Group: PTAC
Part No.: 106018541
Date: May 1999
Installation & Maintenance Data IM 420-1
©1999 AAF–McQuay Incorporated IM 420-1 / Page 1 (Rev. 5/99)
Suite II™ Wall Sleeves
Wall opening requirementBefore installing the unit, check the wall opening to be sure thecabinet/wall sleeve will slide into the opening unobstructed. Formasonry walls, a lintel must be used to provide support over eachopening. The rough opening should measure 161/4" x 42 1/4"(413mm x 1023mm) wide (see note 3, Figure 2). When nosubbase is used, the opening should be a minimum of 3"(76mm) off the floor. This distance is available in 3" (76mm)or 4" (102mm) heights. For units with hydronic heat, thesubbase is 81/4" (210mm). Each subbase has leveling legsproviding for up to 1" (25mm) additional height.
Attac hing cabinet wall slee ve to subbaseAfter the electrical or hydronic subbase has been set in placeand the rough-in for plumbing and/or electrical is complete, thecabinet/wall sleeve can be installed.1. Install cabinet/wall sleeve as described on pages 2 through 4.2. Attach the subbase to the cabinet/wall sleeve using the clips
provided.3. Secure the two sections by installing the clip screws supplied
with the hardware bag.
Figure 1. Wall Sleeve
4. Caulk indoor/outdoor perimeter of cabinet/wall sleeve withresilient caulk such as silicone.
5 . Finish any uncompleted electrical and/or plumbingconnections.
Notes:*Subbase Side Dimension:
Electric: 43/8" to 133/4" (111mm to 349mm)Hydronic: 0" to 133/4" (0mm to 349mm)
**Subbase Height Dimension:Electric: 3" to 4" (76mm to 102mm) with 0" to 1" (0mm to 25m) leveling
screwHydronic: 8" (203mm) with 1/4" (6mm) to 11/4" (32mm) leveling bolts
➀ Unit pictured with subbase installed. Subbase is optional on 208V and 230V units.Subbase is standard on all 265V units and units with hydronic heat. Hydronicsubbase is flush with the front of the cabinet. Electric subbase is flush with wallsleeve.
➁ Subbase extends to front edge of unit when furnished with hydronic heat.
➂ Opening needs to be 165/8" x 425/8" (422mm x 1083mm) when using a louverframe.
Subbase side channels are adiustable from 43/8" to 133/4" (111mm to 349mm).
Figure 2. Unit with Subbase
Note: Wall sleeve shown with optional insulation installed.
TinnermanClips
➤
➤
42"(1067 mm)
133/4"(349 mm)
43"(1092 mm)
161/2"(419 mm)
411/2"(1054 mm)
16" (406 mm)
81/4"(210 mm) *
**22" (559 mm)
➀
4
IM 420-1 / Page 2 (Rev.5/99)
A heavy-gauge, corrosion resistant cabinet/wall sleeve isprovided for each unit. The cabinet/wall sleeve is either shippedin a separate carton, shipped in a multipack of 15 or in a singlecarton with the heating/cooling chassis.
The standard cabinet/wall sleeve is designed to be easilyinstalled in a variety of wall constructions. Note: The center of grav-ity is 101/4" (260mm) from the rear face of the wall sleeve. The wallsleeve must be inserted into the wall at least 101/4" (260mm) or othersupport must be employed. Support can be from a factory suppliedsubbase or from other field supplied materials. Recommendedinstallation procedures are described below.1. Clean the opening of all debris that may interfere with installation.2. If the unit is to be supplied with a subbase, install subbase
before installing cabinet/wall sleeve (see IM 419 or IM 420).3. lf the optional drain kit is to be employed (heat pump only),
see IM 430-2.4. Place a thin pad of soft mortar on the bottom of the opening
and slide in the cabinet/wall sleeve. Be sure to recess the wallsleeve enough to accommodate outside louver. This recessis 3/8" (9.5mm) for stamped louvers and 11/4" (32mm) for ar-chitectural louvers. Louver should be flush to exterior surfacewith complete. Note: The wall sleeve is not intended to re-place the lintel.
5. Level cabinet/wall sleeve in both directions and secure by an-choring with appropriate fasteners. A 5/16" (8mm) hole is pro-vided on each side, 2" (51 mm) down from the top and 2"(51mm) in from the rear of the cabinet/wall sleeve. Additionalholes may be required to firmly secure the cabinet/wall sleeve.Caution: Do not drill holes in the base of the cabinet/wallsleeve. Where a subbase is used, secure wall sleeve to sub-base with clips provided.
6. Caulk the cabinet/wall sleeve to the wall opening on both theinside and outside perimeter. Be careful not to plug the weepholes. Caulking should be resilient, nonhardening type suchas silicone.
Wall sleeve installation — frame and brick
Note : Standard subbase is available in 3" or 4" (76 mm or 102 mm) height.Leveling legs provide adjustment of 1" (25 mm).
Figure 3. Frame and brick with cord connection
STEEL LINTEL (BYOTHERS)
81/4"(209mm)
16"(406mm)
ROOMCABINET
3" MIN.(76mm)
FINISHEDFLOOR OR
CARPET
WALLRECEPTACLEBY OTHERS
CAULKPERIMETER
OUTDOORLOUVER
MOUNTINGSCREWS BY
INSTALLER
133/4"(349mm)
WALL SLEEVE
Figure 4. Frame and brick with standard electrical subbase Figure 5. Frame and brick with hydronic subbase
STEEL LINTELBY OTHERS
43/8"(111mm)
OUTSIDELOUVER
MOUNTINGHOLES BY
INSTALLER
81/4"(209mm)
CAULKPERIMETERBOTHINDOORS &OUTDOORSBEFOREINSTALLINGLOUVER
POWER SUPPLY CONNECT(ALTERNATE ENTRY)
LEVELING LEGFINISHED
FLOOR ORTOP OF
CARPET
SEE NOTE
133/4"(349mm)
WALL SLEEVE
ROOMCABINET
SUBBASE
16"(406mm)
MOUNTINGSCREWS BY
INSTALLER
OUTDOORLOUVER
STEEL LINTEL(BY OTHERS)
HYDRONICHEATINGCOIL
16"(406mm)
81/4"(209mm)
133/4"(349mm)
CAULKPERIMETERBOTHINDOORS &OUTDOORSBEFOREINSTALLINGLOUVER
SUBBASESIDE
CHANNELALTERNATEELECTRICAL
CONNECTIONS
HYDRONICSUBBASE
FINISHEDFLOOR ORCARPET
81/4"(209mm)
ROOMCABINET
WALLSLEEVE
17"(432mm)
17"(432mm)
17"(432mm)
Certified Drawing
IM 420-1 / Page 3 (Rev. 5/99)
Wall sleeve installation–panel wall construction
Note : Standard subbase is available in 3" or 4" (76 mm or 102 mm) height.Leveling legs provide adjustment of 1" (25 mm).
Figure 7. Panel wall construction withstandard electrical subbase Figure 8. Panel wall installation with hydronic subbase
For panel wall and thin wall construction, it is recommended thata louver frame be used.
Panel wall and thin wall construction varies only slightly fromframe and brick construction. Note: The center of gravity is 10"(260mm) from the rear face of the wall sleeve. The wall sleevemust be inserted into the wall at least 10" (260mm) or othersupport must be employed. Support can be from a factorysupplied subbase or from other field supplied materials.Installation for this application is as follows:1. Clean the opening of all debris that may interfere with
installation.2. If the unit is to be supplied with a subbase, install subbase
before installing cabinet/wall sleeve (see IM 419 or IM 420).3. If the optional drain kit is to be employed, see IM 430-3.4. Be sure the cabinet/wall sleeve is mechanically attached to
the wall and caulked to assure a proper seat. It isrecommended that the louver frame be used for this purpose.
5. Recess the wall sleeve so that the louver is flush with theexterior of the building.
6. Level cabinet/wall sleeve in both directions and secure byanchoring with appropriate fasteners or drill additional holesas required to secure firmly. Caution: Do not drill holes in thebase of the cabinet/wall sleeve. Where a subbase is used,secure wall sleeve to subbase with clips provided.
7. Caulk the cabinet/wall sleeve to the wall opening on both theinside and outside perimeter. Be careful not to plug the weepholes. Caulking should be resilient, nonhardening type suchas silicone.
Figure 6. Panel wall construction with cord connection
OUTDOORLOUVER
3"MIN. (76mm) CAULKPERIMETER
BOTHINDOORS &OUTDOORS
MINIMUM 2SUPPORTS FIELD
SUPPLIED
CONDUIT
ROOMCABINET
WALLSLEEVE
133/4"(349mm)
81/4"(209mm)
16"(406mm)
FLOOR
LOUVERFRAME
SEE NOTE
ROOMCABINET
16"(406mm)
81/4"(209mm)
LOUVERFRAME
133/4"(349mm)
ELECTRICALSUBBASE
WALL SLEEVE
POWER SUPPLYCONDUIT
(ALTERNATE ENTRY)SUBBASE SIDE
CHANNEL
GASKET &CAULK
PERIMETER
OUTSIDELOUVER
16"(406mm)
LOUVERFRAME
WALLSLEEVE
POWER SUPPLY CONDUIT(ALTERNATE ENTRY)
CAULKPERIMETER
BOTH INDOORS& OUTDOORS
SUBBASESIDE
CHANNEL
ROOMCABINET
81/4"(209mm)
81/4"(209mm)
OUTDOORLOUVER
133/4"(349mm)
HYDRONICHEATING
COIL
LEVELING LEGSW/1" ADJUSTMENT
RECEPTACLESBY OTHERS
17"(432mm) 17"
(432mm)
17"(432mm)
IM 420-1 / Page 4 (Rev. 5/99)
AAF–McQuay Incorporated
4900 Technology Park Boulevard, Auburn, New York 13021-9030 USA (315) 253-2771
Printed on recycled paper containing at least 10% post-consumer recycled material.
Installation of cabinet/wall sleeves for thick walls requires specialconsideration. Table 1 should be used to determine themaximum wall thickness allowed for the standard cabinet/wallsleeve. For thicker walls, cabinet/wall sleeve extensions areavailable from your representative. Wall sleeve installation in thick walls is similar to frame andbrick installation. Install as follows:1. Clean the opening of all debris that may interfere with
installation.2. If the unit is to be supplied with a subbase, install subbase
before installing cabinet/wall sleeve (see IM 419 or IM 420).3. If the optional drain kit is to be employed (heat pump only),
see IM 430-3.4. If wall thickness exceeds dimensions shown in Table 1, a
cabinet/wall sleeve extension must be used. Once theextension is attached to the cabinet/wall sleeve, place a thinpad of soft mortar on the bottom of the opening and slide inthe wall sleeve/extension assembly. Be sure to recess the wallsleeve enough to accommodate outside louver. This recessis 3/8" (9.5mm) for stamped louvers and 11/4" (32mm) for ar-chitectural louvers. Louver should be flush to exterior surfacewhen completed. Note: The wall sleeve is not intended to re-place the lintel.
5. Level cabinet/wall sleeve in both directions and secure byanchoring with appropriate fasteners or drill additional holesas required to secure firmly. Caution: Do not drill holes in thebase of the cabinet/wall sleeve. Where a subbase is used,secure wall sleeve to subbase with clips provided.
6. Caulk the cabinet/wall sleeve to the wall opening on both theinside and outside perimeter. Be careful not to plug the weepholes. Caulking should be resilient, nonhardening type suchas silicone.
Wall slee ve installation– thic k wall construction
Figure 11. Thick wall installation with hydronic subbase
Figure 9. Thick wall construction with cord connection
Figure 10. Thick wall construction withstandard electrical subbase
Note : ➀ Standard subbase is available in 3" or 4" (76 mm or 102 mm) height.Leveling legs provide adjustment of 1" (25 mm).
➁ Wall sleeve extension is available in various depths and supplied asrequired.
CAULKPERIMETER
OUTDOORLOUVER
MOUNTINGSCREWS BYINSTALLER
WALLSLEEVEEXTENSION
WALLRECEPTACLEBY OTHERS
3"MIN.(76mm)
17"(432mm)
SEETABLE 1
STEELLINTEL (BYOTHERS)
1/8"(3mm)MIN.
81/4"(209mm)
ROOMCABINET
WALLSLEEVE
FLOOR
133/4"(349mm)
SEETABLE 1
16"(406mm)
CAULKPERIMETER
MOUNTINGSCREWS BYINSTALLER
SEENOTE
2133/4"
(349mm)
OUTDOORLOUVER
WALL
SLEEVE
EXTENSION ELECTRICALSUBBASE
81/4"(209mm)
ROOMCABINET
STEELLINTEL(BY OTHERS)
SEE NOTE 1
FLOOR
43/8"MIN.
(111mm)
SEE TABLE 1
1" (25mm)
CAULKPERIMETER
MOUNTINGSCREWS BYINSTALLER
OUTDOORLOUVER
WALLSLEEVEEXTENSION
HYDRONICSUBBASE
HYDRONICHEATING
COIL
81/4"
(209mm)
ROOMCABINET
16"
(406mm)
81/4"
(209mm)
FLOOR
WALL SLEEVE133/4"
(349mm)
STEELLINTEL BYOTHERS
LOUVERTYPE
Stamped
Architectural
NOSUBBASE
STANDARDSUBBASE
HYDRONICSUBBASE
MAXIMUM WALL THICKNESS
14"(356mm)
147/8"(378mm)
91/2"(241mm)
103/8"(264mm)
131/8"(333mm)
14"(356mm)
16"(406mm)
17"(432mm)
17"(432mm)