GE Power Controls Surion
GE Power Controls
Industrial Controls: Surion
GE Power Controls Surion
GE Power Controls
GE Power Controls Surion
GE Power Controls
Designed for switching and protecting three phase induction motors of up to 30kW@400VAC and for loads with rated currents up to 63A
Complete range of modular auxiliaries designed to be mounted without any tools
Fuseless compact starter with necessary accessories in four different frame sizes linking the line with the rest of control devices (contactors M and CL, and overload relays)
Surion, a new manual motor starter line
GE Power Controls Surion
GE Power Controls
Manual motor starters
Auxiliary devices
Accessories
Fuseless starter range (links, baseplates, busbars, etc. ...)
Complete Range
GE Power Controls Surion
GE Power Controls
Frame 1 : GPS1BH / GPS1MH
Rated up to 32A
High breaking capacity
Frame 2 : GPS2BS / GPS2MS
Rated up to 63A
Standard breaking capacity
Frame 2 : GPS2BH / GPS2MH
Rated up to 63A
High breaking capacity
Frame 1 : GPS1BS / GPS1MS
Rated up to 32A
Standard breaking capacity
Complete Range
GE Power Controls Surion
GE Power Controls
Frame 1 : GPS1BS / GPS1MS
Rated up to 32A Standard breaking capacity
Frame 1 : GPS1BH / GPS1MH
Rated up to 32A High breaking capacity
Frame 2 : GPS2BH / GPS2MH
Rated up to 63A High breaking capacity
Frame 2 : GPS2BS / GPS2MS
Rated up to 63A Standard breaking capacity
Complete Product Range
GE Power Controls Surion
GE Power Controls
Two different frames rated up to 32A and 63ARocker level and rotary actuator mechanismThermal / magnetic protection and magnetic protection only Standards / approvalsWorld wide availableComplete range of modular accessories suitable to be used with all the lineShort-circuit proof, 100 / 50kA @400V ACShort-circuit trip is set to 13 times the Ie maxThermal (set by the current dial) protection class 10Coordination with the M and CL contactor range for fuseless starter applicationsTerminal screw for pozidriv 2 screwdriverON / OFF / Tripping position available in all range (on tripping conditions re-set before set)
Main Features
GE Power Controls Surion
GE Power Controls
Worldwide availability, same line, same catalogue number and brand allowing our international customers to order same product throughout the world
Catalogue Number Structure
GE Power Controls Surion
GE Power Controls
Overall 45mm widthMax. rated current 32ASuitable for 3-pole induction motors up to 15kW@400V ACLowest setting range: 0,10 ... 0,16AHighest setting range: 24 ... 32AOperation: rocker levelProtection degree IP20Mechanical / electrical endurance 100.000 operationsTotal number of ranges: 15Modular number of accessoriesFuseless starters: linked up to CL45Thermal and magnetic protection and magnetic onlyBreaking capacity @400V: 100kA up to 10A, 50kA up to 13A and 25kA up to32A
Features of GPS1*S (standard breaking capacity)
GE Power Controls Surion
GE Power Controls
Overall 45mm widthMax. rated current 32ASuitable for 3-pole induction motors up to 15kW@400V ACLowest setting range: 0,10 ... 0,16AHighest setting range: 24 ... 32AOperation: rotary mechanismProtection degree IP20Mechanical / electrical endurance 100.000 operationsTotal number of ranges: 15Modular number of accessoriesFuseless starters: linked up to CL45Thermal and magnetic protection and magnetic onlyBreaking capacity: 100kA up to 13A and 50kA up to 32A
Features of GPS1*H (high breaking capacity)
GE Power Controls Surion
GE Power Controls
Overall 55mm widthMax. rated current 63ASuitable for 3-pole induction motors up to 30kW@400V ACLowest setting range: 6 ... 10AHighest setting range: 45 ... 63AOperation: rotary mechanismProtection degree IP10 (IP20 with the correspondent acc.)Mechanical / electrical endurance 50.000 / 25.000Total number of ranges: 9Modular number of accessoriesFuseless starters: linked up to CL07Thermal and magnetic protection and magnetic onlyBreaking capacity: 100kA up to 10A , 50kA up to 13A and 25kA up to 63A
Features of GPS2*S (standard breaking capacity)
GE Power Controls Surion
GE Power Controls
Overall 55mm widthMax. rated current 63ASuitable for 3p induction motors up to 30kW@400V ACLowest setting range: 6 ... 10AHighest setting range: 45 ... 63AOperation: rotary mechanismProtection degree IP10 (IP20 with the correspondent acc.)Mechanical / electrical endurance 50.000 / 25.000Total number of ranges: 9Modular number of accessoriesFuseless starters: linked up to CL07Thermal and magnetic protection and magnetic onlyBreaking capacity: 100kA up to 13A and 50kA up to 63A
Features of GPS2*H (high breaking capacity)
GE Power Controls Surion
GE Power Controls
Adjustment is sealed by a transparent plastic coverSetting scale for motor currentSetting rangeInstantaneous short circuit releaseManufacturing dateName plateTripping test indicationCatalog numberBrandClear switch setting range indicator throughout the rocker or rotary operating mechanism OFF / TRIPPED / ON "
Frontal Cover
GE Power Controls Surion
GE Power Controls
Terminals: - screw terminal (GPS1) box terminal (GPS2)Remove the plastic cover to fit the frontal auxiliary contact block or alarm blockScrewhead PZ2 & slotted combinationTerminal numbering
Frontal Cover
GE Power Controls Surion
GE Power Controls
IEC label-left side (UL label-right side)Setting rangeApprovals / standardsUtilization categoryInsulation voltage / rated frequencyElectrical drawing :thermal + magnetic or magnetic onlyTerminal capacityScrew head tightening torqueBack up fuse required only if higher short circuitcurrents occurring at the installation pointIcu ultimate short-circuit currentIcs service short-circuit current
Side Labels
GE Power Controls Surion
GE Power Controls
Two different actuators: rocker and rotary handle up to 32A and rotary handle only up to 63A with ON / OFF / Trip switching indicator positionClear identification of the status guaranteeing total protection to the usersUnder tripping condition reset it before setContacts can be open mechanically by operating the trip test mechanism (confirming sequence check of the alarm switch)Trip operating to open the contacts can not be prevented even when the handle is forced in the ON position (Trip Free)
ON / OFF / Tripped Position
GE Power Controls Surion
GE Power Controls
Ambient temperature:operating temperature: -25°C to +60°Cstorage temperature: -40°C to +80°Ctemperature compensation: -20°C to +60°C
Humidity: not to exceed 95%Corrosion resistance:
salt fog: 90h in salt fog chamberwithout corrosion guaranteeing nocorrosion of terminals
Operating altitude: general performance up to 2000 m
Environmental Conditions
GE Power Controls Surion
GE Power Controls
TerminalsGPS1 :Screw terminal M4, self lifting type screw with clamping plateScrew head : PZ2 & slotted combinationTerminal protection : IP20Max. wire size : 6 mm² (stranded with end sleeve)GPS2 :Box terminal M6Screw head : PZ2 & slotted combinationTerminal protection : IP10 (IP20 with correspondent accessory)Max. wire size : 16 mm² (stranded with end sleeve)
Terminal open during transportation
MountingGPS1 : 35mm DIN rail mounting + accessories in panelGPS2 : 35mm DIN rail mounting or direct screw mounting (2 x M4)
Terminals and Mounting
GE Power Controls Surion
GE Power Controls
Mechanical / electrical endurance (max. operational rate : 25 operation / hour)
GPS1 mechanical endurance 100.000 operationselectrical endurance 100.000 operations
GPS2 mechanical endurance 50.000 operationselectrical endurance 25.000 operations
Vibration and shock
Vibration 6g (5-150 Hz) acc. IEC 60068-2-6Shock 30g (pulse width 20ms) acc. IEC 60068-2-27
Rated insulation voltage and rated impulse withstand voltage
GPS1 Uimp = 6 kV AC
GPS2 Uimp = 8 kV AC
Performances
GE Power Controls Surion
GE Power Controls
Breaking capacity
Icu : Ultimate short-circuit breaking capacity,still operational after testing with O-t-CO
Ics : Rated service short-circuit breaking capacity,suitable for normal operating after testingwith O-t-CO-t-CO
(O: off / CO: restart and off / t: time delay)
Ics = 100kA Ics = 100% IcuIcs < 100kA Ics min = 75% Icu
Short-circuit Protection
GE Power Controls Surion
GE Power Controls
Short-circuit Protection
GE Power Controls Surion
GE Power Controls
Short-circuit Protection
GE Power Controls Surion
GE Power Controls
The manual motor starter can be fed at the top or bottom supply terminals without any reduction of the rated values
Back-up fuses are only necessary if there is possibility of a short-circuit current higher than the values indicated on the previous chart for the ultimate short-circuit breaking capacity of the manual motor starter at the installation point of the device
Feeding
GE Power Controls Surion
GE Power Controls
The current of the motor to be protected is set on the setting scale
The short-circuit release is set at the factory to a value equivalent to 13 times the rated current of the manual motor starter
Manual motor starters with thermal overload release aredesigned in accordance with release class 10
All the Surion line is available with magnetic only protection for starter combinations (contactor + overload relay)
In case of overload the relay releases the contactor and the MMS remains closed
Motor Protection
GE Power Controls Surion
GE Power Controls
Thermal release trip currentCurve apply for cold state, at operating temperature thetripping time for overload release are reduced of 25%
For single phase and DC loads the three phases must be connected in series
The magnetic release are based on the rated current Inwhich is the max. value of the setting range of the MMS
If the current is set to a lower value, the tripping current is increased by a corresponding factor
The short-circuit release is set at the factory to a valueequivalent to 13 times the rated current of the manualmotor starter
Tripping Characteristics GPS1
GE Power Controls Surion
GE Power Controls
Thermal release trip currentCurve apply for cold state, at operating temperature thetripping time for overload release are reduced +/-25%
For single phase and DC loads the three phases must beconnected in series
The magnetic release are based on the rated current Inwhich is the max. value of the setting range of the MMS
If the current is set to a lower value, the tripping currentis increased by a corresponding factor
The short-circuit release is set at the factory to a valueequivalent to 13 times the rated current of the manualmotor starter
Tripping Characteristics GPS2
GE Power Controls Surion
GE Power Controls
Auxiliary devices
GE Power Controls Surion
GE Power Controls
1. Auxiliary contacts1A. Frontal1B. Lateral (left or right)
2. Alarm contact block (frontal on the right)
3. Auxiliary / alarm contact (Left)
4. Short-circuit alarm contact block (Left)
5. Shunt trip (Right)
6. Undervoltage trip (Right)
7. Undervoltage release with 2NO early make aux. Contacts ( Right)
8. External handle operator
Complete Auxiliary Range
GE Power Controls Surion
GE Power Controls
Catalogue Number Structure
Worldwide availability, same line, same catalogue number and brand allowing our international customers to order same product throughout the world
GE Power Controls Surion
GE Power Controls
Worldwide availability, same line, same catalogue number and brand allowing our international customers to order same product throughout the world
Catalogue Number Structure
GE Power Controls Surion
GE Power Controls
Single contact 1NO or 1NC
Maximum two contact blocks per manual motor starter (maintaining 45mm and 55mm overall width of the MMS)
Suitable to be used with GPS1 and GPS2
Minimum operational power : 17VDC, 5mA
Rated duty : AC15, DC13 (B300, Q300)
Frontal Auxiliary Contact Block
Electrical drawing
GE Power Controls Surion
GE Power Controls
Two lateral auxiliary blocks, two left mountable and two right mountable
Three versions : 1NO+1NC, 2NO and 2NC
Maximum four (2 left + 2 right) contact blocks per module (GPS1**AR - 32A allow only two lateral blocks)
Suitable to be used with GPS1 and GPS2 (GSP1*SAR - 32A rated current max. two auxiliary contact blocks)
Minimum operational power: 17VDC, 5mA
Rated duty : AC15, DC13 (A600, P300)
Width : 9mm
Lateral Auxiliary Contact Block
Electrical drawing
GE Power Controls Surion
GE Power Controls
Single contact 1NO or 1NC
Front mounting on the right side
Maximum one contact block per manual motor starter (maintaining 45mm and 55mm overall width of the MMS)
Suitable to be used with GPS1 and GPS2
Tripping for short-circuit, overload and auxiliary release
Rated duty : AC15, DC13 (B300, Q300)
Frontal Alarm Contact Block
Electrical drawing
GE Power Controls Surion
GE Power Controls
Side mounting on the left, maximum one per MMSFour versions : 1NO (alarm) + 1NO (auxiliary)
1NO (alarm) + 1NC (auxiliary)1NC (alarm) + 1NO (auxiliary)1NC (alarm) + 1NC (auxiliary)
Mechanical indicator (alarm)Suitable to be used with GPS1 and GPS2Auxiliary contact : minimum operational power : 17VDC, 5mAwith rated duty : AC15, DC13 (A600, P300)Width : 9mmTripping for short-circuit, overload and auxiliary releaseAlarm contact is auto reset and with mechanical indicator
Auxiliary / Alarm Contact Block
Electrical drawing
GE Power Controls Surion
GE Power Controls
Side mounting on the left, can be mounted with auxilary contact blocks or alarm / auxiliary contact blocks on the same side
Two contacts : 1NO+1NC
Mechanical indicator
Suitable to be used with GPS1 and GPS2
Width : 9mm
Tripping for short-circuit
Alarm contact auto reset with mechanical indicator
Rated duty : AC15, DC13 (A600, P300)
Short-circuit Alarm Contact Block
Electrical drawing
GE Power Controls Surion
GE Power Controls
For remote control tripping of the manual motor starter
Side mounting on the right
Suitable to be used with GPS1 and GPS2
Width : 18mm
Coil voltage : 24 to 500 VAC and 24 to 240 VDC can only be energized for short periods
Cannot be used together with the undervoltage trip or any lateral auxiliary contact block right mounted
Shunt Trip
Electrical drawing
GE Power Controls Surion
GE Power Controls
MMS operates once the undervoltage trip is energised
Trips the MMS when the voltage is interrupted and prevents theunintentional restart of the motor when the voltage is recovered
Particularly suitable for emergency stop disconnection
Side mounting on the right
Suitable to be used with GPS1 and GPS2
Width : 18mm
Coil voltage : 24 to 500 VAC
Cannot be used together with a shunt trip device or any lateral block mounted on the right side
Undervoltage Trip
Electrical drawing
GE Power Controls Surion
GE Power Controls
MMS operates once the undervoltage trip is energised
Trips the MMS when the voltage is interrupted and prevents the unintentional restart of the motor when the voltage is recoveredParticularly suitable for emergency stop disconnectionThe 2NO early make auxiliary contacts isolate the undervoltage trip from the supply on both sides when the MMS opens or tripsSide mounting on the right
Two frames (two catalog numbers), one for rocker and another for rotary actuator
Width : 18mm
Coil voltage : 24 to 500 VAC
Cannot be used together with the shunt trip
Electrical drawing
Undervoltage Trip with 2 NO early make aux. contacts
GE Power Controls Surion
GE Power Controls
Electrical connections for auxiliary devices
GE Power Controls Surion
GE Power Controls
Four different types :Standard (black) IP55 for GPS1*HEmergency (yellow/red) IP55 for GPS*1Standard (black) IP55 for GPS2Emergency (yellow/red) IP55 for GPS2Mounting description :
External handle operator
GE Power Controls Surion
GE Power Controls
Features
Two different types : Surface mountingFlush mounting
Available only for installing MMS GPS1S*
IP41 and IP55 degree protection
PE terminal inside
Circuit-breaker is actuated via actuator membrane
Two auxiliary blocks (9 and 18 mm width) can be installed inside the enclosure
Enclosures for Surion MMS
GE Power Controls Surion
GE Power Controls
Accessories
A padlock device can be fitted with 3 padlocks (OFF position)
Conversion kit from IP41 to IP55 in both type of enclosures
Mushroom button can be fitted with : Impulse functionMechanical latchKey lock
Three different colors indicator lamps with 5 voltage ranges
Enclosures for Surion MMS
GE Power Controls Surion
GE Power Controls
Mounting
Inside the enclosures can be fitted :9mm lateral auxiliary block
+18mm lateral block, suitable to be used withundervoltage release for machine tool protection
A conversion kit is necessary to use a 18mm UV Early Make block (GPEUTA)
Enclosures for Surion MMS
GE Power Controls Surion
GE Power Controls
Features
Busbar system provide a simply, time-saving and clearlylaid out to assembly MMS in parallel
The busbar system are suitable from 2 to 5 MMS
Fitted 9mm and 18mm auxiliary blocks is available usingthe appropriated spacing
It can be used with both GPS1* and GPS2* frames, but not together at the same busbar
Accessories
Upper feed-in terminal : upper terminal to supply the system
Busbar cover : to protect empty terminals against accidental contacts.
Busbar System
GE Power Controls Surion
GE Power Controls
Fuseless Starters
GE Power Controls Surion
GE Power Controls
Features
Fuseless starter is the combination of 1 MMS and one or two(reverser) contactors connected each other with a link moduleand assembly in a base plate or busbar adapter
MMS is used to provide protection against the load, usually amotor, from overloads and short-circuits, then fuses orlimiters should be avoid. The contactor is used for switchingtask mainly done in a remote distance
Power with 45mm width device is up to 11kW@400V andwith 55mm width device is up to 30kW@400V
Lateral and front mounting auxiliary blocks can be used withfuseless starter
Base plates and busbar adapter can also be used with the MMS alone
Direct A1-A2 terminal coil accessibility
Coordination type 1 and 2 @ 400/415, 500 V and 690 V
Fuseless Starters
GE Power Controls Surion
GE Power Controls
Main accessories
Link modules : provide mechanical and electrical connection between MMS and contactor
Base plates : base support used to fix the MMS and contactor
Busbar adapter : base support which is capable to be fitted directly onto a busbar, with 40 and 60mm centre line spacing (thickness 5 to 10mm) and just with one operation, mechanical “click on” and electrical connections are done
Fuseless Starters
GE Power Controls Surion
GE Power Controls
Combination structure (BS: Base Plate, BA: Busbar Adapter, W/O: Without)
(*) : mandatory to use BP
Fuseless Starters
GE Power Controls Surion
GE Power Controls
As a support is used a Base Plate (BP) or Busbar Adapter (BA)If MC contactors series are used BP is not required
All Manual Motor Starters are designed to be used as fuseless starters
A link between the MMS and the contactor is mandatory to secure mechanical / electrical connection
Contactors from MC series up to CL07 can be used.Also is possible a reverse assembly using a wiring kit between contactors
Contactor cover
Fuseless Starters : components
GE Power Controls Surion
GE Power Controls
MMS should be mounted on a BP with a 35mm DIN rail or on a BA with 35mm DIN rail or screws
A link is screwed at the MMS
Contactors should be rotated before the assembly to the link
Fit the contactor cover
The contactor is mounted to both the link and the BP or BA
The contactor should be screwed to both the link and the BP or BA
Fuseless Starters : mounting instruction
GE Power Controls Surion
GE Power Controls
Overview Technical Data
GE Power Controls Surion
GE Power Controls
Overview Technical Data
GE Power Controls Surion
GE Power Controls
Overview Technical Data
GE Power Controls Surion
GE Power Controls
GE Power Controls Surion
GE Power Controls
Fuseless Starters
GE Power Controls Surion
GE Power Controls
Fuseless Starters
GE Power Controls Surion
GE Power Controls
Fuseless Starters
GE Power Controls Surion
GE Power Controls
Fuseless Starters
GE Power Controls Surion
GE Power Controls