLINGTOWER

EXHAUST

COOLINGTOWER

INTAKE

MIN. 7.5m

COOLINGTOWER

INTAKE

Figure 1: Enquiries on measuring point in determining the minimum separation distance

2011 Edition (November 2011) Page 1

Page 6: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 6/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Guidance Notes:The minimum horizontal separation shall be measured from the nearest edge of   the cooling

tower exhaust / intake to the nearest edge of  the outdoor air intake, exhaust air outlet or operable

window. Also, horizontal distance shall be considered separately from the vertical distance and

they shall not be summed together or used directional distance to meet the minimum separationrequirement. The figures below illustrate some common misinterpretations with respect to the

CoP(WACS) requirement.

INTAKE LOUVRE INTAKE LOUVRECOOLING COOLINGTOWER

EXHAUSTMin. 7.5m for all

Min. 7.5m for alltypes of building

TOWER

EXHAUST

types of building

COOLING COOLINGTOWER TOWER

INTAKE INTAKE

× √ 

Figure 2: Measuring point shall not be fromthe center of the cooling tower

Figure 3: Measuring point shall be from thenearest edge of the cooling tower exhaust /intake

COOLING TOWER

EXHAUST

COOLING TOWER

EXHAUST Min. 7.5m for alltypes of building

COOLINGTOWER

INTAKE

Min. 7.5m for alltypes of building

COOLINGTOWER

INTAKE

EXHAUSTLOUVRE

EXHAUST

LOUVRE

× √ 

Figure 4: Separation distance shall not bethe sum of horizontal and vertical distance

Figure 5: Horizontal distance shall beconsidered separately from the verticaldistance

2011 Edition (November 2011) Page 2

Page 7: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 7/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

COOLINGTOWER

EXHAUST

COOLINGTOWER

INTAKE

AIR INTAKE/EXHAUSTS ONBUILDING

FACADE

× √ 

Min. 7.5m COOLINGTOWER

INTAKE

COOLINGTOWER

EXHAUST

AIR INTAKE/EXHAUSTS ON

BUILDINGFACADE

Figure 6: Measuring point shall not be thedirectional distance as the separation

distance

Figure 7: Measuring point shall be from thenearest edge of the cooling tower exhaust to

the façade horizontally

INTAKE LOUVRE INTAKE LOUVRE

COOLING TOWER

EXHAUSTMin. 7.5m for alltypes of building COOLING TOWER

EXHAUSTMin. 7.5m for alltypes of building

COOLING COOLING

TOWER TOWER

INTAKE INTAKE

× √ 

Figure 8: Separation distance shall not bethe sum of horizontal and vertical distance

Figure 9: Horizontal distance shall beconsidered separately from the verticaldistance

LOCKED LOCKED

WINDOW/BLANKOFF WINDOW/BLANKOFF

LOUVRE LOUVRE

Min. 20mMin. 20m

COOLING TOWERINTAKE LOUVRE INTAKE LOUVRE

EXHAUST

Min. 7.5m Min. 7.5m Min. 7.5m Min. 7.5m

INTAKE LOUVREEXHAUST LOUVRE INTAKE LOUVREEXHAUST LOUVRE

× √ 

Figure 10: Measuring point shall not befrom the centre of the louvre

Figure 11: Measuring point shall be from thenearest edge of the exhaust / intake louvre

2011 Edition (November 2011) Page 3

Page 8: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 8/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

1.2 Cooling Tower Installation Location (Pedestrian Thoroughfare)

Guidance notes are given below to clarify the following section in the CoP(WACS): Section 4.1.4, Part 1 (p.17)

Background:

It is common to propose locating cooling towers on low-rise podium roof of one, two or severalstoreys high building with an adjacent pedestrian thoroughfare or walkway below running alongthe building boundary or façade. The horizontal separation between the cooling tower exhaustand the pedestrian thoroughfare is less than 7.5 m. The designers often enquire the possible waysto meet the CoP (WACS) requirement and minimise nuisances to the public.

< 7.5m for all typesCOOLING TOWER

EXHAUST

COOLINGTOWER

INTAKE

of building

Figure 12: Separation between the cooling tower exhaust and pedestrian thoroughfare

Guidance Notes:It is required under CoP(WACS) that no pedestrian thoroughfare, area of public access, or place

where people gather together for activities shall be located within 7.5m from the nearest edge of

the cooling tower exhaust. If such minimum separation requirement cannot be met due to site

constraints (e.g. not enough space for setting back cooling towers from the parapet/building

 boundary), some mitigation measures may be considered where appropriate to enable

compliance with the requirement, hence minimise nuisances to the public from the cooling tower.

Below are some examples showing mitigation measures proposed for reference.

2011 Edition (November 2011) Page 4

Page 9: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 9/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

COOLING TOWER

EXHAUST

COOLINGTOWER

INTAKE

< 7.5m

Min. 7.5m

OVERHEAD

COVER

Figure 13: Provide overhead cover above the walkway

< 7.5m

Min. 7.5m

COOLING TOWER

DISCHARGE HOOD

COOLING TOWER

INTAKE

Figure 14: Install discharge hood to re-direct the exhaust air away from the walkway

2011 Edition (November 2011) Page 5

Page 10: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 10/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

1.3 Cooling Tower Installation Location (Extended Ductwork)

Guidance notes are given below to clarify the following section in CoP(WACS):

 Section 4.1.6, Part 1 (p.17)

Background:Some project designers found it is unclear in meeting the minimum separation requirements

when cooling towers are designed to be installed inside a mechanical floor with extended

ductwork to discharge through facade louvres. They find it difficult to arrange the air intake,

exhaust air outlet and operable window on its vertical building façade distant from the cooling

tower to meet the requirements.

COOLING TOWER PLANT ROOM

COOLING TOWER

EXHAUST

COOLING TOWER

INTAKE

FAÇADE WITHWINDOW AND/OR

LOUVRE

Figure 15: Cooling tower installed inside building with extended ductwork for discharge fromfacade louvre

2011 Edition (November 2011) Page 6

Page 11: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 11/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Guidance Notes:If a cooling tower is installed indoor with an extended ductwork for exhaust air, the measurement

shall be from the nearest edge  of the exhaust louvre on the building façade. Air intakes,

exhausts air outlet and operable windows of the vertical building facade shall be distant from the

nearest edge of the cooling tower exhaust by minimum distance of 7.5 m below and/or 20 mabove, as the case may be.

If the requirement cannot be adequately met, the designer may consider in consultation with their

 building design counterpart and/or the facility management whether mechanical locking devices

can be provided to the operable windows and the louvres can be blanked off to comply with

CoP(WCAS) under normal conditions. Cautionary signage shall be provided near the locked

windows to alert occupants.

LOCKED

WINDOW/BLANKOFFLOUVRE

< 20m for all types ofbuildin

COOLING TOWER COOLING TOWERINTAKE EXHAUST

< 7.5m< 7.5m

IF EXHAUST LOUVRE, LOCKED NEED TO BE BLANK WINDOW/BLANKOFF

OFF (EXHAUST) LOUVRE (INTAKE)

Figure 16: Locked window and blank-off louvre on the same facade surface within the restrictedzone

2011 Edition (November 2011) Page 7

Page 12: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 12/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

1.4 Cooling Tower Installed on Roof and Affecting the Adjacent Buildings

Guidance notes are given below to clarify the following section in the CoP(WACS):

 Section 4.2, Part 1

Background:Some project designers found themselves unclear on how to meet the minimum separation

requirement between the cooling tower and the air intake, exhaust air outlet and operable

window on the adjacent building façades. The measuring points are often incorrect and result in

the cross-contaminations between the cooling tower and the adjacent buildings.

EXHAUST LOUVRE

EXHAUST LOUVRE

COOLING TOWEREXHAUST

COOLINGTOWER

INTAKE

Figure 17: Cooling tower installed on roof surrounding by adjacent buildings

2011 Edition (November 2011) Page 8

Page 13: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 13/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Guidance Notes:

In order to minimise nuisance caused by the cooling tower to the adjacent buildings and vice-versa the nuisance caused by the adjacent buildings to the cooling tower; the minimumhorizontal separation distance shall be imposed. The measurement point shall be from thenearest edge of the cooling tower intakes /exhausts to the nearest edge of air intake and operablewindows of the adjacent buildings.

EXHAUST LOUVRE

EXHAUST LOUVRE

Min. 7.5mMin. 7.5m

COOLINGTOWER

EXHAUST

COOLING TOWERINTAKE

Figure 18: Horizontal separation requirement for cooling tower and the adjacent buildings

2011 Edition (November 2011) Page 9

Page 14: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 14/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

1.5 Cooling Tower Installed on Podium Roof

Guidance notes are given below to clarify the following section in the CoP(WACS):

 Section 4.3, Part 1

Background:

In a composite building, it is common to have building blocks located on the podium roof.

Project designers may wish to install cooling towers on the podium roof to provide air-

conditioning for the commercial floors. If the cooling towers are located too close to the

surrounding building blocks, contaminants from the cooling tower, as well as generated noise,

may affect the building users through the air openings (air intakes/exhausts/operable windows)

on the building blocks.

Whist the CoP(WACS) has generally specified a horizontal separation distance of minimum 7.5m from the cooling tower to the nearby air outlets/windows, some cases have raised issues insituations where the air outlets/windows are far above the cooling tower but with a horizontalseparation distance less than 7.5 m. How will the separation distance requirement apply to thesecases?

COOLING TOWEREXHAUST

COOLING TOWERINTAKE

AIRINTAKE/EXHAUSTS

ON BUILDING

FACADE

FAÇADE WITHWINDOW AND/OR

LOUVRE

Figure 19: Cooling tower installed on podium roof

Guidance Notes:

Scenario 1: Separation distance between the cooling tower exhaust and the building’s air

openings (air intake, exhaust air outlet and operable window) above podium roof.

Cooling towers on the podium roof shall generally be located away from the building façade to

meet the minimum horizontal separation distances specified in Table 1.1 of Part 1 of the

CoP(WACS). In particular, the cooling tower exhaust should be away from air intake, exhaust

air outlet and operable windows with a minimum horizontal distance of 7.5 m to avoid potentialrisk of nuisance or spread of Legionella bacteria (if any) arising from the cooling towers. For

2011 Edition (November 2011) Page 10

Page 15: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 15/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

cooling tower on the podium roof with adjacent tall building, all cases with horizontal separation

less than 7.5 m will not be considered acceptable.

Please note that clause 4.3.3 of Part 1 of the CoP(WACS) requires the cooling tower exhaust

shall be discharged away from the operable windows and outdoor air intakes. This can beachieved by a cooling tower discharge hood to direct the exhaust away from the building façade.

COOLING TOWER

DISCHARGE HOOD

COOLING TOWERINTAKE

AIRINTAKE/EXHAUSTSON BUILDING

FACADE

Min 7.5m

Figure 20: Horizontal separation requirement for cooling tower installation on podium roof

Scenario 2: Separation distance between the cooling tower intake/exhaust and the building’s air

openings (air intake, exhaust air outlet and operable window) below podium roof.

Cooling towers on the podium roof should generally be set back from the building parapet with a

minimum horizontal separation distance of 7.5 m to avoid potential risk of nuisance or spread of

Legionella bacteria (if any) arising from the cooling towers to air openings (air intake, exhaust

air outlet and operable window)

In cases where the cooling tower cannot meet the minimum horizontal separation requirement(i.e. separation is less than 7.5 m), designers may consider alternative location. That location

shall have adequate vertical separation distance for the building’s air openings in relation to the

cooling tower. Such distances are shown below (similar to the minimum separation distances in

Table 1.1 in Section 4.1 of CoP (WACS) Part 1):

(a) Between the nearest edge  of cooling tower exhaust and the nearest edge  of podium’s air

intake, exhaust air outlet and operable window: minimum vertical separation of 7.5 m ;

(b) Between the nearest edge  of cooling tower intake and the nearest edge of podium’s air

exhaust outlet: minimum vertical separation of 7.5 m and

2011 Edition (November 2011) Page 11

Page 16: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 16/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

(c) Between the nearest edge  of cooling tower intake and the nearest edge  of podium’s air

intake and operable window: minimum vertical separation of 5 m.

COOLING TOWEREXHAUST

COOLINGTOWER

INTAKE

AIR INTAKE / OPERABLEWINDOW ON BUILDING

FACADE

Min. 7.5m

Min. 5m

< 7.5m

Figure 21: Vertical separation requirement between podium roof cooling tower andbuilding’s air intake and operable window below podium roof

COOLING TOWEREXHAUST

COOLING TOWERINTAKE

EXHAUST AIR OUTLETON BUILDING FACADE

< 7.5m

Min. 7.5m

Figure 22: Vertical separation requirement between podium roof cooling tower andbuilding’s exhaust air outlet below podium roof

2011 Edition (November 2011) Page 12

Page 17: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 17/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

COOLING TOWEREXHAUST

COOLING TOWERINTAKE

EXHAUST AIR OUTLET ONBUILDING FACADE

Min. 7.5m

Figure 23: Horizontal separation requirement between podium roof cooling tower intakeand building’s exhaust air outlet on podium roof

PODIUM ROOF/ ROOF

WINDOW OPENNINGS

Min. 7.5m Min. 7.5m

WINDOW OPENNINGS

LOCKEDWINDOW/BLANK-

OFF LOUVRE

< 7.5m

Min. 7.5m

WINDOW OPENNINGS

LOCKEDWINDOW/BLANK-OFFLOUVRE

Min. 7.5m

WINDOW OPENNINGS

Figure 24: Horizontal separation requirement between podium roof / roof cooling tower andlouvres on building façade

2011 Edition (November 2011) Page 13

Page 18: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 18/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

1.6 Cooling Tower Installed at Indoor with Vertical Discharge through Roof orHorizontal Discharge through Side Wall

Guidance notes are given below to clarify the following section in the CoP(WACS):

 Section 4.4, Part 1

Background:For some high-rise buildings, cooling towers may be housed in a plant room with

discharge/intake through the roof/side walls of the plant room. The discharge and/or intake may

affect or be affected by adjacent buildings if they are not correctly located.

AIR INTAKELOUVRE/OPERABLE

WINDOW

FRESH AIRINTAKE FORCOOLING TOWER

EXHAUST AIRLOUVRE

COOLING TOWERPLANT ROOM

Figure 25: Cooling Tower installed in plant room with vertical discharge through roof andhorizontal intake through side wall

2011 Edition (November 2011) Page 14

Page 19: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 19/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Guidance Notes:In cases where the plant room houses the cooling tower, the horizontal distance between the

 plant room structure/edge and the nearby building’s air opening (air intake, exhaust air outlet and

operable window) is allowed to be less than 7.5 m. However, the exhaust air outlet of the cooling

tower shall have a horizontal separation distance of 7.5 m to the air opening of the adjacent building regardless the position of the plant room. Furthermore, the plant room air intake for the

cooling tower intake shall have a horizontal separation distance of 7.5 m to the exhausts outlet of

the adjacent buildings. The plant room air intake for the cooling tower shall have a horizontal

separation distance of 5 m from air intake and operable window of adjacent buildings.

The measurement point shall be from the nearest edge  of the cooling tower exhaust to the

nearest edge of  the air intake, exhaust air outlet and operable window of adjacent buildings.

AIR INTAKELOUVRE/OPERABLE

WINDOW

Min. 7.5m

FRESH AIRINTAKE FOR

COOLING

TOWER

Min. 5m Min. 7.5mEXHAUST AIR

LOUVRE

COOLING TOWER

PLANT ROOM

Figure 26: Separation requirement between intake lourve / exhaust outlet of indoorcooling tower and the adjacent building air opening

2011 Edition (November 2011) Page 15

Page 20: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 20/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Part B

1.7 Control of Bacterial Growth

Guidance notes are given below to illustrate the following section in the CoP(WACS):

 Section 2.6, Part 2 (p.7)

2011 Edition (November 2011) Page 16

Page 21: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 21/22

 

Implement corrective action

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Guidance Notes:

Control Measures for Legionella

Regarding detection of Legionella in water samples collected from cooling towers, the control

strategies and procedures stated in Section 2.6.1 of Part 2, CoP (WACS). The flow chart below(Figure 27) illustrate the flow chart of Part 2, CoP(WACS) for easy reference.

Water samples collected from

cooling towers and test

Review programmeSystem under control

(a) Maintainquarterly monitoring

(b) Maintain water

treatment programme

 (a) Investigate problem (b) Review water treatment programme

(c) Take necessary remedial action including

immediate on-line disinfection as described in section3.3 and undertake control strategy (3).

Legionella count

Collect and test a water sample within 3 to 7 days

after on-line disinfection

If not detected If detected at

≥10 and< 

100 cfu/mL

If detected at

≥100 and< 

1000 cfu/mL

 Not detected(<10 cfu/mL)

Detected at≥10 and<1,000 cfu/mL

Detected at≥1,000 cfu/mL

If detected at

≥1000 cfu/mL

Strategy (1) Strategy (2)

Strategy (3)

(a) Investigate problem(b) Review water treatment programme

 (c) Take necessary remedial action includingimmediate emergency decontamination as described

in section 3.6 and undertake control strategy (5).

Collect and test a water sample within 3 days after

emergency decontamination

Strategy (4)

Strategy (5)

If not detected If detected at

≥10 and< 

100 cfu/mL

If detected at

≥100 and< 

1000 cfu/mL

Repeat

controlstrategy (2)

Investigate problem andreview water

Collect and test

another watersample.

Collect and testanother water

sample.

If 2 consecutivesamples have no

Legionelladetected,

repeat controlstrategy (1)

Repeatcontrol

strategy (2)

Investigate

 problem andreview water

treatment programme,immediately

carry out

cleaning anddisinfectionagain as

described insection 3.4 and

repeat control

strategy (3)

Immediatelycarry out

cleaning and

disinfection asdescribed in

section 3.4 andundertakecontrol

strategy (5)If 2 consecutivesamples have no

Legionelladetected,repeat control

strategy (1)

If detected at

≥1000 cfu/mL

Investigate

 problem andreview water

treatment

 programme,immediately

carry out system

emergencydecontaminationas described in

section 3.6 andrepeat control

strategy (5)

treatment programme,

immediately

carry outcleaning and

disinfectionagain asdescribed in

section 3.4 and

repeat controlstrategy (5)

Figure 27: Flowchart for Control Strategies for the presence of Legionellae

2011 Edition (November 2011) Page 17

Page 22: Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

7/17/2019 Guidance Notes on Code of Practice for Water-cooled Air Conditioning Systems

http://slidepdf.com/reader/full/guidance-notes-on-code-of-practice-for-water-cooled-air-conditioning-systems 22/22

 

Electrical & Mechanical Services Department Guidance Notes on Code of Practice forWater-cooled Air conditioning Systems

Control Measures for Heterotrophic Micro-organisms

Regarding the Heterotrophic Colony Count (HCC) test results of water samples collected fromcooling towers, the control strategies and procedures stated in Section 2.6.3 of the CoP (WACS),

Part 2 are illustrated in the flow chart below (Figure 28) for easy reference and observation.

Water samples collected fromcooling towers and test

Review Programme operationSystem under control

(a)Maintainmonthly

monitoring(b) Maintain watertreatment

 programme

 (a) Investigate problem(b) Review water treatment programme

(c) Take necessary remedial action includingimmediate on-line disinfection as described insection 3.3 and undertake control strategy (3).

Heterotrophic Colony Count (HCC)

Implement corrective action

(a) Investigate problem(b) Review water treatment programme(c) Take necessary remedial action including

immediate emergency decontamination asdescribed in section 3.6 and undertake control

strategy (5).

Collect and test a water sample within 3 to 7 days after

on-line disinfection

If test result is<100,000 cfu/mL

If test result is

≥100,000 and< 

5,000,000 cfu/mL

If test result is≥5,000,000

cfu/mL

Detected at

<100,000 cuf/ml

Detected at

≥100,000 and<5,000,000 cfu/mLDetected at

≥5,000,000 cfu/mL

If test result is<100,000 cfu/mL

If test result is

≥100,000 and< 

5,000,000 cfu/mL

If test result is≥5,000,000

cfu/mL

Collect and test a water sample within 3 to 7 daysafter emergency decontamination

Strategy (1) Strategy (2) Strategy (4)

Strategy (3) Strategy (5)

Repeat control Immediately Immediately Repeat control Immediately Investigatestrategy (1) carry out carry out strategy (1) carry out problem and

cleaning and cleaning and cleaning and review waterdisinfection disinfection as disinfection treatmentagain as described in again as programme,described in section 3.4 and described in immediatelysection 3.4 and undertake section 3.4 and carry outundertake control undertake emergencycontrol strategy (5) control decontaminationstrategy (2) strategy (4) again as

described in

section 3.6 andrepeat control

strategy (5)

Figure 28: Flow Chart for Control Strategies for the presence of heterotrophic microorganism

2011 Edition (November 2011) Page 18