growatt pcs 500 2016-02...bypass cabinet (optional) transformer transformer transformer transformer...

4
www.ginverter.com Growatt PCS500 Features Growatt PCS500 battery inverter is designed for large volume storage system to Bidirectional Battery Charger/Inverter Touch Screen LCD Flexible Battery Type(li-ion,lead-acid) Comprehensive Protection for Inverter and Battery Multiple Working Mode Presetable Battery Forecast (discharge time, capacity, etc) CAN and RS485 Communication Interface, Modbus Protocol Seamless transfer between on and off grid(with optional ATS cabinet) Flexible design, multiple inverters parallelable GROWATT NEW ENERGY TECHNOLOGY Co.,LTD A: No.28 Guangming Road, Longteng Community, Shiyan, Baoan District, Shenzhen, P.R.China. T: + 86 755 2747 1900 F: + 86 755 2749 1460 E: [email protected] 1.Firm unstable solar power to increase grid power quality 2.Increase the usage of solar energy and reduce grid electricity cost 3.Serve as back up power supply for local electrical equipments during grid power outage 4.Serve as temporary power supply for remote area or certain events

Upload: others

Post on 20-Mar-2020

45 views

Category:

Documents


4 download

TRANSCRIPT

www.ginverter.com

Growatt PCS500

Features

Growatt PCS500 battery inverter is designed forlarge volume storage system to

Bidirectional Battery Charger/Inverter

Touch Screen LCD

Flexible Battery Type(li-ion,lead-acid)

Comprehensive Protection for Inverter and Battery

Multiple Working Mode Presetable

Battery Forecast (discharge time, capacity, etc)

CAN and RS485 Communication Interface, Modbus Protocol

Seamless transfer between on and off grid(with optional ATS cabinet)

Flexible design, multiple inverters parallelable

GROWATT NEW ENERGY TECHNOLOGY Co.,LTD

A: No.28 Guangming Road, Longteng Community, Shiyan, Baoan District, Shenzhen, P.R.China.

T: + 86 755 2747 1900 F: + 86 755 2749 1460E: [email protected]

1.Firm unstable solar power to increase grid power quality

2.Increase the usage of solar energy and reduce grid electricity cost

3.Serve as back up power supply for local electrical equipments during grid power outage

4.Serve as temporary power supply for remote area or certain events

AC(Grid-connected)

Rated power

Voltage range

Rated frequency

Rated voltage

Output from

PF

THDI

Frequency range

Datasheet

500KVA

250V - 362V

50/60Hz

315V

3/N/PE

0.9lagging~0.9leading

<3%

47~51.5/57~61.5Hz

Growatt PCS500

DC(battery)

AC(off-grid)

Max power

Current regulation

Voltage regulation

Voltage range

Rated current

Voltage ripple

Current ripple

Max current

Input numbers

Rated voltage

Rated frequency

Overload capability

THDU

Datasheet

Rated voltage

550KW

500-820V

920A

<3%

<2%

1100A

1

315Vac

50/60Hz

110%-10 mins120%-1 min

Growatt PCS500

600V

≤1%linear

±1%

±1%

Communication

Display

Communication interface

Touch screen LCD

RS485/CAN

General Information

Maximum efficiency

Environment compatibility

Noise

Altitude

Environment temperature

Cooling

Dimension (W/H/ )D

Weight

Humidity

97.5%

<65dB

5000m(derated above 3000m)

-25 °C ... +55 °C

Air Forced

2000/2180/850mm

1620KG

0 ~95% non-condensing

Transfer between on/off grid Manual(default)

Automatic(optional)≤20ms

IP 20

Peak-shaving Mode

Typical Application

Grid export limit

Load power

www.ginverter.com

Energy flow

Communication

Power cable

Diesel generator

Mode 2

In the morning,

solar power is

not enough, grid

and solar supply

local load together

Diesel generator

Mode 3

Solar power is

higher than load

power, it supplies

local load, charges

battery at the

same time

Diesel generator

Mode 4

Solar power

decreases to below

load power, battery

discharges to

supply local load at

the same time

Diesel generator

Mode 1

At night, battery

is fully discharged,

grid supplies local

load

bypass cabinet (optional)

bypass cabinet (optional)

bypass cabinet (optional)

bypass cabinet (optional)

Transformer

Transformer

Transformer

Transformer

www.ginverter.com

NOTE:

1.Output power of inverter and PCS can be controled by the feedback information from power sensor.value ajustable

2.LPC stands for power control unit

Typical Application

Back-up Mode

Energy flow

Communication

Power cable

bypass cabinet (optional)

Diesel generator

Transformer

bypass cabinet (optional)

Diesel generator

Transformer

Mode 2

Mode 1

When grid is absent,

bypass cabinet disconnects grid automatically,battery discharges to supply local load together with solar when Diesel generator is starting up

When diesel generator is started, ATS connects diesel generator automatically to supply local load together with battery and solar