generac guardian series standby generators 30 kw · qt030 service disconnect utility supply from...
TRANSCRIPT
FEATURES
®
¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
¡ TEST CRITERIA: PROTOTYPE TESTED NEMA MG1-22 EVALUATION SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. An unequalled ±1% voltage regulation.
¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
¡ GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.
GENERAC® GUARDIAN® SERIES STANDBY GENERATORS
30 kWIncludes:
• Generac Naturally Aspirated
Gaseous Fueled 1.6L Engine
• Two Line LCD Tri-lingual
Digital Nexus™ Controller
• Isochronous Electronic Governor
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1% Voltage Regulation
• Natural Gas or LP Operation
• UL 2200 Listed
Standby Power Rating Model QT030 (Bisque) - 30 kW 60Hz
Liquid-Cooled Engine Generator Sets
Meets EPA Emission Regulations
Application & Engineering Data
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271).
QT030
GENERATOR SPECIFICATIONSTYPE Synchronous
ROTOR INSULATION Class F
STATOR INSULATION Class F
TELEPHONE INTERFERENCE FACTOR (TIF) <50
ALTERNATOR OUTPUT LEADS 3 PHASE 4 wire
BEARINGS Sealed Ball
COUPLING Flexible Disc
LOAD CAPACITY (STANDBY RATING) 30 kW
EXCITATION SYSTEM Direct
VOLTAGE REGULATIONTYPE Electronic
SENSING Single Phase
REGULATION ± 1%
GENERATOR FEATURESRevolving field heavy duty generatorDirectly connected to the engineOperating temperature rise 120 °C above a 40 °C ambientInsulation is Class F rated at 130 °C riseAll models are fully prototyped tested
ENCLOSURE FEATURES
Galvanized steel weather protective enclosure
Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.
�Enclosed critical grade muffler
Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
�Small, compact, attractive
Makes for an easy, eye appealing installation.
ENGINE SPECIFICATIONSMAKE Generac
MODEL In line
CYLINDERS 4
DISPLACEMENT 1.6 Liter
BORE 3.15
STROKE 3.13
COMPRESSION RATIO 9.75:1
INTAKE AIR SYSTEM Naturally Aspirated
VALVE SEATS Replaceable
LIFTER TYPE Hydraulic
GOVERNOR SPECIFICATIONSTYPE Electronic
FREQUENCY REGULATION Isochronous
STEADY STATE REGULATION ± 0.25%
ENGINE LUBRICATION SYSTEMOIL PUMP Gear
OIL FILTER Full flow spin-on cartridge
CRANKCASE CAPACITY 4 Quarts
ENGINE COOLING SYSTEMTYPE Closed
WATER PUMP Belt driven
FAN SPEED 2550
FAN DIAMETER 15 inches
FAN MODE Pusher
FUEL SYSTEMFUEL TYPE Natural gas, propane vapor
CARBURETOR Down Draft
SECONDARY FUEL REGULATOR Standard
FUEL SHUT OFF SOLENOID Standard
OPERATING FUEL PRESSURE 5” - 14” H2O
ELECTRICAL SYSTEMBATTERY CHARGE ALTERNATOR 12V 30 Amp
STATIC BATTERY CHARGER 2 Amp
RECOMMENDED BATTERY Group 26, 525CCA
SYSTEM VOLTAGE 12 Volts
OPERATING DATAKW RATING (LP/NG) 30/27
ENGINE SIZE 1.6 Liter 4 cyl. inline
GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size
120/240V, 1-phase, 1.0 pf120/208V, 3-phase, 0.8 pf120/240V, 3-phase, 0.8 pf
303030
12510490
150125100
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)
Exercise cycle25% of rated load50% of rated load75% of rated load100% of rated load*
Natural Gas(ft3/hr.)
60145260370470
Propane (gal/hr.) cu ft/hr 0.7 24 1.6 58 2.8 103 4.0 147 5.1 187
ENGINE COOLING
Air flow (inlet air including alternator and combustion air) ft3/min.System coolant capacity US gal.Heat rejection to coolant BTU/hr.Max. operating air temp. on radiator °C (°F)Max. ambient temperature °C (°F)
1,8002.0
131,00060 (150)50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz cfm 95
SOUND EMISSIONS IN DBA
Exercising at 7 metersNormal operation at 7 meters
6272
EXHAUST
Exhaust flow at rated output 60 Hz cfmExhaust temp. at muffler outlet °F
2601025
ENGINE PARAMETERS
Rated synchronous RPM 60 Hz 3600
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration3% for every 10 °C above - °C
1.65% for every 10 °F above - °FAltitude Deration
1% for every 100 m above - m3% for every 1000 ft. above - ft.
2577
183600
* Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.KW rating is based on LPG Fuel and may derate with natural gas.
Generac® Guardian® Series Standby Generator - 30 kW ®
INTERCONNECTIONS
NEXUS™ CONTROL FEATURES2-Line Plain Text LCD Display Simple user interface for ease of operationMode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser
-Off Stops unit. Power is removed. Control and charger still operate.-Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds StandardEngine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)Engine Warm-up 5 secondsEngine Cool-Down 1 minuteStarter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.Smart Battery Charger StandardAutomatic Voltage Regulation with Over and Under Voltage Protection StandardAutomatic Low Oil Pressure Shutdown StandardOverspeed Shutdown Standard, 72HzHigh Temperature Shutdown StandardOvercrank Protection StandardSafety Fused StandardFailure to Transfer Protection StandardLow Battery Protection Standard50 Event Run Log StandardFuture Set Capable Exerciser StandardIncorrect Wiring Protection StandardInternal Fault Protection StandardCommon External Fault Capability StandardGovernor Failure Protection Standard
QT030
SERVICE DISCONNECTUTILITY SUPPLY FROM
CUSTOMER LOAD(DISTRIBUTION PANEL)
ON
N1N2
194/15B23
E1 E2
QT SERIES ENGINE GENERATORCONNECTION PANEL
NEUTRAL BLOCK
NUMBERS TOTERMINAL NUMBERS
MATCH WIRENOTE:
NOTE:POWER LEADS AND TRANSFER SWITCH LEADSTO BE RUN IN TWO DIFFERENT CONDUITS.
EXCEPTIONS:IF THE INSULATION RATING ON ALL WIRING ISRATED FOR 600V AND THE LENGTH OF THECONDUIT IS 30ft OR LESS IT IS ACCEPTABLE TO INCLUDEGENERATOR CONTROL & POWER WIRING IN ONE CONDUIT
LIQUID COOLED INSTALLATION
57329-F350A LUG
GROUND48850-T
0C4449A-T
NOTE WIRE ORIENTATIONWARNING
TRANSFER
DC COMMON
CU
STOM
ER C
ON
NEC
TION
S
23
0
194+12VDC (C2 & VR2)
(C1 & VR1)
STANDBY
UTILITY
TRANSFER SWITCH
N1 N2
E2E1
T1 T2
0
0194/15B
23
N2N1
T1 E1 E2 T2
N1 N2
GROUND
NEUTRAL BLOCK
*Single and three phase connections may vary , refer to the owner’s manual for specific connection information.
INSTALLATION LAYOUT
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com©2010 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0187680SBY-B / Printed in U.S.A. 06/22/10
®
QT030