GE Molded Case Circuit Breakers F225 Line Circuit Breakers 70-250 Amperes-TFJ Noninterchangeable Trip 70-225A TFK, THFK Interchangeable Trip 480 or 600 volts ac 250 Volts dc Frame Note: All TFJ, TFK and THFK breakers are UL listed as HACR. r Type TFJ—Noninterchangeable Trip Includes line and load lugs. Suitable for reverse feed. Ampere Rating Adjustable Trip Range Amp Lo Hi Complete Breaker 480 Vac Max. Catalog Number List Price, GO-135B Two-Pole 70 80 90 100 110 125 150 175 200 225 250 225NA 600 700 600 600 660 600 700 800 900 1000 1000 - 900 1000 900 1250 1250 1250 1500 1750 2000 2250 2250 - TFJ224070WL TFJ224080WL TFJ224090WL TFJ224100WL TFJ224110WL TFJ224125WL TFJ224150WL TFJ224175WL TFJ224200WL TFJ224225WL TFJ226Y225®@© $1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 803.00 Complete Breaker 600 Vac Max. Catalog Number List Price, GO-135B Three-Pole TFJ236070WL TFJ236080WL TFJ236090WL TFJ236100WL TFJ236110WL TFJ236125WL TFJ236150WL TFJ2361 75WL TFJ236200WL TFJ236225WL TFJ236250WL TFJ236Y225CS© $1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 2075.00 1174.00 Copper/ Aluminum Lugs TCAL24 ® TCAL24 Wire Size #4-300 kcmil ® Types TFK, THFK—Interchangeable Trip Ampere Rating Adjustable Trip Range Amp Lo Hi Complete Circuit Breaker Includes Line and Load Lugs Standard Catalog Number List Price, GO-135B Hi-Break- Catalog Number List Price, GO-135B Trip Unit Only Use with Standard and Hi-Break Frames List Price, GO-135B Frame Only Catalog Number List Price, GO-135B Terminal Lugs for Front Connection (Copper/Aluminum)® ] Catalog Number (Order 1 line and 1 load per pole) List Price, GO-135B Wire Size Two-Pole, 480 Volts ac Max., 250 Volts dc Max. 70 80 90 100 110 125 150 * 175 200 225 225NA 600 700 600 600 660 600 700 aoff- 900 1000 900 1000 900 1250 1250 1250 1500 4.750 2060, 2250 TFK224070WL TFK224080WL TFK224090WL TFK224100WL TFK224110WL TFK224125WL TFK224150WL TFK224175WL TFK2242QOWL "TFK229225WL TFK226Y225®®® $1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 937.00 THFK224070WL THFK224080WL THFK224090WL THFK224100WL THFK224110WL THFK224125WL THFK224150WL THFK224175WL THFK224200WL THFK224225WL $2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 - TFK226T070 TFK226T080 TFK226T090 TFK226T100 TFK226T110 TFK226T125 TFK226T150 TFK226T175 TFK226T200 TFK226T225 TFKY2© $337.00 337.00 337.00 337.00 337.00 337.00 337.00 337.00 337.00 337.00 148.00 TFK224FOOO Standard Frame THFK224FOOO Hi-Break Frame $753.00 1946.00 TCAL24 $8.00 #4-300 kcmil Three-Pole, 600 Volts ac Max., 250 Volts dc Max. 70 80 90 100 110 125 150 175 200 225 225A Mag Only 225NA 600 700 600 600 660 600 700 800 900 1000 600 1000 - 900 1000 900 1250 1250 1250 1500 1750 2000 2250 1400 2250 TFK236070WL TFK236080WL TFK236090WL TFK236100WL TFK236110WL TFK236125WL TFK236150WL TFK236175WL TFK236200WL TFK236225WL TFK236Y225® © 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1174.00 THFK236070WL THFK236080WL THFK236090WL THFK236100WL THFK236110WL THFK236125WL THFK236150WL THFK236175WL THFK236200WL THFK236225WL - 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 - TFK236T070 TFK236T080 TFK236T090 TFK236T100 TFK236T110 TFK236T125 TFK236T1 50 TFK236T175 TFK236T200 TFK236T225 TFK236TM1225® TFK236TM2225® TFKY3© 445.00 445.00 445.00 445.00 445.00 445.00 445.00 445.00 445.00 445.00 555.00 555.00 208.00 TFK236FOOO Standard Frame THFK236FOOO Hi-Break Frame 914.00 2294.00 TCAL24 g f\e\ O.UU #4-300 kcmil ® Molded-case switch. Complete switch includes line and load lugs. UL listed only when ordered as a complete switch. Internal accessory installation requires dummy trip unit. See page 4-51 for additional details. © Not UL listed. ® For optional lugs, see page 4-62. © 600 volts maximum. ® TC024 load end. Wire range #4-300 kcmil copper only. Accessories: See pages 4-48 to 4-65. 4-22 1999 Issue Prices and data subject to change without notice

Upload: doankiet

Post on 16-May-2018

219 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: GE Molded Case Circuit Breakers F225 Line Circuit … Molded Case Circuit Breakers F225 Line Circuit Breakers 70-250 Amperes-TFJ Noninterchangeable Trip 70-225A TFK, THFK Interchangeable

GE Molded Case Circuit Breakers

F225 Line Circuit Breakers70-250 Amperes-TFJ Noninterchangeable Trip70-225A TFK, THFK Interchangeable Trip480 or 600 volts ac250 Volts dc

Frame

Note: All TFJ, TFK and THFKbreakers are UL listed asHACR. r

Type TFJ—Noninterchangeable TripIncludes line and load lugs. Suitable for reverse feed.

AmpereRating

Adjustable Trip RangeAmp

Lo Hi

Complete Breaker480 Vac Max.

Catalog NumberList

Price,GO-135B

Two-Pole708090

100110125150175200225

250

225NA

600700600600660600700800900

1000

1000

-

9001000900

1250125012501500175020002250

2250

-

TFJ224070WLTFJ224080WLTFJ224090WLTFJ224100WLTFJ224110WLTFJ224125WLTFJ2241 50WLTFJ224175WLTFJ224200WLTFJ224225WL

TFJ226Y225®@©

$1122.001122.001122.001122.001122.001122.001122.001122.001122.001122.00

803.00

Complete Breaker600 Vac Max.

Catalog NumberList

Price,GO-135B

Three-PoleTFJ236070WLTFJ236080WLTFJ236090WLTFJ236100WLTFJ236110WLTFJ236125WLTFJ236150WLTFJ2361 75WLTFJ236200WLTFJ236225WL

TFJ236250WL

TFJ236Y225CS©

$1407.001407.001407.001407.001407.001407.001407.001407.001407.001407.00

2075.00

1174.00

Copper/Aluminum

Lugs

TCAL24

®

TCAL24

WireSize

#4-300kcmil

®

Types TFK, THFK—Interchangeable Trip

AmpereRating

AdjustableTrip Range

Amp

Lo Hi

Complete Circuit BreakerIncludes Line and Load Lugs

Standard

Catalog NumberList

Price,GO-135B

Hi-Break-

Catalog NumberList

Price,GO-135B

Trip Unit Only

Use withStandard

andHi-BreakFrames

ListPrice,

GO-135B

Frame Only

Catalog NumberList

Price,GO-135B

Terminal Lugs forFront Connection

(Copper/Aluminum)® ]

Catalog Number(Order 1 lineand 1 loadper pole)

ListPrice,

GO-135BWireSize

Two-Pole, 480 Volts ac Max., 250 Volts dc Max.708090

100110125150 *175200225

225NA

600700600600660600700aoff-900

1000

9001000900

12501250125015004.7502060,2250

TFK224070WLTFK224080WLTFK224090WLTFK224100WLTFK224110WLTFK224125WLTFK224150WLTFK224175WLTFK2242QOWL

"TFK229225WL

TFK226Y225®®®

$1122.001122.001122.001122.001122.001122.001122.001122.001122.001122.00

937.00

THFK224070WLTHFK224080WLTHFK224090WLTHFK224100WLTHFK224110WLTHFK224125WLTHFK224150WLTHFK224175WLTHFK224200WLTHFK224225WL

$2315.002315.002315.002315.002315.002315.002315.002315.002315.002315.00

-

TFK226T070TFK226T080TFK226T090TFK226T100TFK226T110TFK226T125TFK226T150TFK226T175TFK226T200TFK226T225

TFKY2©

$337.00337.00337.00337.00337.00337.00337.00337.00337.00337.00

148.00

TFK224FOOOStandardFrame

THFK224FOOOHi-BreakFrame

$753.00

1946.00

TCAL24 $8.00 #4-300kcmil

Three-Pole, 600 Volts ac Max., 250 Volts dc Max.708090

100110125150175200225

225AMagOnly

225NA

600700600600660600700800900

1000

6001000

-

9001000900

1250125012501500175020002250

14002250

TFK236070WLTFK236080WLTFK236090WLTFK236100WLTFK236110WLTFK236125WLTFK236150WLTFK236175WLTFK236200WLTFK236225WL

——

TFK236Y225® ©

1407.001407.001407.001407.001407.001407.001407.001407.001407.001407.00

——

1174.00

THFK236070WLTHFK236080WLTHFK236090WLTHFK236100WLTHFK236110WLTHFK236125WLTHFK236150WLTHFK236175WLTHFK236200WLTHFK236225WL

——

-

2787.002787.002787.002787.002787.002787.002787.002787.002787.002787.00

——

-

TFK236T070TFK236T080TFK236T090TFK236T100TFK236T110TFK236T125TFK236T1 50TFK236T175TFK236T200TFK236T225

TFK236TM1225®TFK236TM2225®

TFKY3©

445.00445.00445.00445.00445.00445.00445.00445.00445.00445.00

555.00555.00

208.00

TFK236FOOOStandardFrame

THFK236FOOOHi-BreakFrame

914.00

2294.00 TCAL24 g f\e\O.UU#4-300kcmil

® Molded-case switch. Completeswitch includes line and loadlugs. UL listed only whenordered as a complete switch.

Internal accessory installationrequires dummy trip unit. Seepage 4-51 for additionaldetails.

© Not UL listed.® For optional lugs, see page

4-62.© 600 volts maximum.

® TC024 load end. Wire range#4-300 kcmil copper only.

Accessories:See pages 4-48 to 4-65.

4-22 1999 Issue Prices and data subject to change without notice

Page 2: GE Molded Case Circuit Breakers F225 Line Circuit … Molded Case Circuit Breakers F225 Line Circuit Breakers 70-250 Amperes-TFJ Noninterchangeable Trip 70-225A TFK, THFK Interchangeable

GF Molded Case Circuit Breakers

Molded Case Circuit Breakers ,Spectra RMS™, Spectra RMS™ with MicroVersaTrip Plus™ Trip Units, Spectra RMS™ withMicroVersaTrip PM™ Trip Units, Thermal Magnetic and J/K with MicroVersaTrip® HMS-9 andPower+™ 4 Trip Units

How to OrderQLine• Thermal Magnetic Circuit Breakers• Molded-Case Switches

The catalog number as shown in the following pages includes thecomplete breaker or switch. TQD and TJD breakers are completewith Cu/AI line and load lugs.Spectra RMS™• Circuit Breakers

Determine the required breaker frame, 1C rating, and loadrequirements. Select frame, trip unit (rating plug), and lug, ifrequired, catalog numbers from the tables on pages 4-18 and4-19. Select field-mounted internal accessory catalog numbers,if required, on page 4-47. Select field-mounted externalaccessory catalog numbers, if required, on pages 4-48 through4-65. Order as separate items. For Spectra breakers withMicroVersaTrip Plus Trip Units or MicroVersaTrip PM Trip Unitsrefer to page 4-26 through 4-35.

• Mag-Break Motor Circuit ProtectorsDetermine the required frame and ampere requirements.Select frame, trip unit (rating plug), and lug, if required, catalognumbers from the table on page 4-42. Select accessories asnoted above for circuit breakers. The same accessories areused with both circuit breakers and motor circuit protectors.Order as separate items.

• Molded-Case SwitchesDetermine the required frame and ampere requirements.Select frame and lug, if required, catalog numbers from the tableon page 4-20. Rating plugs are not used. Select accessories asnoted above for circuit breakers. Internal accessories do notrequire dummy trips. The same accessories are used with bothcircuit breakers and molded-case switches. Order as separateitems.

Unless otherwise noted, all circuit breakers are UL listed in File E-11592.Molded-case switches are UL listed in File E-57546. Field-InstallableInternal Accessories are UL listed in File E-57253. Distribution CableAccessories for MicroVersaTrip Plus Trip Units and MicroVersaTrip PM TripUnits are UL listed in File E-57253.

E150 LineThermal Magnetic Circuit BreakersMagnetic Circuit BreakersMolded-Case Switches

The catalog numbers as shown in the following pages include thecomplete breaker or switch. All devices listed come with Cu/AI lineand load lugs. If line lugs are not required on a breaker, eliminate"WL" from catalog number; for molded-case switches see page4-3. Unless otherwise noted, all circuit breakers are UL listed inFile E-11592. Molded-case switches are UL listed in File E-57546.F 225 Line• Thermal Magnetic Circuit Breakers• Magnetic Circuit Breakers• Molded-Case Switches

These breakers are available with either noninterchangeable trips(designated Type TFJ) or interchangeable trips (designated TypesTFK/THFK). When ordering Type TFJ, catalog number includes

complete breaker, trip unit, Cu/AI line and load lugs factoryassembled. If line lugs are not required on a breaker, eliminate"WL" from catalog number, and subtract price of line lugs fromprice of complete breaker. If interchangeable trip (Types TFK/THFK) is required order one of two ways. "Complete circuitbreaker" price includes frame, trip, Cu/AI line and load lugs. Unitswill be shipped unassembled unless specified on order "must befactory assembled." If line lugs are not required on a breaker,eliminate "WL" from catalog number, and subtract price of linelugs from price of complete breaker. To order the frame, trip, andlugs separately, select the required components from table.Magnetic breakers must be ordered as components. A completebreaker consists of frame, trip unit, one line lug per pole and oneload lug per pole. Price of "Complete Circuit Breaker" vs. orderingframe, trip, and line and load lugs separately is the same.Molded-case switches can also be ordered as complete units(designated TFK—Y) or as separate components. They are ULlisted only as complete units. To indicate required lugs, seepage 4-3.Unless otherwise noted, all circuit breakers are UL listed in FileE-11592. Molded-case switches are UL listed in File E-57546.J 600 Line• Thermal Magnetic Circuit Breakers• Magnetic Circuit Breakers• Molded-Case Switches -These breakers are available with either noninterchangeable trip(designated Type TJJ) or interchangeable trip (designated TypeTJK and THJK). Type TJJ catalog numbers include frame, trip,Cu/AI line, and load lugs factory assembled. If line lugs are notrequired on the breaker, eliminate "WL" from catalog number, andsubtract price of line lugs from price of complete breaker.TJK breakers are available in two frames, 400 ampere frame(125 to 400 amperes) and 600 ampere frame (250 to 600 • .amperes). Trip units are not interchangeable between frames."Complete Circuit Breaker" price includes frame, trip unit, Cu/AIline, and load lugs. Unit will be shipped unassembled unless orderspecifies "must be factory assembled." If line lugs are notrequired, eliminate "WL" from catalog number and subtract priceof line lugs from price of complete breaker.To order the frame, trip, and lugs separately, select the requiredcomponents from table. Magnetic breakers must be ordered ascomponents. A complete breaker consists of frame, trip, and oneline and one load lug per pole.Price of ordering "Complete Circuit Breaker" vs. frame, trip, andline and load lugs separately is the same.Molded-case switches can also be ordered as complete units(designated Type TJK—Y) or as separate components. They areUL listed only as complete units. To indicate required lugs, seepage 4-3.Unless otherwise noted, all circuit breakers are UL listed in FileE-11592. Molded-case switches are UL listed in File E-57546.

(continued on next page)

4-2 1999 Issue Data subject to change without notice

Page 3: GE Molded Case Circuit Breakers F225 Line Circuit … Molded Case Circuit Breakers F225 Line Circuit Breakers 70-250 Amperes-TFJ Noninterchangeable Trip 70-225A TFK, THFK Interchangeable

GE Molded Case Circuit Breakers

K1200 Line• Thermal Magnetic Circuit Breakers• Magnetic Breakers• Molded-Case SwitchesThese breakers are available only with interchangeable trip units.Two frame sizes are available, the 800 ampere frame (300 to 800amperes) and the 1200 ampere frame (600 to 1200 amperes). Tripunits are not interchangeable between frames.

"Complete Circuit Breaker" price includes frame, trip, Cu/AI line,and load lugs. Units will be shipped unassembled unless specified"must be factory assembled." If line lugs are not required on thebreaker, eliminate "WL" from catalog number and subtract priceof line lugs.

To order the frame, trip, and lugs separately, select the requiredcomponents from table. Magnetic circuit breakers must beordered as components. A complete breaker consists of frame,trip and one line and one load lug per pole. Price of ordering"Complete Circuit Breaker" vs. frame, trip, and line and load lugsseparately is the same.

Molded-case switches can also be ordered as complete units(designated Type TKMA—Y) or as separate components. Theyare UL listed only as complete units. To indicate required lugs,see the table below.

x Unless otherwise noted, all circuit breakers are UL listed in FileE-11592. Molded-case switches are UL listed in File E-57546.R Frame—1000/1600/2000 Amp Molded-Case Circuit Breakers• Solid-state MicroVersaTrip Plus™ or MicroVersaTrip PM™

Trip Unit• Interchangeable trip unit via rating plugs• 65 and 100 kA ratings available• Standard and 100% rated versions• Uses standard Power Break* accessories• Stationary/manual onlyCurrent Limiting Circuit Breakers• 150, 225, 400 and 600 ampere frame sizes• UL listed interrupting ratings are 200 kA at 240 and 480 volts ac

maximum and 50 kA at 600 volts ac maximum• Thermal magnetic constructionCircuit Breakers with MicroVersaTrip' Trip Units• Solid-state construction with MicroVersaTrip RMS-9 digital rms

sensing microprocessor trip units.• Available in J and K frame construction with ampere ratings from

60-1200A.For ordering information see pages 4-36 through 4-41. UL listed,File E-11592. All breakers are UL listed in File E-11592.Tri-Break' Line• Integrally Fused Thermal Magnetic Circuit Breakers• Integrally Fused Magnetic Circuit Breakers• Integrally Fused Molded-Case Switches

Molded Case Circuit BreakersThese breakers are available in four types. Type TB1 (15-100amperes) catalog numbers include frame, trip, line and load lugs,and current limiters all factory assembled. Types TB4 (125 to 400amperes), TB6 (300 to 600 amperes) and TB8 (600 to 800 amperes)include frame, trip and limiters, factory assembled, but do notinclude line or load lugs. If line and load lugs are required, orderseparately. Unless otherwise noted, TB1, TB4, TB6, and TB8breaker components are UL listed in File E-42263. Fusedmolded-case switches are UL listed in File E-57546.Mag-Break9 Line• Magnetic only circuit breakers (motor circuit protectors)

These breakers are available only with noninterchangeableadjustable magnetic trip, in frame Types E, F, J, K, and Tri-Break.All breakers are shipped factory assembled, complete with Cu/AIline and load lugs.

All magnetic only circuit breakers and limiters are UL ComponentRecognized in Files E-11592 and E-66390, respectively, unlessotherwise noted.

AccessoriesOrder accessories from the appropriate table:

Thermal Magnetic Circuit Breakers, Magnetic Circuit Breakers, andMolded-Case Switches®—pages 4-48 to 4-65.MicroVersaTrip RMS-9 or 4-function Solid-State Circuit Breakers— .pages 4-48 to 4-65.

© Installation of accessories in molded-case switches requires dummytrip; see page 4-51 for information. Dummy trip not required forTri-Break or Q Line molded-case switches.

Spectra RMS™ Breakers—pages 4-47 to 4-65.Spectra RMS™ Breakers with MicroVersaTrip Plus™ Trip Units orMicroVersaTrip PM™ Trip Units—pages 4-32 to 4-35 and 4-47 to 4-65.

Molded-Case Circuit Breaker and SwitchTerminal Configuration CodeOrder standard Cu/AI lugs by using suffix codes presented. Order lugsseparately if special lugs are required. For optional lugs, see page 4-62.

Breaker/SwitchType

TQD/TJD

Molded CaseBreakers,ThermalMagneticMoldedCaseSwitchSpectra RMS™BreakersJ.K.MicroVersaTrip"BreakersMine Duty™BreakersMag- Break*Breakers

Suffix

BlankLoadLugsOnly

LoadLugsOnly

Line andLoadLugsNo

Lugs

NoLugs

NoLugs

Line andLoad Lugs

WL

Line andLoad Lugs

Line andLoad Lugs

-

XL

-

-

NoLugs

X2LineLugsOnly

LineLugsOnly

LineLugsOnly

LL

NoLugs

NoLugs

LoadLugsOnly

Order Lugs Separately

Order Lugs Separately

Order Lugs Separately

- - - —

For E 150 circuit breakers suffix XL is used to specify "no lugs".

Data subject to change without notice 1999 Issue 4-3

Page 4: GE Molded Case Circuit Breakers F225 Line Circuit … Molded Case Circuit Breakers F225 Line Circuit Breakers 70-250 Amperes-TFJ Noninterchangeable Trip 70-225A TFK, THFK Interchangeable

pi N II

GE Molded Case Circuit Breakerst. VERTICAL Molded Case Circuit Breakers

Quick Reference GuideRatings do not apply to molded-case switches.

TJJ, TJK, THJK TFJ, TFK, THFK

E150 (UL File E-11592; Fixed Thermal Magnetic Trip Unit; CSA LR 57114)

Jlte^

CircuitBreakerType

TEY®

TEB®

TED®

THED®

TEL®

AmpereRating

15-100

10-1009>

10-100

15-10010-150

15-30

15-100

15-1001 1 0 - 1 5 0

-15-150

No.Poles

12

3

1

2

3

1

2 '

3

1

2

3

3

MaximumVoltage Rating

ac277

120

277,347®480

600

277,347®

480

480,600

600

do125

250

125

250

125

250

500

125

250

-

UL Listed Interrupting Ratings—rms Symmetrical Amps (In Thousands)ac Voltage

12065

10

-

-

120/240

-

-

100

240

14

65

10

18

65

65

42

100

277

14

1 4

-

14

65

-

-

480

-

-

10

1 8

25

65

600

-

-

1 4

18

25

do Voltage1251 01 0—

5——

10

20®

-

-

250

1 0

5

10

10

20®

10

-

500®—

10

-

Dimensions(In.)

H

5'/4

65/ie

6^16

65/16

65/ie

W

1

2

3

1%

2%'

4Vfr

1%

23/4

41*

1%

41/a

4'/B

D

3'/18

3%

3%

3%

ytte

A

-

24'/64

Z"A>

2"/tn

27/16

B

-

2'%4

21%4

21s/64

2'%2

c

-

"/16

__

1 '/16

——

"/,6

11/16

E

-

s%2

23/32

2%2

2%2

Approx.Ship Wt./Std. Pack

26 lb/2424 lb/1 2

28 lb/8

26 lb/24

24lb/1228 lb/8

26 lb/24

24lb/12

28 lb/8

3Vz lb/1

"225 (UL File E-11592; TFJ, Fixed Thermal Magnetic Trip Unit; TFK, THFK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)

CircuitBreaker

Type

TFJ®

TFK®

THFK®

TFL®

AmpereRating

70-225

70-250

70-225

70-225

70-225

No.Poles

2

3

2

3

2

3

3

MaximumVoltage Rating

ac480

600

480

600

480

600

600

dc

250

500

250

250

-

UL Listed Interrupting Ratings —rms Symmetrical Amps (In Thousands)ac Voltage

120

-

120/240

100

240

25

25

65

100

277

-

480

22

22

25

65

600

1 8

_

18

1 8

25

dc Voltage125

-

2501 0

10®

10

20®

-

500®—

10

_

-

Dimensions(in.)

H

10'/8

101*

10'/B

101*

W

41*

4%

41*

'41*

D

3'Vie

31yi«

3^18

3«/16

A

3%

3%

37/6

3%

B

3'/B

3%

3%

3%

C

"/16

"/,e

"/16

11/16

E

1 3 /16 •

1*i6

1Vie

1*ie

Approx.Ship Wt./Std. Pack

10 lb/1

12 lb/110 lb/112 lb/110 lb/112 lb/1

-

J600 (UL File E-11592; TJJ, Fixed Thermal Magnetic Trip Unit; TJK, THJK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)

TJK4

THJK4

250-600

250-600

2

3

2

3

2

3

2

3

600

600

250

500

250

500

250

250

-

42

65

30

35

2210

20

10

20®

40

40

-

' 20®

20

_

81/4

3'3/16

3%

315/16 3^16

3«/16

1% 1*6

16lb/117'/2lb/1

18 lb/120 lb/116 lb/1

17Vzlb/1

18 lb/120 lb/1

K1200 (UL File E-11592; Interchangeable Thermal Magnetic Trip Unit; CSA LR 40350)

TKM8

TKM12

THKM12

2

3

2

3

2

3

2

3

600250

500

250

42

65 35

.2210

20 <D

40®

22

—8'/4

5'/2

5/2

SQ/IB

5"/16

1%

1%

%

%

33 lb/1

39 lb/138 lb/1

41VMW133 lb/139 lb/138 lb/1

41 14 lb/1

UL listed with poles in seriesfor 500 Vdc ungroundedbattery applications.

© All UL listed as HACR type.® 10 amp not UL listed.

® UL listed/CSA Certified for10kA @ 347 Vac (TED) and18kA@ 347V (THED). Alsorated 10kA @ 480V but notUL listed.

© UL listed at 10,000 amps.® Discontinued© Also 10,000 amps at 500 Volts

dc. Not UL listed.

500 Vdc on TJJ only.

(continued on page 4-8)

Data subject to change without notice 1999 Issue 4-7