GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 1 ~

 

GPRS Ethernet 

Data Logger   Technical Guide 

  [Version 8.1] 

 

GSX8  support GPRS, SMS 

GSN8  support GPRS, SMS, Ethernet 

NSX8  support Ethernet 

GSX8‐WF  support Wi‐Fi 

Smart Data Logger 

 

 

 

 

Revision 140603[V1.0G]

Page 2: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 2 ~

Contents

1.  Overview................................................................................................................................................. 3 

2.  Features .................................................................................................................................................. 4 

3.  Schematics .............................................................................................................................................. 5 

4.  Specification ........................................................................................................................................... 6 

5.  Network Module .................................................................................................................................... 6 

6.  Board ...................................................................................................................................................... 7 

7.  Power Input ............................................................................................................................................ 8 

8.  Input Output Schematics ....................................................................................................................... 9 

9.  Sensors/Transducers Connection & Calibration ................................................................................. 12 

10.  PC Connection via USB ......................................................................................................................... 13 

11.  SIM Card Installation ............................................................................................................................ 13 

12.  PC Connection via Ethernet ................................................................................................................. 14 

13.  Power Up .............................................................................................................................................. 15 

14.  Start Up ................................................................................................................................................. 16 

15.  Communication Protocol & Data Format ............................................................................................ 18 

16.  Simultaneous Data over GPRS and SMS .............................................................................................. 18 

17.  Data over Ethernet ............................................................................................................................... 19 

18.  Enquiry Command ................................................................................................................................ 20 

19.  Setup Command ................................................................................................................................... 34 

20.  How Data Logger response on alarm? ................................................................................................. 35 

21.  Temperature Alarm Time Delay .......................................................................................................... 36 

22.  Capturing, Logging & Upload ............................................................................................................... 37 

23.  Testing Data Upload ............................................................................................................................. 38 

24.  TCP and UDP Operation ....................................................................................................................... 40 

25.  Safety and Regulatory Notice .............................................................................................................. 41 

26.  Manufacturer’s Disclaimer Statement ................................................................................................ 42 

 

   

Page 3: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 3 ~

1. Overview 

GSX8 Data Logger are standalone RTU integrated with a 16 bit ARM MCU and low power consumption 

design. It’s built in digital processor, external interface, hardware watchdog, digital input, digital 

output, analog input and GPRS communication module. Wide operating temperature, electromagnetic 

resistant, anti‐vibrant and numerous interface protocols provide a highly reliable design for industrial 

application.  

GSX8 is powered by 10~15VDC, and backup by internal rechargeable battery. Internal rechargeable 

battery maintains data and continuous operation when power loss. 

GSX8‐HV is dedicatedly designed for temperature & humidity measurement supporting max. 8 x 

temperature channels, 1 x humidity channel and 2 x analog channel 

GSX8‐MS is integrated with Modbus protocol support 

 

 

(1) GSX8 supports GPRS and SMS data upload 

 

(2) NSX8 supports Ethernet data upload 

 

(3) GSN8 supports GPRS, SMS and Ethernet data upload 

 

(4) GSX8‐WF supports Wi‐Fi data upload 

 

 

 

   

Page 4: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 4 ~

2. Features 

Standard Features 

8 x Temperature Channels [GSX8‐HV], 2 x Temperature Channels [GSX8‐MS] 

Modbus Device Support [GSX8‐MS] 

1 x Humidity Channel 

8 x High Precision AD Sensor Channel 

4 x Pulse Channels 

10 x Digital Alarm Inputs 

4 x Relay Output 

4 x 4‐digits Numeric LED (Optional) 

Power loss / resume alarm 

Programmable Upload Interval (5 seconds ~ one day) 

Programmable Logging Interval (1 minute ~ 60 minutes) 

Programmable data capturing type, range, start point, alarm high/low 

1 x USB Port for local setup 

4MB Non‐volatile Memory storing  data logged and setup parameters on power loss 

35000 data records logged ‐ max. 120 days data with records every 5 minutes 

Expandable Memory SD Card Slot 

 

GSX8, GSN8 

Supports data upload via GPRS and SMS on schedule, triggered by alarm, or manual check 

Real Time Alarm Report via SMS and/or GPRS Data 

Support local and remote setup via SMS / GPRS 

Support Dynamic Domain Name or Fixed IP 

Support UDP or TCP protocol data transmission 

 

NSX8, GSN8 

1 x 10/100Mbps Ethernet Port for network setup and/or data transmission 

Support UDP or TCP protocol data transmission 

 

GSX8‐WF 

Wi‐Fi 11b/g/n for data transmission 

Support active and passive mode 

   

Page 5: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 5 ~

3. Schematics 

 

Server Receiving Data via GPRS& Ethernet 

 

 

 

 

 

 

 

   

Page 6: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 6 ~

4. Specification 

DC Power Source:  10 ~ 15VDC, 2A 

Internal Backup:  Rechargeable Battery DC7.4V, 1Ah 

  Enclosure:  Metal Casing,  165 x 130 x 30 mm 

 

Current  200mA (Data Upload) 

  20~50mA (standby) 

Peak Pulse Current  < 1A 

Internal 5V DC Output:  max. 0.1A 

Operating Temp:  ‐50˚C ~ +70˚C 

Standby Temp:  ‐50˚C ~ +80˚C 

 

  Safety: 

Do not touch the antenna 

GSM 900MHz, 2W max. / GSM 1800MHz, 1W max. 

Not designed for medical equipment or aerospace application 

 

5. Network Module 

GPRS  

Wireless:  It supports GSM and GPRS class 10. 

    GSM 850  E‐GSM 900  DCS 1800  PCS1900 

  Rx band (MHz)  869~894  925~960  1805~1880  1930~1990 

  Tx band (MHz)  824~849  880~915  1710~1785  1850~1910 

  Rx Sensitivity  ‐109 dBm  ‐109 dBm  ‐108 dBm  ‐108 dBm 

  Tx Sensitivity  33 dB  33 dB  30 dB  30dB 

  RF Rating  2W  2W  1W  1W  

  Loading Resistance  50 Ohm 

  GSM Quad:  Cinterion MC55i Quad Band   [850/900/1800/1900] 

  3G Version:  Cinterion EHS5 Quad Band   [850/900/1800/1900] 

    Cinterion EHS6 Five Band  [800/850/900/1800/2100] 

 

Ethernet 

Ethernet:  10/100Mbps Ethernet  

    RJ45 Port 

 

Wi‐Fi 

Wi‐Fi 11b/g/n    

Page 7: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 7 ~

6. Board 

Internal Layout 

 

  

 

Front Panel 

 

  

 

Back Panel 

 

  

 

Page 8: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 8 ~

7. Power Input 

7.1 DC Power Input 

Power Voltage Source  9~15V DC should be connected to POW and GND. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.2 Internal Rechargeable Battery 

Short the pins BAT‐1 and BAT‐2 to turn on the rechargeable battery 

When device is not in use, open the pins connection to save the power of rechargeable 

battery 

When external DC power is connected and BAT pins are shorted, device is powered by 

external power and internal battery is being charged.  

Charging will be automatically stopped when battery is full. 

When external power input is lost, device will be powered by internal battery. 

 

   

+ _ 

Page 9: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 9 ~

8. Input Output Schematics 

8.1 Analog Sensor Input 

AD01 ‐ 08 

Analog Channel  AD01 ~ 02  AD03 ~ 08 

  Jumper  No Jumper 

Input Type  Current  Voltage  Voltage  Current 

Range  DC 4~20mA  DC 0 ~ 5V  DC 0 ~ 2V  DC 4~20mA 

Input Impedance R  250 Ω  15K Ω  15K Ω  250 Ω 

 

 

8.2 Digital Input   

IN01 [Power Loss/Resume] 

External Power Loss / Resume Alarm 

 

IN02 ‐ 03 [Optical‐Coupled Digital Input] 

a) On/Off – power type   

Triggered Level > 20ms 

Input Resistance 1KΩ, 1/4W, DC5~24V voltage 

b) Pulse Channel – power type 

Pulse Frequency Measure > 20ms 

Input Resistance 1KΩ, 1/4W, DC5~24V voltage 

 

IN04 ‐ 05 [Programmable Channel] 

a) On/Off – dry contact 

b) Pulse Channel – dry contact 

 

8.3 Programmable Input   

GSX8‐MS   

* IN06 – 11  [On/Off Alarm Input – dry contact] 

 

GSX8‐HV 

Programmable as: 

* T3 – T8   [Temperature Channel] 

  * IN06 – 11  [On/Off Alarm Input – dry contact]   

Page 10: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 10 ~

 

8.4 Relay Output 

Max. Loading:  DC24V @1A, AC220V @1A 

 

OUT 1 – 2 

  Jumper 1‐2 short:  Normal Close 

  Jumper 2‐3 short:  Normal Open 

 

OUT 3 – 4 

  No Jumper:  Normal Open 

 

 

Wiring Diagram 

 

 

 

 

 

 

8.5 RS232 & RS485 Port  

GSX8‐MS only 

ModBus Protocol via RS232 or RS485 Port 

Support Modbus Meter and Sensor 

 

 

 

 

   

Page 11: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 11 ~

 

8.6 Temperature Sensor Input 

Digital Temperature Sensors T‐V2 must be used 

Internal DC 5V is capable of providing power for 8 sensors 

Support max. 150 meter shielded cable 

Sensor should ONLY be connected to T1 ~ T8 channel (T1 ~ T2 only for GSX8‐MS) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.7 Temperature & Humidity Sensor Input 

Temperature & Humidity Combo Sensor TH‐V3 must be used 

Internal DC 5V is capable of providing power for the sensor 

Support max. 150 meter shielded cable 

Sensor should ONLY be connected to T & H channel 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

Temperature Sensor 

Model:      DS18B20 

Temperature Range:  ‐50 ~ 125C 

Accuracy:    0.5C 

T_V2:      max. 150 meter cable 

Color Code: 

T_V1  Red / Blue / Black 

T_V2  Red / Yellow / Black 

Humidity Sensor 

Model:      CHM‐01A 

Humidity Range:  0 ~ 100%RH 

Accuracy:     5%RH 

TH_V3:      max. 150 meter cable 

Page 12: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 12 ~

9. Sensors/Transducers Connection & Calibration 

Sensor Output:  Current Type 

Range:  4 ~ 20mA 

Jumper:  1‐2 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  3 wire type  2 wire type 

 

 

Sensor Output:  Voltage Type 

Range:  0 ~ 5V DC 

Jumper:  3‐4 

 

 

 

 

 

 

 

When sensor output is 0~10V DC, 250 precise resistor can be connected in serial for 5VDC range. 

Signal converter can be used for higher accuracy. 

 

  Make sure that the connection of sensor devices is followed according to its output type. Wrong 

wiring may damage not only the sensor but also the data logger. 

   

Page 13: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 13 ~

10. PC Connection via USB 

USB Port is available for PC connection running “GSX8_Setup” Software locally: 

configuration  setup 

data download  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11. SIM Card Installation 

1) Press the yellow button to release the SIM card caddy as shown below. 

2) Insert the SIM card into caddy. 

3) Make sure that the golden contact is facing down when inserting the SIM card caddy. 

4) PIN of SIM Card must be disabled   

Page 14: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 14 ~

12. PC Connection via Ethernet 

Ethernet Port is available for PC connection running “GSX8_Setup” Software over network: 

configuration setup 

data download 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

Page 15: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 15 ~

13. Power Up 

Connect the AC power adaptor to the unit 

Power: DC10‐15V, 2A 

Connect BAT‐1 and BAT‐2 when internal rechargeable battery is connected 

 

 

 

 

 

 

 

LED Status: 

  Status 1  Status 2  Normal  Error 

LED1  Flash @3s    Flash @3s  Flash @1s 

LED2  Fast Flash: Network Registration  6 x Flash: Data Upload  Off   

LED3  Flash – power alarm  4 x Flash: SMS Send or Receive  Off   

LED4    Flash: Command Setting  Off   

LED5    Flash : RS485 Communication  Off   

LED6    Flash: RS232 Communication  Off   

LED7    On: AD Channel Alarm  Off   

LED8    On: IN Channel Alarm  Off   

   

+ _ 

Page 16: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 16 ~

14. Start Up 

14.1) Power On 

Signal LED 

OFF>ON  GPRS network registration success 

    OFF  GPRS network registration fail  

a) GPRS module defective 

b) SIM card defective 

c) Network Unavailable 

d) GSX8 Device Setup not configured properly 

       

Note: GPRS network registration takes about 1 ~ 1.5 minutes 

 

During the first time start up, GPRS registration usually fails because of incomplete 

configuration of GPRS network properties. 

 

 

14.2) Ethernet Network Setup  

Data Logger IP Address  

Data Logger IP Port 

Data Logger IP Subnet 

 

Page 17: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 17 ~

 

14.3) GPRS Data Logger Network Setup 

Use mobile phone sending SMS command to setup the following parameters.  

Use PC and “GSX8_Setup” Software to setup the following parameters 

1) When public fixed IP is available, please follow the steps below in sequence. 

GPRS Access Point    (APN) 

Server IP Port 

Server IP Address 

Domain Name is left blank 

 2) When no public fixed IP is available, dynamic domain name is needed.  

GPRS Access Point   (APN) 

Server IP Port 

Server IP Address is left blank 

Domain Name    (please visit 

www.dyndns.com/support/kb/what_is_dns.html) 

 

After GPRS network registration, the green GPRS LED on “GSX8_Setup Software” screen indicates 

the proper network access.  

 

 

14.4) Server PC Network Setup 

1) When public fixed IP is available, please follow the steps below. 

Configure public fixed IP address in Server PC if it is connected to Internet directly 

Configure router WAN IP as public fixed IP address and port forward to server local LAN IP 

if server PC is connected to Internet via router 

Open the Server port in firewall and router 

 2) When no public fixed IP is available, dynamic domain name is needed.  

Use DDNS service e.g. http://www.dyndns.com, and apply for a domain name 

Router port must be forwarded to server local LAN IP 

Use the DNS tool to map the domain name and server local LAN IP address 

Open the Server port in firewall and router 

 

 

Page 18: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 18 ~

15. Communication Protocol & Data Format 

Communication Protocol:  UDP, TCP, SMS, Ethernet 

 

Data Header Description: 

STA  Real Time Data 

STB  Packet Data 

STC  Parameters Check 

STD  Historical Data  

STH  1st Level Alarm Data  

STG  2nd Level Alarm Data 

STA  Alarm Message 

STS  Acknowledge Message to Setup Command 

 

 

 

16. Simultaneous Data over GPRS and SMS 

When GPRS data upload is unsuccessful, GSX8 will redial and try to connect to GPRS network for re‐

uploading the data. 

During the redial interval or re‐uploading the data via GPRS DATA, any SMS command will be lost and 

schedule SMS data upload will also be dismissed. 

Therefore, when the GPRS data upload interval is short, it is recommended to select a longer SMS 

upload interval and vice versa. 

It normally takes about 45~60 seconds to complete an incoming SMS command or outgoing SMS data 

upload. 

 

 

   

Page 19: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 19 ~

17. Data over Ethernet 

 17.1) Ethernet Data 

Both UDP & TCP protocol are supported in Ethernet Data. 

Packet Data format over Ethernet is supported only when GPRS is enabled. 

 

17.2) Data Upload Interval 

Upload Interval is the same for both GPRS and Ethernet Data. 

 

17.3) Can the server receiving GPRS data and the server receiving Ethernet data the same computer? 

Computer installed with Ultimate Server software will be able to receive data over GPRS 

and Ethernet at the same time. 

  GPRS Server IP:  server receiving data over GPRS 

Ethernet Server IP:  server receiving data over Ethernet 

 

 

 

 

   

Page 20: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 20 ~

18. Enquiry Command 

A) Real Time Status Check  

Mode:  GPRS Data, GSM SMS, USB, Ethernet 

Command:  999999#STATUS# 

 

GPRS Reply Message:  Live Data 

#STA:000000,000;L:310;TM:090516195102;D:1;T:01;C:25;A01:00000;A02:0.578;A03:00000;A04:00

000;A05:00000;A06:00000;A07:00000;A08:00000;A09:00000;A10:00000;A11:00000;P01:00000000

;P02:00000000;P03:00000000;P04:00000000;K01:13333330000000000;O01:0000;8F# 

 

SMS Reply Message: Live Data 

#STA:000000,000;L:310;TM:03/04/2009,09:34;D:1;T:01;C:25;A00:0.166;A01:00000;A02:0.578;A03:

00000;A04:00000;A05:00000;A06:00000;A07:00000;A08:00000;A09:00000;A10:00000;A11:00000;

A12:00000;A13:31.00;A14:30.93;P01:00000000;P02:00000000;P03:00000000;P04:00000000;P05:0

0000000;P06:00000000;K01:13333330000000000;O01:0000;8F# 

 

P.S.:  Max. 160 characters in each SMS message, second SMS messages with header STA: will be 

sent when data is more than 160 characters. 

 

 

#STA: 000000,000  STA    Header: Live Data 

  000000  Station ID 

  000    Hardware Version 

 

L:310  Number of characters in packet from “S” to the last “;” inclusive 

TM:0702011200  Current Date Time of GPRS Data Logger (yymmddhhmm) 

 

D:1  Logging Interval 

 

 

 

 

 

T: 01  Number of records in each data packet 

 

C: 08  Counter of packets uploaded 

D  Data Logging Interval 

5  1 minute 

1  5 minutes 

2  15 minutes 

3  30 minutes 

4  60 minutes 

Page 21: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 21 ~

  It is used to check any loss of data packet. 

  It should be increasing and reset to 00 when it is over 99. 

 

A01:00000  Value captured on AD Channel 1  [A02, A03… A11 are the same] 

 

 

P01:01234212  Accumulated Pulses captured  [P02, P03… P06 are the same] 

  It is accumulated, and reset to 0 when it is over 99999999 

 

K:xyyyyyyzzzzzzzz  First digit   x – status of power source 

    1:  AC power input is ON 

    0:  AC power input is OFF (now powered by battery) 

  2nd ~ 7th digit  yyyyyy – status of Digital Channel 01 ~ 06 

    3:  Configured as Pulse Channel 

    1:  Configured as On/Off Channel, Alarm Input is closed 

    0:  Configured as On/Off Channel, Alarm Input is open 

  8th ~17th digits  zzzzzzzzzz – status of Digital Channel 07 ~ 16 

    1:  Configured as On/Off Channel, Alarm Input is closed 

    0:  Configured as On/Off Channel, Alarm Input is open  

 

O01:0000  indicates the status of Digital Output [Relay Output] 

    1  Close 

    0  Open   

8F  Parity Check 

#  End Symbol 

 

   

Page 22: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 22 ~

B) Automatic schedule data upload 

Mode:  GPRS Data, GSM SMS, RS232, Ethernet 

Command:  upload is on schedule, and no command is necessary 

Reply Message:  upload is in packet data 

 

#STB:000000,000;L:642;TM:0906121535;D:1;T:03;C:17; 

A01:‐0.24|‐0.24|‐0.24;A02:‐0.24|‐0.24|‐0.24;A03:‐0.24|‐0.24|‐0.24;A04:‐0.24|‐0.24|‐0.24;A05:‐

0.24|‐0.24|‐0.24;A06:‐0.24|‐0.24|‐0.24;A07:‐0.24|‐0.24|‐0.25;A08:‐0.25|‐0.25|‐0.24;A09:‐0.24|‐

0.24|‐0.25;A10:‐0.24|‐0.24|‐0.24;A11:‐0.24|‐0.24|‐0.24; 

A11:‐0.24|‐0.24|‐0.24;A13:‐0.06|‐0.06|‐0.06;A14:‐0.06|‐0.06|‐0.06; 

P01:00000016|00000016|00000016;P02:00000006|00000006|00000006;P03:00000005|0000000

5|00000005;P04:00000009|00000009|00000009; 

K01:13333330000000000|13333330000000000|13333330000000000;O01:0000|0000|0000;19# 

 

#STB: 000000,000  STB    Header: Packet Data 

  000000  Station ID 

  000    Hardware Version 

 

L:642  Number of characters in packet from “S” to the last “;” inclusive 

TM: 0906121535  Starting Date Time of Data Packet (yymmddhhmm) 

 

D:1  Logging Interval 

 

T: 03  Number of records in the data packet 

C: 08  Counter of packets uploaded 

 

|    Data record separator 

    Each data record interval will be defined by parameter D 

XX  Parity Check 

#  End Symbol 

 

In this example:  Upload Interval is 15 minutes 

  Logging Interval is 5 minutes 

  Records at 15:35, 15:40, 15:45 are packed into the data 

 

 

D  Data Logging Interval 

5  1 minute 

1  5 minutes 

2  15 minutes 

3  30 minutes 

4  60 minutes 

Page 23: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 23 ~

Another Example:  Upload Interval is 30 minutes 

  Logging Interval is 15 minutes 

 

  D: 2    Logging Interval is 15 minutes 

  T:02    Number of records is 2 in this data packet 

      Records at 15:30, 15:45 are packed into the data 

 

#STB:000000,000;L:475;TM:0906121530;D:2;T:02;C:17; 

A00:00000|00000;A01:‐0.24|‐0.24;A02:‐0.24|‐0.24;A03:‐0.24|‐0.24;A04:‐0.24|‐0.24;A05:‐0.24|‐

0.24;A06:‐0.24|‐0.24;A07:‐0.24|‐0.24;A08:‐0.25|‐0.25;A09:‐0.24|‐0.24;A10:‐0.24|‐0.24;A11:‐

0.24|‐0.24;A12:‐0.24|‐0.24;A13:‐0.06|‐0.06;A14:‐0.06|‐0.06; 

P01:00000016|00000016;P02:00000006|00000006;P03:00000005|00000005;P04:00000009|0000

0009;P05:00000006|00000006;P06:00000006|00000006; 

K01:13333330000000000|13333330000000000;O01:0000|0000;19# 

 

 

 

   

Page 24: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 24 ~

C) Historical Data Manual Retrieval  

Mode:  GPRS Data, USB Port [SMS is not supported], Ethernet 

Command:  999999#REDEEM090512161004# 

REDEEM  historical data retrieval 

0712281645  starting date time on 2009‐05‐12 at 16:45 

04  number of records to be retrieved each packet 

 Reply Message: 

#STD:000000,000;L:809;TM:0905161610;D:1;T:04;C:18; 

A01:‐0.24|‐0.24|‐0.24|‐0.24;A02:‐0.24|‐0.24|‐0.24|‐0.24; 

A03:‐0.24|‐0.24|‐0.24|‐0.24;A04:‐0.24|‐0.24|‐0.24|‐0.24;A05:‐0.24|‐0.24|‐0.24|‐0.24; 

A06:‐0.24|‐0.24|‐0.24|‐0.24;A07:‐0.24|‐0.24|‐0.24|‐0.24;A08:‐0.24|‐0.24|‐0.24|‐0.24; 

A09:‐0.24|‐0.24|‐0.24|‐0.24;A10:‐0.24|‐0.24|‐0.24|‐0.24;A11:‐0.24|‐0.24|‐0.24|‐0.24; 

A11:‐0.24|‐0.24|‐0.24|‐0.24;A13:33.06|32.00|33.18|33.18;A14:31.68|30.87|31.62|31.87; 

P01:00000000|00000000|00000000|00000000;P02:00000000|00000000|00000000|00000000; 

P03:00000000|00000000|00000000|00000000;P04:00000000|00000000|00000000|00000000; 

K01:13333330000000000|13333330000000000|13333330000000000|13333330000000000; 

O01:0000|0000|0000|0000;48# 

 

STD:000000,000  STD  Historical Data Packet 

    000000 Station ID 

    000  Hardware Version 

 

L:809  Number of characters in packet from “S” to the last “;” inclusive 

TM: 0905161610  Starting Date Time of Data Packet (yymmddhhmm) 

D:1  Logging Interval 

 

T:04  Number of records in the data packet 

    4 records at 16:10, 16:15, 16:20, 16:25 

are in the data packet 

 

C:07  Counter of packets uploaded 

  It is used to check any loss of data packet. 

  It should be increasing and reset to 00 when it is over 99. 

 

 

D  Data Logging Interval 

5  1 minute 

1  5 minutes 

2  15 minutes 

3  30 minutes 

4  60 minutes 

Page 25: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 25 ~

AD Channel record data:   

A01:3.323|3.323|3.323|3.323   

 

Pulse Channel record data: 

P01: 00087032|00087679|0008790|0008790   

 

Digital Input On/Off record data:   

K: 13333330000000000|13333330000000000|13333330000000000|13333330000000000 

 

|  Data record separator 

48    Parity Check 

#    End Symbol 

 

 

GPRS Data & USB 

Max. number of records to be retrieved each time:  99 records 

Max. number of records each data packet:    30 records 

When more than 30 records are retrieved, more than one data packets will be sent . 

For example, 46 records are to be retrieved from the Data Logger. 

2 packets will be delivered. 

1st packet: 30 records 

2nd packet: 16 records 

 

GSM SMS   

Only one record can be retrieved each time via SMS owing to the limitation of SMS text length. 

 

 

Storage Period: 

1) Internal Memory: 1MB 

2) Records can be kept in the device at about 90 days when logging interval is at 15 minutes. 

3) The storage period can be longer than 90 days when logging interval is set at 60 min. 

4) When there is no record data on selected date, packet data will only include characters “9”. 

   

Page 26: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 26 ~

D) System Parameters Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK1# 

Reply Message:   

#STC1:000000,000;L:395;TM:1111141028;PS:999999,888888;SA:1;SD:02,1,1;CP:,0;AP1:012345678

9012345678;AP2:0123456789012345678;AP3:0123456789012345678;AP4:0123456789012345678

;AP5:0123456789012345678;AP6:0123456789012345678;AP7:0123456789012345678;AP8:01234

56789012345678;65# 

 

#STC1:000000,000  Header, Station ID, Hardware Version 

L:227  Number of characters in packet from “S” to the last “;” inclusive 

 

TM: 0905161954  Current date time of GPRS Data Logger (yymmddhhmm) 

PS:999999,888888  Check Password, Setup Password 

 

SA:2  Data Logging Interval 

 

 

 

 

 

 

 

SD:xx,y,z  Upload Interval, Data Format, Number of times data is uploaded 

  xx:   GPRS Upload Interval  GSX8‐HV  

    Ethernet Upload Interval  GSN8‐HV, NSX8‐HV 

 

 

    y=0:  Live Data 

    y=1:   Packet Data 

 

    z= number of re‐upload 

 

 

 

  When upload interval is 24 hours, data is uploaded every day at 8:00am.  

   

SA  Data Logging Interval 

0  No Save 

5  1 minute 

1  5 minutes 

2  15 minutes 

3  30 minutes 

4  60 minutes 

xx = 00  No Upload  05  15 minutes 

12  5 seconds  06  30 minutes 

13  15 seconds  07  1 hour 

01  30 seconds  08  2 hours 

02  1 minute  09  6 hours 

03  2 minutes  10  12 hours 

04  5 minutes  11  24 hours 

Page 27: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 27 ~

 

CP:yyyyyyyyyyy,X  Control Center Phone Number (receiving SMS), Upload Interval via SMS 

 

 

 

 

 

 

AP1:xxxxxxxxxxx  Alarm Phone Number 1 

  AP2 is the same for alarm phone number 2 

  AP8 is the same for alarm phone number 8 

 

 

65  Parity Check 

#  End Symbol 

   

X = 0  No Upload  5  1 hour 

1  1 minute  6  2 hours 

2  5 minutes  7  6 hours 

3  15 minutes  8  12 hours 

4  30 minutes  9  24 hours 

Page 28: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 28 ~

E) System Parameters Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK2# 

Reply Message:   

#STC2:000000,000;L:395;ID:internet;IA1:1;IP1:125.124.128.246;IY1:;IH1:07000;IT1:0136;IR1:0920;I

U1:1;IC1:1;ER:0000;IE:0;INA:;IWD:;SIMP:000000;XH:31;46;# 

 

#STC2:000000,000  Header, Station ID, Hardware Version 

L:395  Number of characters in packet from “S” to the last “;” inclusive 

 

 

ID:internet  GPRS APN (Access Point Network) 

IA1:1  Server Location    1: Fixed IP    0: Domain Name 

IP1: 210.3.32.70  Server Fixed IP Address 

IY1:dyndns.com  Domain Name 

IH1:5600  Server Port  

T1:  Acknowledge Interval 

IR1:  Redial Period 

IU1:1  Connection Protocol    1: UDP Protocol 0: TCP Protocol 

 

ER:0000  GPRS Module Status 

  First Digit  0: Module Normal  1: Module Defect 

  Second Digit  0: SIM Card Normal  1: SIM Card Defect 

  Third Digit  0: GPRS Connection Normal  1: Connection Error 

  Fourth Digit  0: SIM PIN Normal  1: SIM PIN Error 

 

IE:0  0  APN User Account disabled 

  1  APN User Account enabled 

INA:  APN User Name 

IWD:  APN Password 

SIMP:  SIM PIN 

XH:29  Network Signal Strength 

3C  Parity Check 

#  End Symbol 

   

Page 29: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 29 ~

F) Input Channel Parameters Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK3# 

Reply Message:   

#STC3:000000,000;L:556;AD01:01,0,5.000,0.000,AD02:02,0,5.000,0.000,AD03:03,0,5.000,0.000,AD

04:04,0,5.000,0.000,AD05:05,0,5.000,0.000,AD06:06,0,5.000,0.000,AD07:07,0,5.000,0.000,AD08:0

8,0,5.000,0.000,AD09:09,0,100.0,0.000,AD10:10,0,80.00,0.000,AD11:11,0,80.00,0.000,INP1:01;INP

2:02;INP3:03;INP4:04;INP5:00;INP6:00;INP7:00;INP8:00;C5# 

 

#STC2:000000,000  Header, Station ID, Hardware Version 

L:556  Number of characters in packet from “S” to the last “;” inclusive 

 

AD01:   xx,y,aaaaa,bbbbb 

  Analog Digital Channel 01 

  xx  00: disable     

01: AD1 02: AD2  03: AD3  04:AD4  05:AD5  06:AD6  07:AD7  08: AD8 

09:SDAD9  10:T1/AD10  11:T2/AD11  12: MDBUS‐AD12 

13: MDBUS‐AD13 14:MDBUS‐AD14  15: MDBUS‐AD15  16: MDBUS‐AD16 

17:MDBUS‐AD17  18: MDBUS‐AD18  19:MDBUS‐AD19 

  y:   0:disable  1: enable  2: alarm enable 

  aaaaa    Hi Alert Value 

  bbbbb   Lo Alert Value   

 

When AD input source is 4~20mA current type and input resistance is configured as 250 ohm, the 

start zero should be 1.000 (0.004A x 250  = 1V). 

 

AD02~11  same as AD01 

INP1:AA  Pulse Channel 01 

  AA   00:disable 

01:DIN1  02:DIN2  03:DIN3  04:DIN4   

05:MDBUS‐PU5  06:MDBUS‐PU6  07: MDBUS‐PU7  08:MDBUS‐PU8  

09:MDBUS‐PU9  10: MDBUS‐PU10  11: MDBUS‐PU11  13:MDBUS‐PU12 

 

   

Page 30: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 30 ~

G) AD & DI Parameters Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK4# 

Reply Message:   

#STC4:000001,000;L:306;AIN1:5.000,0.000,1.000;AIN2:5.000,0.000,1.000;AIN3:5.000,0.000,1.000;

AIN4:5.000,0.000,1.000;AIN5:5.000,0.000,1.000;AIN6:5.000,0.000,1.000;AIN7:5.000,0.000,1.000;AI

N8:5.000,0.000,1.000;AIN9:150.0,0.000,0.000;DI01:0;DI02:1;DI03:1;DI04:0;DI05:0;DI06:1;DI07:0;DI

08:0;DI09:0;DI10:0;DI11:0;60;# 

AIN1:xxxxx,yyyyy,zzzzz 

AD Channel 01 

xxxxx  Upper Range Limit 

yyyyy  Lower Range Limit 

zzzzz  Start Zero 

 

DI01:m 

Digital Channel 01 

y  0:disable 

1:pulse channel 

2: NC triggered alarm 

3: NO triggered alarm 

4: Change State triggered alarm 

 

 

 

 

   

Page 31: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 31 ~

H) Output Channel Parameters Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK5# 

Reply Message:   

#STC5:000001,000;L:210;BTM1:0002;BTM2:0002;BTM3:0002;BTM4:0002;CTM1:0003;CTM2:0003;

CTM3:0003;CTM4:0003;CO1:0000000000000000000000;CO2:0000000000000000000000;CO3:000

0000000000000000000;CO4:0000000000000000000000;BA;# 

 

#STC5:000000,000  Header, Station ID, Hardware Version 

L:153  Number of characters in packet from “S” to the last “;” inclusive 

 

BTM1:0002  Alarm Triggered Relay Time Lapse (seconds) 

CTM1:0003  Command Controlled Relay Time Lapse (seconds) 

C01:0000000000000000000000 

  C01    Relay Output 1 

  Digit 1~11  AD01, AD02, AD03 … AD11 

  0: disable  1:2nd level high alarm  2: 2nd level low alarm 

  Digit 12~22  K01, K02 … K11 

  0: disable  1:NC triggered alarm  2: NO triggered alarm 

 

BA  Parity Check 

#  End Symbol 

   

 

I) RS232/RS485 Parameters Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK6# 

Reply Message:   

#STC6:000001,000;L:405;ZDAD1:001,00000,3,0;ZDAD2:001,00002,3,0;ZDAD3:001,00004,3,0;ZDAD

4:001,00006,3,0;ZDAD5:101,00008,3,0;ZDAD6:101,00010,3,0;ZDAD7:101,00012,3,0;ZDAD8:101,00

014,3,0;ZDPU1:001,00000,0,0;ZDPU2:001,00002,0,0;ZDPU3:001,00004,0,0;ZDPU4:001,00006,0,0;Z

DPU5:101,00008,0,0;ZDPU6:101,00010,0,0;ZDPU7:101,00012,0,0;ZDPU8:101,00014,0,0;RS232B:3,

0,00;RS45B:3,0,019,00;YB:0;;YV:0.000;YA:0.000;PLC:00,;7F;# 

 

ZDAD1:001,00000,3,0 

ZDAD1  Modbus ZAD01 Channel 

Page 32: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 32 ~

001  SADR Modbus Address 

00000  Data Register Address 

3  Data Type 

0  0: Disconnect 

  1: RS485 Modbus Meter 

  2: RS232 Modbus Meter 

 

ZDPU1:001,00000,0,0 

ZDPU1  Modbus ZP01 

001  SADR Modbus Address 

00000  Data Register Address 

3  Data Type 

0  0: Disconnect 

  1: RS485 Modbus Meter 

  2: RS232 Modbus Meter 

 

RS232B:3,0,00  3: Baud Rate 

  0: Even, 1: Odd, 3: None 

  00: Protocol 

 

RS45B:3,0,019,00  3: Baud Rate 

  0: Even, 1: Odd, 3: None 

  019: RS485 delay time 

  00: Protocol 

 

YB:0;;YV:0.000;YA:0.000 

  YB: Modbus Power Transducer Model 

  YV: Max. Voltage 

  YA: Max. Current 

 

PLC:00  Modbus Protocol 

 

 

   

Page 33: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 33 ~

J) Alarm Parameters Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK7# 

Reply Message:   

#STC7:000001,000;L:134;CPH1:0000000000000000000000;CPH2:0000000000000000000000;CPH3

:0000000000000000000000;CPH4:0000000000000000000000;79;# 

Command:  999999#CHEACK8# 

Reply Message:   

#STC8:000001,000;L:134;CPH5:0000000000000000000000;CPH6:0000000000000000000000;CPH7

:0000000000000000000000;CPH8:0000000000000000000000;8A;# 

 

CPH1:  A01, A02, A03, … A11 

  K01, K02, K03, … K11 

  0: Alarm Disable 

  1: SMS Alarm 

  2: Call Alarm 

  3. SMS & Call Alarm 

 

 

K) SMS Alarm Message Check 

Mode:  GPRS DATA, GSM SMS, USB, Ethernet 

Command:  999999#CHEACK9# 

Reply Message:   

Alarm Resume Normal SMS Message 

 

 

 

L) Version Check 

Mode:  GPRS Data, GSM SMS, USB, Ethernet 

Command:  999999#VAR# 

Reply Message:  GSX8 VA‐1 2014‐03‐12 

   

Page 34: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 34 ~

19. Setup Command 

To learn the detail of each command and reply message, please refer to “Command Log” tab using 

GSX8_Setup Software. 

 

 

    

 

 

 

   

Page 35: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 35 ~

20. How Data Logger response on alarm? 

Alarm is triggered when Digital Input state is changed or AD Input reading is higher or lower than user 

preset values. User can be alerted via Ethernet, SMS or GPRS when alarm is triggered. 

 

When first level alarm is triggered: 

Live Data will be uploaded to Server via GPRS or Ethernet    header: STH 

Live Data will be sent to Control Centre via SMS      header: STH 

Alarm Text will be sent to Alarm Phone via SMS      header: STA 

 

When second level alarm is triggered: 

Live Data will be uploaded to Server via GPRS or Ethernet    header: STG 

Live Data will be sent to Control Centre via SMS      header: STG 

Alarm Text will be sent to Alarm Phone via SMS      header: STA 

 

 

     

Example: 

When Temperature 1 is over alert high value “85.00”, message “It is hot” is sent to user. 

Alarm Phone receives alarm text message:   

STA:000000:TM:2009/12/08/16:10;A13:85.00,It is hot 

 

Centre receives data message:   

#STH:000000,000;L:310;TM:03/04/2009,09:34;D:1;T:01;C:25;A00:0.166;A01:00000;A02:0.578;A0

3:00000;A04:00000;A05:00000;A06:00000;A07:00000;A08:00000;A09:00000;A10:00000;A11:00

000;A12:00000;A13:31.00;A14:30.93;P01:00000000;P02:00000000;P03:00000000;P04:00000000

;P05:00000000;P06:00000000;K01:13333330000000000;O01:0000;8F# 

 

   

Page 36: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 36 ~

21. Temperature Alarm Delay Time 

Alarm is triggered when TEMP 1 ~ 8 temperature reading is higher or lower than user preset 

values.  

Alarm will only be valid when the temperature keeps at higher or lower level for the time delay. 

User will only be alerted via SMS, GPRS or Ethernet only after the preset delay. 

When temperature reading returns to normal level within the time delay, the alarm will be 

cancelled. 

 

Configure the Temperature Alarm Delay Time: 

Command:   888888#TDY:xxxx# 

        Y:    Temperature Channel (TEMP 1 ~ 8) 

      xxxx    Delay Time (0000 ~ 9999 seconds) 

 

 

Note:   When the freezer or cold storage door is open for a while, the temperature may rise to an 

alert level during the worker operation. It is useful to avoid this kind of false alarm. 

     

   

Page 37: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 37 ~

22. Capturing, Logging & Upload 

1. Data Capturing 

It captures data from sensors every 2 seconds checking the alarm levels. 

 2. Data Logging 

It logs the captured data into its internal memory in interval of 5/15/30/60 minutes options. 

Logging interval is user programmable. 

Every logging interval, one record of data will be stored in internal memory. 

 3. Data Upload 

It uploads the logged data records in interval from 5 second up to once a day. 

Upload interval is user programmable. 

 

4. Packet Data 

When “Packet Data” is selected, more than one data records will be uploaded in packet. 

For example: 

Logging Interval = 5 minutes  Upload Interval = 15 minutes 

At 8:00 am, GSX8 will upload three data records logged at 7:50, 7:55, and 8:00 am in one packet. 

At 8:15 am, GSX8 will upload three data records logged at 8:05, 8:10, and 8:15 am in one packet. 

 

5. Live Data 

When “Live Data” is selected, only the last and real time data record will be uploaded. 

For example: 

Logging Interval = 5 minutes  Upload Interval = 15 minutes 

At 8:00 am, GSX8  will upload one data record captured at 8:00 am. 

At 8:15 am, GSX8  will upload one data record captured at 8:15 am.  

Data records at 8:00, 8:05, 8:10 and 8:15 am will be logged (saved) in internal memory. But only 

data captured at 8:00 and 8:15 am will be uploaded. 

 6. Instant Data Upload 

When GSX8 receives 999999#STATUS# command, it will capture the instant data and upload it. 

That means it will upload the real time data upon this command.  

However, this data record will not be logged (saved) in internal memory. 

   

Page 38: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 38 ~

23. Testing Data Upload 

A) Testing GPRS Data Upload 

Free bundled testing software “GSX8_Centre” is used to test the GPRS connection, data upload and 

device operation. Both UDP and TCP are supported. 

 

 

 

Please check carefully your local network and router configuration. In the example case: 

GPRS Data Logger – server network configuration 

GPRS Server IP:    210.3.133.88 

Server Port:   9050 

 

Computer running the GSX8_Centre should have the following network properties. 

Computer IP:    192.168.0.12 

Local Port:    9050 

 

 

Router Setup 

When router is installed between the PC and Internet, please open the ports for UDP and TCP. 

 

Firewall Setup 

Click “GSX8_Centre” program as exception in Firewall or disable the firewall. 

Open the ports defined by GSX8_Centre in the firewall setting. 

 

 

   

Page 39: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 39 ~

 

B) Testing Ethernet Data Upload 

Free bundled testing software “GSX8_Centre [UDP]” is used to test the GPRS connection, data 

upload and device operation. Only UDP is supported via Ethernet. 

 

 

Please check carefully your local network and router configuration. In the example case: 

Ethernet Data Logger – its own network configuration 

Device IP:    192.168.0.200 

Device Port:   7005 

 

Ethernet Data Logger – server network configuration 

Server IP:    192.168.0.18 

Server Port:   6005 

 

Computer running the GSX8_Centre should have the following network properties. 

GSX8 Centre IP:    192.168.0.18 

Local Port:    6005 

 

 

Please refer to “GSX8_Centre” manual for detail. 

   

Page 40: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 40 ~

24. TCP and UDP Operation 

(1) Data Format: TCP 

This is a type of handshake data transmission with auto data recovery to ensure accuracy. When 

the network signal coverage is weak, data transmission bandwidth will be huge. 

 

(2) Data Format: UDP 

This is a type of data upload without checking the data accuracy. Data transmission bandwidth 

can be expected or preset in advance. 

In UPD format, packet data is considered as a secure way of data transmission to ensure the 

receipt of data in control centre.  

GSX8 sends out the data packet to control centre (CTR IP).  CTR IP replies with “@888” message 

once it receives the data. GSX8 will try to resend the data packet if reply message “@888” is not 

received. 

 

 

(3) Data Acknowledge 

When Server receives the data from GSX8, it will be acknowledged with the GSX8 current port 

number and IP address. A confirmation message “@888” will be replied to GSX8. If any control is 

necessary, CTR IP can send the command as “@888xxxxxxx” (e.g. @888888888#SDx:y#) to GSX8 

at the same time. Usually, this method of sending command is secure because the port number 

and IP address of GSX8 will remain unchanged within 60 seconds after GSX8 sends out data. It is 

normal that the port number and IP address of GSX8 will only be released when GPRS Internet 

connection is idle after 60 seconds. 

 

   

Page 41: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 41 ~

25. Safety and Regulatory Notice 

All applicable regulatory compliance statements, product certification markings, and safety and 

electromagnetic compatibility (EMC) standards and regulations the Data Logger is compliant with. 

 

European Union Declaration of Conformity 

Statement 

We, 3gtrack.com declare under our sole responsibility that the product GSX8 GPRS Data Logger is in 

conformity with all applicable essential requirements necessary for CE marking, following the provisions of 

the European Council Directives 2004/108/EC (EMC Directive) and 2006/95/EC (Low Voltage Directive). 

 

 

The product is properly CE marked demonstrating this conformity and is for distribution within all member 

states of the EU with no restrictions. 

This product follows the provisions of the European Directives 2004/108/EC and 2006/95/EC. 

 

Customer Support Links 

View or download product support information from easemind website: 

http://www.easemind.hk 

http://www.easemind.net 

or email contact at:  [email protected] 

   

Page 42: GPRS Ethernet Data Loggermicrodatafi.myqnapcloud.com/ajurit/EaseMind/GSX/GSX8-WF/...GPRS Ethernet Multipoint Data Logger GSX8 /GSN8 / NSX8 Technical Guide ~ 3 ~ 1. Overview GSX8 Data

GPRS Ethernet Multipoint Data Logger  GSX8 /GSN8 / NSX8 Technical Guide 

~ 42 ~

26. Manufacturer’s Disclaimer Statement 

The  information  in  this  document  is  subject  to  change  without  notice  and  does  not  represent  a 

commitment on  the part of  the  vendor. No warranty or  representation,  either expressed or  implied,  is 

made with  respect  to  the quality,  accuracy or  fitness  for  any particular purpose of  this document.  The 

manufacturer  reserves  the  right  to make  changes  to  the  content of  this document and/or  the products 

associated with it any time without obligation to notify any person or organization of such changes. In no 

event will  the manufacturer  be  liable  for  direct,  indirect,  special,  incidental  or  consequential  damages 

arising out of the use or inability to use this product or documentation, even if advised of the possibility of 

such damages. This document contains materials protected by copyright. All rights are reserved. No part of 

this manual may be  reproduced or  transmitted  in  any  form, by  any means or  for  any purpose without 

expressed written  consent of  its authors. Product names appearing  in  this document are mentioned of 

identification purposes only. All  trademarks, product names or brand names preparing  in  this document 

are registered property of their respective owners. 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trademarks 

Smart Data Logger, GSX4 and GSX8 are the registered trademarks of Easemind Technology Ltd.