Golder Associates Ltd. 2390 Argentia Road Mississauga, Ontario, Canada L5N 5Z7 Telephone: (905) 567-4444 Fax: (905) 567-6561 OFFICES ACROSS NORTH AMERICA, SOUTH AMERICA, EUROPE, AFRICA, ASIA AND AUSTRALASIA REPORT ON ASBESTOS BUILDING MATERIALS SURVEY SIR SANDFORD FLEMING ACADEMY 50 AMEER AVENUE SAP ID# 3081 Submitted to: Toronto District School Board Facility Services 15 Oakburn Crescent Toronto, Ontario M2N 2T5 DISTRIBUTION: 3 Copies - Toronto District School Board, Toronto, Ontario 2 Copies - Golder Associates Ltd., Mississauga, Ontario October 2007 06-1113-212

Upload: lamkiet

Post on 10-Feb-2018

218 views

Category:

Documents


1 download

TRANSCRIPT

Golder Associates Ltd.

2390 Argentia Road Mississauga, Ontario, Canada L5N 5Z7 Telephone: (905) 567-4444 Fax: (905) 567-6561

OFFICES ACROSS NORTH AMERICA, SOUTH AMERICA, EUROPE, AFRICA, ASIA AND AUSTRALASIA

REPORT ON

ASBESTOS BUILDING MATERIALS SURVEY

SIR SANDFORD FLEMING ACADEMY 50 AMEER AVENUE

SAP ID# 3081

Submitted to:

Toronto District School Board

Facility Services

15 Oakburn Crescent

Toronto, Ontario

M2N 2T5

DISTRIBUTION:

3 Copies - Toronto District School Board, Toronto, Ontario

2 Copies - Golder Associates Ltd., Mississauga, Ontario

October 2007 06-1113-212

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - i - 06-1113-212

Golder Associates

TABLE OF CONTENTS

1.0 INTRODUCTION ......................................................................................... 1 1.1 Scope of Work ....................................................................................... 1

2.0 METHODOLOGY ........................................................................................ 1 2.1 General Information ............................................................................... 1 2.2 Area Identification .................................................................................. 2 2.3 System Classification ............................................................................. 2 2.4 Asbestos Sampling and Analysis ........................................................... 3 2.5 Sampled and Presumed ACM Materials (PACM) ................................... 4 2.6 Existing Sample Data ............................................................................. 5 2.7 Condition of Material .............................................................................. 5 2.8 Accessibility of Material .......................................................................... 7 2.9 Response Actions .................................................................................. 8 2.10 Limitations of Survey .............................................................................. 9 2.11 General Recommendations .................................................................. 10

3.0 FINDINGS ................................................................................................. 11 3.1 Site-Specific Information ...................................................................... 11 3.2 Confirmed And Presumed ACM ........................................................... 12

4.0 RECOMMENDATIONS ............................................................................. 12 5.0 Limitations and Use of Report ................................................................... 12 6.0 CLOSURE ................................................................................................. 13 ATTACHMENT Abbreviations and Definitions

TABLES Table 1: Bulk Material Sampling Requirements Table 2: Specific Sampling and Assumption Criteria Table 3: Condition of Spray Applied Fireproofing, Thermal/Acoustic Insulation and Texture Finishes Table 4: Mechanical Insulation Table 5: Non-friable and Potentially Friable Material Table 6: Evaluation of ACM Debris Table 7: Accessibility Table 8: Response Actions Table 9: Action Matrix Table Table 10: Site-Specific Information

APPENDICES Appendix I: Figure SP: Site Location Plan Figure 1: ACM and Sample Location Plan (Floor 1)

Figure 2: ACM and Sample Location Plan (Floor 2) Appendix II: Laboratory Results Appendix III: Summary of All Asbestos-Containing Materials (ACM & PACM) Appendix IV: Room-by-Room Details: Summary Report by Location

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 1 - 06-1113-212

Golder Associates

1.0 INTRODUCTION

At the request of the Toronto District School Board (“TDSB”), Golder Associates Ltd. (“Golder”)

conducted a survey of Sir Sandford Fleming Academy (the Site) to identify building materials

that may contain asbestos. The survey was performed with the objective of compiling an

inventory of asbestos-containing materials (ACMs) and providing recommendations to manage

these materials in accordance with Ontario Regulation 278/05, Regulation respecting Asbestos on

Construction Projects and in Buildings and Repair Operations, made under the Occupational

Health and Safety Act.

1.1 Scope of Work

Golder’s scope of work for this project included the following:

• A review of available Site information including Site plans and existing surveys as well as interviews with available personnel familiar with the Site;

• A Site reconnaissance and walk through (room-by-room) to identify suspect ACMs;

• Sample collection of suspected ACMs;

• Analysis of samples using an independent laboratory accredited by the National Voluntary Laboratory Accreditation Program (NVLAP);

• Transfer of information to eFacility database; and

• Preparation and delivery of a report identifying the presence, location and condition of ACMs (friable and non-friable) and, where necessary, recommendations for repair and or removal of damaged or deteriorated ACMs.

Where possible, Golder used existing reports and data detailing any previous findings related to ACMs.

2.0 METHODOLOGY

2.1 General Information

For the purposes of this survey, all materials used in the construction of the site are considered to

be building “components”. Each component, even those not suspected to contain asbestos, are

assigned a number and are addressed as one “homogeneous material” throughout a building.

Homogeneous Materials are defined by O. Reg. 278/05 as materials that are uniform in colour

and texture. A component number refers to a homogeneous material throughout its full extent,

even if its occurrence is not contiguous or physically connected.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 2 - 06-1113-212

Golder Associates

2.2 Area Identification

The Site was typically assessed on a room-by-room or area-by-area basis. Each room or area was

then assigned a number. Collectively, rooms or areas are referred to as “areas” in this

assessment. Areas are typically defined as one room, but may include several interconnected

rooms or a portion of a room as identified on the attached drawings. Room or area numbers

provided by TDSB were generally utilized where they were provided. Not all numbers were

necessarily utilized and additional numbers were added as required to accurately delineate areas

for the purposes of collecting asbestos information.

2.3 System Classification

Areas were broken down into “systems” to document the materials present. Systems are used to

group various building materials, referred to as “Components”, into easily recognisable categories

which indicate where they are located. All Components are associated with a system (e.g., wall,

floor, piping, mechanical). The systems were broken down for each area as described below:

Floor: The floor or lower surface of an area. May include the roofing material in the “roof” area description. May not be present in areas such as vertical pipe chases or two-storey areas.

Wall : Walls or vertical perimeter of an area. May include the exterior walls for the “exterior” area of a Site. May not be present if area is defined as a portion of an area with no vertical perimeter surfaces.

Ceiling: An architectural or acoustical upper barrier or surface in an area which is typically suspended from, or attached to, the upper structural element (deck). May not be present in vertical shafts or where structural deck is exposed.

Structure: Structural element of the Site which usually refers to the concrete or metal upper deck, beams, columns or joists in an area or the fireproofing material applied to the surface of these materials.

Ductwork : Ducts and associated connectors which facilitate air movement between areas.

Piping Systems: Pipes which typically transport liquids and are commonly insulated. Does not include conduit for electrical services.

Mechanical Equipment: Boilers, chillers, hot water tanks, air handling units and other mechanical equipment typically present in mechanical rooms.

Other: Other items that don’t fit into the above categories including chalk boards, bench tops, window sealers or fire doors.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 3 - 06-1113-212

Golder Associates

2.4 Asbestos Sampling and Analysis

The survey included a visual assessment of areas accessible at the time of the survey in order to

determine the type and extent of ACMs within the Site.

Bulk samples of each “homogeneous material” or “component” suspected to contain asbestos

were collected and submitted for laboratory analysis. The number of samples of each

“homogeneous material” was in accordance with Table 1 “Bulk Material Samples” of O. Reg.

278/05. Sample analysis of each “homogeneous material” was stopped at the first positive result.

Table 1 - Bulk Material Sampling Requirements

Type of material Size of area of homogeneous material Minimum

# of samples

Surfacing material, including without limitation material that is applied to surfaces by spraying, by troweling or otherwise. Examples include acoustical plaster on ceilings and fireproofing materials on structural members

Less than 90 square metres (969 square feet) 3 90 or more square metres, but less than 450 square metres (4,844 square feet) 5

450 or more square metres 7

Thermal insulation, except as described below

any size 3

Thermal insulation patch Less than 2 linear metres (6.6 linear feet) or 0.5 square metres (5.4 square feet) 1

Other material Any size 3

Sample collection consisted of obtaining a small volume of suspect material, placing it in an

individual plastic bag, and submitting it to an independent laboratory (International Asbestos

Testing Laboratories (IATL) of Mt. Laurel, N.J. or EMSL Analytical Inc of Westmount, N.J.) for

asbestos content analysis. Both labs are certified under The National Voluntary Laboratory

Accreditation Program (NVLAP) for Laboratory Proficiency. Samples were assigned a sample

number and series number to indicate how many samples of each homogeneous material, or

component, were collected. For example, the first sample of a component would be 3147-1-

3007-3171-01, where 3147 is the SAP ID#, 1 is the building at the Site (may be more than one),

3007 is a generic component code, 3171 is the component number, and 01 is the first sample of

this component. Samples of materials suspected of containing asbestos were submitted, along

with a chain of custody, to the lab for asbestos content analysis. The laboratory was instructed to

stop once a positive result (0.5% or greater) was obtained for any sample in a homogeneous

material group. Some samples may be identified by the laboratory to contain multiple phases or

layers which require separation and individual analysis of each separate phase or layer.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 4 - 06-1113-212

Golder Associates

Samples were analyzed for asbestos type and percentage content using Polarized Light

Microscopy in accordance with U.S. Environmental Protection Agency (USEPA) methodologies

and dispersion staining techniques (EPA 600/R-93/116). Samples were analyzed to a minimum

detection limit of 0.5% to meet the requirements of O.Reg. 278/05. The identification of asbestos

fibres in bulk materials is based on a collective set of parameters dependent on the unique shape

and crystallographic properties of each fibre as viewed through the microscope. This method is

useful for the qualitative identification of asbestos and the semi-quantitative determination of

asbestos content in bulk materials expressed as a percent of projected area. The method identifies

types of asbestos and also measures percent of asbestos as perceived by the analyst in comparison

to standard area projections and the analyst’s experience. Analytical results are reported from

trace (less than the limit of detection), to the percentage counted or estimated. Materials reported

to contain less than 0.5% asbestos, including those referred to as less than the limit of detection

(<LOD), are not considered to be asbestos-containing under current regulations.

2.5 Sampled and Presumed ACM Materials (PACM)

For the purposes of this assessment, specific materials (components) have been designated as

“Presumed Asbestos-Containing Materials” (PACM) and have not been sampled. Materials

presumed to contain asbestos may also be referred to as “Assumed” or “Suspect” materials.

Other materials have been designated as requiring sampling wherever they were present. As

required by O.Reg. 278/05, all PACM shall be treated as ACM until appropriate sampling proves

otherwise. All references to ACM in this report shall include PACM unless specifically noted

otherwise. Specifically designated materials are presented in Table 2.

Table 2 - Specific Sampling and Assumption Criteria

Material Sampled Materials Presumed to Contain Asbestos (PACM) • ceiling tiles • pipe covering papers • texture coatings • textiles • pipe and other mechanical

insulation • sprayed fireproofing

• vinyl floor tile • vinyl sheet flooring • asbestos cement board • asbestos cement pipe • gaskets and packing • expansion joints • flex connections • roofing felts and sealers • putty. caulking, window glazing and mastics • friction materials • drywall joint compound • wall and ceiling plaster • concealed vermiculite • other suspect materials

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 5 - 06-1113-212

Golder Associates

2.6 Existing Sample Data

Existing bulk sampling information was obtained by Golder through reviewing existing surveys

or other information provided by TDSB. Where possible, Golder has relied on laboratory results

from previously collected samples, referred to as Historical Samples. Historical samples are

denoted in this report and it’s appendices by “-H” at the end of the sample number. In some

instances, final copies of the original laboratory reports were not available for review. In these

cases, the reported type and percentage of asbestos present may be approximate. This

information was used only if the surveyor, based on their experience with asbestos materials,

could clearly associate the historical sample information with the material (component) present at

the Site. Although historical sample information was used to confirm the presence of asbestos in

suspect materials, components were not deemed to be non-asbestos based on historical samples

unless they were of recent vintage and met all requirements outlined in O. Reg. 278/05. Existing

analytical data for materials that were analyzed to a detection limit of greater than 0.5% or

materials that could not be clearly linked to materials existing at the Site, as determined during

this survey, were not relied upon.

2.7 Condition of Material

Each ACM and PACM identified as part of this assessment was evaluated based on it’s condition.

The criteria used to assess the condition of a material, as defined by TDSB, are summarized in

Tables 3, 4, 5 and 6.

Table 3 - Condition of Spray Applied Fireproofing, Thermal/Acoustic Insulation and Texture Finishes

Good

Surface of material shows no significant signs of damage, deterioration or delamination. Good condition includes fireproofing or texture finishes that are not encapsulated or painted and where no delamination or damage is observed, and encapsulated fireproofing or texture finishes where the encapsulation has been applied after the damage or fallout occurred.

Poor Sprayed materials show signs of damage, delamination or deterioration. Significant delamination to surface of ACM spray.

The above table refers to evaluating the condition of ACM sprayed or trowelled fireproofing, sprayed or trowelled thermal/acoustic insulation (non-mechanical), or texture, decorative or acoustic finishes. In observation areas where damage exists in isolated locations, both good and poor condition may be applicable. The extent or percentage of each condition has been recorded. Fair condition has not been utilized in the evaluation of sprayed fireproofing or texture coat finishes The evaluation of ACM sprayed or trowelled fireproofing, sprayed or trowelled thermal insulation (non-mechanical), or texture, decorative or acoustic finishes which are present above ceilings, may be limited by building components such as ducts or full height walls that obstruct observations.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 6 - 06-1113-212

Golder Associates

Table 4 - Mechanical Insulation

Good

Insulation is completely covered in jacketing and exhibits no evidence of damage or deterioration. No insulation is exposed. Includes conditions where the jacketing has minor damage (i.e., scuffs or stains), but the jacketing is not penetrated.

Fair

Minor penetrating damage to jacketed insulation (cuts, tears, nicks, deterioration or delamination) or undamaged insulation that had never been jacketed. Insulation is exposed but not showing surface disintegration. The extent of missing insulation ranges from minor to none. Damage can be repaired.

Poor Original insulation jacket is missing, damaged, deteriorated or delaminated. Insulation is exposed and significant areas have been dislodged. Damage cannot be readily repaired.

The evaluation of mechanical insulation may be limited by building components such as ducts or full height walls that obstruct observations. It is not possible to observe each foot of mechanical insulation from all angles.

Table 5 - Non-friable and Potentially Friable Material

Good No significant damage. Material may be cracked or broken but is stable and not likely to become friable upon casual contact. If there is no friable debris present, the condition is rated as good

Poor Material is severely damaged. Loose debris is present or binder has disintegrated to the point where the material has become friable.

The condition of non-friable or potentially friable ACM, such as ceiling tiles, drywall joint compound and plaster finishes containing asbestos and manufactured products such as asbestos cement products (Transite) have the potential to become friable when handled. Potentially Friable refers to ceiling tiles which can become friable very easily, vinyl sheet flooring with asbestos backing paper which can remain stuck to the substrate during removal of the vinyl, heavily deteriorated non-friable materials and wall plaster which is considered friable at the time of demolition. The evaluation of the condition of non-friable and potentially friable materials does not utilize a fair condition rating.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 7 - 06-1113-212

Golder Associates

Table 6 - Evaluation of ACM Debris

Poor Debris from ACM (friable or non-friable) is inherently in a deteriorated state having become dislodged from the source material.

The presence of ACM debris is noted separately from the presumed ACM source and is referred to as debris. The identification of the exact location or presence of debris on the top of ceiling tiles is limited by the number of observations made and the presence of building components such as ducts or full height walls that obstruct observations. Note: Workers are advised to be watchful for the presence of debris when accessing or working in proximity to mechanical insulation or above ceilings in areas with ACM regardless of the reported presence or absence of debris.

2.8 Accessibility of Material

Materials are rated based on the ease with which they can be reached, and therefore physically

disturbed. The accessibility of materials known or suspected of being ACM is rated according to

the criteria presented in Table 7:

Table 7 - Accessibility

Access (A)

Materials within reach (from floor level) of all Site users. These also include materials in gymnasiums, workshops, and storage areas where activities of the Site users may result in disturbance of ACM not normally within reach from floor level. Visibility would typically be noted as “YES” for these items, except for under sinks, in closets, or other commonly accessed spaces.

Access (B)

Materials in frequently entered maintenance areas of the Site within reach of maintenance staff, without the need for a ladder. Includes materials within reach from a fixed ladder or catwalk (i.e., tops of equipment, mezzanines, and frequently entered pipe chases, tunnels and service areas). Visibility would typically be noted as “YES” for these items.

Access (C)

Materials above 8'-0" where use of a ladder is required to reach the ACM. Only includes ACM materials that are exposed to view without the removal or opening of other building components such as ceiling tiles, or service access doors or hatches. Does not include materials in infrequently accessed service areas of the Site. Visibility would be noted as “YES” for these items.

Access (D)

Materials that can not be reached without removing a building component, including lay-in ceilings or access panels in solid ceiling systems. Includes rarely entered crawl spaces, attic spaces, etc. Observations will be limited to the extent visible from access points. Visibility would be noted as “NO” for these items.

Access (E)

Materials behind inaccessible solid ceiling systems, walls or mechanical equipment, etc., where demolition of the ceiling, wall or equipment etc. is required to reach the ACM. These materials are visually identified by the surveyor, often with difficulty, and there may be uncertainty associated with them. Evaluation of condition and extent of ACM is limited or impossible, depending on the surveyor's ability to visually examine these materials. Visibility would be noted as “NO” for these items.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 8 - 06-1113-212

Golder Associates

2.9 Response Actions

For each ACM or assumed ACM identified, a specific response action has been assigned. The

assigned response action is based on consideration of condition and accessibility. These actions

are based on the likely risk posed by the material. Damaged materials that are easily accessible

pose the greatest risk and good condition materials in inaccessible areas pose the least risk.

Response actions range from immediate clean-up of debris to ongoing routine inspections of non-

friable material in good condition.

In any building with friable asbestos, current regulations require implementation of an Asbestos

Management Program (AMP) which includes provisions for training and routine inspections of

ACM. As of November 1, 2007, these regulations will further require implementation of an AMP

for buildings containing non-friable ACM. Depending on the condition and the accessibility of

ACMs, more active measures such as repair or removal may be required. In the event of a

building alteration, it will be necessary to remove all ACM, regardless of condition, that is likely

to be disturbed by planned renovation, demolition or maintenance work. Response Actions and

their definitions are presented in Table 8.

Table 8 - Response Actions

Action 1

Immediate Clean-Up of Debris Restrict access that is likely to cause a disturbance of the ACM debris and clean up ACM debris immediately. The surveyor will immediately (within 24 hours) notify TDSB’s Environmental Coordinator of this condition.

Action 2

Type 2 Precautions for Entry into Areas with ACM Debris Restrict access to the area to persons utilizing Type 2 asbestos precautions as per O.Reg. 278/05. These precautions will be required until the ACM debris has been cleaned up, and the source of the debris has been stabilized or removed.

Action 3 ACM Removal Required for Compliance Remove ACM in compliance with regulatory requirements of O.Reg. 278/05.

Action 4 Type 2 Access into Areas Where ACM is Present and Likely to be Disturbed Use Type 2 asbestos precautions as per O.Reg. 278/05 when entry or access into an area is likely to disturb the ACM. .

Action 5 ACM Repair Repair ACM found in fair condition, and not likely to be damaged again or disturbed by normal use of the area or room.

Action 6 Routine Inspection Maintain routine inspection of ACM to monitor condition.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 9 - 06-1113-212

Golder Associates

Based on the accessibility and action criteria presented above, the following Action Matrix Table,

Table 9, outlines appropriate action codes for all ACM and PACM identified.

Table 9 – Action Matrix Table

Access Condition

Debris Good Fair Poor

(A) Action 6 Action 5 Action 3 Action 1

(B) Action 6 Action 5 Action 3 Action 1

(C) Action 6 Action 5 Action 4 Action 2

(D) Action 6 Action 6 Action 4 Action 2

(E) Action 6 Action 6 Action 6 Action 6

2.10 Limitations of Survey

Only accessible areas of the Site were examined during our assessment. An accessible area is

defined as an area above a suspended ceiling tile, within a manufactured access hatch or behind a

closed door, not impeded by any structure, article or item. Ceiling spaces (between suspended

ceiling and structural deck) that were not accessible at the time of this assessment should be

considered to contain asbestos until proven otherwise. If these spaces are to be accessed for any

reason, such as a roof leak, etc., an inspection should be conducted by a competent person and

any suspect ACM should be sampled or presumed to contain asbestos. An enclosed area that

requires demolition to gain entry or a temporary access hatch that is not readily opened is

considered inaccessible. This report reflects the observations of accessed areas, and analytical

results of materials sampled during the survey.

Carpets were not removed to determine materials below as it is possible that asbestos materials

may be present under a portion of the carpeted area. Asbestos-containing flooring material

should be suspected below all carpets until proven otherwise. In addition, mastic associated with

any floor tiles or baseboards should be considered to contain asbestos until proven otherwise.

Similarly, equipment such as exhaust stacks and metal-clad breaching, boilers, kilns, electrical

components and mechanical piping and ducting were not disassembled for assessment.

Subsequently, materials such as refractory, gaskets and other internal components should be

considered suspect ACM until sampled and proven otherwise. Roofing components and building

envelope materials such as window caulking or glazing were not sampled and should be

presumed asbestos-containing until proven otherwise.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 10 - 06-1113-212

Golder Associates

Analytical results reflect the sampled materials at the specific sample locations. Materials that

were visually similar in colour and texture were referenced to specific analyzed samples and were

considered to be of like composition and grouped as one homogeneous material.

Golder has relied on certain sample analysis results provided in documents supplied by TDSB

and prepared by others as detailed in Section 2.3 of this report.

Only suspect materials identified by TDSB and as detailed in Section 2.2 of this report were

sampled, with limited exceptions as determined by surveyors at the time of assessment.

2.11 General Recommendations

Should planned renovations involve the removal of materials confirmed or presumed to be

asbestos-containing, all appropriate precautions, as detailed in O. Reg. 278/05, must followed.

This survey was conducted to identify asbestos materials in accessible areas that require

monitoring as part of an Asbestos Management Program. It is possible that undiscovered ACMs

may be present within inaccessible locations such as wall cavities or above inaccessible ceilings.

Asbestos may also be present in materials that are inaccessible or not visible during a non-

invasive assessment. Materials such as adhesive mastic (may be used virtually anywhere) for

various items, including stick-up ceiling tiles, mirrors, etc., and packing compound in bell and

spigot joints of cast iron drain pipes may contain asbestos but are not easily confirmed without

causing significant damage to the associated materials. It is recommended that a more

comprehensive and invasive survey be conducted prior to any planned demolition or renovations

that involve entering previously inaccessible areas or inaccessible materials. If encountered

during future renovations or demolition, suspect materials should be treated as asbestos-

containing until proven otherwise.

If any ACM is present within the Site, an Asbestos Management Program (AMP) must be

maintained as per the requirements of Section 7 and 8 of O. Reg. 278/05. The AMP would

include provisions for regular assessments of all identified ACMs, appropriate procedures for

dealing with ACMs, and training, as appropriate, for all occupants who may come into contact

with ACMs.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 11 - 06-1113-212

Golder Associates

3.0 FINDINGS

3.1 Site-Specific Information

Information relating to the assessment of this Site is presented in Table 10:

Table 10 – Site-Specific Information

SIR SANDFORD FLEMING ACADEMY SAP ID# 3081

Approximate Bldg. Size (ft2): 121,935 # of Levels (floors) including basement(s): 2

Region: NW Use: Secondary School

Year of Construction: 1964 Additions (years of Construction): 1965

Surveyed By: Golder Associates Ltd. Survey Date(s): Apr. 4, 5, 11, 12, 2007

The findings of this assessment have been summarized in tabular form and are presented in the

attached appendices. Floor plans indicating sample locations and mapping of confirmed ACMs

are presented in Appendix I. Location numbers are typically situated on a grey dot representing

the centroid of the area. If two numbers are too close together to be shown clearly, one number

will be moved to make for clear identification. These numbers are easily identified as they are

not on top of a grey dot but situated very close to them.

Please note that all materials may not be mapped on these plans. Also note that Golder has used

the numbers on drawings provided by TDSB where possible and added new numbers if

appropriate numbers describing the location were not available. Some of the numbers provided

by TDSB were not used by Golder in this survey (multiple numbers in one area, etc.) and are not

presented on Golder’s drawings. Similarly, some area location/room numbers, typically for roofs

and a limited number of other areas, are referenced on the drawings but do not have a room or

floor plan associated with them.

The location, quantity and extent of ACM has been identified throughout the Site based on the

findings during Golder’s information review and Site assessment. Following the sampling

protocol outlined in Section 2.1 of this report, a total of 57 samples were obtained of materials

suspected of containing asbestos from the Site and submitted, along with a chain of custody, for

asbestos content analysis. This number represents the total number of samples that were

collected and/or analysed, which may have included multiple layers of a particular material,

where each layer was considered a sample.

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 12 - 06-1113-212

Golder Associates

3.2 Confirmed And Presumed ACM

Confirmed and Presumed ACMs were identified within accessible areas of the Site. Floor plans

indicating sample locations and mapping of confirmed ACMs is presented in Appendix I.

Locations of historical samples, which were not collected during this assessment, are not shown

on the floor plans. Details of bulk sample analytical results (Laboratory Results) are presented in

Appendix II with listings of all ACMs (Summary of All Asbestos-Containing Materials, ACM &

PACM), presented in Appendix III. A listing of all materials identified, presented by location

(Room-by-Room Details: Summary Report by Location), is presented in Appendix IV.

4.0 RECOMMENDATIONS

Based on the findings of this assessment, actions have been assigned for each ACM identified.

Actions required for all ACMs are presented in the Summary of All Asbestos-Containing

Materials in Appendix III and the Room-by-Room Details, Summary Report by Location in

Appendix IV. All ACMs require routine inspection as indicated in TDSB Asbestos Management

Program and O. Reg. 278/05. All components (materials) identified in this report as ACM or

PACM should be considered as such wherever they are present within the building. Anyone

doing work at this site should be familiar with the contents of this report prior to conducting any

work that could disturb any building materials.

• An asbestos management program should be maintained for this facility as presumed or

confirmed asbestos-containing materials are present;

• Inaccessible areas (7884, 7912, 7913, 7972, 8024) and spaces such as above inaccessible

ceilings or in wall or pipe spaces, should be considered to contain asbestos until they can

be accessed and properly assessed;

• Non-asbestos, spray-applied fireproofing is present on steel mesh in many locations

throughout the building. The space between the fireproofing and substrate could not be

accessed during our survey and is considered inaccessible; and,

• No immediate remedial action is required at this Site at this time.

5.0 LIMITATIONS AND USE OF REPORT

The conclusions and recommendations contained in this assessment report are based upon

professional opinions with regard to the subject matter. These opinions are in accordance with

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 13 - 06-1113-212

Golder Associates

currently accepted industry practices for asbestos surveys and regulatory requirements for

sampling and identifying ACMs and are subject to the following inherent limitations:

1. The data and findings presented in this report are valid as of the date of the investigation. The passage of time, manifestation of latent conditions or occurrence of future events may warrant further exploration at the Site, analysis of the data, and re-evaluation of the findings, observations, and conclusions expressed in this report.

2. The data reported and the findings, observations, conclusions, and recommendations expressed in this report are limited by the Scope of Work. The Scope of Work was defined by the request of the client, the time and budgetary constraints imposed by the client, and availability of access to the Site.

3. Because of the limitations stated above, the findings, observations, conclusions, and recommendations expressed by Golder in this report are not, and should not be, considered an opinion concerning compliance of any past or present owner or operator of the Site with any federal, provincial or local laws or regulations.

4. No warranty or guarantee, whether expressed or implied, is made with respect to the data or the reported findings, observations, and conclusions, which are based solely upon Site conditions in existence at the time of investigation.

5. Golder will not be responsible for any real or perceived decrease in a property value, its saleability or ability to gain financing through the reporting of information in this report.

6. Golder’s assessment reports present professional opinions and findings of a scientific and technical nature. While attempts were made to relate the data and findings to applicable environmental and occupational health & safety laws and regulations, the report shall not be construed to offer legal opinion or representations as to the requirements of, nor compliance with, environmental and occupational health & safety laws, rules, regulations or policies of federal, provincial, or local governmental agencies. Any use of the assessment report constitutes acceptance of the limits of Golder’s liability. Golder’s liability extends only to its client and not to other parties who may obtain this assessment report. Issues raised by the report should be reviewed by appropriate legal counsel.

6.0 CLOSURE

We trust that this report meets your requirements. If you have any questions regarding the

content of this report, please do not hesitate to contact the undersigned.

GOLDER ASSOCIATES LTD.

Christopher Nielsen, B.Sc., CCEP

Senior Environmental Health and Safety Specialist

Toronto District School Board October 2007

SAP ID# 3081 – Sir Sandford Fleming Academy - 14 - 06-1113-212

Golder Associates

Andreas Wagner, M.Eng., CIH, ROH Principal, Director, Environmental Health & Safety CLN/AW/

Golder Associates

ATTACHMENT

ABBREVIATIONS AND DEFINITIONS

Golder Associates

ABBREVIATIONS AND DEFINITIONS

Abbreviations: SM, MED, LG Small, Medium and Large, respectively

<LOD Less than the Limit of Detection for the Analytical Method used. Typically 0.5% or 0.25%, or may indicate that no asbestos was identified in sample.

“ – “ Not applicable or no information required for this cell. When present under “Asbestos Type” column in Appendix IV, indicates that corresponding material is not considered to be asbestos-containing.

ACM Asbestos-Containing Material, defined as material that contains 0.5% or more asbestos by dry weight

FTG Fitting on a mechanical system including elbow, tee joint, valve, joint or end.

N/A Not Applicable

TBD To Be Determined

PACM Presumed Asbestos-Containing Material – must be treated as ACM until proven otherwise through bulk sample analysis

PLM Polarized Light Microscopy (asbestos identification procedure)

RND Round

SPF Spray-applied fireproofing

STR Straight section of pipe, duct or other mechanical system

VFT Vinyl Floor Tile

VSF Vinyl Sheet Flooring

Definitions:

Accessibility – A Accessible to anyone

Accessibility – B Accessible without a ladder

Accessibility – C Above eight feet and visible

Accessibility – D Above eight feet and not visible

Accessibility – E Inaccessible

Action Code – 1 Restrict access that is likely to cause a disturbance of the ACM debris and clean up ACM debris immediately

Action Code – 2 Restrict access to the area to persons using Type 2 precautions in accordance with O. Reg. 278/05 until the ACM debris has been cleaned up and the source of the debris has been stabilized or removed

Action Code – 3 Remove ACM in compliance with O. Reg. 278/05

Action Code – 4 Use Type 2 asbestos precautions in accordance with O. Reg. 278/05 when entry or access into an area is likely to disturb ACM

Action Code – 5 Repair ACM found in fair condition and not likely to be damaged again, or disturbed by normal use of the area or room

Action Code – 6 Maintain routine inspection of ACM

Asbestos Fibrous silicate materials including actinolite, amosite, anthophyllite, chrysotile, crocidolite and tremolite as defined in O. Reg. 278/05, s.1(2).

Asbestos I Primary type, by %, of asbestos present in a sample, as presented in the Laboratory Results Appendix

Asbestos II Secondary type, by percentage, of asbestos present in a sample, as presented in the Laboratory Results Appendix

Component Construction material used in building which is deemed to be a homogeneous material (consistent in colour and texture) and is treated as a unit throughout its extent within the building (e.g., plaster, concrete, or parging cement)

Homogeneous Material Homogeneous Materials are materials that are uniform in colour and texture and includes the material throughout its full extent, even if its occurrence is not contiguous or physically connected.

To Be Determined To be determined (TBD) through the inspection and sampling protocol, as required by O.Reg 278/05, for those areas that were not accessible during the initial survey. ACM is presumed to be present unless proven otherwise through sampling and accredited lab analysis and reports.

Not Applicable System is not present or no suspect material is associated with the system at the location

Not Found System or suspect material associated with it was not found to be present

Not Tested or

Sample Not Analyzed Previous sample of this homogeneous material was found to be positive for asbestos; therefore further analysis is not required.

Golder Associates

APPENDIX I

FLOOR PLANS WITH SAMPLE LOCATIONS AND ACM MAPPING

Base Data - CANMAP v2005.4Datum: NAD 83 Projection: UTM Zone 17N

REFERENCE

SITE LOCATION PLAN3081 - SIR SANDFORD FLEMING AC50 AMEER AVENUETORONTO, ONTARIO

FIGURE: SPPROJECT No. 06-1113-212PROJECT

TITLE

ASBESTOS SURVEY - NORTHWEST REGIONTORONTO DISTRICT SCHOOL BOARD

"

RANEE AVE

REGINA AVE

VARNA DR

BAYCREST AVE

SULTANA AVE

RIDGEVALE DR

BROOKVIEW DRLYNNHAVEN RD

HIGHWAY 401

NEPTUNE DR

ALLEN RD

FLEMINGTON RD

KIRKLAND BLVD

ROBERTA DR

RONDALE BLVD

BRUCEWOOD CRES

WASDALE CRES

LAWRENCE AVE W

PRINCE CHARLES DR

RAJAH ST

KHEDIVE AVE

REPLIN RDDREXEL RD

CATHER CRES

MANOR HAVEN RD

MIKADO AVE

DORNEY CRT

NEPTUNE DRHIGHWAY 401

HIGHWAY 401

ALLEN RD

RAJAH ST

³

LEGEND0 500 1,000 1,500250

Feet" Site Location

Express WayArterial RoadLocal road

SITE LOCATION

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!!

!

!

!

!

!!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!!

!

!!

!

!

!

!

!

!

!

! !!

!

!

!

!

!!

!

!

!

!!

!

!

!

!

!

!!

!

!

!!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

A

A

A

A

A

A

7949-1

99848

99458

99457

99446

99445

99444

99443

99442

99441

7949

7948

7947 79467945

7944

79437942

7941

7938

79377936

7935

79347933

79327931

793079297928

7927

7925

79247923

792279217920

79197918

7917

79167915

7914

7911

7910 7909

7908

79077906

79057904

7903

7902

7901

7900

78997898

7897

78967895

7894

7893

7892

7891

78907889

7888

7887

78867885

7884

78837882

7881

7880

7879

7878

7877 7876

7875

7874

7873

7872

7871

7870

7869

78687867

7866

78657864

7862

7861

78607859

7858

7857

3081-1-3008-051-01,02,03

3081-1-3008-036-01,02,03

3081-1-4008-039-01,02,03

3081-1-3008-038-01,02,03

3081-1-3006-019-01,02,03

3081-1-3006-029-01,02,03

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!!

!

!

!

!

!!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!!

!

!!

!

!

!

!

!

!

!

! !!

!

!

!

!

!!

!

!

!

!!

!

!

!

!

!

!!

!

!

!!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

A

A

A

A

A

A

7949-1

99848

99458

99457

99446

99445

99444

99443

99442

99441

7949

7948

7947 79467945

7944

79437942

7941

7938

79377936

7935

79347933

79327931

793079297928

7927

7925

79247923

792279217920

79197918

7917

79167915

7914

7911

7910 7909

7908

79077906

79057904

7903

7902

7901

7900

78997898

7897

78967895

7894

7893

7892

7891

78907889

7888

7887

78867885

7884

78837882

7881

7880

7879

7878

7877 7876

7875

7874

7873

7872

7871

7870

7869

78687867

7866

78657864

7862

7861

78607859

7858

7857

3081-1-3008-051-01,02,03

3081-1-3008-036-01,02,03

3081-1-4008-039-01,02,03

3081-1-3008-038-01,02,03

3081-1-3006-019-01,02,03

3081-1-3006-029-01,02,03

PROJECT

TITLE

Drawings based on plans provided by the Toronto District School Board.REFERENCE

0 50 100 15025Feet

G:\P

rojec

ts\20

06\06

-1113

-212_

TDSB

\GIS

\MXD

s\Draf

t\auto

\batch

\A_3

081_

1_1.m

xd

ACM AND SAMPLE LOCATION PLANFLOOR 13081 - SIR SANDFORD FLEMING AC50 AMEER AVENUETORONTO, ONTARIO

ASBESTOS SURVEY - NORTHWEST REGIONTORONTO DISTRICT SCHOOL BOARD FIGURE: 1.1

PROJECT No. 06-1113-212

1. This drawing is schematic only and is to be read in conjunction with theaccompanying text.2. Some numbers provided by the Toronto District School Board have not been used.

NOTESRoof ID: 68437Exterior ID: 68437-1,7926

³N

Description of Asbestos-Containing MaterialsMechanical System

Pipe Insulation

3.Only sampled materials and/or confirmed ACM is shown on the drawing. Shaded areas represent the presence of one or more Asbestos-Containing Material (ACM) component(s). Cross reference to Appendix IV -“Room by Room Details - Summary Report By Location” for specifics.

LEGENDLEGEND!A

!A

Sample #Positive Sample LocationSample #Negative Sample Location Not Tested Sample Location Sample #!A

Location/Room!

Sample # Location Component # Description3081-1-3006-019-01,02,03

7924 19 1x1 large/med. pinholes, tetris pattern

3081-1-3006-029-01,02,03

99443 29 1x1 lrg irregular fissures

3081-1-3008-036-01,02,03

7868 36 2x4 sml random fissures, dense sml/med pinholes

3081-1-3008-038-01,02,03

7869 38 2x4 off-white, random sml/med pinholes

3081-1-3008-051-01,02,03

7897 51 2 x 4 sml/med. pinholes, circular pattern, dimpled

3081-1-4008-039-01,02,03

7869 39 Fibrous SPF On Beam, Deck, Joist

FOR ROOM DESCRIPTIONS REFER TO FIGURE 1.2

PROJECT

TITLEDrawings based on plans provided by the Toronto District School Board.REFERENCE

G:\P

rojec

ts\20

06\06

-1113

-212_

TDSB

\GIS

\MXD

s\Draf

t\auto

\batch

\A_3

081_

1_1.2

.mxd

ACM AND SAMPLE LOCATION PLANFLOOR 13081 - SIR SANDFORD FLEMING AC50 AMEER AVENUETORONTO, ONTARIO

ASBESTOS SURVEY - NORTHWEST REGIONTORONTO DISTRICT SCHOOL BOARD FIGURE: 1.2

PROJECT No. 06-1113-212

1. This drawing is schematic only and is to be read in conjunction with theaccompanying text.2. Some numbers provided by the Toronto District School Board have not been used.

NOTES

3.Only sampled materials and/or confirmed ACM is shown on the drawing. Shaded areas represent the presence of one or more Asbestos-Containing Material (ACM) component(s). Cross reference to Appendix IV -“Room by Room Details - Summary Report By Location” for specifics.

Location Description Location Description7857 Classroom, rm.103 (103) 7932 Washroom - Girls7858 Storage Room (Cannot identity room) 7933 Caretakers Room7859 Office / Admin. Area (Cannot 7934 Washroom

identity room) 7935 Caretakers Room (Cannot identity7860 Storage Room (Cannot identity room) room)7861 Caretakers Room, service room 7936 Closet (Cannot identity room)7862 Washroom 7937 AV Room7864 Caretakers Office (Cannot identity 7938 Change Room

room) 7941 Storage Room7865 Caretakers Office, Mr. Downes office 7942 Shower7866 Storage Room 7943 Change Room7867 Corridor 7944 Washroom - Boys7868 Caretakers Room 7945 Washroom - Girls7869 Classroom, rm.105 (105) 7946 Shower7870 Caretakers Room 7947 Shower7871 Storage Room, rm.110 (110) 7948 Courtyard7872 Kitchen 7949 Corridor7873 Cafetorium 7949-1 Corridor7874 Stage 99441 Stairwell7875 Staff Room, staff dining room 99442 Stairwell

(Cannot identity room) 99443 Stairwell7876 Office / Admin. Area, committee room 99444 Stairwell

(Cannot identity room) 99445 Stairwell7877 Storage Room 99446 Stairwell7878 Washroom - Girls 99457 Gym7879 Washroom - Boys 99458 Stairwell7880 Classroom (104) 99848 Stairwell7881 Staff Room7882 Cafetorium7883 Main Office (112)7884 Empty Room, vault7885 Storage Room7886 Principal Office7887 Vice - Principals Office7888 Office / Admin. Area (Cannot

identity room)7889 Mechanical Room7890 Storage Room7891 Entrance Foyer7892 Storage Room7893 Office / Admin. Area, guidance7894 Photocopy Room7895 Office / Admin. Area7896 Office / Admin. Area, silva martins7897 Office / Admin. Area7898 Office / Admin. Area7899 Storage Room7900 Classroom, rm.106 (Cannot identity

room)7901 Classroom, rm.107 (107)7902 Classroom, rm.108 (108)7903 Classroom, rm.109 (109)7904 Storage Room7905 Change Room, boys7906 Storage Room, english bookroom7907 Classroom (101)7908 Storage Room (Cannot identity room)7909 Classroom, rm.102 (102)7910 Storage Room7911 Classroom, rm.111 (111)7912 Empty Room (Cannot identity room)7913 Empty Room (Cannot identity room)7914 Washroom – Staff Male7915 Washroom – Staff Female7916 Corridor (Cannot identity room)7917 Change Room7918 Change Room, dramatic arts (104)7919 Office / Admin. Area7920 Storage Room7921 Storage Room7922 Storage Room7923 Corridor7924 Office / Admin. Area, female

instructor office7925 Storage Room7927 Gym7928 Washroom7929 Electrical Room7930 Electrical Room7931 Washroom - Boys

CONTINUED FROM FIGURE 1.1

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!

!

!!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!!

!

!

!

!

!

!

AA

A

A

A

A

A

A

!A

8016-4

8007-1

8016-1

8016-2

8016-3

8017-1

99456

99455

99454

99453

99452

99451

99450

99449

99448

99447

8029

8028

8027

8026

8025

8024

8023

8022

8021

8020

8019

8018

8017

8016

8015

80148013

8012

8011

8010

8009

8008

8007

80068005

8004

8003

8002

80018000

79997998

7997

7996

7995

7994

7993

7992

7991

7990

79897988

79877986

79857984

79837982

79817980

7979

7978

7977

7976

7975

7974

7973

7971

7970

79697968

7967

7966

7965

7964

7963

7962

7961

7960

7959

7958

7957

7956

7955

7954

79537952

79517950 3081-1-6005-057-01,02,03

3081-1-5005-056-01,02,03

3081-1-3008-054-01,02,03

3081-1-3008-062-01,02,03

3081-1-3008-061-01,02,03

3081-1-3006-026-01,02,03

3081-1-5005-027-01,02,03 3081-1-3006-025-01,02,03

3081-1-3006-055-01,02,03

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!

!

!

!!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!

!!

!

!

!

!

!

!

AA

A

A

A

A

A

A

!A

8016-4

8007-1

8016-1

8016-2

8016-3

8017-1

99456

99455

99454

99453

99452

99451

99450

99449

99448

99447

8029

8028

8027

8026

8025

8024

8023

8022

8021

8020

8019

8018

8017

8016

8015

80148013

8012

8011

8010

8009

8008

8007

80068005

8004

8003

8002

80018000

79997998

7997

7996

7995

7994

7993

7992

7991

7990

79897988

79877986

79857984

79837982

79817980

7979

7978

7977

7976

7975

7974

7973

7971

7970

79697968

7967

7966

7965

7964

7963

7962

7961

7960

7959

7958

7957

7956

7955

7954

79537952

79517950 3081-1-6005-057-01,02,03

3081-1-5005-056-01,02,03

3081-1-3008-054-01,02,03

3081-1-3008-062-01,02,03

3081-1-3008-061-01,02,03

3081-1-3006-026-01,02,03

3081-1-5005-027-01,02,03 3081-1-3006-025-01,02,03

3081-1-3006-055-01,02,03

PROJECT

TITLE

Drawings based on plans provided by the Toronto District School Board.REFERENCE

0 50 100 15025Feet

G:\P

rojec

ts\20

06\06

-1113

-212_

TDSB

\GIS

\MXD

s\Draf

t\auto

\batch

\A_3

081_

1_2.m

xd

ACM AND SAMPLE LOCATION PLANFLOOR 23081 - SIR SANDFORD FLEMING AC50 AMEER AVENUETORONTO, ONTARIO

ASBESTOS SURVEY - NORTHWEST REGIONTORONTO DISTRICT SCHOOL BOARD FIGURE: 2.1

PROJECT No. 06-1113-212

1. This drawing is schematic only and is to be read in conjunction with theaccompanying text.2. Some numbers provided by the Toronto District School Board have not been used.

NOTESRoof ID: 68437Exterior ID: 68437-1,7926

³N

Description of Asbestos-Containing MaterialsCeiling Tiles

Pipe Insulation

!!

!!

!!

!!

!!

!!

!!

!!

!!

!!Ceiling Tiles,Pipe Insulation

3.Only sampled materials and/or confirmed ACM is shown on the drawing. Shaded areas represent the presence of one or more Asbestos-Containing Material (ACM) component(s). Cross reference to Appendix IV -“Room by Room Details - Summary Report By Location” for specifics.

LEGENDLEGEND!A

!A

Sample #Positive Sample LocationSample #Negative Sample Location Not Tested Sample Location Sample #!A

Location/Room!

Sample # Location Component # Description3081-1-3006-025-01,02,03

7978 25 1x1 med/lrg pinholes, random pattern

3081-1-3006-026-01,02,03

7977 26 1x1 rough texture, random sml/med pinholes

3081-1-3006-055-01,02,03

8007-1 55 1x1 random large/med. pinholes

3081-1-3008-054-01,02,03

8008 54 2x4 stippled random small pinholes

3081-1-3008-061-01,02,03

8017 61 2x4 random slashes, sml/med pinholes

3081-1-3008-062-01,02,03

8016 62 2x4 width-wise fissures w/dimples, sml/med pinholes

3081-1-5005-027-01,02,03

7977 27 Corrugated Cellulose On Straight Run Pipe

3081-1-5005-056-01,02,03

99455 56 Cellulose with dark layer

3081-1-6005-057-01,02,03

7951 57 Tar Paper Over Fiberglass

FOR ROOM DESCRIPTIONS REFER TO FIGURE 2.2

PROJECT

TITLEDrawings based on plans provided by the Toronto District School Board.REFERENCE

G:\P

rojec

ts\20

06\06

-1113

-212_

TDSB

\GIS

\MXD

s\Draf

t\auto

\batch

\A_3

081_

1_2.2

.mxd

ACM AND SAMPLE LOCATION PLANFLOOR 23081 - SIR SANDFORD FLEMING AC50 AMEER AVENUETORONTO, ONTARIO

ASBESTOS SURVEY - NORTHWEST REGIONTORONTO DISTRICT SCHOOL BOARD FIGURE: 2.2

PROJECT No. 06-1113-212

1. This drawing is schematic only and is to be read in conjunction with theaccompanying text.2. Some numbers provided by the Toronto District School Board have not been used.

NOTES

3.Only sampled materials and/or confirmed ACM is shown on the drawing. Shaded areas represent the presence of one or more Asbestos-Containing Material (ACM) component(s). Cross reference to Appendix IV -“Room by Room Details - Summary Report By Location” for specifics.

Location Description Location Description7950 Classroom, rm.212 (212) 8021 Shower7951 Caretakers Room, service rm. 8022 Gym7952 Office / Admin. Area, rm.213 (213) 8023 Other Workshop7953 Storage Room, storage 8024 Hub Room7954 Classroom, rm.214 (214) 8025 Cafetorium7955 Teachers Workroom, prep.rm.a 8026 Courtyard7956 Other Workshop, rm.218 (218) 8027 Gym7957 Classroom, rm.216 (216) 8028 Storage Room, chemical storage7958 Classroom, rm.220 (220) 8029 Storage Room7959 Office / Admin. Area, communications 99447 Stairwell

& language studies (223) 99448 Stairwell7960 Classroom, rm.223/222 (224) 99449 Stairwell7961 Classroom, rm. 224 and 225 (225) 99450 Stairwell7962 Storage Room, office 99451 Stairwell7963 Classroom, rm.226 (226) 99452 Stairwell7964 Classroom, rm.211 (211) 99453 HVAC/Fan Room, fan rm.27965 HVAC/Fan Room, fan rm.5 (#5) 99454 Storage Room, SAC-projection rm.7966 Washroom - Boys 99455 HVAC/Fan Room, fan rm.37967 Washroom – Staff Male 99456 Corridor7968 Washroom - Girls7969 Washroom – Staff Female7970 Classroom, rm.215 (215)7971 Classroom, rm.215 computer rm. (217)7972 Office / Admin. Area, office7973 Classroom, rm. (219)7974 HVAC/Fan Room, fan rm.17975 Storage Room, prep rm.7976 Classroom, rm.221 (221)7977 Change Room7978 Office / Admin. Area7979 Gym, fitness room7980 Classroom, rm.227 (227)7981 Classroom, rm.228 (228)7982 Classroom, rm.210 (210)7983 Classroom, rm.209 (209)7984 HVAC/Fan Room, fan rm.4 (#4)7985 Washroom - Boys7986 HVAC/Fan Room, fan rm.6 (fan room

#6)7987 Washroom - Boys7988 Classroom, rm.229 (229)7989 Classroom, rm.230 (230)7990 Washroom - Girls7991 Gym7992 Classroom, rm.208 (208)7993 Office / Admin. Area, rm.205 (205)7994 Office / Admin. Area, rm.204 (204)7995 Washroom - Girls7996 Washroom – Staff Male7997 Washroom – Staff Female7998 Washroom – Staff Male7999 Caretakers Room, service room8000 Classroom, rm.231 (231)8001 Classroom, rm.232 (232)8002 Classroom, rm.2338003 Office / Admin. Area, rm.234 (234)8004 Storage Room, rm.235 (Cannot

identity room)8005 Library8006 Storage Room, rm.207 (207)8007 Library

8007-1 Computer Room8008 Library office, workroom8009 Library office8010 Classroom, rm.203 (203)8011 Storage Room8012 Classroom, rm.202 (202)8013 Storage Room8014 Classroom, rm.201 (201)8015 Caretakers Room8016 Corridor

8016-1 Corridor8016-2 Corridor8016-3 Corridor8016-4 Corridor

8017 Corridor8017-1 Corridor

8018 Boiler / Furnace Room8019 Other Workshop, prep.rm.8020 Shower (Cannot identity room)

CONTINUED FROM FIGURE 2.1

Golder Associates

APPENDIX II

LABORATORY RESULTS

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Laboratory Results

Appendix II

Page: 1Golder Associates

Refer to Attachment for Definitions and Abbreviations

29 1x1 lrg irregular fissures 3081-1-3006-029-03

2973085 115534 99443 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Grey Ceiling Tile; 1x1

29 1x1 lrg irregular fissures 3081-1-3006-029-02

2973084 115534 99443 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Grey Ceiling Tile; 1x1

29 1x1 lrg irregular fissures 3081-1-3006-029-01

2973083 115534 99443 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Grey Ceiling Tile; 1x1

25 1x1 med/lrg pinholes, random pattern

3081-1-3006-025-01

2973077 115534 7978 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

25 1x1 med/lrg pinholes, random pattern

3081-1-3006-025-02

2973078 115534 7978 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

25 1x1 med/lrg pinholes, random pattern

3081-1-3006-025-03

2973079 115534 7978 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

19 1x1 large/med. pinholes, tetris pattern

3081-1-3006-019-03

2973076 115534 7924 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

17 Parging Cement On Fittings 3081-1-0000-17-01-H

3081-1-0000-17-01-H

N/A N/A N/A 70 Chrysotile N/A Not Tested N/A Historical Data - TDSB Central Files

19 1x1 large/med. pinholes, tetris pattern

3081-1-3006-019-01

2973074 115534 7924 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

19 1x1 large/med. pinholes, tetris pattern

3081-1-3006-019-02

2973075 115534 7924 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

26 1x1 rough texture, random sml/med pinholes

3081-1-3006-026-01

2973080 115534 7977 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

27 Corrugated Cellulose On Straight Run Pipe

3081-1-5005-027-02

2973114 115534 7977 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Brown Fibrous

27 Corrugated Cellulose On Straight Run Pipe

3081-1-5005-027-03

2973115 115534 7977 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Brown Fibrous

28 Parging On Straight Run Pipe 3081-1-0000-28-01-H

3081-1-0000-28-01-H

N/A N/A N/A 50 Chrysotile N/A Not Tested N/A Historical Data - TDSB Central Files

27 Corrugated Cellulose On Straight Run Pipe

3081-1-5005-027-01

2973113B 115534 7977 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 2;Black Tar Paper

26 1x1 rough texture, random sml/med pinholes

3081-1-3006-026-02

2973081 115534 7977 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

26 1x1 rough texture, random sml/med pinholes

3081-1-3006-026-03

2973082 115534 7977 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 1x1

27 Corrugated Cellulose On Straight Run Pipe

3081-1-5005-027-01

2973113A 115534 7977 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 1;Brown Fibrous

Building: 1 (Sir Sandford Fleming Academy)

Component Sample # Lab Sample #

Lab Report Number

Location Test Method

Asbestos I %

Asbestos I Type

Asbestos II %

Asbestos II Type

LOD %

Additional Comments

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Laboratory Results

Appendix II

Page: 2Golder Associates

Refer to Attachment for Definitions and Abbreviations

54 2x4 stippled random small pinholes

3081-1-3008-054-02

2973099 115534 8008 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

54 2x4 stippled random small pinholes

3081-1-3008-054-03

2973100 115534 8008 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

55 1x1 random large/med. pinholes

3081-1-3006-055-01

2973086 115534 8007-1 PLM 2.4 Amosite N/A Not Tested 0.25 Off-White Ceiling Tile; 1x1

51 2 x 4 sml/med. pinholes, circular pattern, dimpled

3081-1-3008-051-02

2973096 115534 7897 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

51 2 x 4 sml/med. pinholes, circular pattern, dimpled

3081-1-3008-051-03

2973097 115534 7897 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

54 2x4 stippled random small pinholes

3081-1-3008-054-01

2973098 115534 8008 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

55 1x1 random large/med. pinholes

3081-1-3006-055-02

2973087 115534 8007-1 PLM N/A Not Tested N/A Not Tested 0.25 Sample not analyzed because previous sample tested positive

51 2 x 4 sml/med. pinholes, circular pattern, dimpled

3081-1-3008-051-01

2973095 115534 7897 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

38 2x4 off-white, random sml/med pinholes

3081-1-3008-038-01

2973092 115534 7869 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

38 2x4 off-white, random sml/med pinholes

3081-1-3008-038-02

2973093 115534 7869 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

36 2x4 sml random fissures, dense sml/med pinholes

3081-1-3008-036-03

2973091 115534 7868 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

36 2x4 sml random fissures, dense sml/med pinholes

3081-1-3008-036-01

2973089 115534 7868 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

36 2x4 sml random fissures, dense sml/med pinholes

3081-1-3008-036-02

2973090 115534 7868 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

39 Fibrous SPF On Beam, Deck, Joist

3081-1-4008-039-03

2973112 115534 7869 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Grey Insulation

45 Parging Cement On Seam & Joints And Pins

3081-1-0000-45-01-H

3081-1-0000-45-01-H

N/A N/A N/A 70 Chrysotile N/A Not Tested N/A Historical Data - TDSB Central Files

39 Fibrous SPF On Beam, Deck, Joist

3081-1-4008-039-02

2973111 115534 7869 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Grey Insulation

38 2x4 off-white, random sml/med pinholes

3081-1-3008-038-03

2973094 115534 7869 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

39 Fibrous SPF On Beam, Deck, Joist

3081-1-4008-039-01

2973110 115534 7869 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Grey Insulation

Building: 1 (Sir Sandford Fleming Academy)

Component Sample # Lab Sample #

Lab Report Number

Location Test Method

Asbestos I %

Asbestos I Type

Asbestos II %

Asbestos II Type

LOD %

Additional Comments

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Laboratory Results

Appendix II

Page: 3Golder Associates

Refer to Attachment for Definitions and Abbreviations

57 Tar Paper Over Fiberglass 3081-1-6005-057-03

2973121C 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 3;Tan Insulation

60 2x4 length-wise fissures w/ sml pinholes, dimpled

3081-1-3008-060-01

2973101 115534 8017-1 PLM 3.1 Amosite N/A Not Tested 0.25 Off-White Ceiling Tile; 2x4

60 2x4 length-wise fissures w/ sml pinholes, dimpled

3081-1-3008-060-02

2973102 115534 8017-1 PLM N/A Not Tested N/A Not Tested 0.25 Sample not analyzed because previous sample tested positive

57 Tar Paper Over Fiberglass 3081-1-6005-057-02

2973120C 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 3;Tan Insulation

57 Tar Paper Over Fiberglass 3081-1-6005-057-03

2973121A 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 1;Brown Wrap

57 Tar Paper Over Fiberglass 3081-1-6005-057-03

2973121B 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 2;Brown/Black Tar Paper

57 Tar Paper Over Fiberglass 3081-1-6005-057-02

2973120B 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 2;Brown/Black Tar Paper

56 Cellulose with dark layer 3081-1-5005-056-02

2973117 115534 99455 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Brown/Grey Fibrous

56 Cellulose with dark layer 3081-1-5005-056-03

2973118A 115534 99455 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 1;Grey Fibrous

56 Cellulose with dark layer 3081-1-5005-056-01

2973116B 115534 99455 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 2;Black Tar Paper

55 1x1 random large/med. pinholes

3081-1-3006-055-03

2973088 115534 8007-1 PLM N/A Not Tested N/A Not Tested 0.25 Sample not analyzed because previous sample tested positive

56 Cellulose with dark layer 3081-1-5005-056-01

2973116A 115534 99455 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 1;Grey Fibrous

57 Tar Paper Over Fiberglass 3081-1-6005-057-01

2973119C 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 3;Tan Insulation

57 Tar Paper Over Fiberglass 3081-1-6005-057-02

2973120A 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 1;Brown Wrap

57 Tar Paper Over Fiberglass 3081-1-6005-057-01

2973119B 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 2;Brown/Black Tar Paper

56 Cellulose with dark layer 3081-1-5005-056-03

2973118B 115534 99455 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 2;Black Tar Paper

57 Tar Paper Over Fiberglass 3081-1-6005-057-01

2973119A 115534 7951 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Layer 1;Brown Wrap

Building: 1 (Sir Sandford Fleming Academy)

Component Sample # Lab Sample #

Lab Report Number

Location Test Method

Asbestos I %

Asbestos I Type

Asbestos II %

Asbestos II Type

LOD %

Additional Comments

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Laboratory Results

Appendix II

Page: 4Golder Associates

Refer to Attachment for Definitions and Abbreviations

61 2x4 random slashes, sml/med pinholes

3081-1-3008-061-03

2973106 115534 8017 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

61 2x4 random slashes, sml/med pinholes

3081-1-3008-061-02

2973105 115534 8017 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

62 2x4 width-wise fissures w/dimples, sml/med pinholes

3081-1-3008-062-01

2973107 115534 8016 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

62 2x4 width-wise fissures w/dimples, sml/med pinholes

3081-1-3008-062-03

2973109 115534 8016 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

62 2x4 width-wise fissures w/dimples, sml/med pinholes

3081-1-3008-062-02

2973108 115534 8016 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

60 2x4 length-wise fissures w/ sml pinholes, dimpled

3081-1-3008-060-03

2973103 115534 8017-1 PLM N/A Not Tested N/A Not Tested 0.25 Sample not analyzed because previous sample tested positive

61 2x4 random slashes, sml/med pinholes

3081-1-3008-061-01

2973104 115534 8017 PLM <LOD No Asbestos Detected

N/A Not Tested 0.25 Tan Ceiling Tile; 2x4

Building: 1 (Sir Sandford Fleming Academy)

Component Sample # Lab Sample #

Lab Report Number

Location Test Method

Asbestos I %

Asbestos I Type

Asbestos II %

Asbestos II Type

LOD %

Additional Comments

Golder Associates

APPENDIX III

SUMMARY OF ALL ASBESTOS-CONTAINING MATERIALS

(ACM & PACM)

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Summary of All Asbestos-Containing Materials

Appendix III - ACM & PACM

Golder Associates Page: 1

Refer to Attachment for Definitions and Abbreviations

28 Parging On Straight Run Pipe Yes 7890; 7925; PIPING SYSTEMS 11.00 linear feet A Yes 50 Chrysotile 6

21 Transite Asbestos Cement No 7991; WALL 1,350.00 square feet C Yes N/A Presumed 6

21 Transite Asbestos Cement No 7857; 7859; 7860; 7916; WALL 785.00 square feet A Yes N/A Presumed 6

20 Plaster Yes 7893; 7897; 7898; 7899; CEILING 320.00 square feet D No N/A Presumed 6

20 Plaster Yes 7891; 7942; 7991; 8017; 8017-1; 99456; 99848;

CEILING 2,255.00 square feet C Yes N/A Presumed 6

17 Parging Cement On Fittings Yes 7967; PIPING SYSTEMS 5 each B No 70 Chrysotile 6

17 Parging Cement On Fittings Yes 7908; 7927; 7976; 7991; 8029; PIPING SYSTEMS 16 each C Yes 70 Chrysotile 6

17 Parging Cement On Fittings Yes 7889; 7904; PIPING SYSTEMS 31 each B Yes 70 Chrysotile 6

17 Parging Cement On Fittings Yes 7861; 7867; 7869; 7882; 7895; 7905; 7906; 7909; 7911; 7936; 7944; 7949; 7949-1; 7963; 7979; 8016-2; 8016-4; 8017; 8022; 99456;

PIPING SYSTEMS 282 each D No 70 Chrysotile 6

16 Other Suspect Piping - in gym No 7927; 7991; PIPING SYSTEMS 15.00 linear feet C Yes N/A Presumed 6

15 Bell & Spigot Joints No 7928; 7967; 7977; PIPING SYSTEMS 16 each B No N/A Presumed 6

15 Bell & Spigot Joints No 7927; PIPING SYSTEMS 3 each C Yes N/A Presumed 6

15 Bell & Spigot Joints No 7871; 7878; 7949-1; 8016-2; PIPING SYSTEMS 50 each D No N/A Presumed 6

15 Bell & Spigot Joints No 7871; 7920; PIPING SYSTEMS 5 each A Yes N/A Presumed 6

15 Bell & Spigot Joints No 7868; 7974; 8018; 99453; PIPING SYSTEMS 39 each B Yes N/A Presumed 6

13 Plaster Yes 99441; 99445; WALL 80.00 square feet C Yes N/A Presumed 6

13 Plaster Yes 7881; 7882; 7891; 7949; 7949-1; 8016; 8016-1; 8016-2; 8016-3; 8016-4; 8017; 8017-1; 99456; 99458;

WALL 15,980.00 square feet A Yes N/A Presumed 6

Building: 1 (Sir Sandford Fleming Academy)

Component Description of Material Friable Locations System Quantity Units Accessibility Visible Asbestos % Type Action Code

Component Details Asbestos Content

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Summary of All Asbestos-Containing Materials

Appendix III - ACM & PACM

Golder Associates Page: 2

Refer to Attachment for Definitions and Abbreviations

31 Window Sealers No 7867; OTHER 1 each C Yes N/A Presumed 6

31 Window Sealers No 7861; 7864; 7865; 7904; 8018; OTHER 7 each B Yes N/A Presumed 6

31 Window Sealers No 7857; 7858; 7859; 7869; 7872; 7875; 7880; 7881; 7882; 7883; 7886; 7887; 7888; 7890; 7895; 7896; 7900; 7901; 7902; 7903; 7907; 7908; 7909; 7911; 7915; 7919; 7949; 7949-1; 7950; 7952; 7954; 7955; 7956; 7957; 7958; 7959; 7960; 7961; 7962; 7963; 7964; 7970; 7980; 7981; 7982; 7983; 7988; 7989; 7992; 7993; 7994; 8000; 8001; 8002; 8003; 8004; 8005; 8007; 8007-1; 8008; 8009; 8010; 8012; 8014; 8016; 8016-2; 8016-3; 8016-4; 99444; 99447; 99448; 99449; 99450; 99451; 99452; 99458;

OTHER 190 each A Yes N/A Presumed 6

30 Horizontal Drywall Bulkhead No 7955; 7959; OTHER 20.00 square feet A Yes N/A Presumed 6

30 Horizontal Drywall Bulkhead No 7892; 7900; 7903; OTHER 165.00 square feet D No N/A Presumed 6

30 Horizontal Drywall Bulkhead No 7860; 7869; 7880; 7887; 7888; 7901; 7902; 7903; 7907; 7909; 7918; 7919; 7950; 7952; 7960; 7961; 7964; 7982; 7983; 7988; 7989; 7992; 8000; 8002; 8003; 8004; 8005; 8012; 8014;

OTHER 1,050.00 square feet C Yes N/A Presumed 6

3 Other Vinyl Floor Tile No 7864; 7865; 7935; 7951; 8018; FLOOR 675.00 square feet B Yes N/A Presumed 6

3 Other Vinyl Floor Tile No 7857; 7858; 7859; 7860; 7867; 7869; 7871; 7874; 7875; 7876; 7881; 7882; 7883; 7885; 7886; 7887; 7888; 7890; 7892; 7893; 7894; 7895; 7896; 7898; 7900; 7901; 7902; 7903; 7906; 7907; 7908; 7909; 7910; 7911; 7916; 7918; 7919; 7920; 7921; 7922; 7924; 7925; 7926; 7936; 7937; 7941; 7950; 7952; 7953; 7954; 7955; 7956; 7957; 7958; 7959; 7960; 7961; 7962; 7963; 7964; 7970; 7971; 7973; 7976; 7977; 7978; 7979; 7980; 7981; 7982; 7983; 7988; 7989; 7992; 7993; 7994; 8000; 8001; 8002; 8003; 8004; 8006; 8008; 8010; 8011; 8012; 8013; 8014; 8015; 8016; 8016-1; 8016-2; 8016-3; 8016-4; 8017; 8017-1; 8023; 8028; 8029; 99454; 99456; 99848;

FLOOR 63,365.00 square feet A Yes N/A Presumed 6

Building: 1 (Sir Sandford Fleming Academy)

Component Description of Material Friable Locations System Quantity Units Accessibility Visible Asbestos % Type Action Code

Component Details Asbestos Content

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Summary of All Asbestos-Containing Materials

Appendix III - ACM & PACM

Golder Associates Page: 3

Refer to Attachment for Definitions and Abbreviations

53 Vinyl Sheet Flooring Yes 8007; FLOOR 500.00 square feet A Yes N/A Presumed 6

50 Flexible Shingle No 68437; OTHER 1 each B Yes N/A Presumed 6

5 Drywall And Joint Compound No 8016-2; WALL 200.00 square feet D No N/A Presumed 6

5 Drywall And Joint Compound No 7882; 7929; 7930; 7949; 7949-1; 99443; 99445; 99446; 99447; 99448; 99449; 99450; 99452;

WALL 1,920.00 square feet C Yes N/A Presumed 6

5 Drywall And Joint Compound No 7874; 7885; 7892; 7893; 7895; 7896; 7897; 7898; 7899; 7900; 7906; 7911; 7954; 7956; 7957; 7961; 7963; 7970; 8002; 8007; 8007-1; 8008; 8009; 8016; 8016-1; 8016-2; 8016-3; 8016-4; 8017; 8017-1; 8019; 8022; 8023; 99444; 99454; 99456;

WALL 9,690.00 square feet A Yes N/A Presumed 6

49 Built Up Membrane Roof No 68437; OTHER 1 each B Yes N/A Presumed 6

48 Drywall Column Enclosure Yes 7974; STRUCTURE 220.00 square feet B Yes N/A Presumed 6

47 Flexible Duct Connector Yes 7974; DUCTWORK 5 each A Yes N/A Presumed 6

47 Flexible Duct Connector Yes 7965; 7984; 99453; 99455; DUCTWORK 33 each B Yes N/A Presumed 6

47 Flexible Duct Connector Yes 7955; DUCTWORK 2 each D No N/A Presumed 6

45 Parging Cement On Seam & Joints And Pins

Yes 7930; DUCTWORK 50.00 square feet B Yes 70 Chrysotile 6

44 Drywall Beam Enclosure No 7930; 7965; 7974; 7984; 99453; 99455; STRUCTURE 500.00 square feet C Yes N/A Presumed 6

42 Cellulose & Tar Paper On Straight Run Pipe

Yes 7878; 8016-1; 99456; PIPING SYSTEMS 67.00 linear feet D No N/A Presumed 6

41 Plaster Column Enclosure Yes 7959; STRUCTURE 10.00 square feet C No N/A Presumed 6

41 Plaster Column Enclosure Yes 7882; 8004; 8016-3; 8016-4; STRUCTURE 945.00 square feet A Yes N/A Presumed 6

40 Transite Asbestos Cement No 7857; 7858; 7859; 7860; CEILING 980.00 square feet C Yes N/A Presumed 6

37 Vertical Drywall Bulkhead No 7871; 7900; 7957; 7958; 8001; OTHER 250.00 square feet A Yes N/A Presumed 6

34 Other Suspect Piping in receiving area

No 7867; PIPING SYSTEMS 10.00 linear feet D No N/A Presumed 6

33 Boiler Gasket Yes 8018; MECHANICAL EQUIPMENT

2 each B Yes N/A Presumed 6

Building: 1 (Sir Sandford Fleming Academy)

Component Description of Material Friable Locations System Quantity Units Accessibility Visible Asbestos % Type Action Code

Component Details Asbestos Content

Date: 11/8/2007

Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

Job Number : 06-1113-212Summary of All Asbestos-Containing Materials

Appendix III - ACM & PACM

Golder Associates Page: 4

Refer to Attachment for Definitions and Abbreviations

7 Drywall And Joint Compound No 99446; CEILING 100.00 square feet A Yes N/A Presumed 6

7 Drywall And Joint Compound No 7898; CEILING 40.00 square feet C No N/A Presumed 6

7 Drywall And Joint Compound No 7892; 7893; 8016; CEILING 570.00 square feet D No N/A Presumed 6

7 Drywall And Joint Compound No 7857; 7859; 7860; 7861; 7862; 7864; 7865; 7866; 7867; 7870; 7872; 7873; 7877; 7878; 7879; 7882; 7894; 7897; 7899; 7910; 7914; 7915; 7916; 7920; 7922; 7924; 7925; 7926; 7928; 7931; 7932; 7933; 7935; 7943; 7944; 7945; 7947; 7949; 7949-1; 7951; 7953; 7954; 7955; 7962; 7966; 7967; 7968; 7969; 7970; 7977; 7979; 7985; 7987; 7990; 7995; 7997; 7998; 7999; 8011; 8013; 8015; 8016; 8016-1; 8016-2; 8016-3; 8016-4; 8020; 8028; 99441; 99443; 99445; 99449; 99458;

CEILING 22,905.00 square feet C Yes N/A Presumed 6

60 2x4 length-wise fissures w/ sml pinholes, dimpled

Yes 8016-4; 8017-1; CEILING 675.00 square feet C Yes 3.1 Amosite 6

59 Transite Fume Hood No 7958; OTHER 10.00 square feet A Yes N/A Presumed 6

58 Transite Counter Top No 7957; 7958; OTHER 300.00 square feet A Yes N/A Presumed 6

55 1x1 random large/med. pinholes

Yes 7980; 7981; 8007-1; CEILING 2,695.00 square feet C Yes 2.4 Amosite 6

Building: 1 (Sir Sandford Fleming Academy)

Component Description of Material Friable Locations System Quantity Units Accessibility Visible Asbestos % Type Action Code

Component Details Asbestos Content

Golder Associates

APPENDIX IV

ROOM-BY-ROOM DETAILS

SUMMARY REPORT BY LOCATION

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 1Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 95.00 0.00 0.00 0.00 95.00 square feet

- Presumed No Yes A 6

WALL Wood 14 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Transite Asbestos Cement 40 85.00 0.00 0.00 0.00 85.00 square feet

- Presumed No Yes C 6

Location: Floor 1: 7858 Quantity/ConditionTotal

Location Details: Storage Room (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

CEILING Transite Asbestos Cement 40 780.00 0.00 0.00 0.00 780.00 square feet

- Presumed No Yes C 6

CEILING Drywall And Joint Compound 7 1300.00 0.00 0.00 0.00 1300.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1300.00 0.00 0.00 0.00 1300.00 square feet

- Presumed No Yes A 6

WALL Transite Asbestos Cement 21 500.00 0.00 0.00 0.00 500.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7857 Quantity/ConditionTotal

Location Details: Classroom, rm.103 (103) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 2Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 145.00 0.00 0.00 0.00 145.00 square feet

- Presumed No Yes C 6

CEILING Transite Asbestos Cement 40 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes C 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 145.00 0.00 0.00 0.00 145.00 square feet

- Presumed No Yes A 6

WALL Transite Asbestos Cement 21 115.00 0.00 0.00 0.00 115.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7859 Quantity/ConditionTotal

Location Details: Office / Admin. Area (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7858 Quantity/ConditionTotal

Location Details: Storage Room (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 3Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Drywall And Joint Compound 7 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 1 0 0 0 1 each 70 Chrysotile Yes No D 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7861 Quantity/ConditionTotal

Location Details: Caretakers Room, service room (No access above ceiling. )

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Transite Asbestos Cement 21 155.00 0.00 0.00 0.00 155.00 square feet

- Presumed No Yes A 6

CEILING Transite Asbestos Cement 40 65.00 0.00 0.00 0.00 65.00 square feet

- Presumed No Yes C 6

CEILING Drywall And Joint Compound 7 130.00 0.00 0.00 0.00 130.00 square feet

- Presumed No Yes C 6

OTHER Horizontal Drywall Bulkhead 30 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 130.00 0.00 0.00 0.00 130.00 square feet

- Presumed No Yes A 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7860 Quantity/ConditionTotal

Location Details: Storage Room (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 4Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 410.00 0.00 0.00 0.00 410.00 square feet

- Presumed No Yes B 6

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 1: 7864 Quantity/ConditionTotal

Location Details: Caretakers Office (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7862 Quantity/Condition Total Location Details: Washroom (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes B 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7861 Quantity/ConditionTotal

Location Details: Caretakers Room, service room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 5Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes B 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 105.00 0.00 0.00 0.00 105.00 square feet

- Presumed No Yes B 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 105.00 0.00 0.00 0.00 105.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7865 Quantity/ConditionTotal

Location Details: Caretakers Office, Mr. Downes office (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 410.00 0.00 0.00 0.00 410.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes B 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7864 Quantity/ConditionTotal

Location Details: Caretakers Office (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 6Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 365.00 0.00 0.00 0.00 365.00 square feet

- Presumed No Yes C 6

PIPING SYSTEMS Parging Cement On Fittings 17 16 0 0 0 16 each 70 Chrysotile Yes No D 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes C 6

PIPING SYSTEMS Fibreglass 23 - - - - - - - - - - - -

PIPING SYSTEMS Other Suspect Piping in receiving area 34 10.00 0.00 0.00 0.00 10.00 linear feet - Presumed No No D 6

FLOOR Other Vinyl Floor Tile 3 365.00 0.00 0.00 0.00 365.00 square feet

- Presumed No Yes A 6

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7867 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 220.00 0.00 0.00 0.00 220.00 square feet

- Presumed No Yes C 6

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7866 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 7Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 21 0 0 0 21 each 70 Chrysotile Yes No D 6

STRUCTURE Fibrous SPF On Beam, Deck, Joist 39 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 955.00 0.00 0.00 0.00 955.00 square feet

- Presumed No Yes A 6

CEILING 2x4 off-white, random sml/med pinholes 38 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7869 Quantity/Condition Total Location Details: Classroom, rm.105 (105) (Open)

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Vinyl Flexible Duct Connector 35 - - - - - - - - - - - -

CEILING 2x4 sml random fissures, dense sml/med pinholes 36 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 6 0 0 0 6 each - Presumed No Yes B 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

Location: Floor 1: 7868 Quantity/Condition Total Location Details: Caretakers Room (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 8Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 1 0 0 0 1 each - Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 875.00 0.00 0.00 0.00 875.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 2x4 sml random fissures, dense sml/med pinholes 36 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Bell & Spigot Joints 15 20 0 0 0 20 each - Presumed No No D 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7871 Quantity/Condition Total Location Details: Storage Room, rm.110 (110) (Open)

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 130.00 0.00 0.00 0.00 130.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7870 Quantity/Condition Total Location Details: Caretakers Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Horizontal Drywall Bulkhead 30 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

Location: Floor 1: 7869 Quantity/Condition Total Location Details: Classroom, rm.105 (105) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 9Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Drywall And Joint Compound 7 445.00 0.00 0.00 0.00 445.00 square feet

- Presumed No Yes C 6

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7873 Quantity/Condition Total Location Details: Cafetorium (No access above ceiling. )

WALL Concrete Block 4 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 565.00 0.00 0.00 0.00 565.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7872 Quantity/Condition Total Location Details: Kitchen (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Corrugated Cellulose On Straight Run Pipe 27 - - - - - - <LOD No Asbestos Detected

- - - -

OTHER Vertical Drywall Bulkhead 37 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Location: Floor 1: 7871 Quantity/Condition Total Location Details: Storage Room, rm.110 (110) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 10Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 530.00 0.00 0.00 0.00 530.00 square feet

- Presumed No Yes A 6

Location: Floor 1: 7875 Quantity/ConditionTotal

Location Details: Staff Room, staff dining room (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 1200.00 0.00 0.00 0.00 1200.00 square feet

- Presumed No Yes A 6

FLOOR Wood 14 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes A 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

Location: Floor 1: 7874 Quantity/Condition Total Location Details: Stage (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7873 Quantity/Condition Total Location Details: Cafetorium (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 11Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 140.00 0.00 0.00 0.00 140.00 square feet

- Presumed No Yes A 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7876 Quantity/ConditionTotal

Location Details: Office / Admin. Area, committee room (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7875 Quantity/ConditionTotal

Location Details: Staff Room, staff dining room (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 12Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Bell & Spigot Joints 15 15 0 0 0 15 each - Presumed No No D 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Cellulose & Tar Paper On Straight Run Pipe 42 35.00 0.00 0.00 0.00 35.00 linear feet - Presumed Yes No D 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 175.00 0.00 0.00 0.00 175.00 square feet

- Presumed No Yes C 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7878 Quantity/Condition Total Location Details: Washroom - Girls (Open)

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7877 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 13Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 85.00 0.00 0.00 0.00 85.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

FLOOR Carpet 43 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7880 Quantity/Condition Total Location Details: Classroom (104) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 115.00 0.00 0.00 0.00 115.00 square feet

- Presumed No Yes C 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7879 Quantity/Condition Total Location Details: Washroom - Boys (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 14Golder Associates

Refer to Attachment for Definitions and Abbreviations

WALL Drywall And Joint Compound 5 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes C 6

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 4400.00 0.00 0.00 0.00 4400.00 square feet

- Presumed No Yes C 6

WALL Plaster 13 1700.00 0.00 0.00 0.00 1700.00 square feet

- Presumed Yes Yes A 6

WALL Wood 14 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 5400.00 0.00 0.00 0.00 5400.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7882 Quantity/Condition Total Location Details: Cafetorium (No access above ceiling. )

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 935.00 0.00 0.00 0.00 935.00 square feet

- Presumed No Yes A 6

WALL Plaster 13 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed Yes Yes A 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7881 Quantity/Condition Total Location Details: Staff Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 15Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1280.00 0.00 0.00 0.00 1280.00 square feet

- Presumed No Yes A 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7883 Quantity/Condition Total Location Details: Main Office (112) (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 0 30 0 0 30 each 70 Chrysotile Yes No D 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

STRUCTURE Plaster Column Enclosure 41 750.00 0.00 0.00 0.00 750.00 square feet

- Presumed Yes Yes A 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

OTHER Window Sealers 31 4 0 0 0 4 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7882 Quantity/Condition Total Location Details: Cafetorium (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 16Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 260.00 0.00 0.00 0.00 260.00 square feet

- Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 105.00 0.00 0.00 0.00 105.00 square feet

- Presumed No Yes A 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7885 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

CEILING To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

Location: Floor 1: 7884 Quantity/Condition Total Location Details: Empty Room, vault (No access to location)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 17Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

OTHER Horizontal Drywall Bulkhead 30 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes C 6

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7887 Quantity/Condition Total Location Details: Vice - Principals Office (No access above ceiling. )

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Wood 14 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 320.00 0.00 0.00 0.00 320.00 square feet

- Presumed No Yes A 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7886 Quantity/Condition Total Location Details: Principal Office (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 18Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 1: 7889 Quantity/Condition Total Location Details: Mechanical Room (room under stairs - Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7888 Quantity/ConditionTotal

Location Details: Office / Admin. Area (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7887 Quantity/Condition Total Location Details: Vice - Principals Office (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 19Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Plaster 13 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed Yes Yes A 6

Location: Floor 1: 7891 Quantity/Condition Total Location Details: Entrance Foyer (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging On Straight Run Pipe 28 1.00 0.00 0.00 0.00 1.00 linear feet 50 Chrysotile Yes Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7890 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Diatomaceous Earth 52 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 25 0 0 0 25 each 70 Chrysotile Yes Yes B 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7889 Quantity/Condition Total Location Details: Mechanical Room (room under stairs - Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 20Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Vinyl Flexible Duct Connector 35 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No No D 6

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No No D 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 175.00 0.00 0.00 0.00 175.00 square feet

- Presumed No Yes A 6

WALL Drywall And Joint Compound 5 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes A 6

CEILING 2 x 4 sml/med. pinholes, circular pattern, dimpled 51 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7892 Quantity/Condition Total Location Details: Storage Room (Open)

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Plaster 20 420.00 0.00 0.00 0.00 420.00 square feet

- Presumed Yes Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7891 Quantity/Condition Total Location Details: Entrance Foyer (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 21Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 235.00 0.00 0.00 0.00 235.00 square feet

- Presumed No Yes C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 235.00 0.00 0.00 0.00 235.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7894 Quantity/Condition Total Location Details: Photocopy Room (No access above ceiling. )

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

CEILING 2 x 4 sml/med. pinholes, circular pattern, dimpled 51 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No No D 6

CEILING Plaster 20 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed Yes No D 6

FLOOR Other Vinyl Floor Tile 3 700.00 0.00 0.00 0.00 700.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 320.00 0.00 0.00 0.00 320.00 square feet

- Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7893 Quantity/ConditionTotal

Location Details: Office / Admin. Area, guidance (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 22Golder Associates

Refer to Attachment for Definitions and Abbreviations

WALL Drywall And Joint Compound 5 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 1: 7896 Quantity/Condition Total Location Details: Office / Admin. Area, silva martins (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

CEILING 2 x 4 sml/med. pinholes, circular pattern, dimpled 51 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes A 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 0 3 0 0 3 each 70 Chrysotile Yes No D 6

PIPING SYSTEMS Fibreglass 23 - - - - - - - - - - - -

Location: Floor 1: 7895 Quantity/Condition Total Location Details: Office / Admin. Area (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7894 Quantity/Condition Total Location Details: Photocopy Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 23Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

CEILING Plaster 20 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed Yes No D 6

CEILING 2 x 4 sml/med. pinholes, circular pattern, dimpled 51 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Drywall And Joint Compound 5 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes A 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7897 Quantity/Condition Total Location Details: Office / Admin. Area (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING 2 x 4 sml/med. pinholes, circular pattern, dimpled 51 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Fibreglass 23 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7896 Quantity/Condition Total Location Details: Office / Admin. Area, silva martins (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 24Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

CEILING 2 x 4 sml/med. pinholes, circular pattern, dimpled 51 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

CEILING Plaster 20 80.00 0.00 0.00 0.00 80.00 square feet

- Presumed Yes No D 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7899 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

CEILING 2 x 4 sml/med. pinholes, circular pattern, dimpled 51 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed No No C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 80.00 0.00 0.00 0.00 80.00 square feet

- Presumed No Yes A 6

WALL Drywall And Joint Compound 5 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

CEILING Plaster 20 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed Yes No D 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Fibreglass 23 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7898 Quantity/Condition Total Location Details: Office / Admin. Area (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 25Golder Associates

Refer to Attachment for Definitions and Abbreviations

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

OTHER Vertical Drywall Bulkhead 37 25.00 0.00 0.00 0.00 25.00 square feet

- Presumed No Yes A 6

CEILING 2x4 sml random fissures, dense sml/med pinholes 36 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 175.00 0.00 0.00 0.00 175.00 square feet

- Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 815.00 0.00 0.00 0.00 815.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 15.00 0.00 0.00 0.00 15.00 square feet

- Presumed No No D 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

Location: Floor 1: 7900 Quantity/Condition Total Location Details: Classroom, rm.106 (Cannot identity room) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7899 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 26Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1015.00 0.00 0.00 0.00 1015.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7902 Quantity/Condition Total Location Details: Classroom, rm.108 (108) (Open)

FLOOR Other Vinyl Floor Tile 3 1140.00 0.00 0.00 0.00 1140.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Location: Floor 1: 7901 Quantity/Condition Total Location Details: Classroom, rm.107 (107) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 27Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 6 0 0 0 6 each 70 Chrysotile Yes Yes B 6

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes B 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7904 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1045.00 0.00 0.00 0.00 1045.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 85.00 0.00 0.00 0.00 85.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No No D 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Location: Floor 1: 7903 Quantity/Condition Total Location Details: Classroom, rm.109 (109) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 28Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 105.00 0.00 0.00 0.00 105.00 square feet

- Presumed No Yes A 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 0 5 0 0 5 each 70 Chrysotile Yes No D 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 320.00 0.00 0.00 0.00 320.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7906 Quantity/ConditionTotal

Location Details: Storage Room, english bookroom (No access above ceiling. )

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 0 20 0 0 20 each 70 Chrysotile Yes No D 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7905 Quantity/ConditionTotal

Location Details: Change Room, boys (No access above ceiling. includes 7938.)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 29Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 115.00 0.00 0.00 0.00 115.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7908 Quantity/Condition Total Location Details: Storage Room (Cannot identity room) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 865.00 0.00 0.00 0.00 865.00 square feet

- Presumed No Yes A 6

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7907 Quantity/Condition Total Location Details: Classroom (101) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7906 Quantity/ConditionTotal

Location Details: Storage Room, english bookroom (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 30Golder Associates

Refer to Attachment for Definitions and Abbreviations

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 805.00 0.00 0.00 0.00 805.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 0 6 0 0 6 each 70 Chrysotile Yes No D 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7909 Quantity/ConditionTotal

Location Details: Classroom, rm.102 (102) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Parging Cement On Fittings 17 9 1 0 0 10 each 70 Chrysotile Yes Yes C 5

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7908 Quantity/Condition Total Location Details: Storage Room (Cannot identity room) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 31Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 500.00 0.00 0.00 0.00 500.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 0 15 0 0 15 each 70 Chrysotile Yes No D 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7911 Quantity/ConditionTotal

Location Details: Classroom, rm.111 (111) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7910 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 32Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7913 Quantity/ConditionTotal

Location Details: Empty Room (Cannot identity room) (doesn't exist - No access to location)

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

Location: Floor 1: 7912 Quantity/ConditionTotal

Location Details: Empty Room (Cannot identity room) (doesn't exist - No access to location)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7911 Quantity/ConditionTotal

Location Details: Classroom, rm.111 (111) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 33Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 135.00 0.00 0.00 0.00 135.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7915 Quantity/ConditionTotal

Location Details: Washroom – Staff Female (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 110.00 0.00 0.00 0.00 110.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7914 Quantity/Condition Total Location Details: Washroom – Staff Male (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER To Be Determined - - - - - - - - TBD - - - -

Location: Floor 1: 7913 Quantity/ConditionTotal

Location Details: Empty Room (Cannot identity room) (doesn't exist - No access to location)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 34Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR To Be Determined - - - - - - - - TBD - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7917 Quantity/ConditionTotal

Location Details: Change Room (No access above ceiling. refer to 7923)

CEILING Drywall And Joint Compound 7 270.00 0.00 0.00 0.00 270.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 290.00 0.00 0.00 0.00 290.00 square feet

- Presumed No Yes A 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Transite Asbestos Cement 21 15.00 0.00 0.00 0.00 15.00 square feet

- Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7916 Quantity/ConditionTotal

Location Details: Corridor (Cannot identity room) (No access above ceiling. Includes 7939 and 7940.)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7915 Quantity/ConditionTotal

Location Details: Washroom – Staff Female (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 35Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 65.00 0.00 0.00 0.00 65.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 280.00 0.00 0.00 0.00 280.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7918 Quantity/ConditionTotal

Location Details: Change Room, dramatic arts (104) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7917 Quantity/ConditionTotal

Location Details: Change Room (No access above ceiling. refer to 7923)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 36Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 4 0 0 0 4 each - Presumed No Yes A 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes A 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7920 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 65.00 0.00 0.00 0.00 65.00 square feet

- Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7919 Quantity/Condition Total Location Details: Office / Admin. Area (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 37Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 405.00 0.00 0.00 0.00 405.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 405.00 0.00 0.00 0.00 405.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 1: 7922 Quantity/Condition Total Location Details: Storage Room (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 290.00 0.00 0.00 0.00 290.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7921 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7920 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 38Golder Associates

Refer to Attachment for Definitions and Abbreviations

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes A 6

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

Location: Floor 1: 7924 Quantity/ConditionTotal

Location Details: Office / Admin. Area, female instructor office (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

WALL Concrete Block 4 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7923 Quantity/Condition Total Location Details: Corridor (No access above ceiling. includes 7917)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7922 Quantity/Condition Total Location Details: Storage Room (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 39Golder Associates

Refer to Attachment for Definitions and Abbreviations

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 80.00 0.00 0.00 0.00 80.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 80.00 0.00 0.00 0.00 80.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Parging On Straight Run Pipe 28 10.00 0.00 0.00 0.00 10.00 linear feet 50 Chrysotile Yes Yes A 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7925 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7924 Quantity/ConditionTotal

Location Details: Office / Admin. Area, female instructor office (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 40Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Drywall And Joint Compound 7 110.00 0.00 0.00 0.00 110.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 2 0 0 0 2 each - Presumed No No B 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7928 Quantity/Condition Total Location Details: Washroom (No access above ceiling. )

FLOOR Wood 14 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

OTHER Wood 14 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 3 0 0 0 3 each - Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Other Suspect Piping - in gym 16 3.00 0.00 0.00 0.00 3.00 linear feet - Presumed No Yes C 6

PIPING SYSTEMS Parging Cement On Fittings 17 1 0 0 0 1 each 70 Chrysotile Yes Yes C 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Location: Floor 1: 7927 Quantity/Condition Total Location Details: Gym (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 41Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Parging Cement On Seam & Joints And Pins 45 50.00 0.00 0.00 0.00 50.00 square feet

70 Chrysotile Yes Yes B 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Uninsulated 2 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 85.00 0.00 0.00 0.00 85.00 square feet

- Presumed No Yes C 6

STRUCTURE Drywall Beam Enclosure 44 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed No Yes C 6

CEILING Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7930 Quantity/Condition Total Location Details: Electrical Room (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

CEILING Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes C 6

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7929 Quantity/Condition Total Location Details: Electrical Room (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 42Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 185.00 0.00 0.00 0.00 185.00 square feet

- Presumed No Yes C 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7932 Quantity/Condition Total Location Details: Washroom - Girls (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 155.00 0.00 0.00 0.00 155.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7931 Quantity/Condition Total Location Details: Washroom - Boys (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 43Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7934 Quantity/Condition Total Location Details: Washroom (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes C 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7933 Quantity/Condition Total Location Details: Caretakers Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 44Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Parging Cement On Fittings 17 12 0 0 0 12 each 70 Chrysotile Yes No D 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 55.00 0.00 0.00 0.00 55.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 7936 Quantity/ConditionTotal

Location Details: Closet (Cannot identity room) (Limited view above ceiling)

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes B 6

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7935 Quantity/ConditionTotal

Location Details: Caretakers Room (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 45Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

Location: Floor 1: 7938 Quantity/ConditionTotal

Location Details: Change Room (Refer to 7905. - Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 55.00 0.00 0.00 0.00 55.00 square feet

- Presumed No Yes A 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7937 Quantity/Condition Total Location Details: AV Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7936 Quantity/ConditionTotal

Location Details: Closet (Cannot identity room) (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 46Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Plaster 20 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed Yes Yes C 6

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

Location: Floor 1: 7942 Quantity/Condition Total Location Details: Shower (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 75.00 0.00 0.00 0.00 75.00 square feet

- Presumed No Yes A 6

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7941 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7938 Quantity/ConditionTotal

Location Details: Change Room (Refer to 7905. - Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 47Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 1: 7944 Quantity/Condition Total Location Details: Washroom - Boys (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7943 Quantity/Condition Total Location Details: Change Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7942 Quantity/Condition Total Location Details: Shower (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 48Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

Location: Floor 1: 7946 Quantity/Condition Total Location Details: Shower (No access above ceiling. refer to 7947)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7945 Quantity/Condition Total Location Details: Washroom - Girls (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Parging Cement On Fittings 17 1 4 0 0 5 each 70 Chrysotile Yes No D 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes C 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7944 Quantity/Condition Total Location Details: Washroom - Boys (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 49Golder Associates

Refer to Attachment for Definitions and Abbreviations

WALL Concrete 9 - - - - - - - - - - - -

FLOOR Not Found 1 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

Location: Floor 1: 7948 Quantity/Condition Total Location Details: Courtyard (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 240.00 0.00 0.00 0.00 240.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7947 Quantity/Condition Total Location Details: Shower (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7946 Quantity/Condition Total Location Details: Shower (No access above ceiling. refer to 7947)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 50Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 30 0 0 0 30 each 70 Chrysotile Yes No D 6

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

WALL Plaster 13 1100.00 0.00 0.00 0.00 1100.00 square feet

- Presumed Yes Yes A 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Wood 14 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 550.00 0.00 0.00 0.00 550.00 square feet

- Presumed No Yes C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 1400.00 0.00 0.00 0.00 1400.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7949 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 1: 7948 Quantity/Condition Total Location Details: Courtyard (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 51Golder Associates

Refer to Attachment for Definitions and Abbreviations

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Plaster 13 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed Yes Yes C 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 99441 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 500.00 0.00 0.00 0.00 500.00 square feet

- Presumed No Yes C 6

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Plaster 13 2750.00 0.00 0.00 0.00 2750.00 square feet

- Presumed Yes Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 950.00 0.00 0.00 0.00 950.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

PIPING SYSTEMS Parging Cement On Fittings 17 35 0 0 0 35 each 70 Chrysotile Yes No D 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 5 0 0 0 5 each - Presumed No No D 6

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 7949-1 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 52Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 70.00 0.00 0.00 0.00 70.00 square feet

- Presumed No Yes C 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes C 6

Location: Floor 1: 99443 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

Location: Floor 1: 99442 Quantity/Condition Total Location Details: Stairwell (Refer to 8018 - Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 99441 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 53Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Terrazzo 6 - - - - - - - - - - - -

Location: Floor 1: 99445 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes A 6

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 99444 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 99443 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 54Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes A 6

WALL Drywall And Joint Compound 5 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 99446 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Drywall And Joint Compound 5 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes C 6

CEILING Drywall And Joint Compound 7 70.00 0.00 0.00 0.00 70.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

WALL Plaster 13 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed Yes Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 99445 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 55Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Drywall And Joint Compound 7 180.00 0.00 0.00 0.00 180.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Plaster 13 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed Yes Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 1: 99458 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

CEILING To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

Location: Floor 1: 99457 Quantity/Condition Total Location Details: Gym (Refe to 7927. - Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 99446 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 56Golder Associates

Refer to Attachment for Definitions and Abbreviations

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

CEILING Plaster 20 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed Yes Yes C 6

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes A 6

FLOOR Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 99848 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 1: 99458 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 57Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Tar Paper Over Fiberglass 57 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 95.00 0.00 0.00 0.00 95.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 95.00 0.00 0.00 0.00 95.00 square feet

- Presumed No Yes B 6

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

PIPING SYSTEMS Cellulose with dark layer 56 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7951 Quantity/ConditionTotal

Location Details: Caretakers Room, service rm. (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 750.00 0.00 0.00 0.00 750.00 square feet

- Presumed No Yes A 6

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 25.00 0.00 0.00 0.00 25.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7950 Quantity/ConditionTotal

Location Details: Classroom, rm.212 (212) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 58Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 145.00 0.00 0.00 0.00 145.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7953 Quantity/Condition Total Location Details: Storage Room, storage (No access above ceiling. )

DUCTWORK Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 735.00 0.00 0.00 0.00 735.00 square feet

- Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 25.00 0.00 0.00 0.00 25.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7952 Quantity/ConditionTotal

Location Details: Office / Admin. Area, rm.213 (213) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7951 Quantity/ConditionTotal

Location Details: Caretakers Room, service rm. (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 59Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Drywall And Joint Compound 7 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes A 6

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1020.00 0.00 0.00 0.00 1020.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7954 Quantity/ConditionTotal

Location Details: Classroom, rm.214 (214) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 145.00 0.00 0.00 0.00 145.00 square feet

- Presumed No Yes C 6

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7953 Quantity/Condition Total Location Details: Storage Room, storage (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 60Golder Associates

Refer to Attachment for Definitions and Abbreviations

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes A 6

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

CEILING Drywall And Joint Compound 7 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 260.00 0.00 0.00 0.00 260.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

MECHANICAL EQUIPMENT

Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Corrugated Cellulose On Straight Run Pipe 27 - - - - - - <LOD No Asbestos Detected

- - - -

DUCTWORK Flexible Duct Connector 47 2 0 0 0 2 each - Presumed Yes No D 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7955 Quantity/ConditionTotal

Location Details: Teachers Workroom, prep.rm.a (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7954 Quantity/ConditionTotal

Location Details: Classroom, rm.214 (214) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 61Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Vertical Drywall Bulkhead 37 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes A 6

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1040.00 0.00 0.00 0.00 1040.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7957 Quantity/Condition Total Location Details: Classroom, rm.216 (216) (Open)

STRUCTURE Fibrous SPF On Beam, Deck, Joist 39 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 630.00 0.00 0.00 0.00 630.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 350.00 0.00 0.00 0.00 350.00 square feet

- Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

Location: Floor 2: 7956 Quantity/Condition Total Location Details: Other Workshop, rm.218 (218) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 62Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

Location: Floor 2: 7959 Quantity/ConditionTotal

Location Details: Office / Admin. Area, communications & language studies (223) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1360.00 0.00 0.00 0.00 1360.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Transite Counter Top 58 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes A 6

OTHER Transite Fume Hood 59 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes A 6

OTHER Vertical Drywall Bulkhead 37 15.00 0.00 0.00 0.00 15.00 square feet

- Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

Location: Floor 2: 7958 Quantity/Condition Total Location Details: Classroom, rm.220 (220) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Transite Counter Top 58 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes A 6

Location: Floor 2: 7957 Quantity/Condition Total Location Details: Classroom, rm.216 (216) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 63Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes C 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 775.00 0.00 0.00 0.00 775.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7960 Quantity/ConditionTotal

Location Details: Classroom, rm.223/222 (224) (No access above ceiling. )

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

STRUCTURE Plaster Column Enclosure 41 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed Yes No C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 8 0 0 0 8 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7959 Quantity/ConditionTotal

Location Details: Office / Admin. Area, communications & language studies (223) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 64Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 245.00 0.00 0.00 0.00 245.00 square feet

- Presumed No Yes A 6

Location: Floor 2: 7962 Quantity/Condition Total Location Details: Storage Room, office (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 810.00 0.00 0.00 0.00 810.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 140.00 0.00 0.00 0.00 140.00 square feet

- Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes C 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7961 Quantity/ConditionTotal

Location Details: Classroom, rm. 224 and 225 (225) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 14 0 0 0 14 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7960 Quantity/ConditionTotal

Location Details: Classroom, rm.223/222 (224) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 65Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 5 0 0 0 5 each 70 Chrysotile Yes No D 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 890.00 0.00 0.00 0.00 890.00 square feet

- Presumed No Yes A 6

WALL Drywall And Joint Compound 5 250.00 0.00 0.00 0.00 250.00 square feet

- Presumed No Yes A 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

Location: Floor 2: 7963 Quantity/Condition Total Location Details: Classroom, rm.226 (226) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 245.00 0.00 0.00 0.00 245.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7962 Quantity/Condition Total Location Details: Storage Room, office (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 66Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Drywall Beam Enclosure 44 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

DUCTWORK Vinyl Flexible Duct Connector 35 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

DUCTWORK Flexible Duct Connector 47 8 0 0 0 8 each - Presumed Yes Yes B 6

PIPING SYSTEMS Corrugated Cellulose On Straight Run Pipe 27 - - - - - - <LOD No Asbestos Detected

- - - -

Location: Floor 2: 7965 Quantity/Condition Total Location Details: HVAC/Fan Room, fan rm.5 (#5) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 770.00 0.00 0.00 0.00 770.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7964 Quantity/ConditionTotal

Location Details: Classroom, rm.211 (211) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 67Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 85.00 0.00 0.00 0.00 85.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 12 0 0 0 12 each - Presumed No No B 6

PIPING SYSTEMS Parging Cement On Fittings 17 5 0 0 0 5 each 70 Chrysotile Yes No B 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7967 Quantity/Condition Total Location Details: Washroom – Staff Male (Open)

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 265.00 0.00 0.00 0.00 265.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7966 Quantity/Condition Total Location Details: Washroom - Boys (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Uninsulated 2 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 7965 Quantity/Condition Total Location Details: HVAC/Fan Room, fan rm.5 (#5) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 68Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 75.00 0.00 0.00 0.00 75.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7969 Quantity/ConditionTotal

Location Details: Washroom – Staff Female (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 265.00 0.00 0.00 0.00 265.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7968 Quantity/Condition Total Location Details: Washroom - Girls (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 7967 Quantity/Condition Total Location Details: Washroom – Staff Male (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 69Golder Associates

Refer to Attachment for Definitions and Abbreviations

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 800.00 0.00 0.00 0.00 800.00 square feet

- Presumed No Yes A 6

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1400.00 0.00 0.00 0.00 1400.00 square feet

- Presumed No Yes A 6

WALL Wood 14 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 1350.00 0.00 0.00 0.00 1350.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7970 Quantity/ConditionTotal

Location Details: Classroom, rm.215 (215) (No access above ceiling. kiln present.)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7969 Quantity/ConditionTotal

Location Details: Washroom – Staff Female (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 70Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 635.00 0.00 0.00 0.00 635.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 2: 7973 Quantity/Condition Total Location Details: Classroom, rm. (219) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

Location: Floor 2: 7972 Quantity/ConditionTotal

Location Details: Office / Admin. Area, office (doesn't exist - No access to location)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 635.00 0.00 0.00 0.00 635.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 7971 Quantity/Condition Total Location Details: Classroom, rm.215 computer rm. (217) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 71Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 15 0 0 0 15 each - Presumed No Yes B 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Fibreglass And Uninsulated 8 - - - - - - - - - - - -

DUCTWORK Flexible Duct Connector 47 5 0 0 0 5 each - Presumed Yes Yes A 6

STRUCTURE Drywall Beam Enclosure 44 180.00 0.00 0.00 0.00 180.00 square feet

- Presumed No Yes C 6

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Metal 11 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Vinyl Flexible Duct Connector 35 - - - - - - - - - - - -

STRUCTURE Drywall Column Enclosure 48 220.00 0.00 0.00 0.00 220.00 square feet

- Presumed Yes Yes B 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

Location: Floor 2: 7974 Quantity/Condition Total Location Details: HVAC/Fan Room, fan rm.1 (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

STRUCTURE Fibrous SPF On Beam, Deck, Joist 39 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 7973 Quantity/Condition Total Location Details: Classroom, rm. (219) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 72Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 880.00 0.00 0.00 0.00 880.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 1 0 0 0 1 each 70 Chrysotile Yes Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7976 Quantity/ConditionTotal

Location Details: Classroom, rm.221 (221) (No access above ceiling. )

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7975 Quantity/ConditionTotal

Location Details: Storage Room, prep rm. (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 73Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 med/lrg pinholes, random pattern 25 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7978 Quantity/Condition Total Location Details: Office / Admin. Area (No access above ceiling. )

CEILING 1x1 rough texture, random sml/med pinholes 26 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 485.00 0.00 0.00 0.00 485.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Corrugated Cellulose On Straight Run Pipe 27 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Bell & Spigot Joints 15 2 0 0 0 2 each - Presumed No No B 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7977 Quantity/Condition Total Location Details: Change Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 74Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Fibreglass 23 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 4 0 0 0 4 each 70 Chrysotile Yes No D 6

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 75.00 0.00 0.00 0.00 75.00 square feet

- Presumed No Yes A 6

FLOOR Ceramic 12 - - - - - - - - - - - -

FLOOR Rubber - non-slip 22 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 75.00 0.00 0.00 0.00 75.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7979 Quantity/Condition Total Location Details: Gym, fitness room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7978 Quantity/Condition Total Location Details: Office / Admin. Area (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 75Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 random large/med. pinholes 55 765.00 0.00 0.00 0.00 765.00 square feet

2.4 Amosite Yes Yes C 6

FLOOR Other Vinyl Floor Tile 3 765.00 0.00 0.00 0.00 765.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7981 Quantity/ConditionTotal

Location Details: Classroom, rm.228 (228) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 random large/med. pinholes 55 730.00 0.00 0.00 0.00 730.00 square feet

2.4 Amosite Yes Yes C 6

FLOOR Other Vinyl Floor Tile 3 730.00 0.00 0.00 0.00 730.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7980 Quantity/ConditionTotal

Location Details: Classroom, rm.227 (227) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 76Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 750.00 0.00 0.00 0.00 750.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 2: 7983 Quantity/ConditionTotal

Location Details: Classroom, rm.209 (209) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 735.00 0.00 0.00 0.00 735.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7982 Quantity/ConditionTotal

Location Details: Classroom, rm.210 (210) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7981 Quantity/ConditionTotal

Location Details: Classroom, rm.228 (228) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 77Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Flexible Duct Connector 47 11 0 0 0 11 each - Presumed Yes Yes B 6

DUCTWORK Vinyl Flexible Duct Connector 35 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Drywall Beam Enclosure 44 70.00 0.00 0.00 0.00 70.00 square feet

- Presumed No Yes C 6

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7984 Quantity/Condition Total Location Details: HVAC/Fan Room, fan rm.4 (#4) (Open)

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7983 Quantity/ConditionTotal

Location Details: Classroom, rm.209 (209) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 78Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

Location: Floor 2: 7987 Quantity/Condition Total Location Details: Washroom - Boys (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Uninsulated 2 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 7986 Quantity/Condition Total Location Details: HVAC/Fan Room, fan rm.6 (fan room #6) (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 140.00 0.00 0.00 0.00 140.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7985 Quantity/Condition Total Location Details: Washroom - Boys (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 79Golder Associates

Refer to Attachment for Definitions and Abbreviations

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 765.00 0.00 0.00 0.00 765.00 square feet

- Presumed No Yes A 6

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7988 Quantity/ConditionTotal

Location Details: Classroom, rm.229 (229) (No access above ceiling. )

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 340.00 0.00 0.00 0.00 340.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7987 Quantity/Condition Total Location Details: Washroom - Boys (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 80Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

Location: Floor 2: 7990 Quantity/Condition Total Location Details: Washroom - Girls (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 775.00 0.00 0.00 0.00 775.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7989 Quantity/ConditionTotal

Location Details: Classroom, rm.230 (230) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7988 Quantity/ConditionTotal

Location Details: Classroom, rm.229 (229) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 81Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Parging Cement On Fittings 17 2 0 0 0 2 each 70 Chrysotile Yes Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Plaster 20 400.00 0.00 0.00 0.00 400.00 square feet

- Presumed Yes Yes C 6

FLOOR Wood 14 - - - - - - - - - - - -

WALL Transite Asbestos Cement 21 1350.00 0.00 0.00 0.00 1350.00 square feet

- Presumed No Yes C 6

PIPING SYSTEMS Other Suspect Piping - in gym 16 12.00 0.00 0.00 0.00 12.00 linear feet - Presumed No Yes C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 7991 Quantity/Condition Total Location Details: Gym (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 300.00 0.00 0.00 0.00 300.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7990 Quantity/Condition Total Location Details: Washroom - Girls (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 82Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 210.00 0.00 0.00 0.00 210.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 7993 Quantity/ConditionTotal

Location Details: Office / Admin. Area, rm.205 (205) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 750.00 0.00 0.00 0.00 750.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7992 Quantity/ConditionTotal

Location Details: Classroom, rm.208 (208) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 83Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 175.00 0.00 0.00 0.00 175.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 2: 7995 Quantity/ConditionTotal

Location Details: Washroom - Girls (No access above ceiling. no hatch access)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 235.00 0.00 0.00 0.00 235.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7994 Quantity/ConditionTotal

Location Details: Office / Admin. Area, rm.204 (204) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7993 Quantity/ConditionTotal

Location Details: Office / Admin. Area, rm.205 (205) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 84Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

Location: Floor 2: 7997 Quantity/ConditionTotal

Location Details: Washroom – Staff Female (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7996 Quantity/ConditionTotal

Location Details: Washroom – Staff Male (No access above ceiling. refer to 7998)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7995 Quantity/ConditionTotal

Location Details: Washroom - Girls (No access above ceiling. no hatch access)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 85Golder Associates

Refer to Attachment for Definitions and Abbreviations

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 135.00 0.00 0.00 0.00 135.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7998 Quantity/ConditionTotal

Location Details: Washroom – Staff Male (No access above ceiling. includes 7996)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 155.00 0.00 0.00 0.00 155.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7997 Quantity/ConditionTotal

Location Details: Washroom – Staff Female (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 86Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 800.00 0.00 0.00 0.00 800.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8000 Quantity/ConditionTotal

Location Details: Classroom, rm.231 (231) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 100.00 0.00 0.00 0.00 100.00 square feet

- Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 7999 Quantity/ConditionTotal

Location Details: Caretakers Room, service room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 87Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 785.00 0.00 0.00 0.00 785.00 square feet

- Presumed No Yes A 6

STRUCTURE Fibrous SPF On Beam, Deck, Joist 39 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 med/lrg pinholes, random pattern 25 - - - - - - <LOD No Asbestos Detected

- - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Vertical Drywall Bulkhead 37 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8001 Quantity/ConditionTotal

Location Details: Classroom, rm.232 (232) (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8000 Quantity/ConditionTotal

Location Details: Classroom, rm.231 (231) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 88Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 360.00 0.00 0.00 0.00 360.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 8003 Quantity/ConditionTotal

Location Details: Office / Admin. Area, rm.234 (234) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 220.00 0.00 0.00 0.00 220.00 square feet

- Presumed No Yes A 6

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 760.00 0.00 0.00 0.00 760.00 square feet

- Presumed No Yes A 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8002 Quantity/Condition Total Location Details: Classroom, rm.233 (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 89Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Carpet 43 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8005 Quantity/Condition Total Location Details: Library (Open)

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 340.00 0.00 0.00 0.00 340.00 square feet

- Presumed No Yes A 6

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Plaster Column Enclosure 41 15.00 0.00 0.00 0.00 15.00 square feet

- Presumed Yes Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8004 Quantity/ConditionTotal

Location Details: Storage Room, rm.235 (Cannot identity room) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 11 0 0 0 11 each - Presumed No Yes A 6

OTHER Horizontal Drywall Bulkhead 30 80.00 0.00 0.00 0.00 80.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8003 Quantity/ConditionTotal

Location Details: Office / Admin. Area, rm.234 (234) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 90Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8006 Quantity/ConditionTotal

Location Details: Storage Room, rm.207 (207) (No access above ceiling. )

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes C 6

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

Location: Floor 2: 8005 Quantity/Condition Total Location Details: Library (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 91Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 random large/med. pinholes 55 1200.00 0.00 0.00 0.00 1200.00 square feet

2.4 Amosite Yes Yes C 6

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 550.00 0.00 0.00 0.00 550.00 square feet

- Presumed No Yes A 6

FLOOR Carpet 43 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 8007-1 Quantity/Condition Total Location Details: Computer Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

WALL Drywall And Joint Compound 5 600.00 0.00 0.00 0.00 600.00 square feet

- Presumed No Yes A 6

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Carpet 43 - - - - - - - - - - - -

FLOOR Vinyl Sheet Flooring 53 500.00 0.00 0.00 0.00 500.00 square feet

- Presumed Yes Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 4 0 0 0 4 each - Presumed No Yes A 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8007 Quantity/Condition Total Location Details: Library (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 92Golder Associates

Refer to Attachment for Definitions and Abbreviations

WALL Drywall And Joint Compound 5 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

FLOOR Carpet 43 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 2: 8009 Quantity/Condition Total Location Details: Library office (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 250.00 0.00 0.00 0.00 250.00 square feet

- Presumed No Yes A 6

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 370.00 0.00 0.00 0.00 370.00 square feet

- Presumed No Yes A 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8008 Quantity/ConditionTotal

Location Details: Library office, workroom (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8007-1 Quantity/Condition Total Location Details: Computer Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 93Golder Associates

Refer to Attachment for Definitions and Abbreviations

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 950.00 0.00 0.00 0.00 950.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 med/lrg pinholes, random pattern 25 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8010 Quantity/ConditionTotal

Location Details: Classroom, rm.203 (203) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING 2x4 stippled random small pinholes 54 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 8009 Quantity/Condition Total Location Details: Library office (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 94Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 855.00 0.00 0.00 0.00 855.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Horizontal Drywall Bulkhead 30 25.00 0.00 0.00 0.00 25.00 square feet

- Presumed No Yes C 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8012 Quantity/ConditionTotal

Location Details: Classroom, rm.202 (202) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 95.00 0.00 0.00 0.00 95.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 95.00 0.00 0.00 0.00 95.00 square feet

- Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8011 Quantity/Condition Total Location Details: Storage Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 95Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Cellulose 1x1 glue-on ceiling tile 46 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 830.00 0.00 0.00 0.00 830.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8014 Quantity/ConditionTotal

Location Details: Classroom, rm.201 (201) (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 120.00 0.00 0.00 0.00 120.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8013 Quantity/ConditionTotal

Location Details: Storage Room (No access above ceiling. limited access to room due to clutter)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8012 Quantity/ConditionTotal

Location Details: Classroom, rm.202 (202) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 96Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Corrugated Cellulose On Straight Run Pipe 27 - - - - - - <LOD No Asbestos Detected

- - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 35.00 0.00 0.00 0.00 35.00 square feet

- Presumed No Yes A 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 35.00 0.00 0.00 0.00 35.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8015 Quantity/Condition Total Location Details: Caretakers Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Horizontal Drywall Bulkhead 30 25.00 0.00 0.00 0.00 25.00 square feet

- Presumed No Yes C 6

OTHER Chalkboard - non suspect 18 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Window Sealers 31 2 0 0 0 2 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8014 Quantity/ConditionTotal

Location Details: Classroom, rm.201 (201) (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 97Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING 2x4 width-wise fissures w/dimples, sml/med pinholes

62 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 460.00 0.00 0.00 0.00 460.00 square feet

- Presumed No Yes C 6

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1380.00 0.00 0.00 0.00 1380.00 square feet

- Presumed No Yes A 6

WALL Plaster 13 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed Yes Yes A 6

WALL Drywall And Joint Compound 5 345.00 0.00 0.00 0.00 345.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8016-1 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

CEILING 2x4 width-wise fissures w/dimples, sml/med pinholes

62 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 1100.00 0.00 0.00 0.00 1100.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 2740.00 0.00 0.00 0.00 2740.00 square feet

- Presumed No Yes A 6

WALL Plaster 13 3300.00 0.00 0.00 0.00 3300.00 square feet

- Presumed Yes Yes A 6

WALL Drywall And Joint Compound 5 550.00 0.00 0.00 0.00 550.00 square feet

- Presumed No Yes A 6

CEILING Drywall And Joint Compound 7 500.00 0.00 0.00 0.00 500.00 square feet

- Presumed No No D 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

Location: Floor 2: 8016 Quantity/Condition Total Location Details: Corridor (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 98Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 10 0 0 0 10 each - Presumed No No D 6

CEILING Drywall And Joint Compound 7 1200.00 0.00 0.00 0.00 1200.00 square feet

- Presumed No Yes C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 10 0 0 0 10 each 70 Chrysotile Yes No D 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING 2x4 width-wise fissures w/dimples, sml/med pinholes

62 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Plaster 13 1650.00 0.00 0.00 0.00 1650.00 square feet

- Presumed Yes Yes A 6

FLOOR Other Vinyl Floor Tile 3 3290.00 0.00 0.00 0.00 3290.00 square feet

- Presumed No Yes A 6

WALL Drywall And Joint Compound 5 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No No D 6

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 410.00 0.00 0.00 0.00 410.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8016-2 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Cellulose & Tar Paper On Straight Run Pipe 42 20.00 0.00 0.00 0.00 20.00 linear feet - Presumed Yes No D 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8016-1 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 99Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 4 0 0 0 4 each - Presumed No Yes A 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

WALL Plaster 13 700.00 0.00 0.00 0.00 700.00 square feet

- Presumed Yes Yes A 6

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 230.00 0.00 0.00 0.00 230.00 square feet

- Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 920.00 0.00 0.00 0.00 920.00 square feet

- Presumed No Yes A 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

STRUCTURE Plaster Column Enclosure 41 90.00 0.00 0.00 0.00 90.00 square feet

- Presumed Yes Yes A 6

CEILING Drywall And Joint Compound 7 460.00 0.00 0.00 0.00 460.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8016-3 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8016-2 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 100Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

CEILING Plaster 20 300.00 0.00 0.00 0.00 300.00 square feet

- Presumed Yes Yes C 6

FLOOR Other Vinyl Floor Tile 3 740.00 0.00 0.00 0.00 740.00 square feet

- Presumed No Yes A 6

WALL Plaster 13 900.00 0.00 0.00 0.00 900.00 square feet

- Presumed Yes Yes A 6

WALL Drywall And Joint Compound 5 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8017 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

CEILING 2x4 length-wise fissures w/ sml pinholes, dimpled 60 75.00 0.00 0.00 0.00 75.00 square feet

3.1 Amosite Yes Yes C 6

CEILING Drywall And Joint Compound 7 460.00 0.00 0.00 0.00 460.00 square feet

- Presumed No Yes C 6

STRUCTURE Plaster Column Enclosure 41 90.00 0.00 0.00 0.00 90.00 square feet

- Presumed Yes Yes A 6

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 920.00 0.00 0.00 0.00 920.00 square feet

- Presumed No Yes A 6

WALL Plaster 13 700.00 0.00 0.00 0.00 700.00 square feet

- Presumed Yes Yes A 6

WALL Drywall And Joint Compound 5 230.00 0.00 0.00 0.00 230.00 square feet

- Presumed No Yes A 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 4 0 0 0 4 each - Presumed No Yes A 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 12 0 0 0 12 each 70 Chrysotile Yes No D 6

Location: Floor 2: 8016-4 Quantity/Condition Total Location Details: Corridor (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 101Golder Associates

Refer to Attachment for Definitions and Abbreviations

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING 2x4 length-wise fissures w/ sml pinholes, dimpled 60 600.00 0.00 0.00 0.00 600.00 square feet

3.1 Amosite Yes Yes C 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

WALL Plaster 13 1710.00 0.00 0.00 0.00 1710.00 square feet

- Presumed Yes Yes A 6

FLOOR Other Vinyl Floor Tile 3 1795.00 0.00 0.00 0.00 1795.00 square feet

- Presumed No Yes A 6

CEILING Plaster 20 570.00 0.00 0.00 0.00 570.00 square feet

- Presumed Yes Yes C 6

WALL Drywall And Joint Compound 5 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes A 6

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8017-1 Quantity/Condition Total Location Details: Corridor (Open)

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 22 0 0 0 22 each 70 Chrysotile Yes No D 6

CEILING 2x4 random slashes, sml/med pinholes 61 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8017 Quantity/Condition Total Location Details: Corridor (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 102Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 400.00 0.00 0.00 0.00 400.00 square feet

- Presumed No Yes A 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 8019 Quantity/Condition Total Location Details: Other Workshop, prep.rm. (Open)

CEILING Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Metal 11 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 35.00 0.00 0.00 0.00 35.00 square feet

- Presumed No Yes B 6

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Boiler Gasket 33 2 0 0 0 2 each - Presumed Yes Yes B 6

MECHANICAL EQUIPMENT

Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Window Sealers 31 3 0 0 0 3 each - Presumed No Yes B 6

PIPING SYSTEMS Bell & Spigot Joints 15 10 0 0 0 10 each - Presumed No Yes B 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Woven Flexible Duct Connector 32 - - - - - - - - - - - -

Location: Floor 2: 8018 Quantity/Condition Total Location Details: Boiler / Furnace Room (includes 99442 - Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 103Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8021 Quantity/Condition Total Location Details: Shower (No access above ceiling. refer to 8020)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 350.00 0.00 0.00 0.00 350.00 square feet

- Presumed No Yes C 6

FLOOR Ceramic 12 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8020 Quantity/ConditionTotal

Location Details: Shower (Cannot identity room) (No access above ceiling. includes 8021)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 104Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 225.00 0.00 0.00 0.00 225.00 square feet

- Presumed No Yes A 6

FLOOR Other Vinyl Floor Tile 3 220.00 0.00 0.00 0.00 220.00 square feet

- Presumed No Yes A 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Location: Floor 2: 8023 Quantity/Condition Total Location Details: Other Workshop (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

WALL Drywall And Joint Compound 5 250.00 0.00 0.00 0.00 250.00 square feet

- Presumed No Yes A 6

CEILING New Ceiling Tile 24 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Ceramic 12 - - - - - - - - - - - -

FLOOR Rubber - non-slip 22 - - - - - - - - - - - -

WALL Ceramic 12 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 12 0 0 0 12 each 70 Chrysotile Yes No D 6

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

Comments: Ceiling space was not fully accessible at the time of assessment due to obstructions by mechanical or structural elements or limited points-of-entry. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8022 Quantity/Condition Total Location Details: Gym (Limited view above ceiling)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 105Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

Location: Floor 2: 8025 Quantity/ConditionTotal

Location Details: Cafetorium (refer to 7882 & 7874, top of café/stage - Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

Location: Floor 2: 8024 Quantity/Condition Total Location Details: Hub Room (No access to location)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8023 Quantity/Condition Total Location Details: Other Workshop (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 106Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING Drywall And Joint Compound 7 170.00 0.00 0.00 0.00 170.00 square feet

- Presumed No Yes C 6

FLOOR Other Vinyl Floor Tile 3 170.00 0.00 0.00 0.00 170.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 2: 8028 Quantity/ConditionTotal

Location Details: Storage Room, chemical storage (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

CEILING To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

Location: Floor 2: 8027 Quantity/Condition Total Location Details: Gym (refer to 7927 - No access to location)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

CEILING To Be Determined - - - - - - - - TBD - - - -

STRUCTURE To Be Determined - - - - - - - - TBD - - - -

FLOOR To Be Determined - - - - - - - - TBD - - - -

WALL To Be Determined - - - - - - - - TBD - - - -

DUCTWORK To Be Determined - - - - - - - - TBD - - - -

OTHER To Be Determined - - - - - - - - TBD - - - -

MECHANICAL EQUIPMENT

To Be Determined - - - - - - - - TBD - - - -

PIPING SYSTEMS To Be Determined - - - - - - - - TBD - - - -

Location: Floor 2: 8026 Quantity/Condition Total Location Details: Courtyard (refer to 7948 - Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 107Golder Associates

Refer to Attachment for Definitions and Abbreviations

WALL Drywall And Joint Compound 5 40.00 0.00 0.00 0.00 40.00 square feet

- Presumed No Yes C 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 2: 99447 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 465.00 0.00 0.00 0.00 465.00 square feet

- Presumed No Yes A 6

WALL Brick/Block/Concrete 10 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 2 0 0 0 2 each 70 Chrysotile Yes Yes C 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

Location: Floor 2: 8029 Quantity/Condition Total Location Details: Storage Room (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Fibreglass 23 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 8028 Quantity/ConditionTotal

Location Details: Storage Room, chemical storage (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 108Golder Associates

Refer to Attachment for Definitions and Abbreviations

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 405.00 0.00 0.00 0.00 405.00 square feet

- Presumed No Yes C 6

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 99448 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 99447 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 109Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes C 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 99450 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

CEILING Drywall And Joint Compound 7 60.00 0.00 0.00 0.00 60.00 square feet

- Presumed No Yes C 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 10.00 0.00 0.00 0.00 10.00 square feet

- Presumed No Yes C 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

DUCTWORK Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 99449 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 110Golder Associates

Refer to Attachment for Definitions and Abbreviations

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 50.00 0.00 0.00 0.00 50.00 square feet

- Presumed No Yes C 6

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 99452 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Terrazzo 6 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 99451 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 99450 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 111Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Other Vinyl Floor Tile 3 200.00 0.00 0.00 0.00 200.00 square feet

- Presumed No Yes A 6

WALL Concrete Block 4 - - - - - - - - - - - -

Location: Floor 2: 99454 Quantity/ConditionTotal

Location Details: Storage Room, SAC-projection rm. (No access above ceiling. no access to Hub rm.)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Fibreglass And Uninsulated 8 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

STRUCTURE Drywall Beam Enclosure 44 80.00 0.00 0.00 0.00 80.00 square feet

- Presumed No Yes C 6

STRUCTURE Concrete 9 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Bell & Spigot Joints 15 8 0 0 0 8 each - Presumed No Yes B 6

DUCTWORK Flexible Duct Connector 47 8 0 0 0 8 each - Presumed Yes Yes B 6

DUCTWORK Vinyl Flexible Duct Connector 35 - - - - - - - - - - - -

Location: Floor 2: 99453 Quantity/Condition Total Location Details: HVAC/Fan Room, fan rm.2 (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Window Sealers 31 1 0 0 0 1 each - Presumed No Yes A 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 99452 Quantity/Condition Total Location Details: Stairwell (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 112Golder Associates

Refer to Attachment for Definitions and Abbreviations

PIPING SYSTEMS Cellulose with dark layer 56 - - - - - - <LOD No Asbestos Detected

- - - -

DUCTWORK Fibreglass And Uninsulated 8 - - - - - - - - - - - -

DUCTWORK Flexible Duct Connector 47 6 0 0 0 6 each - Presumed Yes Yes B 6

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

WALL Concrete Block 4 - - - - - - - - - - - -

FLOOR Concrete 9 - - - - - - - - - - - -

STRUCTURE Drywall Beam Enclosure 44 80.00 0.00 0.00 0.00 80.00 square feet

- Presumed No Yes C 6

CEILING Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Floor 2: 99455 Quantity/Condition Total Location Details: HVAC/Fan Room, fan rm.3 (Open)

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Drywall And Joint Compound 5 150.00 0.00 0.00 0.00 150.00 square feet

- Presumed No Yes A 6

CEILING 1x1 lrg irregular fissures 29 - - - - - - <LOD No Asbestos Detected

- - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Floor 2: 99454 Quantity/ConditionTotal

Location Details: Storage Room, SAC-projection rm. (No access above ceiling. no access to Hub rm.)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 113Golder Associates

Refer to Attachment for Definitions and Abbreviations

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

WALL Not Found 1 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

FLOOR Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Location: Exterior: 68437-1 Quantity/Condition Total Location Details: Exterior (Open)

CEILING Plaster 20 425.00 0.00 0.00 0.00 425.00 square feet

- Presumed Yes Yes C 6

CEILING 2x4 random slashes, sml/med pinholes 61 - - - - - - <LOD No Asbestos Detected

- - - -

STRUCTURE Concrete 9 - - - - - - - - - - - -

FLOOR Other Vinyl Floor Tile 3 1115.00 0.00 0.00 0.00 1115.00 square feet

- Presumed No Yes A 6

WALL Plaster 13 1060.00 0.00 0.00 0.00 1060.00 square feet

- Presumed Yes Yes A 6

WALL Drywall And Joint Compound 5 20.00 0.00 0.00 0.00 20.00 square feet

- Presumed No Yes A 6

DUCTWORK Uninsulated 2 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Fibreglass And Uninsulated 8 - - - - - - - - - - - -

PIPING SYSTEMS Parging Cement On Fittings 17 17 0 1 0 18 each 70 Chrysotile Yes No D 4

PIPING SYSTEMS Cellulose & Tar Paper On Straight Run Pipe 42 12.00 0.00 0.00 0.00 12.00 linear feet - Presumed Yes No D 6

Location: Floor 2: 99456 Quantity/Condition Total Location Details: Corridor (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)

Date: 11/14/2008

Job Number : 06-1113-212Facility : 3081 - Sir Sandford Fleming Academy

Client : Toronto District School Board

All Components

Appendix IV - Room-by-Room Details: Summary Report By Location

Page: 114Golder Associates

Refer to Attachment for Definitions and Abbreviations

FLOOR Not Found 1 - - - - - - - - - - - -

WALL Not Found 1 - - - - - - - - - - - -

PIPING SYSTEMS Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Not Found 1 - - - - - - - - - - - -

OTHER Flexible Shingle 50 1 0 0 0 1 each - Presumed No Yes B 6

STRUCTURE Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

OTHER Built Up Membrane Roof 49 1 0 0 0 1 each - Presumed No Yes B 6

Location: Roof: 68437 Quantity/Condition Total Location Details: Roof (Open)

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

WALL Concrete Block 4 - - - - - - - - - - - -

CEILING 1x1 large/med. pinholes, tetris pattern 19 - - - - - - <LOD No Asbestos Detected

- - - -

FLOOR Other Vinyl Floor Tile 3 140.00 0.00 0.00 0.00 140.00 square feet

- Presumed No Yes A 6

PIPING SYSTEMS Uninsulated 2 - - - - - - - - - - - -

OTHER Not Found 1 - - - - - - - - - - - -

MECHANICAL EQUIPMENT

Not Found 1 - - - - - - - - - - - -

STRUCTURE Not Found 1 - - - - - - - - - - - -

DUCTWORK Not Found 1 - - - - - - - - - - - -

CEILING Drywall And Joint Compound 7 30.00 0.00 0.00 0.00 30.00 square feet

- Presumed No Yes C 6

Comments: Ceiling space was inaccessible at the time of assessment. Asbestos-containing materials (ACM) may exist in the ceiling space. If this space is to be accessed for any reason, such as a roof leak, etc., an inspection should be conducted by a competent person and any suspect ACM should be sampled or presumed to contain asbestos.

Location: Exterior: 7926 Quantity/Condition Total Location Details: Change Room (No access above ceiling. )

System Material Description Component Good Fair Poor Debris Quantity Units Asbestos %

Asbestos Type

Friable Visible Accessibility Action Code

Building: 1 (Sir Sandford Fleming Academy)