Getting Started – SENTRON powermanager V2.0 1 Installation Step 1: Installing SENTRON powermanager SENTRON powermanager is delivered on a CD-ROM equipped with an Autorun program. To start the installation, simply insert the CD-ROM into the drive. If the Autorun program does not start, run the "Start.exe" on the CD-ROM. Notes: If you have copied the set-up files to a directory on your computer or network please make sure there are no blanks in the directory name. During the installation procedure you have to: Select English or German as installation language Accept the license conditions Insert your user names Insert the installation path Select the installation type “complete” (as beginner) Step 2: Installing ALM (Automation License Manager) You find the Automation License Manager that is needed for licensing also on the product CD-ROM. Please start the setup.exe file in the „Automation License Manager“ directory and follow the installation instructions. Step 3: Transferring licenses Using the ALM (start -> programs -> Siemens Automation) please transfer the licenses from the USB stick to your computer. In case that you also bought the extension packages you get additional USB sticks. 1

Upload: vuthuan

Post on 30-Aug-2018

310 views

Category:

Documents


11 download

TRANSCRIPT

Page 1: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Getting Started – SENTRON powermanager V2.0

1 Installation Step 1: Installing SENTRON powermanager SENTRON powermanager is delivered on a CD-ROM equipped with an Autorun program. To start the installation, simply insert the CD-ROM into the drive. If the Autorun program does not start, run the "Start.exe" on the CD-ROM. Notes: If you have copied the set-up files to a directory on your computer or network please make sure there are no blanks in the directory name. During the installation procedure you have to:

• Select English or German as installation language • Accept the license conditions • Insert your user names • Insert the installation path • Select the installation type “complete” (as beginner)

Step 2: Installing ALM (Automation License Manager) You find the Automation License Manager that is needed for licensing also on the product CD-ROM. Please start the setup.exe file in the „Automation License Manager“ directory and follow the installation instructions. Step 3: Transferring licenses Using the ALM (start -> programs -> Siemens Automation) please transfer the licenses from the USB stick to your computer. In case that you also bought the extension packages you get additional USB sticks.

1

Page 2: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

2 Starting a project Step 1: opening the Console Please start Start -> Programs -> SENTRON -> SENTRON powermanager V2.0 -> Console. The Console and LogViewer are opening. Step 2 (optional): Changing the archive settings If you would like to archive more than 25 devices or a lot more measuring points of each device than the default settings you need to change the size of the archives. Please see the readme file for detailed instructions. Step 3: Starting the Managers Please select the project powermanager in the Console and click on the green light icon to start it.

The Managers for running the project will be started sequentially and change their status to 2 (green). You may follow the events in the LogViewer. The login window is opening automatically. Note: If you would like to create additional projects you have to open the project

administration with and copy the project powermanager_template.

2

Page 3: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Step 4: Logging in Please use the standard user „root“ (no password required) to log in.

The User Interface of the project is opening.

3

Page 4: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

3 Engineering In the user interface of the project you can copy your factory with using areas and devices. Step 1: Creating areas To give your system a structure you can create areas. Please select in the context menu of System1 the area administration.

With you can create new areas. The new areas will appear in the tree view of your factory. Step 2: Creating devices To create devices please select “create device” and pick a device type in the context menu of System1 or your area.

Name the device as related to the factory part where it is installed. Depending on the device type and size of your project it might take a while to create a device. After creating the device the engineering view is opening automatically. The created devices will appear in the tree view of your project.

4

Page 5: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Step 3: Engineering of devices Notes: The communication protocol of the PAC devices has to be changed to Modbus TCP in order that SENTRON powermanager can communicate with the devices. SENTRON PAC 3200 and PAC 4200 are able to communicate directly via Ethernet with SENTRON powermanager. You only have to insert an IP address and press the safe button.

5

Page 6: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Communication with the SENTRON PAC 3100 is only possible via an Ethernet gateway that converts MODBUS RTU to MODBUS TCP. Please insert the IP address of your gateway, select an access point and the unit ID of your device. You can choose between the slots of a PAC 4200 and any gateway.

The communication via a gateway is also available for the SENTRON PAC 3200. If you are missing specific units supported by your device you can change them under „units and factors“ in SENTRON powermanager. Under the configuration tab you can choose which measuring points:

• are being transferred from the device. • are being shown under the “selected value” tab (see step 4) • are being archived • are being controlled for alerts

If you would like to change the settings for archiving please see the instructions in the readme file. Under the Extended configuration tab you may change the names of measuring values. Under the Alert configuration tab you may change the alert messages.

6

Page 7: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Step 4: Starting communication The communication with the devices can be started via the context menu of System1, the areas or the devices itself.

Communicating devices will be shown with a green check mark in the tree view. You are also able to see the current measuring values of this device.

Choosing a filter will change the shown measuring values. Under the selected values tab you will see the values you have marked in the device engineering. As default you will see the measuring values of the group overview. SENTRON PAC 4200 devices have an additional tab harmonics where you can see either 17 or 31 harmonics.

7

Page 8: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

For the devices PAC 3100, PAC 3200 and PAC 4200 you may send commands for reset maxima, minima and counters under the command tab. Information saved in the device like serial number and firmware version are shown under the “device data” tab

8

Page 9: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

4 Reporting

4.1 Requirements Before you are able to use the reporting the following actions need to be done:

1. Opening the reporting with the -button . The reporting start screen is opening in EXCEL. 2. If you are getting an error message you need to execute a batch file. You find the file reportReg.bat on the product CD-ROM in the directory „reportRegEdit“. This file registers all the necessary dlls in the registry. Please keep in mind that you need administrator rights to execute this batch file under WINDOWS VISTA. 3. Creating the archive structure

After entering the password “erAdmin” the archive structure will be created.

4.2 Creating the cost center report The reporting tool will be described by using a cost center report. Step 1: Creating a new template Please click on the new template button and choose cost center report as the format.

9

Page 10: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Step 2: Choosing the report type Please choose with the cursor buttons which report type is used for this template.

The colors for the minima and maxima marks can be changed by clicking on the colored buttons.

10

Page 11: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

With checking the „Print preview after creation of report“ checkbox you will automatically get the print preview after creating the report. With checking the “Log changes” checkbox all changes made to the created protocols will be archived and shown on an automatically created sheet. After clicking OK you will see the report template in Excel. Step 3: Changing the security settings Please change the macro security level (tools->Macro->Security) to low. Step 4: Creating tariff sets To add tariff sets please open Report->configuration->tariff set.

After entering the password “erAdmin” you may add new tariff sets with a click on .

Please enter a name for the tariff set and define the times and costs for every tariff you want. These tariff sets are automatically available at the cost center configuration.

11

Page 12: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Step 5: Creating cost centers Creating cost centers over the menu Report->configuration->Cost Centers

After entering the password „erAdmin“ you may add cost centers with the button.

Please name the cost center and assign a tariff set. Step 6: Creating DPs For the first DP you have to click in the first cell in column C and then open the menu Template->Insert DP.

Please choose a counter value of the data point type and assign one cost center. In this example we chose the counter value of a PAC 4200 device. It is important that the wanted device is marked (here System1:PAC4200) and the units of the measuring point and the cost center are the same. If you want to change the units you can create a virtual counter in the project tree and use this one fort he cost center report template.

12

Page 13: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

To insert further DPs you have to copy the column of the first DP and then go to the menu Template->Modify DP while the cursor is in the first row of the next column. Step 7: Saving the template Please save the template under a file name that does not end with a number. Step 8: Creating the report Please click on the new report button and choose the template you want to use in the opening window. In the opening window please select the report type and the time range for the new report. Step 9: Saving the report Please save the report under a name of your choice.

13

Page 14: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

5 Creating trends

To create a new trend view, please click on the -button. Step 1: Copying the trend configuration Please mark in the trend configuration window the default trend configuration _VarTrend_STDLIB_general and click the copy-button. After naming the new trend configuration it will appear in the trend configuration list:

14

Page 15: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Step 2: Editing the trend configuration Please mark the new created trend configuration and click the edit-button. Uncheck the “Use $-parameters” option and assign a data point with the datapoint selector to the selected curve.

If you would like to get a trend for more than one data point please select a different curve and assign a data point. Under the scale and style tabs you can change the design of the curves if you want to. Step 3: Setting the time range Please click the forward-button while marked the wanted trend configuration and define the time range you would like to see the data for. After clicking the view-button the curve will be displayed.

15

Page 16: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

6 Creating users The user “root” is one of the predefined users. For your system you should create further users with specific authorizations. Step 1: Opening User administration

Please open the system Management with the -button, then the Permission-tab and

click on the -button. The User administration window with all the predefined users with their groups and authorization levels is opening. Step 2: Adding a new user

Please click on the “Add user”-button.

16

Page 17: Getting Started – SENTRON powermanager V2 - sea.siemens… · Getting Started – SENTRON ... SENTRON PAC 3200 and PAC 4200 are able to communicate directly ... You only have to

Step 3: Configuring user properties

Please insert a unique user name, a full name and a short description. After that select the language and add the group membership via the cursors. There are the following authorization levels: Group name Group ID Authorization level

root 0 root

para 1 Administration

operatorAll 2 Advanced operator

operator 3 Normal operator

guest 4 Visualization

With the password-button you can define a password for the new user. After clicking OK the new user with all of its properties will appear in the user administration and can be used for the next login.

17