DESCRIPTION
Generalised Droop Control for Power Management in a Multi-Terminal HVDC System. Kamila Nieradzinska, Grain Adam, W . Leithead and Olimpo Anaya-Lara University of Strathclyde. Outline of Presentation. North Sea Connection VSC-HVDC Control strategy DC-voltage droop control - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/1.jpg)
![Page 2: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/2.jpg)
Generalised Droop Control for Power Management in a Multi-Terminal HVDC SystemKamila Nieradzinska, Grain Adam,
W. Leithead and Olimpo Anaya-Lara
University of Strathclyde
![Page 3: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/3.jpg)
• North Sea Connection• VSC-HVDC• Control strategy• DC-voltage droop control• Test system configuration • Results• Conclusions
Outline of Presentation
![Page 4: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/4.jpg)
North Sea Connections
![Page 5: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/5.jpg)
What is VSC
• VSC = Voltage Source(d) Converter
• Capacitor is normally used as energy storage
• VSC uses a self-commutated device such as GTO (Gate Turn Off Thyristor) or IGBT (Insulated Gate Bipolar Transistor)
![Page 6: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/6.jpg)
• Power transfer over long distances
• Lower power losses compared to AC transmission
• Independent control over active and reactive power
• Voltage support
• Wind farm is decoupled from the onshore grid,
• Connected to the weak network
• Black start capability
Why VSC-HVDC…
![Page 7: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/7.jpg)
Point-to-point Connection
G
Wind FarmVSC1 VSC2
T2T1C1
C2
C3
C4
HVDCGrid
Different control strategies employed for offshore wind farm and onshore grid.
![Page 8: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/8.jpg)
Vector Control
• Three-phase rotating voltage and current are transformed to the dq reference frame
• Comparative loops and PI controllers are used to generate the desired values of M and and fed their values to the VSC
• Phase-locked-loop (PLL) is used to synchronize the modulation index.
+-
+-
PI
PI
+-
+-
PI
PI abc
dq
PLL
abc
dq
VSC converter
*A
*B
*di
*qi
dM
qM
di
qi
av
bv
cv
dqv
dqi
Outer controllers
inner controllers
The controlled parameters
from the system (P, Q, Vdc, Vac)
abci
v abc
![Page 9: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/9.jpg)
Inner ControllerResponsible for controlling the current in order to protect the converter from overloading during system disturbances
Control Strategies – Inner Controller
qcd d sdv u Li v
cq q sqdv u Li v
PI+
-*sdi d
u
ωLsdi
PI+-
*sqi
qu
ωLsqi
cdv
cqv
sqv
sdv-
-
+
-
+
+
* *( ) ( )pi iid d d d du k i i k i i dt
* *( ) ( )q pi q q ii q qu k i i k i i dt
![Page 10: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/10.jpg)
Outer controllerResponsible for providing the inner controller with the reference values, where different controllers can be employed, such as:
DC and AC voltage controllers
The Active and reactive power controllers
The frequency controller
Control Strategies – Outer Controller
**sd
sd
Pi
v
**sq
sd
Qi
v
* * *( ) ( )sd pdc dc dc idc dc dci k V V k V V dt
* * *( ) ( )sq pac ac ac iac ac aci k V V k V V dt
PI+-
*
dcV
dcV*
sdi
PI+-
*
acV
acV*
sqi
(a) (b)
x*P
sdv
*
sdi x
*Q
sdv
*
sqi
(a) (b)
![Page 11: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/11.jpg)
Controllers Schematics
dq
abc
PWM
PI-ud
*
ωL
ωL
-+
isd
Md
vsd
isd
PI-uq
*-
+
vsd
isq
+
+
isq
+
-
PI-
+Mq
Inner
controllers
-+
*÷
PI
vsd
P*
ƒ
*ƒ
Outer
controllersV
V*
+
+
dq
abc
PWM
PIud
*
ωL
ωL
-+
isd
Md
vsd
isd
PIuq
*-
+
vsd
isq
+
+
isq
+
-
PI-
+Mq
Inner
controllers
-+ PI
*
Outer
controllersV
V*
Vdc
Vdc
+
+
Wind farm side VSC
Onshore grid side VSC
Active power and AC voltages control
DC and AC voltages control
![Page 12: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/12.jpg)
DC Voltage Droop Control
The proposed droop control provides a reference voltage to the DC voltage controller ‘i’ taking into account the voltage at the support node ‘j’ as shown in equation:
![Page 13: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/13.jpg)
Test System Configuration
G
G
G
B1
B2
B3
B4
B5
B6
B7
PCC1
PCC2
PCC3
Vdc+droop control
Vdc+droop control
Vdc(master)WF1
WF2
400MVA
400MVA
400MVA
400MVA
400MVA
400MVA
400MVA
VSC1
VSC2
VSC3
VSC4
VSC5
33kV/132kV500MVA
33kV/132kV500MVA
132kV/400kV500MVA
132kV/400kV500MVA
132kV/400kV500MVA
![Page 14: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/14.jpg)
Power Balance – Droop Control ON
Time 0 - 1.5 1.5 - 3 3 – 4.5 4.5 - 6 6 – 7.5 7.5 - 9 VSC3 255 450 350 255 160 65 VSC4 255 175 220 255 295 330 VSC5 255 140 195 255 310 370
![Page 15: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/15.jpg)
DC Voltage – Droop Control ON
![Page 16: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/16.jpg)
Test System Configuration with Loss of VSC4
G
G
G
B1
B2
B3
B4
B5
B6
B7
PCC1
PCC2
PCC3
Vdc+droop control
Vdc+droop control
Vdc(master)WF1
WF2
400MVA
400MVA
400MVA
400MVA
400MVA
400MVA
400MVA
VSC1
VSC2
VSC3
VSC4
VSC5
33kV/132kV500MVA
33kV/132kV500MVA
132kV/400kV500MVA
132kV/400kV500MVA
132kV/400kV500MVA
![Page 17: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/17.jpg)
Power Balance – Droop Control ON (No VSC4)
Time 0 - 1.5 1.5 - 3 3 – 4.5 4.5 - 6 6 – 7.5 VSC3 33.3 % 50 % 62.5 % 50 % 75 % VSC4 33.3 % 25 % 0 % 0 % 0 % VSC5 33.3 % 25 % 37.5 % 50 % 25 %
![Page 18: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/18.jpg)
Conclusions
• The controller can respond to any power demand
• There are significant advantages in terms of power flow controllability
• This can prove to be very advantageous for connection of variable wind generation and assist in the power balancing of interconnected networks.
![Page 19: Generalised Droop Control for Power Management in a Multi-Terminal HVDC System](https://reader034.vdocuments.mx/reader034/viewer/2022051316/56813c35550346895da5b361/html5/thumbnails/19.jpg)