® Job Name: Job Number: Model Numbers: Page SPECIFICATION SUBMITTAL GRAFIK Eye® QS Control Unit LUTRON 1 2 3 4 Off Preset Close Open Description GRAFIK Eye® QS is the premier energy-saving light and shade control. The GRAFIK Eye® QS control unit includes an astronomic timeclock, intuitive lighting presets, and direct shade control. Additionally, the GRAFIK Eye® QS control unit is compatible with all Lutron wired QS products and systems, including Quantum® systems. Mechanical Dimensions 4$ in (119 mm) 94 in (239 mm) 4 in (10 mm) 2 in (51 mm) Front View Side View Fits into a 4-gang U.S. backbox, 3` in (89 mm) deep; Lutron P/N 241-400 System Topology Example of Wired System QSE-CI-NWK-E Sivoia® QS shade seeTouch® QS wallstation seeTouch® QS wallstation Wired occupancy sensor GRAFIK Eye® QS wireless control unit GRAFIK Eye® QS wireless control unit Wired QS link Quantum® processor QS Sensor Module Energi Savr NodeTM unit Preset Dimming Controls 369309 Rev. B 1 11.17.11 Control Unit

Upload: dodung

Post on 28-Jun-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

GRAFIK Eye® QS Control Unit

LUTRON

1

2

3

4

Off

Preset

Close

Open

DescriptionGRAFIK Eye® QS is the premier energy-saving light and shade control. The GRAFIK Eye® QS control unit includes an astronomic timeclock, intuitive lighting presets, and direct shade control. Additionally, the GRAFIK Eye® QS control unit is compatible with all Lutron wired QS products and systems, including Quantum® systems.

Mechanical Dimensions

4$ in (119 mm)

94 in (239 mm) 4 in

(10 mm) 2 in (51 mm)

Front View Side View

Fits into a 4-gang U.S. backbox, 3` in (89 mm) deep; Lutron P/N 241-400

System Topology

LUTRONLUTRON

LUTRON LUTRON

LUTRON

LUTRON LUTRON

LUTRON

LUTRON

LUTRON

LUTRONLUTRON

LUTRON LUTRON

LUTRON

LUTRON LUTRON

LUTRON

LUTRON

LUTRON

Example of Wired System

QSE-CI-NWK-E

Sivoia® QS shade

seeTouch® QS

wallstation

seeTouch® QS

wallstation

Wired occupancy

sensor

GRAFIK Eye® QS wireless control unit

GRAFIK Eye® QS wireless control unit

Wired QS link

Quantum® processor

QS Sensor Module

Energi Savr NodeTM unit

Preset Dimming Controls

369309 Rev. B 1 11.17.11

Control Unit

Page 2: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

Features•Pushbuttonrecalloffourpresetlightingscenes,plusOff.

•Twelve(12)additionalscenesaccessiblethroughother QS devices, such as seeTouch® QS wallstations.

•Optionalintegratedshadecontrolbuttons,whichcanalsobeaddedtotheunitafterinstallation.

•Masteroverridebuttonstoraiseandloweralllights.•Allowssetupoflightingscenesandshadepresets

using buttons on the control unit. •Built-ininfrared(IR)receiver.•ExternalIRconnection.•Built-inastronomictimeclock.• Infoscreenshowszonelightlevelpercentage,energysavings,zonelabeling,andprogramming.

•Lockoutoptionpreventsaccidentalchanges.•Oneoccupancysensorinputand24V powerfor

occupancy sensor.•QScommunicationlinkforseamlessintegrationoflights,motorizedwindowtreatments,occupancysensors,wallstations,andintegrationinterfaces.

•CompatiblewithallLutronQSsystemcomponents.•Backlitbuttonswithengravingmakeuniteasyto

locate and operate.•Availableinavarietyofcolorsandfinishes.

LUTRON

OK

Optional shade control keypad

Zone control

Infraredreceiver

USB type mini B

Infoscreen

Lighting control keypad

1

2

3

4

Off

Off

Preset

Close

1

2

3

4

Open

Preset

Close

Open

Note: General Engraving (-EGN) shown.

Preset Dimming Controls

369309 Rev. B 2 11.17.11

Control Unit

Page 3: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Model Numbers:

PageSPECIFICATION SUBMITTAL

Job Name:

Job Number:

Key Design Features•LightningstrikeprotectionmeetsANSI/IEEEstandard62.41-1980.Canwithstandvoltagesurgesofupto 6000 V andcurrentsurgesofupto3000A.

•Testedtowithstand16kVelectrostaticdischargewithoutdamage or memory loss.

•RTISSTM-equipped:Compensatesinrealtimeforincominglinevoltagevariations(novisibleflickerwith+/-2%changeinRMSvoltagepercycle,and+/-2%Hzchangeinfrequencypersecond).

•Powerfailurememoryretainsprogrammingandlightlevelsettingsforupto10yearsintheeventofapowerloss.

•TheGRAFIKEye® QS control unit supplies 3 Power Draw Units (PDUs) on the QS link. Forcompleteinformation,see“PowerDrawUnitsontheQS Link,” Lutron PN 369405.

•Faceplateishingedatthetopandbottom,andstaysopenat180°foreaseofaccess.

Scene and Shade Buttons•Large,roundedbuttonsareeasytouse.•Backlitbuttonswithoptionalengravingmakeiteasytofindandtooperatethecontrolunitinlowlightconditions(backlight can be disabled).

•Optionalbuttonengravingisangleduptotheeyeforeasy reading.

•Predefinedlabelstickersareincludedforfieldlabeling.•4presetlightingscenes,plusOff,areaccessiblefromthefrontofthecontrolunit.

•12additionalscenesarestoredinthecontrolunitandareaccessiblefromseeTouch® QS wallstations and QSinterfaces.

•Lightlevelsfadesmoothlybetweenscenes.Fadetimecanbesetdifferentlyforeachscene:0to59seconds,or1to60minutes.MaximumfadetimefromOffis 3 seconds.

Input Power•120-127V 50/60Hz•220-240V 50/60Hz

Listings (120 - 127 V )•UL•CSA•NOM•CEC(Title24)

Environment•32to104°F(0to40°C).•Relativehumiditylessthan90%non-condensing.

Lighting Sources/Load TypesControlsthefollowinglightingsourceswithasmooth,continuoussquarelawdimmingcurveoronafullconduction non-dim basis:

• Incandescent•Halogen•Magneticlow-voltagetransformer•LutronTu-Wire®electronicfluorescentdimmingballast•AdvanceMarkX® electronic dimming ballast•Neonandcoldcathode•Non-dim(incandescent,magneticlow-voltage,Tu-Wire®,

or neon/cold cathode)•CreeLR4/6,120V fixtures(forloadingcapacities,pleaserefertotheLEDreportcardlocatedat www.lutron.com/LEDtool)

Pleasereferto“Capacities”formoreinformation.

Controlsthefollowinglightingsourceswithasmooth,continuoussquarelawdimmingcurveoronafullconduction non-dim basis through separate Lutron power interfaces:

•Electroniclow-voltagetransformer•LutronHi-lume® and Eco-10®electronicfluorescent

dimming ballast•Non-dim•0-10V

Specifications

Preset Dimming Controls

369309 Rev. B 3 11.17.11

Control Unit

Page 4: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

Astronomic Timeclock• Integraltoallunits.•7dailyschedulesavailable.•Oneavailableholidayscheduleisprogrammablebydate

up to one year in advance.•25eventsperdaymaximum.•TimeclockeventsareprogrammabletocontrolscenesthataffectanyEnergiSavrNodeTM unit connected on the QS link without changing the local scene on the GRAFIK Eye® QS control unit.

•Astronomictimesareprogrammablebyintegralcitydatabase or by entering latitude and longitude. Times automatically adjust throughout the year based on location.

•AutomaticallyadjustsforDaylightSavingTime(DST),adjustedforthenewdates;DSTisprogrammable.

•Localtimeclockeventscanactivateanyofthefollowingfeatures:

-Scenes1to16andOff - Any available shade presets -StartandEndafterhoursmode -EnableandDisabledaylightingforallzones/groups -EnableandDisableoccupancyforoccupancy/vacancy

sensors -EnableandDisableoccupiedeventsforalloccupancy

sensors

System Communications and Capacities•Low-voltagetypeIECPELV/NEC® Class 2 wiring connectscontrolunits,wallstations,motorizedshades,andcontrolinterfaces.

•AQSsystemcanhaveupto100devicesand100zones.

Infrared• Infrared(IR)receiverallowsinfraredtransmitterstoselect8scenes,raise/lowerlightingzones,orraise/lowershades.

•Transmitterbuttonsimitatebuttonsonfaceplate.•50ft(15m)lineofsightrange.•TerminalblockinfraredinputforconnectiontoawiredIRinputfromthird-partyequipment.

• IRcanbedisabledviaprogramming.•WorkswithLutronGRX-ITandGRX-8ITinfraredremote

controls.

Shade Control•TheGRAFIKEye® QS control unit can include up to 3

shade button columns. Each column has backlit open, preset, close, and raise/lower buttons.

•Eachshadebuttoncolumncanbeprogrammedtooperateoneshadeoragroupofshades.(Shadesmaybe assigned to more than one shade button column).

•Faceplatesareavailablewith1,2and3shadebuttoncolumns.

Zone Control•Eachzonehasadedicatedraiseandlowerbuttontoadjustthezone.

•Eachzonehasadedicated7LEDbargraphforlevelstatus.Percentageoflightlevelandenergysavedisdisplayedontheinfoscreen.

•AllzoneinformationhasbluebacklitLEDs.Backlightturnsoffwhenidlefor30seconds.

Info Screen•OLED(organicLED)screenisviewablefromallangles.•Screenturnsoffwhenidlefor30seconds.•Programmablezonelabels.•Programmablescenelabels.•Statusofreal-timezonepercentageandenergysavings.•Programmabletimeclockschedules.•Programmableshadelabels.

Specifications

Preset Dimming Controls

369309 Rev. B 4 11.17.11

Control Unit

Page 5: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

SpecificationsAccessory Controls: seeTouch® QS Wallstations (QSWS2)

•WiredseeTouch®QSwallstationsprovidethefollowingfeatures:

-Accesstooneormoreofthe16scenesontheGRAFIKEye® QS control unit

-Zonetoggle,partitioning,sequencing,finetune,panicmode, and timeclock enable/disable

- Contact closure inputs -Certainfunctionsareonlyavailableonspecific

wallstationconfigurations.RefertotheseeTouch® QS specificationsubmittal.

Accessory Controls: QS Sensor Module (QSM2)•TheQSSensorModuleprovidesameanstolinkwired

or wireless occupancy and daylight sensors to a GRAFIK Eye® QS control unit via the wired QS link.

- Occupancy sensors wired (or wirelessly linked) to a QS Sensor Module can be used by one or more GRAFIK Eye® QS control units on the wired link.

- Daylight sensors wired (or wirelessly linked) to a QS Sensor Module can be used by one or more GRAFIK Eye® QS control units on the wired link.

-Infraredsensorscancontroleitheroneormorezonesor scenes on the GRAFIK Eye® QS control unit. Functionalityvaries;refertothedocumentationfortheQSSensorModulefordetails.

- Pico® wireless controls wirelessly linked to a QS Sensor Modulecanbeusedtocontroloneormorezonesorscenes on the GRAFIK Eye® QS control unit.

Accessory Controls: Contact Closure Input/Output Interface (QSE-IO)

•Recallspresetlightlevelsforthefollowingsetofsceneson the GRAFIK Eye® QS control unit:Scenes1-4andOff Scenes9-12andOff Scenes5-8andOff Scenes13-16andOff

•Sequencescenes5-16,Enable/DisableZoneLockout,Enable/Disable Scene Lockout, Enable/Disable Panic Mode, Enable/Disable Timeclock.

•OccupancySensors.Anindividualinputcountsas1occupancysensorfortheGRAFIKEye® QS control unit. Each input can be assigned to either Scene Control or ZoneControl(pleaserefertotheOccupancySensor(s)sectionofthisguide).

• ZoneToggle.Allowsaninputtotoggleoneormorezonestoapresetlevelandoff.

•ShadeOutputmode.AShadeColumnontheGRAFIKEye® QS control unit can be linked to control outputs 1-3 and/or outputs 4-5 on the QSE-IO.

Accessory Controls: DMX Output Interface (QSE-CI-DMX)

•AnyzoneontheGRAFIKEye® QS control unit can be mappedtoanysingleDMX512Channel.

•AnyzoneontheGRAFIKEye® QS control unit can be simultaneouslymappedtoanythreeDMX512channels(providing RGB/CMY control).

•DMXloadscannotbeusedwithdaylighting.

Accessory Controls: Ethernet and RS232 Interface (QSE-CI-NWK-E)

•AllowsformonitoringandcontroloftheoutputsandlocalscenesoftheGRAFIKEye® QS control unit.

Accessory Controls: QS Keyswitch Wallstations (QSWS2-KS)

•RecallspresetlightlevelsforanytwoscenesincludingOff.•Allowsfine-tuning(raise/lowerlevel)ofazoneorgroupofzones.

•Starts/Stopsscenesequencings(Scenes1-4orScenes5-16)

•Enables/DisablesTimeclock•Enables/Disablesoccupancysensors•Enables/Disableddaylightsensors•AllowstoggleofZone(s)toapresetlevelandoff.•Enables/Disablespanicmode.•Starts/Stopsafterhoursmode.

Other Accessory Controls and Devices•EnergiSavrNodeTM QS (ESN).Seethespecificationsubmittalforcompletedetails.

Occupancy Sensor(s)•TheGRAFIKEye® QS control unit works with occupancy

sensors through either: -SceneControl:Uptofoursensorsactivateuser-selectable

occupancy and vacancy scenes. -ZoneControl:uptofoursensorsperzoneactivateuser-

selectedoccupancyandvacancyzonelevels.•Occupancysensorsmayinclude: -ContactclosuresensorswiredtoCCIinputonbackof

GRAFIK Eye® QS control unit - Wired or wireless sensors connected QS Sensor Module

(QSM)• Ifanysensorinagroupdetectsoccupancy,thenthe

GRAFIK Eye® QS control unit will go to the designated occupancysceneorzonelevel.

• Ifallsensorsinagroupdetectvacancy,thentheGRAFIKEye® QS control unit will go to the designated vacancy sceneorzonelevel.

Preset Dimming Controls

369309 Rev. B 5 11.17.11

Control Unit

Page 6: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

Preset Dimming Controls

369309 Rev. B 6 11.17.11

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

Control Unit

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

Specifications

Daylight Sensor(s)•TheGRAFIKEye® QS control unit allows daylight sensors tocontroloneormorelightingzonestoadjustelectriclight levels based on measured daylight levels.

•Daylightsensorsmayinclude: - Wired or wireless sensors connected to a QS sensor

module (QSM)•AdaylightsensorcancontroloneormoreGRAFIKEye® QScontrolunitzones:

-Eachzonecanbecalibratedtotargetlightlevels -Azonecanbecontrolledbynomorethanonedaylight

sensor•Daylightcontrolcanbeenabledordisabledonascene-

by-scene basis -Bydefault,daylightcontrolisenabledinallscenes

Note: Daylight control through the GRAFIK Eye® QS controlunitonlyaffectslightingloads.Shadegroupscannot be controlled by daylight sensors. Daylighting does notaffectDMXorRGB/CMYDMXloads.

Contact Closure Input (CCI) with Power Supply Output

•EachGRAFIKEye® QS control unit has one contact closure input (Terminal A).

- The attached device must provide a dry contact closure or solid-state output.

- Input is miswire-protected up to 36 V .•Thecontactclosureiscapableofacceptingthefollowingtypesofinputs:

-Maintained(default):TheGRAFIKEye® QS control unit will act on both a contact closure and a contact open/release event.

- Momentary: The GRAFIK Eye® QS control unit will act on only contact closure events.

•EachGRAFIKEye® QS control unit can supply 50 mA maximum at 24 V .

-Usefulforpoweringoccupancysensors. -Anauxiliarypowersupplymustbeusedifthedevice

requires more than 50 mA.

•TheCCIiscapableofoperatinginthefollowingmodes -Occupancy:Ifanoccupancysensoriswireddirectlyto

the GRAFIK Eye® QS control unit. - Emergency: This setting allows the GRAFIK Eye® QS

control unit to work with a LUT-ELI. When an emergency situationisdetected,alllightswillgotofullon,andnooperations will be allowed until the emergency signal is cleared.

-Afterhours:AllowstheCCItostartandendtheafterhoursmode.

- Timeclock: Allows the CCI to enable and disable the timeclock.

-SceneLockout:Preventstheuserfrommakinganychanges to the control unit. The current scene will stay on until the CCI enables normal operation.

-SaveNever:Preventsanychangesfrombeingsavedwhilethe CCI is being used.

-DisableCCI:TheCCIwillhavenoeffectonthesystemandwillnotappearonthelistofavailablesensors.

Security Lockout Password•A4-characterpassword(usingcharactersAtoZand0

to 9) can be enabled/disabled to lock out access to the Programming Menu.

•BydefaultthereisnopasswordenabledontheGRAFIKEye® QS control unit.

• Ifcasethe4-digitpasswordisforgotten,contactLutronTechnical Support to regain access.

Page 7: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

220 - 240 V 50 / 60 Hz 120 - 127 V 50 / 60 Hz

Unit Capacity (watts) 3000 2000

MLV 3000 VA / 2400 W 2000 VA / 1600 W

Zone Capacity (watts) 40 – 1200 25 – 800

MLV 40 – 1200 VA / 40 – 960 W 25 – 800 VA / 25 – 600 W

Load Type Notes (Zones 1, 2 and 3)•Allelectroniclow-voltage(ELV)lightingusedwithaninterfacemustberatedforreversephasecontroldimming.BeforeinstallinganELVlightsource,verifywiththemanufacturerthattheirtransformercanbedimmed.Whendimming,anELVinterface(suchasthePHPM-PA-DV-WH)mustbeusedwiththecontrolunit.

•Notallzonesmustbeconnected;however,connectedzonesmusthaveaminimumloadasspecifiedabove.•Maximumtotallightingloadforamagneticlow-voltage(MLV)variesbyinputvoltage: -120-127V : 800 VA / 600 W - 220 - 240 V : 1200 VA / 960 W•MaximumtotallightingloadforLutronTu-Wire®andAdvanceMarkX®electronicdimmingballasts(120to127V only)mustnotexceed6Aperzoneor16Aperunit.

•Nozonemaybeloadedwithmorethanthecapacityspecifiedabove.Forhigherwattageapplications,orfor277Vapplications,useLutronpowermodulePHPM-PA,PHPM-WBX,PHPM-PA-DV,PHPM-SW,orPHPM-WBX-DV.

•Forcontrollinglow-wattageloads(CFL,LED)inanon-dimapplication,contactLutronTechnicalSupportfortheappropriate solution.

System Limits•TheQSwiredcommunicationlinkislimitedto100devicesor100zones.

Capacities

®

Preset Dimming Controls

369309 Rev. B 7 11.17.11

Control Unit

Page 8: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

GRAFIK Eye® QS Control UnitCustom Color Options and Model Numbers You must order a Base Unit and a Faceplate KitSee Standard Color Combinations page for faceplate, stripe, and button colors

QSGFP - - Faceplate Prefix

Color/ Finish

Number ofShadeColumns

Omit = none 1 = 1 column 2 = 2 columns 3 = 3 columns

Architectural Matte FinishesStandard (ship in 48 hours)White WHIvory IVBeige BEGray GRBrown BRBlack BLAlmond ALLight Almond LA

Architectural Metal FinishesBright Brass BBBright Chrome BCBright Nickel BNSatin Brass SBSatin Chrome SCSatin Nickel SNAntique Brass QBAntiqueBronze QZ

Anodized Aluminum FinishesClear CLABlack BLABrass BRA

Satin Color Matte FinishesSnow SWBiscuit BIEggshell ESTaupe TPMidnight MNLimestone LSStone STDesert Stone DSTerracotta TCHot HTGoldstone GSPalladium PDPlum PLTurquoise TQBluestone BGSea Glass SGGreenbriar GBSienna SIMerlot MRMocha Stone MS

Top Door Color

Faceplate Kit (includes coordinating stripe and buttons)

Faceplate Custom Color/Finish Codes

Keypad Engraving

Code

Keypad Engraving Codes

Omit = Unengraved Shipswithengravingcertificatethatcustomer can redeem at no charge

EGN = General Engraving

NST = Non-Standard Text Engraving Please visit the GRAFIK Eye® QS website at www.lutron.com/grafikeyeqs forcustomengravingforms.Submitcompletedformwithorder,andunitwillshipengravedasspecifiedbycustomer.

Omit = same as unit

T = Translucent

Base Unit

QSGR - _ PPrefix

Number ofZones 3=3zones

4=4zones6=6zones

Phase Control Triac

OK

1 2 3 4 5 69 10 11 12 13 14 7 815 16

9-161-8

1

2

3

4

Off

OK

1 2 3 4 5 69 10 11 12 13 14 7 815 16

9-161-8

Open

Preset

Close

Lighting keypad

Shade column

Example:

QSGR-6P6-zonebaseunit andQSGFP-2IV-EGNIvoryfaceplatekitwithtwoshade columns and general engraving

Preset Dimming Controls

369309 Rev. B 8 11.17.11

Control Unit

Page 9: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

QSGB - 5B - WH - Custom Button

KitPrefixKeypad

Engraving Code

Button Configuration

3BRL = 3-button with raise/lower (shade column)

5B = 5-button (lighting keypad)

Button Color/ Finish

GRAFIK Eye® QS Control UnitCustom Options and Model Numbers See previous page for Other Custom Model NumbersSee Standard Color Combinations page for faceplate, stripe, and button colors

Custom Button Kit

Button Kit Custom Color/Finish CodesArchitectural Matte FinishesWhite WHIvory IVBeige BEGray GRBrown BRBlack BLAlmond ALLight Almond LA

Satin Color Matte FinishesSnow SWBiscuit BIEggshell ESTaupe TP

Custom Stripe Kit

QSGS - WHStripe

Kit Prefix

Stripe Color/Finish

Stripe Custom Color/Finish CodesSame as Faceplate colors on previous page

Keypad Engraving Codes

Omit = Unengraved Shipswithengravingcertificatethatcustomer can redeem at no charge

EGN = General Engraving

NST = Non-Standard Text Engraving Please visit the GRAFIK Eye® QS website at www.lutron.com/grafikeyeqs forcustomengravingforms.Submitcompletedformwithorder,andunitwillshipengravedasspecifiedbycustomer.

OK

1 2 3 4 5 69 10 11 12 13 14 7 815 16

9-161-8

1

2

3

4

Off

OK

1 2 3 4 5 69 10 11 12 13 14 7 815 16

9-161-8

Open

Preset

Close

Lighting keypad

Shade column

Preset Dimming Controls

369309 Rev. B 9 11.17.11

Control Unit

Page 10: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

GRAFIK Eye® QS Control Unit Standard Color CombinationsSee previous pages for Custom Model Numbers

Suffix Faceplate (F) Stripe (S) Button (B)Architectural MatteWH White Gray WhiteIV Ivory Beige IvoryBE Beige Ivory BeigeGR Gray Black GrayBR Brown Black BrownBL Black Gray BlackAL Almond Light Almond AlmondLA Light Almond Almond Light AlmondArchitectural MetalBB Bright Brass Black BlackBC Bright Chrome Black BlackBN Bright Nickel Black BlackSB Satin Brass Black BlackSC Satin Chrome Black BlackSN Satin Nickel Black BlackQB Antique Brass Black BlackQZ AntiqueBronze Black BlackAnodizedCLA Clear Black BlackBLA Black Black BlackBRA Brass Black Black

Suffix Faceplate (F) Stripe (S) Button (B)Satin MatteMN Midnight Gray BlackTP Taupe Gray TaupeSW Snow Gray SnowES Eggshell Beige EggshellBI Biscuit Eggshell BiscuitLS Limestone Gray GrayST Stone Gray GrayDS Desert Stone Taupe TaupeTC Terracotta Taupe TaupeBG Bluestone Gray GrayHT Hot Taupe TaupeMR Merlot Taupe TaupeSI Sienna Brown BrownGB Greenbriar Gray GraySG Sea Glass Gray GrayMS Mocha Stone Taupe TaupeGS Goldstone Ivory IvoryPD Palladium Gray GrayPL Plum Taupe TaupeTQ Turquoise Gray Gray

LUTRON

1

2

3

4

Off

Preset

Close

Open

F(faceplate)

F(faceplate)

B (buttons)

S (stripe)

Faceplateiscomprisedofatopandbottom.The bottom will always be the color indicated under“faceplate.”Thetopmaybethesamecolorortranslucent.Usethechartforfaceplatesthathavethesamecolortopandbottom.Ifatranslucentlidischosen,thestripe will automatically be the same color as the bottom lid.

Example:IfyouorderQSGR-4P-1WH,yourGRAFIKEye®QScontrolunitwith4lightingzonesand1shadezonewillcomewithawhitefaceplate(both top and bottom), gray stripe, and white buttons.

Preset Dimming Controls

369309 Rev. B 10 11.17.11

Control Unit

Page 11: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

Preset Dimming Controls

369309 Rev. B 11 11.17.11

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

Control Unit

Wiring Diagrams

12

34

12

AB

C

123456LN

Load wiring

Communication link

Occupancy sensor/contact closure input and 24 V power

IR input

Terminations

Page 12: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

Preset Dimming Controls

369309 Rev. B 12 11.17.11

Control Unit

Power Group Wiring ExampleOntheQSlink,therearedevicesthatsupplypoweranddevicesthatconsumepower.EachdevicehasaspecificnumberofPowerDrawUnits(PDUs)iteithersuppliesorconsumes.APowerGroupconsistsofonedevicethatsupplies power and one or more devices that consume power; each Power Group may have only one power-supplying device.RefertotheQSLinkPowerDrawUnitsspecificationsubmittal(LutronPN369405)formoreinformationconcerning PDUs. Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the diagram. Between devices on the QS link that supply power, connect only terminals 1, 3, and 4 (NOT terminal 2), shown by the letter B on the diagram.Wiring can be T-tapped or daisy-chained.

LUTRON

LUTRON LUTRON

LUTRON

LUTRON

LUTRON

Power Group 1

Power Group 2

Power Group 3

A

A

A

B

B

B(Do not connect

terminal 2: 24 V )

(Do not connect terminal 2: 24 V )

(Do not connect terminal 2: 24 V )

Connect all 4 terminals within a power group:

1: Common 2: 24 V3 and 4: Data

Connect only 3 terminals between power groups:

1: Common 3 and 4: Data

Do not connect Terminal 2: 24 V

A

B

GRAFIK Eye® QScontrol unit Supplies PDUs

QS Power SupplySupplies PDUs

Energi Savr NodeTM QS unit Supplies PDUs

Control Interfaces Consume PDUs

Control Interfaces Consume PDUs

Quantum® panel Supplies PDUs

Wallstations Consume PDUs

Wallstations Consume PDUs

Wallstations Consume PDUs

QS Sensor Module with wired Occupancy SensorConsumes PDUs

Wireless Occupancy Sensordoes not consume PDUs

Page 13: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

Mounting

Line Voltage Wiring

Standard 4-gang U.S. wallbox, 3.5 in (89 mm) deep

12

34

12

AB

C

1 2 3 4 5 6 L N

Distribution Panel120 - 127 V 50 / 60 Hz

or220 - 240 V 50 / 60 Hz

12

34

12

AB

C

1 2 3 4 5 6 L N

To Load 1

To Load 2

To Load 3

To Load 4

To Load 5

To Load 6

Rear of QS control unit

•Pullpowerwiringfromdistributionpanelandtolightfixtures.•Eachlinevoltageterminalcanacceptone12AWG(2.5mm2) wire.•ConsultLutronfornon-dimrelaywiringand/orloadsideemergencytransferwiring.

Mounting screws (4)

GRAFIK Eye® QS control unit

Hinged bottom lid

Hinged top lid

Line voltage (hot/live) is labeled L.

Preset Dimming Controls

369309 Rev. B 13 11.17.11

Control Unit

Page 14: GRAFIK Eye QS Wired Domestic - Lutron Electronics · Model Numbers: SPECIFICATION SUBMITTAL Page Job Name: Job Number: Key Design Features • Lightning strike protection meets ANSI/IEEE

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

IEC PELV/NEC® Class 2 QS System Wiring•Wiringcanbedaisy-chainedorT-tapped.•Wiringmustberunseparatelyfromline/mainsvoltage.•Totallengthofcontrollinkmustnotexceed2000ft(610m).

LUTRON

LUTRON

LUTRON

LUTRONLUTRON

LUTRON

LUTRON

LUTRON

LUTRON

LUTRON

LUTRON LUTRON LUTRON

LUTRON

GRAFIK Eye® QS Control Unit

Sivoia® QS Shade

seeTouch® QS wallstations

LUTRON

LUTRON

LUTRON

LUTRONLUTRON

LUTRON

LUTRON

LUTRON

LUTRON

LUTRON

LUTRON LUTRON LUTRON

LUTRON

Daisy-Chain Wiring Example

T-Tap Wiring Example

GRAFIK Eye® QS Control Unit

Sivoia® QS Shade

Sivoia® QS smart panel

Sivoia® QS smart panel

seeTouch® QS wallstations

Preset Dimming Controls

369309 Rev. B 14 11.17.11

Control Unit

Wire Sizes (check compatibility in your area)

QS Link Wiring Length Wire Gauge Lutron Cable Part Number

Lessthan500ft(153m) Power (terminals 1 and 2)1 pair 18 AWG (1.0 mm2) GRX-CBL-346S(non-plenum)

GRX-PCBL-346S(plenum)Data (terminals 3 and 4)1 twisted, shielded pair 22 AWG (0.5 mm2)

500to2000ft(153 to 610 m)

Power (terminals 1 and 2)1 pair 12 AWG (4.0 mm2) GRX-CBL-46L(non-plenum)