Gas Fireplace Framing Guide
2020
Models 21 TRV 3615 HO ProBuilder 42 Linear ProBuilder 24 CF 564 TRV 25K 4415 HO ProBuilder 54 Linear ProBuilder 36 CF 564 TRV 25K CF 4415 HO ST ProBuilder 72 Linear ProBuilder 42 CF 564 HO 6015 HO 864 TRV 31K 4237 Clean Face 864 TRV 31K CF 854 ST
Note: For General Reference Only. Aways consult the product Installation Manual
for exact installation information.
Installation Manuals can be found at www.fireplacex.com
or by scanning the QR code on each page
P a g e | 2
21TRV Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
35-7/8"(912mm)
(204mm)
(216mm)(124mm)
(102mm)
8" External Diameter
13-5/8"*
45°
20-1/8"
See "Gas Line
Requirements" for
Details on the Gas Inlet
7-1/2"*
4-7/8"
Nailing Brackets
4"
Nailing
Bracket
(Framing)
27-1/4"
Rear Vent Configuration
8-1/2"
12-3/8"*
Top Vent Configuration
Lifting Bracket (may
be bent down)34-1/8"(867mm)
(512mm)
(693mm)
(315mm)(191mm)
(346mm)* See "Clearances" and "Framing Dimensions" for details.
NOTE: 1/2" clearance is required to the angled sides and rear of the fireplace.
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
Raised Platform
Optional Hearth
Minimum
57"(1448mm)
Ceiling
If using an elbow directly off the
fireplace, the vent will be centered
41-3/4" (1061mm) above the base o
the fireplace.
20-1/4"(515mm)
48-3/4" Min.(1239mm)
14"(356mm)
Firestop
(required)
Vent Clearances:
1" (26mm) to the sides, 1" (26mm) below, and 3" (77mm)
above the vent to combustibles.
34-1/4"(870mm)
27-1/4"(693mm)
Vent Clearances:1" (26mm) to the sides 1" (26mm) below3" (77mm) above
20.25"(515mm)
(315mm)
34-1/4"
12-3/8"
Firestop
(required)
Center of Rear Vent
34-1/4" (870mm) Min. Enclosure Height
(870mm)
P a g e | 3
564 TRV 25K Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
37-1/4"*
947mm17-1/4"*
439mm
28-1/2"*724mm
30-1/4"768mm
1"25mm
28-3/4"
730mm
18-7/8"
480mm
31-3/4"
794mm
Top Vent Configuration
8" (203mm) Diameter Vent 4-3/4"
121mm
32-3/4"
832mm
* Includes 1/2" (13mm) clearnance - see "Clearances" and "Framing Dimensions" for details.
Left
a' gaucheFrontavant
Right
droit
Reararrie're
37"
940mm
Lifting Handle
37-3/4"
959mm17-1/2"
445mm
37-1/4"
947mm
MIn. Enclosure
39-1/2" 1004mm
Max. 3"
77mm
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
Rear Vent Configuration
8" (203mm) Diameter Vent
Back of Fireplace
24-1/4"
616mm
P a g e | 4
564 TRV 25K CleanFace Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
Rear Vent Configuration
8" (203mm) Diameter Vent
Back of Fireplace
24-1/4"
616mm
* See "Clearances" and "Framing Dimensions" for details.
31-3/4"807mm
38-1/4"972mm
4-3/4"121mm
Top Vent Configuration
8" (203mm) Ø Vent
Framing OpeningLeft
a' gaucheFrontavant
Right
droitReararrie're
Baseplate
The bottom of the face is
1/8" (4mm) above the baseplate.
5-3/4"
147mm
19-3/4"502mm
37"
940mm
7-5/8"
194mm
33-1/8"
842mm
32-5/8"
829mm
19-1/8" *486mm
28-1/2"*724mm
38-3/4"
985mm19-3/8" 493mm Flush Install
18-7/8" 480mm Extended (Tile Over) Install
37-1/4"
947mm
MIn. Enclosure
39-1/2" 1004mm
������������
Max. 3"
77mm
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
P a g e | 5
564 HO NB Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
36-1/2"
928mm
36-3/4"
936mm
17-3/4"
451mm
56"
1423mm
a
36-1/4"
921mm
Weight: 165 Lbs. (74 kg)
18-1/4" *
464mm
28" *712mm
30-1/4"768mm
33-1/4"845mm
1"25mm
28-3/4"
730mm
18-7/8"
480mm
31-3/4"
807mm
8" (203mm) Diameter Vent
6-1/4"
159mm
32-3/4"
832mm
* See "Clearances" and "Framing Dimensions" for details.
Left
a' gaucheFrontavant
Right
droi t
Reararrie're
36-1/4"928mm
Heat Shield
(must be bent vertically after fireplace is in location)
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
(a) Minimum Enclosure Height
P a g e | 6
864 TRV 31K Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
30-3/4"781mm
Back of Fire
place
Rear Vent Configuration
8" (203mm) Ø Vent
Top Vent Configuration
8" (203mm) Ø Vent
38-1/4"
972mm
36-3/4"933mm
41"
1041mm20-3/4"*
528mm*
38-1/4"972mm
28-5/8"*728mm*
37"
940mm
35-1/4"
895mm
7-1/4"
184mm
1"25mm
* See "Clearances" and "Framing Dimensions" for details.
Optional "CoolSmart TV" or
"Power Heat Duct" Connection
Route the electrical line to
a position to the left rear
of the fireplace.
41-1/4"
1048mm
38-1/2"
978mm
20-3/4" (528mm)
Minimum enclosure height = 38-1/2" (978mm)
P a g e | 7
864 TRV 31K CleanFace Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
43"1093mm
45"1143mm
Min. Enclosure48" 1220mm
22" (559mm)Standard Facing*
22-1/2" (572mm) Submerged Facing*
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
38-1/4"972mm
42-3/4"1086mm
7-1/4"
184mm
Optional "CoolSmart TV" or "Power Heat Duct" Connection
22" *559mm
Baseplate
The bottom of the face is 1/8" (4mm) above the
baseplate.
5-5/8"
143mm
25-7/8"
658mm
44-3/4"1137mm
7-3/4"
197mm
39-1/4"997mm
37"
940mm
* See "Clearances" and "Framing Dimensions" for details.
Top Vent Configuration
8" (203mm) Ø Vent
28-5/8"*728mm*
30-3/4"781mm
Back of Fire
place
Rear Vent Configuration
8" (203mm) Ø Vent
P a g e | 8
864 TV 40K Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
Top Vent Configuration
8" (203mm) Ø Vent
38-1/4"
972mm
36-3/4"933mm
41"
1041mm20-3/4"*
528mm*
38-1/4"972mm
28-5/8"*728mm*
37"
940mm
35-1/4"
895mm
7-1/4"
184mm
1"25mm
* See "Clearances" and "Framing Dimensions" for details.
Optional "CoolSmart TV" or
"Power Heat Duct" Connection
41-1/4"1048mm
38-1/2"978mm
20-3/4" (528mm)
Min. enclosure height NG = 62-3/4" (1594mm) Min. enclosure height LP = 74-3/4" (1899mm)
a
a
P a g e | 9
864 TV 40K CleanFace
Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
43"1093mm
45"1143mm
Min. Enclosure48" 1220mm
22" (559mm)Standard Facing*
22-1/2" (572mm) Submerged Facing*
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
38-1/4"972mm
42-3/4"1086mm
7-1/4"
184mm
Optional "CoolSmart TV" or "Power Heat Duct" Connection
22" *559mm
Baseplate
The bottom of the face is 1/8" (4mm) above the
baseplate.
5-5/8"
143mm
25-7/8"
658mm
44-3/4"1137mm
7-3/4"
197mm
39-1/4"997mm
37"
940mm
* See "Clearances" and "Framing Dimensions" for details.
Top Vent Configuration
8" (203mm) Ø Vent
28-5/8"*728mm*
P a g e | 10
864ST Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
������������������������������������������������������������������������������������������������
������������������������������������������������������������������������������������
�������������������������������������������������������������������������������������������������
Side Vent Configuration8" (203mm) Diameter Vent
38-1/4"972mm
27"
686mm
Top Vent Configuration
8" (203mm) Diameter Vent
Weight: 310 Lbs (140.7 kg)
1" 25mm
35-1/4"895mm
������������������������������������������������������������������������������������������������
�������������������������������������������������������������������������������������������������
37"940mm
38-1/4"972mm
39-1/8"994mm
33-7/8"860mm
41-1/2"1054mm
4-3/8"111mm
3-3/8"86mm
Lifting Handle Tabs
These tabs may be used in conjuction with
the lifting handles (98500711) - make sure
to use the required adapters (250-01038)
41" 1041mm
44" 1118mm
Left
a' gauche Frontavant
Right
droitReararrie're
* The 26" (661mm) dimension is based upon 1/2" (13mm)
drywall around the perimeter of the fireplace on both sides. If
using thicker drywall (or other facing), you will need to adjust this
dimension.
44"
1118mm
Minimum 42"(1067mm)
Fireplace Enclosure Height
NOTE:
The shaded framing must be
installed after placing the fireplace
in position.
The framing above the fireplace
interferes with the top of the fireplace.
If using the side vent configuration, do
not install the framing to the left side
(shown in light gray).
38-1/2"
978mm
26" *
661mm
Back
Front Right
Left
P a g e | 11
3615HO Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
40-3/4" *
1036mm *17" *432mm *
54"1372mm
37-3/8"
924mm
1"25mm
* Includes the requisite clearance to framing (1/8" 4mm to rear , 5/8" 16mm to the sides)
10-3/8"
264mm
15-3/4"
401mm
11-1/4"286mm
947mm37-1/4"
210 lbs.96 Kg.
9-3/8"
239mm
34-3/4"883mm
40-3/4"1036mm
17" 432mm Flush Install
54"1372mm
54"1372mm
a
The fireplace enclosure must be a minimum 54”
1372mm tall (do not build into the fireplace
a
P a g e | 12
4415HO Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
48-3/4" *
1239mm *
1150mm45-1/4"
255 lbs.115 Kg.
17" *
432mm *
37-3/8"
924mm
1"25mm
* Includes the requisite clearance to framing
(1/8" 4mm to rear, 5/8" 16mm to the sides)
10-3/8"
264mm
15-3/4"
401mm
11-1/4"
286mm
60"1524mm
9-3/8"
239mm
34-3/4"883mm
The fireplace enclosure must be a minimum
60” tall (do not build into the fireplace a
48-3/4"
1239mm
60"
1524mm
a60"
1524mm
17"
432mm
P a g e | 13
4415 HO ST Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
* Includes the requisite clearance to framing
(5/8" 16mm to the sides)
16-1/4"
413mm
64"1626mm
275 lbs.125 Kg.
1150mm45-1/4"
37-3/8"
924mm
1"25mm
10-3/8"
264mm
15-3/4"
401mm
11-1/4"
286mm
52-1/4" *
1328mm *
34-3/4"
883mm
8-1/8"
207mm
52-1/4"
1328mm
Minimum 64"(1626mm) Fireplace
Enclosure Height
64"
1626mm
16-1/4" (413mm)
P a g e | 14
6015 HO Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
37-3/8"
924mm
1"25mm
* Includes the requisite clearance to framing (1/8"
4mm to rear, 5/8" 16mm to the sides)
1556mm61-1/4"
350 lbs.
156 Kg.
17" *
432mm *
10-3/8"
264mm
15-3/4"
401mm
11-1/4"
286mm
64-3/4" *
1645mm *
All Other Installations:66"1677mm
LP Min. V ent Installations:72"1829mm
72"1829mm
64-3/4"
1645mm
72"LP
LP
NG
NG
1829mm
17" 432mm
66"1677mm
66"1677mm
9-3/8"
239mm
34-3/4"883mm
P a g e | 15
4237 Clean Face Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
37-1/4"947mm
29-1/4"*743mm*
17-1/4"439mm
43-3/4"1112mm
59-1/4"*1505mm*
53-3/4"1366mm
1" 25mm
39"991mm
51-1/8"1299mm
a
b
c
11-3/8"289mm
WEIGHT:
555 lbs.
252 Kg
10-3/4"274mm
d
e
15-5/8"397mm
* Includes 5/8" (16mm) Standoffs
Standard 28-3/4" (731mm)
Flush 29-1/4" (743mm)
54"
(1372mm) 59-1/2" (1512mm)
Minimum
Enclosure
Height
Minimum Enclosure Height – Minimum Vent Configurations or Any System Height Under 10’
-- Minimum enclosure height is 89” (2261mm) Minimum Enclosure Height –Vent Configurations
with System Height 10’ or Higher
-- Minimum enclosure height is 61” (1550mm) -- Vent must pass vertically through the enclosure before an
elbow is placed on the vent.
P a g e | 16
ProBuilder 24CF Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
15-1/4" (388mm)*
24-5/8" (626mm)*
See "Gas Line Requirements for Details
5" (127mm)
Nailing Brackets
CoolSmartKnock-out
Header Shield
Pipe Shield6" (153mm)
1-5/8" (42mm)
41" (1042mm)
1” (26mm)
1/16” (1.6mm)Bottom of trim toBottom of fireplace
20-3/4”
28-1/4”
(528mm)
(718mm)
*Dimensions Includes the standoffs
25-1/8"(639mm)
41-1/4"(1048mm)
15-1/2"(394mm)
53" (1347mm) Minimum Enclosure Height
Maximum Header Depth 3”
8" External Diameter
See " Electrical Requirements” for details
5" (127mm)
35"(889mm)
37-1/4" (947mm)
12-1/4" (312mm)
5-13/16"
9-7/16"
(127mm)
(229mm)
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
P a g e | 17
ProBuilder 54 Linear Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
4-7/8"
15-7/8" *(404mm) *
34-1/2"(877mm)
20-1/2"
(521mm)
1-1/2"
(38mm)
3-3/4"(96mm)
59-1/8" (1502mm)*
57-3/4" (1467m
m)
210 lbs. 95 Kg.
(124mm)
* Includes the required 1/2" clearance to each side and rear of the fireplace.
34-1/2"(877mm)
a
54-1/2"(1385mm)
15-7/8"(404mm)
59-1/8" (1502mm)
Max. 3"
(77mm)
31"
788mm
9-3/4"
248mm
P a g e | 18
ProBuilder 72 Linear Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
4-7/8"
(124mm)
77-1/8" *
(1959mm) *
275 lbs.125 Kg.
15-7/8" *
(404mm) *
43"
(1092mm)
20-1/2"
(521mm)
75-3/4" (1924mm)
1-1/2"
(38mm)
3-3/4"
(96mm)
* Includes the required 1/2" clearance to each side and rear of the fireplace.
77-1/8"(1959mm)
43"(1092mm)
a68"(1727mm)
15-7/8"(404mm)
Max. 3"
(77mm)
31"
788mm
9-3/4"
248mm
P a g e | 19
ProBuilder 36 CleanFace Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
35"889mm
40-7/8"1039mm
* Includes the required 1/2" clearance to each side and rear of the fireplace.
1-1/2"
38mm
36" 915mm
34-1/8"867mm
1-1/16" 27mm3"
77mm
15-1/4"*388mm*
36-5/8"*931mm*
170 lbs. 77 Kg.
24-1/2"*
623mm*
41"(1042mm)
a
61-7/8"(1572mm)
15-3/4"(401mm)
37-1/8" (943mm)
Max. 3"
(77mm)
37-3/8"
950mm
9-3/8"
239mm
The fireplace enclosure must be a minimum 61-7/8” (1572mm) tall. Do not build into the fireplace enclosure.
a
P a g e | 20
ProBuilder 42 CleanFace Framing Guide
12521 Harbour Reach Drive Mukilteo, WA 98275-5458
Scan for Installation Manual
This document is for reference purposes only. Consult the installation manual BEFORE making installation decisions.
40"1016mm
46"1169mm
* Includes the required 1/2" clearance to each side and rear of the fireplace.
1-5/8"42mm
42" 1067
mm
37-7/8"
963mm
1-1/8" 29mm
3"
77mm
17"*
432mm*
42-1/2"*1080mm*
240 lbs. 109 Kg.
28-1/4"*
718mm*
46-1/4"1175mm
a
68"1728mm
17-1/4"439mm
43" 1093mm
Max. 3"77mm
42-3/8"
1077mm
10-3/4"274mm
The fireplace enclosure must be a minimum 68” (1728mm) tall. Do not build into the fireplace enclosure.
a