geneal 6shfl¿fdwlrqv fcn autonomous controller · pdf filefcn autonomous controller...
TRANSCRIPT
GeneralSpecifications
<<Contents>> <<Index>>
GENERALThis document describes the general specifications of the FCN autonomous controller with NFCP100 CPU module. (FCN is an acronym for field control node.)Notation in this document:•Theterm“FCN”referstothemoduleconsistingtypeautonomouscontrollers.
•Theterm“FCN-100”referstotheautonomouscontrollerswithNFCP100CPUmodule.
ForFunction,refertoFCN/FCJAutonomousControllerFunctions(FCN-100/FCJ),GS34P02Q03-01E.
FCNAutonomousControllerHardware(FCN-100)
YokogawaElectricCorporation2-9-32,Nakacho,Musashino-shi,Tokyo,180-8750JapanTel.:81-422-52-5616URL:http://www.stardom.biz
GS 34P02Q12-01E
GS34P02Q12-01E©CopyrightNov.2001(YK)
34thEditionMar.29,2016(YK)
FEATURES•High-performance,high-reliabilitymodularcontroller•MemorywithECC•Lowheatdissipationeliminatestheneedforafan•AwealthofRASfeatures—CPUself-diagnostics,temperaturemonitoring,I/Odiagnostics,andmore•TheCPU,powersupplymodule,localbus(SBbus),andcontrolnetworkcanallbeduplexed,andallmodulesarehot-swappable.
•Canfunctionaslinkactiveschedulers(LASs)forlow-speedvoltagemode(H1)FOUNDATIONFieldbussegments,andlinkupFOUNDATIONFieldbus-enabledfielddevices.
CONFIGURATIONAnFCN-100consistsofthefollowing:•Basemodule•Powersupplymodule•CPUmodule•SBbusrepeatmodule(extendingtheSBbus,thelocalbusforFCNs,toconnectanextensionunit)•I/Omodules
Therearetwotypesofbasemodule.-NFBU200basemodule(long):Upto2extensionunitsconnectableforI/Oexpansion-NFBU050basemodule(short):Compactanddedicatedtoone-unit-configuration
Maximum I/O Module Configurations
Base Module Unit Configuration Standard Duplexed (*1)
NFBU200basemodule(long)
Controlunitonly Max.8modules Max.6modules
With1extensionunit Max.16modules Max.12modules
With2extensionunit Max.25modules Max.20modules
NFBU050basemodule(short) Controlunit(*2) Max.3modules Notapplicable(*3)
*1: WhenCPUandSBbusrepeatmodulesareduplexed*2: SBbusrepeatmodulescannotbemountedonNFBU050.*3: NeitherpowersupplynorCPUmodulescanbeduplexedonNFBU050.
2
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 34P02Q12-01E Jul.14,2009-00
l Examples of ConfigurationStandard control unit alone
F01E.ai
1SlotUnit:1 2 3 4 5 6 7 8 9 10
Ethernet
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
CP
U
PW
M
DM
Y
Control unit alone with duplexed CPU and power supply modules
F02E.ai
1SlotUnit:1 2 3 4 5 6 7 8 9 10
CP
U
CP
U
PW
M
PW
M
IOM
IOM
IOM
IOM
IOM
IOM
Ethernet
Abbreviation DescriptionPWM PowersupplymoduleCPU CPUmoduleIOM I/OmoduleNFSB SBbusrepeatmoduleDMY DummycoverforpowersupplyModuleSlot
Standard control unit + 2 extension units
F03E.ai
Ethernet
IOM
IOM
IOM
IOM
IOM
IOM
IOM
CP
U
PW
M
DM
Y
1SlotUnit:1 2 3 4 5 6 7 8 9 10
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
PW
M
DM
Y
1SlotUnit:2 2 3 4 5 6 7 8 9 10
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
PW
M
DM
Y
1SlotUnit:3 2 3 4 5 6 7 8 9 10
NFS
BN
FSB
NFS
B
Control unit with duplexed CPU modules, power supply modules, and SB bus + 2 extension units
Note:TheCPUmodule,powersupplymodule,andSBbuscanbemadeduplexindividually,whenrequired.
F04E.ai
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
PW
M
PW
M
NFS
B
NFS
B
NFS
B
NFS
B
1SlotUnit:2 2 3 4 5 6 7 8 9
IOM
IOM
IOM
IOM
IOM
IOM
IOM
IOM
PW
M
PW
M
1SlotUnit:3 2 3 4 5 6 7 8 9 10
1SlotUnit:1 2 3 4 5 6 7 8 9
CP
U
CP
U
PW
M
PW
M
IOM
IOM
IOM
IOM
10
10
Ethernet
NFS
B
NFS
B
Short control unit
F10E.ai
1SlotUnit:1 2 3 4 5
Ethernet
IOM
IOM
IOM
CP
U
PW
M
3<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E
INSTALLATION REQUIREMENTSItem Specification
AmbienttemperatureOperation 0°to55°CTransportation/storage –40°to85°C(*1)
AmbienthumidityOperation 5to95%RH(nocondensation)Transportation/storage 5to95%RH(nocondensation)
Rateofchangeintemperature
Operation Within±10°C/hTransportation/storage Within±20°C/h
Dust 0.3mg/m3orlessProtectionclass IP20Resistancetocorrosivegases ANSI/ISAS71.04ClassG2(Standard)(ANSI/ISAS71.04ClassG3,option)Resistancetovibration 0.15mmP-P(5to58Hz),1G(58to150Hz)Resistancetoshock 15G,11ms(duringpower-off,forsinehalf-wavesinXYZ-directions)Altitude 2000morless
NoiseElectricfield 3V/morless(26MHzto1GHz)Magneticfield 30A/m(AC)orless,400A/m(DC)orlessElectrostaticdischarge 4kVorlesscontactdischarge,8kVorlessaerialdischarge
Grounding Applythegroundingsystemwhichisdefinedbytherulesandstandardsofthecountryortheregion.
Cooling Naturalaircooling
*1: Systemclockmayberesetifthetemperaturefallsbelow-10°C.
Aug.10,2015-00
4
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 34P02Q12-01E
COMPLIANT STANDARDS Item Standards
Safetystandards(*1)(*8)(*15)
CSA CAN/CSA-C22.2No.61010-1
CEMarkingLowVoltageDirectiveEN61010-1(*12)EN61010-2-201(*12)EN61010-2-030
EACMarking CUTR004
EMCstandards
CEMarkingEMCDirective (*12)
EN55011ClassAGroup1(emission)(*13)EN61000-6-2(immunity)(*1)(*2)(*9)EN61000-3-2EN61000-3-3(*3)
RCM EN55011ClassAGroup1(*13)KCMarking KoreaElectromagneticConformityStandardEACMarking CUTR020
StandardsforHazardousLocationEquipment(*4)(*5)
FMNonincendive(*1)
ClassIDivision2,GroupsA,B,C,DT4Class3600:2011Class3611:2004Class3810:2005
ATEXType"n"(*6)(*7)(*12)
II3GExnAnCIICT4GcX(*10)(*14)II3GExnAIICT4GcX(*11)(*14)
EN60079-0:2009EN60079-0:2012EN60079-15:2010
CSANon-Incendive(*1)
ClassIDivision2,GroupsA,B,C,DT4CAN/CSA-C22.2No.0-M91CAN/CSA-C22.2No.0.4-04CAN/CSA-C22.2No.157-92C22.2No.213-M1987TN-078
*1: Fortherack-mountabledevices,DINrail-mountabledevices,andwall-mountabledevicestomeettheSafetyStandardsandEMCStandards,thedevicesmustbeinstalledinalockablemetalcabinet.ThecabinetmustconformtoIEC/EN/CSA61010-2-201orprovidedegreesofprotectionIP3XoraboveandIK09orabove.
*2: Forlightningsurgeimmunity,adevicesuchasalightningarresterneedstobeinstalledexternally.Somemodulecanselectapressureclampterminalblockwithsurgeabsorber.Fordetails,see“TerminalBlock”(GS34P02Q41-01E).
*3: Thespecifiedmagnitudeofthevoltagedropdeterminedbythecablewiringlengthneedsbemet.*4: RefertoTI34P02Q91-01EfortheproductsmeetingNI.*5: Formodulesconformingtoexplosion-proofstandards,refertothesection“I/OModule”andthetable“ListofFCN’s
ModulesandModulesConformingtoExplosionProtectionStandard”ofthisdocument.*6: WhenFCNisusedundertheATEXType“n”environment,theInstructionManual,IM34P02Q11-02E“ExplosionProtection
ofFCN/FCJProducts”isrequiredforsaferinstallationandwiring.*7: Tobecompliantwiththesestandards,theFCNhardwareneedstobeinstalledinalockablemetalcabinetofIP54orhigher
protectionrating.*8: ForensuringtheFCNhardwaretosatisfythesafetystandards,thededicatedbreakersinthepowersupplysidemustbe
installedandconformtothefollowingspecifications. •[CSA]CSAC22.2No.5orUL489 •[CEMarking]EN60947-1andEN60947-3*9: WhenusingtheNFLP121,mountone(A1193MN)ferritecoreontheNFLP121sideofthePROFIBUScabletomeetthe
EMCstandards.*10: AppliedforNFDR541andFCN. “Typeofprotection”ofFCNisincludingthewholemountedmodule.*11: AppliedforproductsexceptforNFDV541.*12: NFDR541iscompliantwiththestandardsonlywhenthevoltageof24VDCorlessisappliedtoitsoutputterminal.*13: AClassAhardwaredeviceisdesignedforuseintheindustrialenvironment.Pleaseusethisdeviceintheindustrial
environmentonly.*14: Symbol‘X’denotesthespecificconditionofuse.See“ExplosionProtectionofFCN/FCJProducts”(IM34P02Q11-02E)for
detail.*15: Tobecompliantwiththesestandards,theFCN’scablewhichisdrawnoutfromthemetal,needstobeusedtheVW-1class
ormoreofflame-retardantcable.
InrelationtotheCEMarking,themanufacturerandtheauthorisedrepresentativefortheProductintheEEAareindicatedbelow:•Manufacturer: YokogawaElectricCorporation(2-9-32Nakacho,Musashino-shi,Tokyo180-8750,Japan)•AuthorisedrepresentativeintheEEA: YokogawaEuropeB.V.(Euroweg2,3825HDAmersfoort,TheNetherlands)
Mar.29,2016-00
5<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E
BASE MODULE AbasemoduleisachassisonwhichvariousfunctionmodulessuchasCPU,powersupply,SBbusrepeat,andI/Omodulesaremountedtoconfigureacontrolunitorextensionunit.
l Features
Model Usage “Number of Mountable I/O Modules”
“Number of Mountable Power Supply Modules” SB Bus
NFBU200ControlUnit 8(*1)
1or2(whenduplexed) DuplexExtensionUnit 9(*2)
NFBU050 ControlUnit 3(*3) 1 Single
*1: TwofromthetenslotsareexclusiveforatleastoneCPUmoduleinthecontrolunit.*2: OnefromthetenslotsisexclusiveforatleastoneSBbusrepeatmoduleintheextensionunit.*3: TwofromthefiveslotsareexclusiveforoneCPUmodule.NoSBbusrepeatmodulescanbemounted.
l Model and Suffix CodesBase Module (long)
Description Model NFBU200 Basemodule(long)
Suffix Codes
-S Standardtype 0 19-inchrack-mounted 1 DINrail-mounted 5 Basictypewithnoexplosionprotection 6 WithISAStandardG3optionandnoexplosionprotection E Basictypewithexplosionprotection F WithISAStandardG3optionandexplosionprotection
Base Module (short)
DescriptionModel NFBU050 Basemodule(short)
Suffix Codes
-S Standardtype 1 DINrail-mounted 5 Basictypewithnoexplosionprotection 6 WithISAStandardG3optionandnoexplosionprotection E Basictypewithexplosionprotection F WithISAStandardG3optionandexplosionprotection
Optional Accessories
Description
Model NFDCV01 DummycoverforI/OmoduleslotNFDCV02 Dummycoverforpowersupplymoduleslot
l Specifications
Item SpecificationModel NFBU200-S0 NFBU200-S1 NFBU050-S1Weight 1.9kg 1.0kg 0.58kgDimensions(WxHxD) 482.6132.540.5mm 44013142.3mm 28313124.2mmMounting 19-inchrack-mounted DINrail-mountedMaximumpowerconsumption
5V Self-consumption 0.4A(max) 0.025A24V Self-consumption 0
Mar.10,2015-00
6
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 34P02Q12-01E
l Dimensions19-inch rack-mounted Model (NFBU200)
44021.3
8.45 465.7482.6
40.5
Unit: mm
17.6
132.
5
57.1
37.7
18.4
F05E.ai
DIN rail-mounted Model (NFBU200)401.5
444
35
Unit: mm
131
16
7
F06.ai
440.2
18181.25
1.9
DIN rail-mounted Model (NFBU050)
16.1273
243.6
24.220.6
283
110
10.5
131
66.5
F11E.ai
Unit: mm
Mar.10,2015-00
7<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E
POWER SUPPLY MODULEMountedonabasemodule,apowersupplymodulesuppliessteadypowertoothermodules.Twopowersupplymodulescanbeinstalledonabasemoduleforredundancy.Thispowersupplymoduleisequippedwithinputterminalsfora24VDCpowersupplyinadditiontothemainpowerinput.The24VDCpowerinputfromtheseterminalsarereferredtoasanalogfieldpowersupplyandfedtoanalogI/Omodulestodrivetheirfieldinterfacecircuitsandsupplypowertotheconnectedfielddevicesthroughthebasemodule.However,whena24VDCpowersupplyisneededfordigitaloutputs,itmustbesuppliedtoindividualterminalsofthecorrespondingI/Omodules.(Fordetails,seetherespectivespecificationsforI/Omodules.)
l Model and Suffix Codes
Description
Model NFPW441 Powersupplymodule(100-120VACinput)
Suffix Codes
-5 Standardtypewithnoexplosionprotection
-E Standardtypewithexplosionprotection
0 Basictype 1 WithISAStandardG3option
Description
Model NFPW442 Powersupplymodule(220-240VACinput)
Suffix Codes
-5 Standardtypewithnoexplosionprotection
0 Basictype 1 WithISAStandardG3option
Description
Model NFPW444 Powersupplymodule(24VDCinput)
Suffix Codes
-5 Standardtypewithnoexplosionprotection
-E Standardtypewithexplosionprotection
0 Basictype 1 WithISAStandardG3option
l Pin AssignmentPower supply terminals (Models NFPW441 and 442)
Pin No. Name Signal
1 FLD24VDC+ 24Vanalogfieldpowersupply(+)(*1)
2 FLD24VDC– 24Vanalogfieldpowersupply(-)(*1)
3 G Groundoflinefilter4 L
Powerinput5 N
Power supply terminals (Model NFPW444)
Pin No. Name Signal
1 FLD24VDC+ 24Vanalogfieldpowersupply(+)(*1)
2 FLD24VDC– 24Vanalogfieldpowersupply(-)(*1)
3 G Groundoflinefilter4 +
Powerinput5 –
*1: WhenanalogI/OmodulessuchasNFAI141(with2-wiretransmitter),NFAI135,NFAI841,NFAB841,NFAI835,NFAF135,andNFAP135areinstalled,ananalogfieldpowersupplyisneeded.
Checking terminals
Pin No. Name Signal 1 +5V-CHK Checkingof5Vsystempower
2 +24V-CHK Checkingof24Vfieldpowersupply
3 GND Signalgrounding
l LEDs
LED Indicator Color Description
SYS-POWER Green Lightswhenthe5Vsystempoweroutputison.
FLD-POWER Green Lightswhenthe24Vfieldpowersupplyison.
Mar.10,2015-00
8
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 34P02Q12-01E
l Dimensions
F07E.ai
49.7146.5133
130
13.5
Unit: mm
l Specifications
Item SpecificationModel NFPW441 NFPW442 NFPW444
Powersupplyinput
Ratedinputvoltage 100to120VAC 220to240VAC 24VDCInputvoltagerange 80to132VAC(rms) 170to264VAC(rms) 21.6to31.2VDCInputfrequency 47to66Hz(Rating:50/60Hz)Inputcurrent Max.1.4A Max.0.7A Max.3.3AFuserating 3.15A 3.15A 6.3ARushcurrent Max.80Afor5msorless Max.90Afor5msorless Max.20ALeakcurrent Max.1mA —Withstandingvoltage 3000VACfor1minute 500VACfor1minuteInsulationresistance 50MΩat500VDCInsensitivemomentarypower-failuretime 10ms(80%) 2ms(90%)
Output
Ratedoutputvoltage +5.1VDCRatedoutputcurrent 0to7.8APeakcurrent 11.8ATotaloutput 40W(60Wpeak)Startuptimeafterpower-on
Max.300msMax.100ms(afterapowerfailureof200mslongwiththeratedinput)
Overvoltageprotection Max.7VOvercurrentprotection Min.105%(shutdownafter4to14secondslongovercurrent)
Analogfieldpowersupply
InputRatedinputvoltage 24VDC±10%Inputcurrent Max.4AFuserating 6.3A
OutputRatedoutputvoltage Inputvoltageminusmatching-diodedropRatedoutputcurrent 4AOvervoltageprotection 35V
Duplexconfiguration Possible(wheninstalledonbasemoduleNFBU200)Weight 0.6kgDimensions(WxHxD) 49.7x130x146.5mm
Mar.10,2015-00
9<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E
CPU MODULEOneCPUmoduleismountedineachcontrolunit,ortwoforaduplexedCPUconfiguration.TheCPUmodulerunsareal-timeoperatingsystem,supportsprogramminglanguagescompliantwiththeIEC61131-3internationalstandard,andservesasaJavavirtualmachine.
l Model and Suffix Codes
DescriptionModel NFCP100 CPUmoduleforFCN
Suffix Codes
-S Standardtype 0 Always0
5 Basictypewithnoexplosionprotection
6 WithISAStandardG3optionandnoexplosionprotection
E Basictypewithexplosionprotection
F WithISAStandardG3optionandexplosionprotection
l Specifications
Item SpecificationModel NFCP100-S0Processor MMX-Pentium166MHz
MemoryMain 128MBwithECCStaticRAM 1MBwithECC,backedupbybattery
Systemcard 1slot
SerialPort(*2) 1RS-232-Cport:D-sub9pins,male(*1)
Communicationmethod Fullduplex
Synchronisation Asynchronous
Baudrate 0.3,1.2,2.4,4.8,9.6,14.4,19.2,28.8,38.4,57.6,or115.2kbps
Networkinterface2Ethernetports:100/10Mbps,100BASE-TXor10BASE-T,RJ45modularjacks
I/Ointerface SBbus(duplex)
RASfeatures Watchdogtimer,temperaturemonitor,etc.
Battery 2700mAHlithiumbattery
Display 3LEDsforCPUstatusindication,2LEDsforLANstatusindication
Switches Reset,shutdown
Powersupply
Supplyvoltage 5VDC±5%
Currentconsumption Max.1800mA
Duplexconfiguration PossibleWeight 0.7kg
Size
Dimensions(WxHxD) 65.8x132x145.7mm
Occupyingslots 2
*1: Connectorsarefastenedusinginchscrewthreads(No.4-40UNC).
*2: AserialportcannotbeusedwhenCPUmodulesareconfiguredinredundancy.
l Pin Assignments of CPU Module’s Serial Port
Table Connector Pin Assignment (D-sub 9-pin, male)
Pin No Signal name Function
1 CD Datachannelreceivingcarrierdetection
2 RD Receivingdata
3 SD Transmissiondata
4 ER Dataterminalready
5 SG Signalground
6 DR Datasetready
7 RS Transmissionrequest
8 CS Transmissionenabled
9 — Not used
F12E.ai
12345
6789
Figure Pin Position (Front View)
l LEDs
Status Indicators
LED Indicator Color DescriptionHRDY Green Lightswhenthehardwareisnormal.RDY Green Lightswhenthesystemisnormal.
CTRL Green Lightswhenthecontrolactionsarecarriedoutnormally.
LAN status indicators (near RJ45 modular jacks)
LED Indicator Color Description
LINK Green Lightswhentheconnectiontoahubisnormal.
ACT Orange Lightswhenthetransmission/receptionison.
Mar.10,2015-00
10
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 34P02Q12-01E
l Dimensions
NFCP100-S00
RESET SYSTEMMEDIA
SHUTDOWN
NETWORKSERIAL
S1
CPU MODULE
F08E.ai
MODELSUFFIXNO.
STYLE
145.7129 13.5(3.2)65.8
Unit: mm
132
130
(2)
N200
NFCP100–OO S1011E07002B
MAC ADDRESS:00006482C001 00006482C002
Made in Japan
SB BUS REPEAT MODULEUsedtoconnectacontrolunittoI/Oextensionunits.ToduplextheSBbus,installtwoSBbusrepeatmodulesineachunit.EachSBbusrepeatmoduleisconnectedtoanotherviaadedicatedT-jointandcable.
l Model and Suffix Codes
Description Model NFSB100 SBbusrepeatmoduleforFCN
Suffix Codes
-S Standardmodel 5 Withnoexplosionprotection E Withexplosionprotection 0 Basictype 1 WithISAStandardG3option
Option Codes
/SBT01 WithanSBbusT-joint
/SBT02 WithanSBbusT-jointwithbuilt-interminator
Note: Whenconnectingacontrolunitandextensionunits,installatbothendsaT-jointwithbuilt-interminatoroneachSBbusrepeatmodule.
Description Models NFSBT01 SBbusT-joint
NFSBT02 SBbusT-jointwithbuilt-interminator
Description Model NFCB301 SBbuscable
Suffix Codes
-C030 Cablelength30cm-C100 Cablelength1m-C200 Cablelength2m-C400 Cablelength4m-C800 Cablelength8m
Mar.10,2015-00
l Specifications
Item Specification Model NFSB100Transmissionmethod SerialcommunicationBaudrate 128MbpsTransmissiondistance Max.8mperline
Extensionunits Max.2units (3unitsincludingacontrolunit)
Duplexconfiguration Possible
Powersupply
Supplyvoltage 5VDC±5%
Currentdissipation Max.500mA
Weight 0.2kg
Size
Dimensions(WxHxD) 32.8x130x142.5mm
Occupyingslots 1
Slotstobeinstalledin SlotNo.10(forsingleSBbus)SlotNos.9and10(forduplexedSBbus)
l LEDs
LED Indicator Color Description STATUS Green Lightswhenthehardwareisnormal.SND Green Lightswhenthetransmissionison.RCV Green Lightswhenthereceptionison.
l Dimensions
F09E.ai
129112 (WITHOUT T-CONN.)
(13.5)142.5
32.8
130
Unit: mm
11<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E
I/O MODULEAnautonomouscontrollerFCNsupportsversatileI/Omodules.Fordetails,refertothefollowinggeneralspecifications:•GS34P02Q31-01E AnalogI/OModules•GS34P02Q35-01E DigitalI/OModules•GS34P02Q36-01E SerialCommunicationModule•GS34P02Q55-01E FoundationFieldbusCommunicationModule•GS34P02Q57-01E PROFIBUS-DPCommunicationModule•GS34P02Q58-01E CANopenCommunicationModule
l List of FCN’s Modules and Modules Conforming to Explosion Protection Standards
Table List of FCN’s Modules and Modules Conforming to Explosion Protection Standards (1/2)
Type Model Function
Explosion protectionFM NI (Non-incen-dive)
ATEX Type “n”
CSA NI (Non-Incen-dive)
BasemoduleNFBU200 Basemodule(long) X X XNFBU050 Basemodule(short) X X X
Powersupplymodule
NFPW441 Powersupplymodule(100-120VACinput) X – XNFPW442 Powersupplymodule(220-240VACinput) – – –NFPW444 Powersupplymodule(24VDCinput) X X X
CPUmodule NFCP100 CPUmoduleforFCN X X XSBbusrepeatmodule NFSB100 SBbusrepeatmoduleforFCN X X X
AnalogI/OModules(*1)
NFAI141 AnalogInputModule(4to20mA,16-channel,Non-Isolated) XX(*2) X XX(*2)
NFAV141 AnalogInputModule(1to5V:differentialinput,16-channel,Non-Isolated) X X X
NFAV142 AnalogInputModule(-10to+10V,16-channel,Non-Isolated) X X X
NFAI841 AnalogI/OModule(4to20mAinput,4to20mAoutput,8-channelinput/8-channeloutput,Non-Isolated) XX(*2) X XX(*2)
NFAB841 AnalogI/OModule(1to5Vinput:differentialinput,4to20mAoutput,8-channelinput/8-channeloutput,Non-Isolated) X X X
NFAV542 AnalogOutputModule(-10to+10V,16-channel,Non-Isolated) X X XNFAI143 AnalogInputModule(4to20mA,16-channel,Isolated) X X XNFAI543 AnalogOutputModule(4to20mA,16-channel,Isolated) X X XNFAV144 AnalogInputModule(-10to+10V,16-channel,Isolated) X X XNFAV544 AnalogOutputModule(-10to+10V,16-channel,Isolated) X X XNFAT141 TC/mVInputModule(16-channel,Isolated) X X XNFAR181 RTDInputModule(12-channel,Isolated) X X XNFAI135 AnalogInputModule(4to20mA,8-channel,Isolatedchannels) X X X
NFAI835 AnalogI/OModule(4to20mA,4-channelinput/4-channeloutput,Isolatedchannels) X X X
NFAP135 PulseInputModule(8-channel,Pulsecount,0to10kHz,Isolatedchannels) X X X
NFAF135 FrequencyInputModule(8-channel,0.1Hzto10kHz,Isolatedchannels) X X X
DigitalI/OModules(*1)
NFDV151 DigitalInputModule(32-channel,24VDC,Isolated) X X X
NFDV157 DigitalInputModule(32-channel,24VDC,PressureClampTerminalsupportonly,Isolated) X X X
NFDV161 DigitalInputModule(64-channel,24VDC) – – –NFDV141 DigitalInputModule(16-channel,100V-120VAC,Isolated) X – XNFDV142 DigitalInputModule(16-channel,200-240VAC) – – –
X: ConformingXX: ConformingconditionallyN.A.: Notapplicable*1: Tousemodulesashazardouslocationequipment(non-incendive),usethespecifiedpressure-clampterminalblocksorMIL
connectorcables(KMS40,KMS50)/MILconnectorterminalblocks(TAS40andTAS50).*2: I/Omoduleswithsuffixcode“withHARTcommunication”donotconformtotheexplosion-proofstandards.
Mar.10,2015-00
12
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 34P02Q12-01E
Table List of FCN’s Modules and Modules Conforming to Explosion Protection Standards (2/2)
Type Model Function
Explosion protectionFM NI (Non-incen-dive)
ATEX Type “n”
CSA NI (Non-Incen-dive)
DigitalI/OModules(*1)
NFDV532 PulseWidthOutputModule(4-channel:UpPulse/DownPulse,24VDC,Isolated) – – –
NFDV551 DigitalOutputModule(32-channel,24VDC,Isolated) X X X
NFDV557 DigitalOutputModule(32-channel,24VDC,PressureClampTerminalsupportonly,Isolated) X X X
NFDV561 DigitalOutputModule(64-channel,24VDC) – – –
NFDR541 RelayOutputModule (16-channel,24to110VDC/100to240VAC,Isolated) XX(*3) XX(*4) XX(*3)
TurbomachineryI/OModules(*5)
NFGS813 ServoModule – – –NFGP813 HighSpeedProtectionModule – – –
CommunicationModules
NFLC121 CANopenCommunicationModule(1-port,10kbpsto1Mbps) – – –NFLF111 Foundationfieldbuscommunicationmodule(4-port) X X X
NFLP121 PROFIBUS-DPCommunicationModule (1-port,9.6kbpsto12Mbps) – – –
NFLR111 RS-232-CCommunicationModule (2-port,300bpsto115.2kbps) X X X
NFLR121 RS-422/RS-485CommunicationModule (2-port,300bpsto115.2kbps) X X X
PressureClampTerminalBlock
NFTA4S PressureClampTerminalBlockforAnalog(16-channel) X X X
NFTT4S PressureClampTerminalBlockforThermocouple/mV (16-channel) X X X
NFTR8S PressureClampTerminalBlockforRTD(12-channel) X X XNFTB5S PressureClampTerminalBlockforDigitalInput(32-channel) X X XNFTD5S PressureClampTerminalBlockforDigitalOutput(32-channel) X X X
NFTI3SPressureClampTerminalBlockforIsolatedAnalogModuleandPulseModule(forNFAI135,NFAP135,NFAF135:8-channel,NFAI835:4-channelinput,4-channeloutput)
X X X
NFTC4S PressureClampTerminalBlockforDigital(16-channel,withdedicatedconnector,withoutsurgeabsorber) X X X
NFTC5S PressureClampTerminalBlockforDigital(32-channel,withdedicatedconnector) X X X
NFTF9S PressureClampTerminalBlockforFoundationFieldbus X X X
TerminalBlockTAS40 MILConnectorTerminalBlock(40PolePlugTypes,M3.5) X X XTAS50 MILConnectorTerminalBlock(50PolePlugTypes,M3.5) X X X
CableNFCB301 SBBusCable X X XKMS40 MILConnectorCable(40PolePlugTypes) X X XKMS50 MILConnectorCable(50PolePlugTypes) X X X
SBBusT-jointNFSBT01 SBBusT-joint X X XNFSBT02 SBBusT-jointwithBuilt-inTerminator X X X
DummyCoverNFDCV01 DummyCoverforI/OModuleSlot N.A. N.A. N.A.NFDCV02 DummyCoverforPowersupplyModuleSlot N.A. N.A. N.A.NFCCC01 MILCableConnectorCover N.A. N.A. N.A.
X: ConformingXX: ConformingconditionallyN.A.: Notapplicable*1: Tousemodulesashazardouslocationequipment(non-incendive),usethespecifiedpressure-clampterminalblocksorMIL
connectorcables(KMS40,KMS50)/MILconnectorterminalblocks(TAS40andTAS50).*2: I/Omoduleswithsuffixcode“withHARTcommunication”donotconformtotheexplosion-proofstandards.*3: Therelayoutputmodule(NFDR541)doesnotconformtotheexplosion-proofstandardswhenitisusedinbetween100to
240VAC..*4: Therelayoutputmodule(NFDR541)iscompliantwiththestandardsonlywhenthevoltageof24VDCorlessisappliedto
itsoutputterminal.*5: ForTurbomachineryI/OModules,refertoGS34P02Q04-01ETurbomachineryControllerOverview.
Aug.10,2015-00
13<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 34P02Q12-01E
CABLE SPECIFICATIONSThefollowingdescribesthespecificationsrequiredforthepowerandgroundingcablesused.Forfieldsignalwiringcables,see“FieldConnections”(GS34P02Q30-01E).
l Applicable CablesInsulatedcablesforindustrialequipmentsuchas:•600Vpolyvinylchlorideinsulatedwires(IV);JISC3307
•Polyvinylchlorideinsulatedwiresforelectricalapparatus(KIV);JISC3316
•600Vgradeheat-resistantpolyvinylchlorideinsulatedwires(HIV);JISC3317
•HeatproofvinylinsulatedwiresVW-1(UL1015/UL1007)
•Controlcables(vinylinsulatedvinylsheathcable)(CVV);JISC3401
l Recommended SizesPowercable:AWG20to14(0.5to2mm2)withring
tongueterminalGroundingcable:AWG14to13(2to2.6mm2)with
ringtongueterminal
l Recommended Solderless TerminalsPowercable:InsulatedM4solderlessterminals,8.5
mmwideorlessGroundingcable:InsulatedM4solderlessterminal,
8.5mmwideorless
FollowthespecificationsrequiredbytheM4solderlessterminalsused.
RESTRICTIONS AND PRECAUTIONS ON INSTALLATION
SeeInstallationGuidefor“STARDOMFCN/FCJInstallationGuide”(TI34P02Q91-01E).
l Limitations of Installation for NFAT141 (the combination of Thermocouple input and Pressure clamp terminal)
Tokeepthereferencejunctioncompensationaccuracy(GS34P02Q31-01E),makesuretomeetthefollowingconditions.Thepressureclampterminalshouldnotbeaffectedbyradiatedheat.•Donotinstallaheat-radiatingunitbeneaththeNFAT141installedunit.
•DonotinstallNFAT141inaplacewhereairflowimpingesdirectly.
•DonotinstallNFAT141nexttotheCPUmodules(NFCP100),powersupplymodules(NFPW44x).
•TheinstallablemodulesnexttotheNFAT141areasfollows.WheninstallingotherthanfollowingI/Omodules,makeanemptyslot(oneormore)ineachside.Installablemodules:NFAT141,NFAR181,NFAV141,
NFAV142,NFAV144,NFAV542
Mar.29,2016-00Subjecttochangewithoutnotice.
l Limitations of Installation for Communication Modules
•AtotalofuptoeightNFLR111/NFLR121canbeinstalledforeachFCN-100.
•AtotalofuptoeightNFLF111/NFLC121/NFLP121canbeinstalledforeachFCN-100.
l Limitations of Installation for I/O Modules WhenyouinstallthefollowingI/Omodules,ensurethattherequiredpowervolumedoesnotexceedtheratedpoweroutputofthepowersupplymodule.FortheamountofpowersupplythateachI/Omodulerequires(5VDCand24VDC),refertotheapplicablegeneralspecifications.
l About Use of NFBU050•NFBU050isdedicatedtocontrolunit.Itcannotbeusedasextensionunit.
•SBbusrepeatmodulecannotbemountedonNFBU050.
l Precaution on NFPW426 (Power Supply Module for FCN-RTU)
NFPW426(PowersupplymoduleforFCN-RTU)cannotbeusedforFCN-100.OnlyNFPW441,NFPW442orNFPW444canbeusedforFCN-100.
For Type “n”WhenFCN-100isusedundertheType“n”environment,theInstructionManual,“ExplosionProtectionofFCN/FCJProducts”(IM34P02Q11-02E)belowisrequiredforsaferinstallationandwiring.
Document No. Name
IM34P02Q11-02E ExplosionProtectionofFCN/FCJProducts
ORDERING INFORMATIONSpecifythemodelandsuffixcodes.Forselectingtherightproductsforexplosionprotection,pleasereferto“STARDOMFCN/FCJInstallationGuide”(TI34P02Q91-01E)withoutfail.
TRADEMARKS•AllbrandorproductnamesofYokogawaElectricCorporationinthisbulletinaretrademarksorregisteredtrademarksofYokogawaElectricCorporation.
•EthernetisaregisteredtrademarkofXeroxCorporation,theUnitedStates.
•PentiumisaregisteredtrademarkofIntelCorporation.
•Othercompanyandproductnamesappearinginthisdocumentaretrademarksorregisteredtrademarksoftheirrespectiveholders.