Page 1: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

GEEnergy

GE Proprietary & Confidential

GE’s “Grid Friendly” Wind Plant Technology

EXECUTIVE EXCHANGE ON THE USE & INTEGRATION OF

RENEWABLE ENERGY IN THE POWER SECTOR

Pedro ArsuagaGE EnergyMadrid, October 21, 2009

Page 2: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 2April 3, 2008

Model: 1.5 Model: 1.5 slesleTechnical Data (General)

Rated Capacity: 1.5 MW

Cut in Wind Speed: 3.5 m/s (7.83 mph)

Cut out Wind Speed: 25 m/s (62.63 mph)

Rated Wind Speed: 14 m/s (31.32 mph)

Hub Diameter: 77 m (252.62 ft)

Hub Height: 80 m (262.47 ft)

Certification: IEC TC IIb Ve50 = 52 m/s

Climate Conditions: Standard Weather Operation: -15 C to +40 C (-5 F to 104 F)

Survival: -20 C to +50 C (-4 F to 122 F)

Noise Level: 104 db (A) average

Page 3: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 3April 3, 2008

Product Characteristics

<= 105 dB(A)Noise level

-15C to +40COperating temperature

25m/sCut out wind speed

3.0m/sCut in wind speed

59.5m/sSurvival wind speed

8.5 m/sAverage wind speed

100mHub height

2.5MWRated Power

100mRotor Diameter

DIBt WZ II, IEC TC IIIa,IEC TC II-b

Wind Regime

Model: 2.5 XLModel: 2.5 XL

Page 4: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 4April 3, 2008

Plant performance solutions

O&M tools

WindFREEReactive Power

Reactive Powereven with no wind

WindRIDE-THRU

Uninterrupted turbineoperation through griddisturbances

WindINERTIA

Inertial response forlarge, short durationfrequency deviations

WindCONTROL

Voltage and power regulation like a conventional plant

WindSCADA

Sophisticated tools to operate, maintain and manage the entire wind plant

WindLAYOUT

Maximizes energycapture throughadvanced turbine siting

AEP improvementGrid friendly capabilities

Page 5: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 5April 3, 2008

Utility systems require that wind power plants:› Provide Controlled and Predictable Power Response From

Variations in Wind, Turbine and Grid Frequency

› Must remain connected to the grid following disturbances – in short, they must remain stable

Good locations for wind plants often entail connection to relatively weak transmission systems

As Wind Power Plants increase in size and contribution …

Wind plants must perform like a conventional power plant

Page 6: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 6April 3, 2008

Ride-Thru Capabilities• Remains on-line and feeds

reactive power through system disturbances

• Meets present and emerging grid requirement with Low/Zero Voltage Ride Through (LVRT/ZVRT) capability

• Meets transmission reliability standards similar to thermal generators

Fault Recovery• Voltage recovery better than

conventional generator Active Power

Reactive Power

Voltage

Apparent Power

Zero Voltage Event

GE's Standard WindRIDE-THRU Offerings

0

20

40

60

80

100

120

140

-1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0

Time (seconds)

Volta

ge a

t Poi

nt o

f In

terc

onne

ctio

n (P

erce

nt)

200 ms

LVRT

ZVRT

HVRT

Synchronous generator swings dramatically

Page 7: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 7April 3, 2008

Voltage at POI

Wind Plant Power Output

Voltage RegulationActual measurements from a

162MW wind plant

Wind Plant Voltag

• Regulates Grid Voltage at Point of Interconnection

• Minimizes Grid Voltage Fluctuations Even Under Varying Wind Conditions

Average Wind Speed

Voltage RegulationLike A Conventional Power Plant

Average Wind Speed

Generator

Transformer

MainTransformer

45 mi.34.5kV

POI

ConverterControl WFMS

Wind Turbine

kW

kVAR

kW

kVAR230kV

Substation

Page 8: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 8April 3, 2008

Active Power Controls

Typical Grid Requirements• Ramp rates• Power curtailment• Power droop w/ frequency

Power Droop Test

0.000

0.200

0.400

0.600

0.800

1.000

1.200

Available Power

Actual Power

Curtailment Example

2% Frequency Increase

50% Power Reduction

Pow

er (k

W)

Freq

uenc

y (H

z)

Pavail

PoutRamp Rate

Pow

er

Power Ramp Rates

Page 9: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 9April 3, 2008

WindCONTROLHardware Overview• Substation Mounted Cabinet

PT&CT Interface to Substation• SCADA HMI

Operates on Wind Plant LAN

Plant Level Controller Orchestrates Operation of Individual Turbines

Page 10: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 10April 3, 2008

Wind Plant Startup

Settings:

Turbines Sequenced On at 20 second Intervals

Ramp Rate Limit 3MW/Min

Wind Plant PowerRamping at less than 3MW/Min

1 Minute Average Ramp Rate (kW/sec)

Turbines transitioning

Online

Pow

er (k

W)

Num

ber

of T

urbi

nes

Onl

ine

Wind Plant Output Controlled During Startup Conditions

Page 11: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 11April 3, 2008

Wind Plant Shutdown

Settings:

Shutdown Interval Set to 5 Minutes

Wind Plant Power

Ramping to Zero in 5 Mins N

umbe

r of

Tur

bine

s O

nlin

eTurbines transitioning

Off-line

Pow

er (k

W)

Wind Plant Output Controlled During Shutdown Conditions

Page 12: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 12April 3, 2008

WindFREE Reactive Power

• Wind Turbine converter can deliver reactive power (kVAR) without wind (kW)

• Benefits weak grids and systems with high wind penetration

• Voltage support continues without active power generation…even following trips

Reactive Power - even without wind

Page 13: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 13April 3, 2008

2.5 WTG Reactive Power Capability

Cos 0.95

Cos 0.90

Available VARWindFREE Reactive Power

Page 14: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 14April 3, 2008

Wind Plant-Wind Turbine Stability Modeling• Good models of wind plants gain importance as wind

penetration levels impact system performance

Positive Sequence Load Flow Model For GE Plant Systems

• Development of stability models is on-going and evolving with equipment capability and validation efforts

– ZVRT and Voltage Response models closely replicate plant performance

Kiv/s+

Vrfq (vref)

WindControl Emulation

11+ sTc

11+ sTr

Vreg

Qmax

Qmin

1/fN Qord

s5

s4

s3-

Kpv

1+ sTv

s2

Qwv

+

+

Slower Refined Plant-Level Control

++

Qcmd

Qgen

Vref

Vmax

Vterm

KVi / s

Vterm + XIQmax

Vmin

Eq"cmd

s0s1

Vterm + XIQmin

KQi / s(efd)

--

Slower WTGQ Control

Fast Initial WTGVoltage Control

Page 15: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

EWEC Grid Friendly Presentation 15April 3, 2008

Field Measurements vs Model for a Wind Plant

RED = PSLF Model

BLUE = Test measurements

POI voltage response

POI reactive power

response

Capacitor switched

offline

Fast Initial WTG

Response

Slower, coordinated plant level Response

Multi-modal response is grid friendly

Page 16: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

• Addresses Reliability Concerns of Grid Operators

• Improves Grid Operability and Security

• Increases Capability of Grids to Successfully Achieve High Levels of Wind Penetration

“Grid Friendly” Wind Power Plant…

Page 17: GE’s “Grid Friendly” Wind Plant Technology · GE Proprietary & Confidential GE’s “Grid Friendly” Wind Plant Technology ... Turbine kW kVAR kW kVAR 230k V Substation. EWEC

Thank you!