Bio-containment
A subsidiary of GRG Inc.
Differences inBSL-2, BSL-3, BSL-3Ag and
BSL-4Labs and Animal Facilities
Michael C. Connor, PEPrincipal
Earl Walls Associates
*CDC-NIH Biosafety in Microbiology and Biomedical Laboratories, 4th edition
Biosafety Level 2 (BSL-2)*. Used with agents of moderate potential hazard to personnel, animals, and the environment, with minimal economic loss to the animal industries
Wall Construction: Gypsum Board or Masonry
Ceiling Construction: Lay-in acoustic tile with vinyl surface
BSL-2 Laboratory
BSL-2 Laboratory
• Design commissioning – verify designed access to various commissioning points of measurement –Volume Control Boxes don’t conflict with cable trays, etc.
• Verify air flows in accordance with air flow schedules.
• Verify space pressurization.
• Verify access to critical components – Pressure and air flow transmitters.
• Verify labeling of all components requiring maintenance.
BSL-2 Laboratory
• Verify HEPA filter integrity in BSC’s by particle count within cabinet.
• Verify installation of any and all other scientific equipment like point of use DI water systems and centrifuges.
• Perform ASHRAE 110 testing on chemical fume hoods.
• Upset test control system – input set point at edge of range and verify ability to return to normal set point within reasonable time period.
• Verify electrical outlets – voltage, polarity, labeling outlets to panel board circuits.
• Verify shunt trip of lab electrical panels.
• Calibrate all HVAC sensors – flow, pressure, temperature, humidity – don’t depend on factory calibration.
• TRAINING – have mechanics responsible for maintenance participate in commissioning process – most important step and most overlooked.
• Document – video tape training sessions, preserve commissioning baseline.
Biosafety Level 3 (BSL-3)* is applicable to clinical,
diagnostic, teaching, research or production facilities
In which work is done with indigenous or exotic
agents which may cause serious or potentially lethal
disease as a result of exposure by the inhalation route.
*CDC-NIH Biosafety in Microbiology and Biomedical Laboratories, 4th edition
Wall Construction: Clean Room panel (BSL-3), Masonry (BSL-3+) or Poured Concrete (BSL-3++)
Ceiling Construction: Clean Room Gasketed Panel System (BSL-3) or Exposed Structure (BSL-3+) or Coated Structure (BSL-3++)
Example of Panel System
Wall Construction: Masonry
BSL-3 Laboratory
BSL-3 Laboratory
BSL-3 Laboratory
• All of the items covered in BSL-2.
• Autoclave qualification.
• Inspect room penetrations and seals – smoke test.
• Verify VHP effectiveness.
• Calibrate local pressure indicators
• Security system qualification
• NSF 49 - 2004 test of BSC’s cabinets
http://www.afm.ars.usda.gov/ppweb/242-01m.htm#H308
USDA-ARS and APHIS
ZOONOTIC DISEASES are diseases caused by infectious agentsthat can be transmitted between (or are shared by) animals and humans.
Biosafety Level 3 Agriculture (BSL-3Ag). Used with pathogens that present a risk of causing infections of animals and plants and causing a great economic harm. (Foot and Mouth Disease is the premier example.)
Wall Construction: Poured Concrete with Coating
Ceiling Construction: Exposed Structure with Coating
BSL-3ag Laboratory
BSL-3ag Laboratory
BSL-3ag Laboratory• All of the requirements for BSL-2 and BSL-3• Autoclave temperature profile.
– Place typical load in autoclave– Thermocouple mapping of chamber with multi channel recorder.
• Air Pressure Resistant (APR) door verification.– Air Compressor– Air Quality
• Wall Coating Testing– Pull-off testing– Spark Testing
• Inspect utility penetrations– Visually inspect BOTH sides of penetrations.
• Helium leak testing of Ducts and HEPA housings– Outboard test– 1 x 10 –5 cc/sec acceptance criteria. 1 x 10-6 cc/sec atmospheric
background level – requires mass spectrometer NOT thermal conductivity equipment to sense at this level.
BSL-3ag Laboratory
• Space Pressure Decay Testing
– Room must hold 500 Pa (+/-) with a maximum decay to 250 Pa in 20 minutes.
– Epoxy Seal conduits with wiring.
– Impervious wall surfaces.
• HEPA Filter challenges per BSL-3.
• Helium leak testing of ductwork between laboratory and HEPA filters.
– All welded ductwork required – increase wall thickness.
– Outboard testing.
BSL-3ag Laboratory
• Pressure decay testing of double wall plumbing drain pipe
– Test Annular space
– Hold negative pressure – limit to 5 psi MAX
• Waste treatment plant endotoxin challenge – 6 log reduction of Colony Forming Units (CFU), heat resistant bacteria (Bacillus Steareothermophillus)used for challenge.
POWERED AIR PURIFYING RESPIRATOR (PAPR)
WATER SHOWER
CHEMICAL SHOWER
BSL-4
CHEMICAL TANK
BSL-4
• Same as BSL-3ag
• Commissioning Breathing Air System
• Commissioning Chemical Shower System
BSL - 4
BSL - 4
American Biological Safety Association web sitehttp://www.absa.org/resriskgroup.html
Information resources:
CDC-NIH Biosafety in Microbiology and Biomedical Laboratories, 4th editionhttp://des.od.nih.gov/
NIH Design and Policy Guidelineshttp://des.od.nih.gov/eWeb/planning/htm/nihpol.htm
USDA/ ARS/ APHIShttp://www.afm.ars.usda.gov/ppweb/242-01m.htm#H308