New Product Available June 2005.The new ‘D range’ of digital intelligent detectors are setting the standards in
technology, innovation and design. The D range is not only incorporating
the latest in digital fire detection technology, but with the low profile sleek
design, caters for the aesthetic requirements demanded by Architects for
today’s prestigious projects.
D-9101
Digital Intelligent
Multi Sensor Smoke Detector
D-9103
Digital Intelligent
Heat Detector
D-9102
Digital Intelligent
Optical Smoke Detector
1
Part Number Part Number
Intelligent Optical Smoke Detector¡ñ Aesthetically pleasing low profile design¡ñ 8 Bit intelligent processor with A/D converter¡ñ Built in algorithm maps for false alarm rejection¡ñ Electronically addressed¡ñ Twin LED’s for 360 degree vision¡ñ Sensitivity adjustable via hand held programming tool¡ñ Removable optical chamber for easy cleaning and maintenance¡ñ Conventional detector version part number C-9102
Intelligent Optical Smoke Detector with Remote
Indicator Output¡ñ Optical detector as above with remote indicator output,¡ñ Intelligent detector part number: I-9102R¡ñ Conventional detector part number: C-9102R
I-9102
Intelligent Dual Heat Detector¡ñ Fixed Temperature and Rate of Rise Detection¡ñ Aesthetically pleasing low profile design¡ñ 8 Bit intelligent processor with A/D converter¡ñ Electronically addressed¡ñ Fixed Temperature response is adjustable via hand held programming tool
between 54°C and 80°C¡ñ Twin LED’s for 360 degree vision¡ñ Conventional detector version part number C-9103
Intelligent Dual Heat Detector with Remote Indicator Output¡ñ Dual Heat detector as above with remote indicator output,¡ñ Intelligent detector part number: I-9103R¡ñ Conventional detector part number: C-9103R
I-9103
Intelligent Ultraviolet Flame Detector¡ñ Sensitive Ultraviolet sensor that detects the UV rays produced by a flame¡ñ Not effected by sunlight.¡ñ Aesthetically pleasing Low profile design¡ñ Dust / corrosion / humidity resistant.¡ñ Electronically addressed¡ñ Standard calibration set to detect a 3cm flame at 6 metres.¡ñ Effective range 12 metres¡ñ Conventional detector version also available (C-9104)
Technical Specifications¡ñ Operating voltage: Loop 24V¡ñ Operating current:
Standby current: 1.5mA
Alarm current 10mA¡ñ Operating environment:
Temperature:- 10 ~+ 50°C
Relative humidity: 95%¡ñ Detection Angle: 80 Degree
¡ñ Dimensions: Diameter: 10cm Height: 5cm
I-9104
2 3
I-9102R
4 Wire Optical Detector -Relay output (normally
open contacts)
Technical Specifications¡ñ Operating voltage: Loop 24V¡ñ Operating current:
Standby current: 0.6mA
Alarm current 2mA¡ñ Operating environment:
Temperature: - 10 ~+ 50°C
Relative humidity: 95%¡ñ Dimensions: Diameter: 10cm Height: 5cm
I-9103R
4 Wire Heat Detector -Relay output (normally open contacts)
Technical Specifications¡ñ Operating voltage: Loop 24V¡ñ Operating current:
Standby current: 0.8mA
Alarm current 1.4mA¡ñ Operating environment:
Temperature:- 10 ~+ 50°C
Relative humidity: 95%¡ñ Dimensions: Diameter: 10cm Height: 5cm
Intelligent Multi Sensor¡ñ Combining all the features of the I-9102 Optical and the I-9103 Dual Heat
Detector to provide the ultimate cover for life safety systems.¡ñ Ideal alternative to Ionisation detectors.¡ñ Conventional detector version part number C-9101
Technical Specifications¡ñ Operating voltage: Loop 24V¡ñ Operating current:
Standby current: 0.8mA
Alarm current 2mA¡ñ Operating environment:
Temperature:- 10 ~+ 50°C
Relative humidity: 95% ¡ñ Dimensions: Diameter: 10cm Height: 5cm
I-9101
Standard Detector Base¡ñ Non polarized terminals and multi-positioning design allows easy direction
adjustment of the addressable detectors.¡ñCompatible with GST conventional detectors using 4K7 Ohm resistor end of
line.(EOL)¡ñ Common base for GST I-9101/2/3/4 and C-9101/2/3/4
Diode Conventional Base¡ñ Diode base version for conventional detectors utilizing the Active End Of
Line(AEOL) (P-9907)¡ñ Compatible base for GST C-9101/2/3/4
DZ-03
DZ-03D
R6602
R6601
Part Number Part Number
4 5
Intelligent Linear Beam Detector¡ñ Suitable for detection coverage of Atriums and Warehouses, Factories,
Tunnels.¡ñ Detection range 10 to 100 metres.¡ñ Alignment indication LED’s and adjustable pivot base for easy beam
alignment¡ñ Reduced installation costs due to intelligent addressable control (no
requirement for local control interfacing and reset)¡ñ Electronically addressed¡ñ Conventional detector (C-9105)
Technical Specifications¡ñ Operating voltage: Loop 24V¡ñ Operating current:
Standby current: 1mA
Alarm current: 2.5mA¡ñ Detection Range: Length from 10 to 100 meters,¡ñ Wiring: Non-polarized two-core 24VDC for emitter
Non-polarized two-core loop for receiver¡ñ Operating environment:
Temperature: -10 ~+ 50°C
Relative humidity: 92%¡ñ Conventional version (C-9105) provides Volt Free N/O fire
contact output
I-9105
Intelligent Reflective Beam Detector¡ñ Range 10-100 Metres,¡ñ 3 selectable levels of sensitivity adjustment.¡ñ Ideal for Atriums, Warehouses, Shopping Centres, Airport Terminals etc.¡ñ Simple and cost effective to install transmitter and reflective ’honey
comb’ mirror¡ñ Quick and easy to set up with the visual signal strength indication, simply
adjust until angle and the Green LED will flash faster or slower
depending on the signal strength, simply adjust until the green LED is
fully lit, replace the cover and the detector will self calibrate to the
desired level.¡ñConvention version(C-9105R) fitted with volt free contacts for fire and fault
conditions.
Technical Specifications¡ñ Operating voltage: Loop 24V¡ñ Operating current:
Standby current: 12mA
Alarm current: 22mA¡ñ Detection Range: Length from 10 to 100 meters,¡ñ Wiring: Non-polarized two-core 24VDC
Non-polarized two-core detection loop¡ñ Operating environment:
Temperature: -10 ~+ 50°C
Relative humidity: 92%
I-9105R
Intelligent Linear Cable Heat Detector¡ñ Fixed temperature linear cable heat detector.¡ñ Typically used to detect overheat in high power cable trays.¡ñ Configurable with single or dual detection cable¡ñ Each detection cable up to 500 meters cable length¡ñ Alarm condition shows cable distance location on fire panel¡ñ Test button on the End of Line Unit.¡ñ Electronically addressed.
Technical Specifications¡ñ Operation Voltage: Loop 24V¡ñ Operation Current:
Monitoring Current: 3mA
Alarm Current: 5mA¡ñAlarm temperature: optional 70°C or 105°C (specified by cable type).¡ñ Operating environment:
Temperature: -10 ~+ 50°C
Relative humidity: 95%¡ñ Dimensions: Interface 162mm x 200mm x 80mm
End of Line Unit 120mm x 80mm x 40mm
I-9106
Battery Optical Smoke Detector¡ñ Self contained Optical Smoke Detector and alarm sounder¡ñ Easy installation¡ñ Test/Reset Button¡ñ Low Battery indication¡ñ Battery Removal will inhibit cover from closing (as per UL standards)¡ñ Connection port to link up to 30 detectors in a single network¡ñ Output to interface with other security equipment.
Technical Specifications¡ñ Power Supply: PP3 DC9V battery, lasting 1+ year¡ñ Alarm Sound Level:>80dB¡ñ Operation Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimensions: 140mm x 54mm(D x H, with base)
S-9102
GST Duct Probe¡ñ Duct probe housing for detection of smoke by sampling moving air inside the
duct.¡ñ Easy maintenance as detector is mounted externally to the duct.¡ñ Pre-wired detector base¡ñ Lid removal raises fault indication at panel.¡ñ Sampling pipes 250mm to 800mm in length, (can be cut to size).¡ñ Compatible with GST addressable and conventional detectors.
DP9100
Part Number Part Number
6 7
Addressable Manual Call Point¡ñ Addressable Manual Call Point (MCP) with re-settable (non breaking) glass¡ñ Additional volt free contacts for local interfacing (i.e. PTZ camera preset)¡ñ Two part plug-in construction with base mounted termination allows for easy
installation and connection.¡ñ MCP can be addressed and plugged in to base at time of commissioning.¡ñ Electronically addressed¡ñ Suitable for semi-flush and surface mount installation¡ñ Conventional MCP version with 470 Ohm alarm contacts part number C-9201
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Operating Current:
Monitoring Current: 0.8mA
Alarm Current: 2mA¡ñ N/O Output Contact: Rating Value 60VDC, 0.1A¡ñ Contact Resistance 100mÙ¡ñ Electronically addressed
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimensions: 90mm x 122mm x 48.5mm
I-9201
Addressable Manual Call Point¡ñ Compatible with latest EN standards.¡ñ Non-breaking re-settable glass (via special key).¡ñTwo part plug-in construction with base mounted termination allows easy
installation and connection.¡ñ Conventional MCP version with 470 Ohm Alarm contacts part number
C-9202
Available from December 2004.
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Operating Current:
Monitoring Current: 0.8mA
Alarm Current: 2mA¡ñ N/O output contact: Rating 100mA/30VDC¡ñ Contact Resistance 100mÙ¡ñ Operating environment:
Temperature: -10 ~+ 50°C
Relative humidity: 95%¡ñ Dimensions: 95mm x 98mm x 40mm
I-9202
Semi Flush mount back box for I-9201 / C-9201 manual call points B-9201
Addressable Combustible Gas Detector¡ñ Available for LPG, Natural Gas and Coal Gas. (Please specify at time of
order)¡ñ Built-in relay contacts for control of Gas Valves / Extract etc¡ñ Built-in sounder with 2 stage alarm¡ñ Manual reset and control (on/off) of relay contacts¡ñ Electronically addressed¡ñ Standalone detector version with Relay contacts for interfacing with
conventional fire panels or security systems part number (C-9602LW)
Technical Specifications¡ñ Operating voltage: Loop 24V¡ñ Operating Consumption: 1.5Watt¡ñ Alarm Level: Pre-alarm 12%LEL
Urgent Alarm: 23%LEL¡ñOutput: K1/K2, N/O contact, 3A/220VAC, active when pre-alarm
V1/V2, active output 3A/5VDC, start when full alarm¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Wiring:
Addressable I-9602LW Non-polarized two-core for loop
Non-polarized two-core for 24VDC power supply (I-
9602LW only)¡ñ Conventional version (C-9602LW) requires 220 VAC
I-9602LW
Handheld Programmer¡ñ Portable programming tool for addressing and testing of intelligent devices¡ñ Programs all loop devices (1-242 addresses per loop)¡ñ Interrogates device for Condition - Manufacturing Batch Number - Date of
manufacture - alarm sensitivity¡ñ Reprogram facility enables adjustment to alarm threshold of detectors.¡ñ Able to switch on or off the rate of rise function of dual heat detector. (I-9103).¡ñ Adjusts input modules to accept N/C or N/O contacts.
P-9910
Part Number Part Number
8 9
Short Circuit Isolator¡ñ Isolates faulty part of the loop in the event of a short circuit¡ñ Automatically resetting once the fault has cleared¡ñ LED status indicator
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Action Current: 2A¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimensions: 120mm x 80mm x 40mm
C-9503
Base Mount Short Circuit Isolator¡ñ Replaces standard detector base (DZ-03)¡ñ Cost effective installation without the need for additional cabling.¡ñ Features as per C-9503.¡ñ Base Type: Diameter: 105mm, Height: 20mm
C-9504
Intelligent Remote Indicator¡ñ Can be program linked to any single or group of devices¡ñ High intensity flashing LED in alarm condition¡ñ Electronically addressed
Technical Specifications¡ñ Operating Voltage: Loop24V¡ñ Operating Current:
Monitoring Current: 0.8mA
Action Current: 16mA¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimensions: 120mm x 80mm x 49mm
I-9314
Powered Remote Indicator¡ñ Conventional Alarm Indicator with local sounder¡ñ Connects to 12 or 24VDC supply.¡ñ Dimensions: 120mm x 80mm x 49mm
C-9314
Remote indicator¡ñRemote indicator for direct connection to detector remote indicator terminals¡ñ Compatible with:
Addressable: I-9102R Optical Detector and I-9103R Dual Heat
Detector.
Conventional: C-9102R Optical Detector and C-9103R Heat
Detector.
C-9314P
Part Number Part Number
10 11
Addressable Sounder and Strobe¡ñTwo parts construction with base mounted termination allows easy installation¡ñ Evacuate only or Alert/Evacuate mode can be set through handheld
programmer.¡ñ Remote start input can be used to co-operation with other systems.¡ñ Strobe provided by high intensity LED cluster¡ñ Electronically addressed.¡ñ Compatible sound with sounder base (I-9402 / C-9402)¡ñ Conventional Sounder and Strobe version part number C-9403.
Technical Specifications¡ñ Operation Voltage: Loop 24V¡ñ Operating Current:
24VDC: Standby Current 3mA, Alarm Current 65mA
Loop: Standby Current 1mA, Alarm Current: 5mA¡ñ Sounder Output 85dB(Alert) and 94dB (Evacuate)¡ñ Wiring:
Non-polarized two-core for loop
Non-polarized two-core for power supply¡ñ Operating environment:
Temperature: -10 ~+ 50°C
Relative humidity: 95%¡ñ Dimension: Diameter 110mm, Height 97.5mm
I-9403
Addressable Sounder¡ñIdentical in appearance and features to the I-9403 but without the strobe
element.¡ñ Alarm Current 35mA
I-9404
Intelligent Sounder Driver¡ñ Cost effective (cable saving) distributed addressable control of conventional
sounder circuits.¡ñ Connects to conventional polarised 24VDC sounders/strobes¡ñ Utilizes two addresses (one for Alert and one for Evacuate Control).¡ñ Two part plug-in construction with base mounted termination allows easy
installation and connection.¡ñ Electronically Addressed
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Operating Current:
Standby Current 1mA
Output: Maximum 1A, polarized¡ñ End of line: 10k ¦¸ .resistor,¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimensions: 120mm x 80mm x 40mm
I-9308
Addressable Sounder Base¡ñ Loop Powered Sounder.¡ñ Can be used as a common base of detector or stand alone with a
cover.¡ñ Two addresses (one for Alert and one for Evacuate tones).¡ñ Conventional version (C-9402) connects directly to sounder circuit.¡ñ Compatible sound with I-9403 / C-9403 Sounder Flasher and I-9404 /
C-9404 Sounder.
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Operating Current:
Standby Current 1mA
Action Current: 7mA¡ñ Sound Output (SPL): 89dB @1 Metre¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimension: Diameter: 10cm Height: 3.5cm (without cover),
4.5cm (with cover)¡ñ C-9402 requires polarized 24VDC supply
I-9402
Addressable Sounder Beacon¡ñ Addressable combined flashing high intensity LED beacon and sounder¡ñ Two part plug-in construction with base mounted termination allowing easy
installation and connection¡ñ Electronically addressed¡ñ Conventional version part number C-9401.
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Operating Current:
24VDC: Standby Current: 10mA; Alarm Current: 160mA;
Loop: Standby Current: 0.8mA; Alarm Current: 6.0mA;¡ñ Alarm volume (SPL): 95dB @1 Meter.¡ñ Wiring:
Non-polarized two-core for loop
Non-polarized two-core for 24VDC power supply¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimension: 144mm x 90mm x 57mm¡ñ C-9401 only needs to connect to normal 24V DC sounder circuit
I-9401
Part Number Part Number
Intelligent Single Input /Output Module¡ñ Addressable I/O with 24V /3Amp relay output contacts¡ñ Input can be configured as NO / NC or self confirmation of output
(programmable via handheld programmer (P9910)¡ñ Two part plug-in construction with base mounted termination allows easy
installation and connection¡ñ Intelligent interface can be addressed and plugged in to base at time of
commissioning¡ñ Electronically addressed¡ñ For surface mount cable installations use surface mount interface back box
(SMIBB-1)
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Operating Current:
Standby Current 1mA
Action Current: 5mA¡ñ Wiring:
Non-polarized two-core for loop
Non-polarized two-core for 24VDC power supply¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimension: 120 x mm 80mm x 40mm
I-9301
Intelligent Double I/O¡ñ All the features of the I-9301 but with 2 independent inputs and outputs¡ñ Inputs can be individually selectable as NO /NC/ self-confirming.
I-9303
Addressable Input Module¡ñ Monitors switch contacts of remote equipment¡ñ Loop powered.¡ñ Inputs programmable for NO or NC contacts (Programmable via P9910
hand held programmer)¡ñ Two part plug-in construction with base mounted termination allows easy
installation and connection¡ñ Intelligent interface can be addressed and plugged in to base at time of
commissioning.¡ñ Electronically addressed¡ñ For surface mount cable installations use surface mount interface back
box (SMIBB-1)
Technical Specifications¡ñ Operating Voltage: Loop 24V¡ñ Operating Current:
Standby Current 1mA
Action Current: 5mA¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimension: 120mm x 80mm x 40mm
I-9300
Addressable Zone Monitor Unit¡ñ Interfaces with conventional fire detection equipment/panels etc¡ñ Can connect up to 15 detectors with Active EOL or up to 25 detectors
with Resistor EOL¡ñ Ideal for integrating Sprinkler Zone Valve and Flow Switches¡ñ Electronically addressed.
Technical Specifications¡ñ Operating Voltage: Loop 24V (24VDC needed for interfacing
conventional detectors)¡ñ Operating Current:
Monitoring Current 0.5mA
Action Current: 5mA¡ñ Capability: 15 conventional detectors¡ñ End of line: 4.7k ¦ ̧ resistor or AEOL¡ñ Active Resistance: 470~680 ¦¸
¡ñ Operating Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimension: 120mm x 80mm x 40mm
I-9319
12 13
Part Number Part Number
Addressable Mini Fire Panel¡ñ Single loop panel¡ñ Can connect up to 128 addressable devises¡ñ 8 zone with manual intervention and control¡ñ Self configurable via panel keyboard¡ñ Easy commissioning making the GST100 an ideal product for electrical
installers
Technical Specifications¡ñ Power supply: 220VAC 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension: 210mm x 297mm x 90mm
GST100
LCD Passive Repeater Panel¡ñ Aesthetically pleasing design with large LCD display¡ñ Compatible with all GST intelligent fire alarm panels¡ñ Back Lit LCD displays all fire information.¡ñ Local sounder mute and scroll alarms buttons.¡ñTwo part plug-in construction with base mounted termination allows easy
installation and connection¡ñ Repeater can be plugged in to base at time of commissioning
Technology Specifications¡ñ Operation Voltage: 24VDC¡ñ Standby Power: 2W¡ñ Max. Power: 5W¡ñ Operation Environment:
Temperature: -10 ~+ 50°C
Relative Humidity: 95%¡ñ Dimension: 234mm x 104mm x 35mm
GST852RP
14 15
Intelligent Single Loop Fire Alarm PanelSingle loop addressable fire detection panel packed with features not
usually associated with smaller systems, providing a high quality solution
at exceptionally good value.¡ñ Loop capacity 235 intelligent devices¡ñ Graphical LCD Display¡ñ 30 Zone indication and manual intervention panel¡ñ Net-workable with all GST fire panels¡ñ Programmable from PC¡ñ Built-in Gas Extinguishing Control¡ñ Integrated Security Alarm Facilities¡ñ Optional Colour Graphics¡ñ Optional Fireman’s Control Panel¡ñ Optional Panel Printer¡ñ Advanced user friendly programming software including ‘Fuzzy Logic’
Technical Specifications¡ñ Power supply: 220 VAC 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension: 400mm x 560mm x 178mm
GST200
Graphical User Interface¡ñ Colour graphic control and display system, providing a complete window
onto the fire detection systems and ancillary equipment.¡ñ Compatible with all GST intelligent fire panels¡ñ Multi-level password control for convenient system management.
LCD Repeater Panel¡ñ AS per GST852RP with additional keys for Silence and Reset of
the fire panel
GST852RPX
GUI
Intelligent Two / Four Loop Fire Alarm Control PanelAddressable fire detection with integrated controls providing the perfect solution
for all medium sized projects¡ñ Loop capacity 242 intelligent devices.¡ñ Large Graphical LCD Display.¡ñ 60 Zone indication and manual intervention panel¡ñ Net-workable with all GST fire panels¡ñ Programmable form PC¡ñ Built-in Gas Extinguishing Control.¡ñ Integrated Security Alarm Facilities¡ñ Optional Fireman’s Control Panel¡ñ Panel Printer¡ñ Optional Colour Graphics¡ñ Advanced user friendly programming software including ‘Fuzzy Logic’.¡ñ GST500/2 Two loop panel can connect up to 480 devices.¡ñ GST500/4 Four loop panel can connect up to 700 devices.
Technical Specifications¡ñ Power supply: 220V AC 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension: 500mm x 700mm x 170mm
GST500/2/4
Part Number Part Number
16 17
Intelligent Modular 1-20 Loop Fire Alarm Control SystemThe larger brother to the GST 500, this fire command system, with modular loop cards
expandable to 20 loops and integrated controls, enables full integration with GST Voice
Alarm and Fire Telephone systems Housed in either rack or console type housings
provides the perfect solution for all medium to large systems¡ñ Loop capacity 242 intelligent devices (up to 4840 addressable points)¡ñ Large Graphical LCD Display¡ñ Zone indication and manual intervention control expandable to 254 zones and
plant overrides¡ñ Net-workable with all GST fire panels¡ñ Programmable form PC¡ñ Built-in Gas Extinguishing Control¡ñ Integrated Security Alarm Facilities¡ñ Optional Fireman’s Control Panel¡ñ Panel Printer¡ñ Optional Colour Graphics¡ñ Advanced user friendly programming software including ‘Fuzzy Logic’¡ñ Total integration with GST addressable Voice Alarm systems¡ñ Total integration with GST addressable Fire Telephone systems
Technical Specifications¡ñ Power supply: 220VAC 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension: 580mm x 520mm x 1873mm (Rack type enclocure)¡ñ Dimension: 1080mm x 1113mm x 1350mm (2 bay console)
GST5000 Intelligent Modular 1-42 loop Fire Alarm Control PanelThe flag ship of the GST range of fire control panels, with its large optional
touch screen or Cursor controlled colour graphic LCD providing a full window
on to the system. Full integration with the GST range of Voice alarm and Fire
telephone systems. Optional Network control via LonWorks, enabling total
integration with the GST Building Management System, providing a seamless
complete control system for the most demanding or projects.¡ñ Expandable to 42 loops¡ñ Large 10” colour LCD display with optional touch screen control¡ñ Loop capacity 242 intelligent devices¡ñ On board colour graphic shows detailed floor plans / maps for exact
location of Alarm¡ñ Network with all GST intelligent panels¡ñ Dirty detector indication for targeted maintenance¡ñ LonWorks network facilities¡ñ Built-in Gas Extinguishing Control¡ñ Integrated Security Alarm facilities¡ñ Advanced user friendly programming software including “Fuzzy Logic”¡ñ Optional Rack or Console type¡ñ Total integration with GST addressable Voice Alarm systems¡ñ Total integration with GST addressable Fire Telephone systems
Technical Specifications¡ñ Power supply: 220VAC 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension: 580mm x 520mm x 1873mm (Rack type
enclocure)¡ñ Dimension: 1080mm x 1113mm x 1350mm (2 bay console)
GST9000
Part Number Part Number
18 19
GST alarmNET System is specially designed for long distance fire alarm network solutions
over a LAN WAN or Internet connection. The system was originally developed for central
monitoring of specialist applications such as remote telecom stations, remote railway
stations, Petrochemical pipe-line pumping stations, unmanned remote facilities Multinational
institutions and Hotel Chains and for central monitoring service providers and Fire brigade
control centre’s.
The GST AlarmNET enables complete control over remote fire control panels in real time.
Including the silencing, isolating and de-isolating of devises, operation of plant equipment,
interrogation of individual detectors analogue value plus much more.
Each main operator is provided with a dual-screens, one for data and the other for graphics,depicting maps and floor plans. Each of the floor plans will display each and every device onthe system, with its current status shown on by its colour, and via the data on the text screen.The user friendly topology of the systems enables the controller to simply and efficientlycontrol the complete operation, simply seamlessly scrolling from one monitor to the otherwith the mouse.Other users can still monitor the system from anywhere in the world (subject to networkaccess) via there lap top PC�s but scrolling between text and graphics window on the singlescreen
GST AlarmNET
Each fire alarm panel connected to the network takes an individual IP address. The control
center is based on a computer utilizing Microsoft Windows. All signals are transferred directly
through the WAN/internet, therefore overcoming any distance limitations that can be found in
standard fire alarm network solutions.
At the control centre, when the fire signal comes in, firstly the local warning alarm will sound,
or digital voice message will broadcast, simultaneously, the geography map will show the
location of the project. Also the detail site drawings can be shown manually with a simple click
of a mouse, indicating the floor plans with exact location of the detector in alarm.
Networks that need to cross public roads or airport runways etc can integrate the GST TCP/IP
AlarmNET with wireless LAN technology provided by other manufacturers.
Conventional Fire Alarm Panels¡ñ 1/2/4/8/16 zone conventional Fire Alarm panels.¡ñ Both End of Line Resister and Active End of Line can be used.¡ñ Day/night mode selected.¡ñ Zone isolate control¡ñ One man test.¡ñ Key-control evacuate over-ride.¡ñ Repeater is available for GST108¡ñ Fire alarm output for remote alarm¡ñ Class change terminal for remote control¡ñ Active EOL enables multiple alarm reporting from same zone¡ñ Active EOL max 15 fire detectors and infinite manual buttons each zone¡ñ Resistor EOL up to 25 detectors and infinite manual buttons each zone
Technical Specifications¡ñ Power supply: 200VAC 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension 380mm x 320mm x 95mm (2 to 16 zone panels)
GST101/102/
104/108/116
Active End of Line¡ñ Active End of Line for conventional fire detection zones.¡ñIt can be used as conventional detector base or work independent with
a cover¡ñ Provides detector removal indication while still enabling alarms down
stream of the missing device to be detected.¡ñ Compatible with all GST conventional panels
Compatible with addressable zone interface I-9319
P-9907
Part Number
20 21
Conventional Gas Extinguishing Control Panel¡ñ Two plus one control panel¡ñ Standalone gas extinguishing control panel¡ñ 2 conventional detection zones achieve double knock control¡ñ Additional standard fire detection zone for other areas (no effect on gas release)¡ñ Automatic and Manual extinguishing control¡ñ Numerical onboard timer control¡ñ Adjustable gas release delay timer¡ñ Duty and Standby Cylinder control¡ñ Two phase evacuation sounders¡ñ Adjustable Solenoid Pulsed output¡ñ Compatible with all GST conventional detectors¡ñ Fully compliant to BS/EN/CE standards¡ñ Built-in PSU and Charger
GST301
Addressable Gas Extinguishing Control Panel¡ñ Compatible with all GST Intelligent Fire Alarm Control Panels¡ñ Sits directly on addressable loop¡ñ Direct intelligent control via addressable Loop¡ñ Capable of controlling up to 6 zones of extinguishing¡ñ Auto and manual control facilities¡ñ Utilises GST intelligent detectors and programming (inc Fuzzy Logic)
for control¡ñ Fully monitored status control¡ñ Duty and Standby Cylinder control¡ñ Requires 24VDC Power supply
GST302/304/
306
Emergency Start/Abort Switch¡ñ Emergency Start/Abort switch for gas extinguishing control¡ñCompatible with GST301/302/304/306 gas extinguishing control panels
C-9317
Gas Extinguishing Warning Indicator¡ñ Normally installed above the entrance to a gas extinguishing control area
¡ñ Will eliminate and activate internal sounder prior to gas release
C-9318
Standalone Gas Extinguishing Control System
Part Number Part Number
22 23
Intelligent Boxed PSU¡ñ 24amp 24 volt DC Intelligent PSU¡ñ Display shows AC input Voltage, DC output Voltage, DC Load (amps)¡ñ Fully monitored with self test facilities¡ñ Addressable intelligence enabling full monitoring and reporting to Fire
Control panel (PSU24-24A)¡ñ Only requires 2x12volt battery for standby power
Technical Specifications¡ñ Power supply:AC220V 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C¡ñ Relative Humidity: 95%
PSU24-24(24A)
Intelligent Power Panel PSU¡ñ 19” Rack Mountable 2U PSU¡ñ 6amp 24volt DC Intelligent PSU¡ñ Display shows AC input Voltage, DC output Voltage, DC Load
(amps)¡ñ Fully monitored with self test facilities¡ñ Requires 2x12volt battery for standby power
PSU24-6RM
Power Supply Unit¡ñ 3amp 24 volt DC Intelligent PSU¡ñ Display shows AC input Voltage, DC output load in Amps.¡ñ Fully monitored with self test facilities¡ñ Addressable intelligence enabling full monitoring and reporting to Fire
Control panel (PSU24-3A)¡ñ Requires 2x 12volt battery for standby power
Technical Specifications¡ñ Power supply:AC220V 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension: 310mm x 400mm x 115mm
PSU24-3(3A)
Intelligent Boxed PSU¡ñ 6amp 24 volt DC Intelligent PSU¡ñ Display shows AC input Voltage, DC output Voltage, DC Load (amps)¡ñ Fully monitored with self test facilities¡ñ Addressable intelligence enabling full monitoring and reporting to Fire
Control panel (PSU24-6A)¡ñ Only requires 2x12volt battery for standby power
Technical Specifications¡ñ Power supply:AC220V 50/60Hz¡ñ Operating Environment:
Temperature: -10 ~+ 40°C
Relative Humidity: 95%¡ñ Dimension: 500mm x 440mm x 170mm
PSU24-6(6A)
1. Using End of Line Resister.
NOTE. In compliance with EN/BS standard, when using EOL Resister, call points should be wired before detec-
tors, so that the removal of any detector will not inhibit call points from operating.
2. Using Active End of Line
AEOL enables call points to be installed in any location on zone (circuit), as will not be affected by removal of
detector (Diode base DZ-03D is required for detectors)
Please pay attention to the polarisation.
C-9201 ConventionalManual Call Point
C-9101 ConventionalOptical / Heat Detector
C-9102 ConventionalOptical Detectors
C-9103 ConventionalHeat Detectors
C-9201 ConventionalManual Call Point
C-9101 ConventionalOptical / Heat Detector
C-9102 ConventionalOptical Detectors
C-9103 ConventionalHeat Detectors
P-9907 Active End of Line
C-9201 ConventionalManual Call Point
C-9101 ConventionalOptical / Heat Detector
C-9102 ConventionalOptical Detectors
C-9103 ConventionalHeat Detectors
P-9907 Active End of Line
26 27
Conventional Fire Alarm System ConnectionConventional Fire Alarm System
With Detector
Without Detector