Gas Fireplace Framing Guide
Models, 21 TRV, 564 SS, 564 SS CF, 564 HO, 864 TRV, 864 TRV CF, 854 ST, 864 HO,
3615 HO, 4415 HO, 4415 HO See-Thru, 6015 HO and 4237 Clean Face
Note: For General Reference Only. Aways consult the product Installation Manual for
exact installation information.
Installation Manuals can be found at www.fireplacex.com
4/24/2017
CAUTION: RESTRICTOR ADJUSTMENT REQUIREDThis heater will not operate properly if the vent restrictor is not set for your specific installation. See “Vent configuration” section in the owner’s installation manual.
FIRST FIRE OR START UPYour appliance has been finished with the highest quality paint. Though this paint dries quickly to the touch, it does not cure or become hard until heated up by the appliance during first fire. For this reason the stove will emit light smoke and have a slight odor. Consult your owner’s manual for the complete paint curing instruc-tions. Partially open doors or windows to minimize smoke & odor.
LA PRECAUCIÓN: EL AJUSTE DE RESTRICTOR REQUERIDOEste calentador no funcionará apropiadamente si el restrictor de abertura no está previsto para su instalación específica. See "La configuración de abertura" corte transversal en el manual de instalación del propietario.
EL PRIMERO FUEGO O COMIENZA PARA ARRIBASSu aparato ha estado terminado con la pintura de mejor calidad. Aunque esta pintura se seca rápidamente al tacto, no hace la cura o becomve duro until cali-enta por el aparato durante el primer fuego. Para esta razón la cocina emitirá humo ligero y tendrá un olor leve. Consulte el manual de su propietario para la pintura completa curar las instrucciones. Abra puertas o ventanas parcialmente para minimizar humo & olor.
WARNING:Sheet metal edges can be sharp
ADVERTENCIA:Los bordes de chapa metálica pueden estar afilados
112-10001
564 SS GSR2 SCR Top Vent Configuration
8" (203mm) Diameter Vent
Framing
Guide
TRAVIS INDUSTRIES
HOUSE OF FIRE
12521 HARBOUR REACH DRIVE
MUKILTEO, WA 98275-5458
28-1/2"* 724mm
<16-3/4" 426mm�
* Includes the required 1/2" (13mm)
clearance.
Minimum Framing Dimensions - Rear Vent Configuration
HINT: place the fireplace so the center
line is at least 5" (127mm) from both
vertical framing members at the rear (this
allows the vent to pass through the
framing without modfications)
Minimum 38" (965mm)
Fireplace Enclosure Height
Route the
electrical line to
a position to the
left rear of the
fireplace.
/.�
33-1/2"
851mm
36-1/2"
Included Firestop (required)
Part# 250-00747
Vent Clearances for B" (203mm) dia. Vent:
1" (25mm) to the sides, 1" (25mm) below,
and 4" (102mm) above the vent to
combustibles
.-·ki··Center of Rear Vent
'J / 24-1/4"
616mm
845mm
Weight: 155 Lbs. (70.4kg)
Minimum Framing Dimensions - Top Vent Configuration
Route the electrical line to
a position to the left rear
of the fireplace.
33-1/2'
,.<'"�
851mm
36-1/2"
927mm
Minimum enclosure height= 38' [=
,,,,� 438mm
y�
927mm The on/off switch/thermostat wire (if
used) should be routed to a location
near the right front of the fireplace.
WARNING: A cut-out for the gas line
may be required on the framing. See
the dimensions under "Gas Line
Connection" for details.
Corner Installations - Rear Vent Configuration A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
7"(178mm) Approximate
(varies due to vent installation) __
6" (152mm) Section for 2x6
(51mm X 152mm) Walls
4" (102mm) Section for 2x4
(51mm X 102mm) Walls
45-3/4"
Minimum 1" (25mm) Clearance
564 SS Firestop
Corner Installations - Top Vent Configuration A typical 45" installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)
45-3/4"
Minimum 1/2" (13mm) Clearance
The on/off switch/thermostat wire (if
used) should be routed to a location
near the right front of the fireplace.
564 DF GSR2 SCR Top Vent Configuration
8" (203mm) Diameter Vent
Framing
Guide
TRAVIS INDUSTRIES
HOUSE OF FIRE
12521 HARBOUR REACH DRIVE
MUKILTEO, WA 98275-5458
28-1/2"*
724mm
<16-3/4"
426mm
* Includes the required 1/2" (13mm)
clearance.
Minimum Framing Dimensions - Rear Vent Configuration
HINT: place the fireplace so the center
line is at least 5" (127mm) from both
vertical framing members at the rear (this
allows the vent to pass through the
framing without modfications)
Minimum 38" (965mm)
Fireplace Enclosure Height
Route the
electrical line to
a position to the
left rear of the
fireplace.
/.�
33-1/2"
851mm
36-1/2"
Included Firestop (required)
Part# 250-00747
Vent Clearances for B" (203mm) dia. Vent:
1" (25mm) to the sides, 1" (25mm) below,
and 4" (102mm) above the vent to
combustibles
.-·ki··Center of Rear Vent
'J / 24-1/4"
616mm
= �
845mm
Weight: 155 Lbs. (70.4kg)
Minimum Framing Dimensions - Top Vent Configuration
Route the electrical line to
a position to the left rear
of the fireplace.
33-1/2'
....<'"�851mm
36-1/2"
927mm
Minimum enclosure height= 38 [ /'
17-1/4"
y�
927mm The on/off switch/thermostat wire (if
used) should be routed to a location
near the right front of the fireplace.
WARNING: A cut-out for the gas line
may be required on the framing. See
the dimensions under "Gas Line
Connection" for details.
Corner Installations - Rear Vent Configuration A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
7"(178mm) Approximate
(varies due to vent installation) __
6" (152mm) Section for 2x6
(51 mm X 152mm) Walls
4" (102mm) Section for 2x4
(51mm X 102mm) Walls
45-3/4"
Minimum 1" (25mm) Clearance
564 SS Firestop
Corner Installations - Top Vent Configuration A typical 45• installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply)
45-3/4"
Minimum 1/2" (13mm) Clearance
The on/off switch/thermostat wire (if
used) should be routed to a location
near the right front of the fireplace.
864TRVGSR2
Framing Guide
TRAVIS INDUSTRIES
HOUSE OF FIRE
12521 HARBOUR REACH DRIVE
MUKILTEO, WA 98275-5458 20-5/8'"
Top Vent Configuration 8" (203mm) 0 Vent
Minimum Framing Dimensions - Top Vent Configuration
Route the electrical line to a position to the left rear of the fireplace.
38-1/2"
978mm
41-1/4"
1048mm
Minimum enclosure height= 38-1/2" (978mm)
_.,/-20-3/4"
-� The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace.
Corner Installations - Top Vent Configuration
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
50-1/2"
15-1/2" 394mm
Minimum 112' (13mm) Clearance
---@
Optional "Extra Room
38-1/4
972mm
Weight: 205 Lbs. (93 Kg)
Rear Vent Configuration 8" (203mm) 0 Vent
30·314" 781mm
Minimum Framing Dimensions - Rear Vent Configuration
HINT: place the fireplace so the center
line is at least 5" (127mm) from both vertical framing members at the rear (this
allows the vent to pass through the framing without modfications)
Route the electrical line to
a position to the left rear of the
fireplace.
38-1/2"
��978mm
41-1/4" 1048mm
Minimum enclosure height= 38-1/2" (978mm)
Included Firestop (required)
Part # 93006094
25-3/4"
Vent Clearances 8" (203mm) dia. Vent:
1" (25mm) to the sides, 1" (25mm) below, and 3" (76mm) above the vent to
combustibles . -··Ir _Center of Rear Vent
::r
38"
965mm
30-3/4"
781mm
-.. �ff ,e;;;
� The on/off switchtthermostat wire (if used) should be routed to a location
near the right front of the fireplace.
Corner Installations - Rear Vent Configuration
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
NOTE
7·112'(91mm) Approximate
{varies due to vent installation)
Most installations use:
6'(152mm)Sectiontor
2X 6Walls(51mm X 152mm)
4"(102mm)Sectionlor
2x4 Walls (21mm X 102mm)
(Travis 1198900166)
50-1/2"
TravisFirestop
Minimum 1" {25mm) Clearance (sku 93006094)
864 TRV CF GSR2
Framing Guide
\�-TRAVIS INDUSTRIES
HOUSE OF FIRE
12521 HARBOUR REACH DRIVE
MUKILTEO, WA 98275-5458
Minimum Framing Dimensions
44.75"
1137mm
42.75"
1086mm
7.25"
28-3/4"
22"
• Includes the required1/2" (13mm) clearance.
/' 22-112" (559mm) Flush
22" (572mm) lile over install
Optional Extra Room Power � Heat Duct Connection
/ / I /r 7.75"
44.75" 1137mm
39.25" 997mm
25.675"
The bottom of the face is 0.125" (4mm) above the baseplate.
Corner Installations - Top Vent Configuration
205 Lbs. (93 Kg)
Rear Vent Configuration 8" (203mm) 0 Vent
30.75" 781mm
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
52-1/4" Min
15-1/2" 394mm
Minimum 1/2" (13mm) Clearance
Corner Installations - Rear Vent Configuration
A typical 45° installation uses the framing dimensions shown in the illustration below (NOTE: all clearances still apply).
NOTE:
7-1/2"(191mm) Approximate
(varies due to vent installation)
Most installations use:
6" (152mm) Section for
4" (102mm) Section for
2x4 Walls (51mm X 102mm)
(Travis# 98900166)
Travis Firestop Minimum 1" {25mm) Clearance (sku 93006094)
52-1/4" Min
6015 HO
Framing Guide
\�-TRAVIS INDUSTRIES
HOUSE OF FIRE
12521 HARBOUR REACH DRIVE
MUKILTEO, WA 98275-5458
7-5/8"
-1-�I
350 lbs_
156 Kg_
34-3/4"
883mm
Minimum Framing Dimensions - LP with Minimum Vent (24" Rise)
® 72"
1829mm
72" 1829mm
64-3/4"
1645mm 17" 432mm Flush Install
@ m /" ,_,,,-- 16-1/2" 420mm Extended The fireplace enclosure must be a minimum ----<" (Tile Over) Install
72" (1829mm) tall (do not build into the fireplace enclosure)
Clearances
• Includes the requisite clearance to framing (1 /8"
4mm to rear, 5/8" 16mm to the sides)
1/2"
12mm
(a) Clearance to Side of Fireplace 5/8" (16mm). Do not place insulation in this space.
LP Min. Vent Installations 72" 1829mm
All Other Installations: 66" 1677mm
NOTE: Drywall or other combustible may contact the side of the fireplace in front of the framing. The material must not protrude in front of the fireplace and may be a maximum W' (13mm) thick.
(b) Clearance to Back of Fireplace 1/8" (4mm). Do not place insulation in this space.
(c) When installed, walls in front of the fireplace must be a minimum 3" (77mm) to the side of the fireplace.
Raised Fireplaces
• The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace and vent.
• The base of the fireplace must be a minimum 66H
below the room ceiling.
The firebox opening is approximately 10.375" (264mm) above the base of the fireplace. For a typical raised fireplace of 36" (915mm), place the fireplace on a platform 25.625" (651mm) tall.
LP MIN VENT APPLICATIONS: Framing opening for LP min vent applications is 72" (1829mm). MAKE SURE TO ACCOMMODATE THE REQUIRED FRAMING OPENING.
Corner Installations
Typically 29"
737mm
Minimum 5/8" (16mm) Clearance
----- ---------- ------- ------- --------- -- ---�-
69" Min. 1753mm