grid insite for control and...

2
Cost-effective smart grid monitoring for the distribution transformer Transformer IQ Technical Specifications gridsense.com Communications MODBUS, DNP3; Ethernet, WiFi, GSM, ASCII over RS232, ASCII over RS485 Integrated Socket-mounted Remote Communications On-Ramp Wireless; Silver Spring Networks; Landis+Gyr; WiFi, GSM/EDGE, or CDMA modem Operating Environment -40C to +85C for fully submersible encapsulated version Channels / Model P D & V RMS Voltage 3 12 RMS Current 3 + Neutral 12 + Neutrals Fault Current 3 12 Fault Duration 3 12 Discrete Inputs 5 24 Analog Inputs N/A 2 Temperatures 4 6 Internal Case Temperature 1 1 Cooling Load 0 3 LTC Change Duration 0 1 LTC Change Energy 0 1 Dissolved Gas Monitoring 8 gases; H20; total combustible gas; total hydrocarbons; MOD- BUS over RS485; Multiple DGA manufacturers supported Grid InSite for Control and Analysis Grid InSite software radically simplifies monitor configuration and control. You’ll seamlessly access real-time data through an intuitive, user-friendly graphical interface as familiar as your desktop. There’s no infrastructure required; all you need is an Internet connection and an Internet device. Data presented in easy-to-analyze formats Plotted, graphed user-selected data set

Upload: tranxuyen

Post on 06-Feb-2018

234 views

Category:

Documents


3 download

TRANSCRIPT

Cost-effective smart grid monitoring for the distribution transformer

Transformer IQ

Technical Specifications

gridsense.com

Communications MODBUS, DNP3; Ethernet, WiFi, GSM, ASCII over RS232, ASCII over RS485

Integrated Socket-mounted Remote Communications

On-Ramp Wireless; Silver Spring Networks; Landis+Gyr; WiFi, GSM/EDGE, or CDMA modem

Operating Environment -40C to +85C for fully submersible encapsulated version

Channels / Model

P D & V

RMS Voltage 3 12

RMS Current 3 + Neutral 12 + Neutrals

Fault Current 3 12

Fault Duration 3 12

Discrete Inputs 5 24

Analog Inputs N/A 2

Temperatures 4 6

Internal Case Temperature 1 1

Cooling Load 0 3

LTC Change Duration 0 1

LTC Change Energy 0 1

Dissolved Gas Monitoring

8 gases; H20; total combustible gas; total hydrocarbons; MOD-BUS over RS485; Multiple DGA manufacturers supported

Grid InSite for Control and Analysis

Grid InSite software radically simplifies monitor configuration and control. You’ll seamlessly access real-time data through an intuitive, user-friendly graphical interface as familiar as your desktop. There’s no infrastructure required; all you need is an Internet connection and an Internet device.

Data presented in easy-to-analyze formats Plotted, graphed user-selected data set

Comprehensive Distribution Transformer Intelligence

Designed for quick, live installation and equipped with an on-board, no-maintenance power source, TransformerIQ provides the in-depth data you need to protect against overload, quickly diagnose and resolve maintenance issues, improve fault restoration time, optimize asset utilization, and predict remaining asset life.

With the increase in EVs and more volatile renewables entering the grid, the distribution system grows more vulnerable, and the threat of overload increases. Protect the grid, identify its vulnerabilities, and maximize its efficiency.

Gain operational information:

- Protect against overload and imbalance

- Accurately determine end-of-line voltage

- Smooth the integration of EVs and PVs into the grid

- Monitor transformer efficiency to quantify volt/VAR efforts

- Perform power factor correction with four-quadrant measurement of true power factor

Improve outage management:

- Improve fault isolation time with line fault information

- Set transformer alarms for temperature, overload, and voltage sag/swell

Identify major power quality issues

- Voltage and current harmonics through to the 31st harmonic on each A, B and C phase

- Voltage sag/swell

- Alarm notifications for harmonic content

- THD on the voltage and current waveforms

Intelligence From Every Link in Your Transformer Chain

Residential Transformer Monitoring Draw deep, valuable intelligence from your vast network of padmount and poletop transformers.

On the residential scale, you’ll protect from overloading in EV and PV situations. You’ll have the information needed to quantify and optimize volt/VAR efforts. With line fault information at your fingertips, you’ll improve fault isolation time as alarms provide early warning of temperature, overload and voltage sag/swell issues. Data points include:

- Fault phase indication- Fault magnitude- Fault duration

Network Vault Transformer Monitoring TransformerIQ addresses the need to affordably monitor multiple-transformers in rooms or cabinets—with discrete data for each individual transformer.

- Rogowski coil or CT current sensing- Voltage monitoring isolates at 300v (L-N)- Provisions for smart grid mesh radios

Small Power Transformer Monitoring Get the benefits of substation transformer monitoring for the small power transformer in an extremely cost-effective package designed for retrofit.

- All operational and fault information captured with feeder sensing- Measures up to four temperatures at different locations (e.g., top and bottom oil, ambient, etc.) on multiple tanks (optional)

- Calculated hot spot temperatures on all monitored windings

Protect assets. Deepen diagnostics. Enhance networks.

Transformer IQ

Grid InSite

Transformer IQ

CommunicationsCellular | Radio | WiFi Client Devices

Poletop

Padmount

Vault

Control Room