g schedule.xlsx

40
Jodhpur Vidyut Vitran Nigam Limi G Shedule of 11 KV Line Part -A 1 2 3 4 1.1 221.41 1.4 33.23 2.1 96.71 103.05 Ludhana(17142101) Feeder From 33/11 Amarpura Chapter Code No DESCRIPTION OF WORK UNIT Rate/ Unit Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations. Km. Trimming of tree branches/plants and preparing route approchases for proposed line. Per tree/ plant Excavation of pit in soil (ordinary) to erect various supports and stay sets including stacking of excavated soil from the edge of excavation. (A) Height of poles/R.S.Joist/M.S. Rail Size of pit 2.1.1 8 Mtr/R.S.Joist/M.S. Rail 1.2mx0.6mx1.35 m deep Pit 2.1.2 9 Mtr/ 1.2mx0.6mx1.50 m deep Pit

Upload: sanjay-swami

Post on 06-Dec-2015

216 views

Category:

Documents


4 download

TRANSCRIPT

Jodhpur Vidyut Vitran Nigam Limited

G Shedule of 11 KV Line Part -AQTY Amount

1 2 3 4 5 6

1.1 221.41 30 6642.3

1.4 33.23 30 996.9

2.1

96.71 220 21276.2

103.05 10 1030.5

Ludhana(17142101) Feeder From 33/11 KV GSS Amarpura

ChapterCode No

DESCRIPTION OF WORK UNIT Rate/ Unit

Conducting route survey as per approved route map and pegging of routewith tee off point section point & double pole locations.

Km.

Trimming of tree branches/plants and preparing route approchases for proposed line.

Per tree/plant

Excavation of pit in soil (ordinary) to erect various supports and stay sets including stacking of excavated soil from the edge of excavation.

(A) Height of poles/R.S.Joist/M.S. Rail Size of pit

2.1.1

8 Mtr/R.S.Joist/M.S. Rail 1.2mx0.6mx1.35 m deep Pit

2.1.2

9 Mtr/ 1.2mx0.6mx1.50 m deep Pit

(C)Stay set/Depth of pit

70.76 70 4953.2

5.2

342.48 220 75345.6

498.61 10 4986.1

2.1.7

6'x 5/8" -0.75x0.5x1.35 m Pit

Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the paymentwill be made at the prevailing Discom store issue rates.

(B) IN RURAL AREA

5.2.5

PCC Poles 8 Mtr. Long (200Kg) Nos.

5.2.6

PCC Poles 9 Mtr. Long (400 Kg)/200 Kg Nos.

5.4

267.44 70 18720.8

6.1

35.56 864 30723.84

Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire

5.4.2

6"x5/8" with 7/10 SWG stay wire Nos.

Fixing of cross arms with clamp on erected support as per design. The nuts &bolts will be supplied by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates.

6.1.211 KV cross arms Nos.

6.3

19.24 150 2886

6.10 24.73 210 5193.3

6.14 11.00 2088 22968

Fixing of LT brackets with clamp on erected support as per design. The nuts &bolts will be supplied by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates.

b 2' long Nos.

Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 1nos.disc.& 1set of H/ W ) on terminal point including fixing ofhardware and strips.

Nos.

Fixing of 11 KV pin insulator with pins. Nos.

6.7

101.33 5 506.65

Fixing and assembly of disc.point channel pair with pilot plates&clamps on erected double pole structure as per design. The nuts &bolts are to be provided by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates.

6.7.2 11 KV line Nos.

7.1

1,454.94 30 43648.2

Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate.

(B) IN RURAL AREA

7.1.11ACSR WEASEL km/cond.

7.3

991.02 30 29730.6

Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

(B) IN RURAL AREA

7.3.4

G.I.Earth wire 6 SWG km/wire

6.16

958.74

5 4793.7

Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

(B)G.O. switch . without earthing blade.

6.16.411kv G.O.switch Set

8.1 371.51

130 48296.3

Total 322698.2G Shedule of S/S Part -B

Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discomstore issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom)

Nos

6.16

534.68 5 2673.4

Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

(B)G.O. switch . without earthing blade.

6.16.6

6.35 KV SFU (single phase) Set

6.21

688.23 5 3441.154.00

5.8 3,502 0.15 525.312

Installation testing as per Nigams norm & commissioning of 6.35/.24 KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire/strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates,

16/25 KVA Nos

6.28 (a) Fixing of PG clamp of Weasel /Rabbit Conductor Nos.

Fixing of all type of fabricated material on erected supports with nut & bolts as per approved design & drawing of sub-station.

MT.

8.4

1,085.84

5 5429.2

Total 12069.06G Shedule of LT Part -C

2.1

96.71 40 3868.4

Earthing on 6.35/.24 KV S/S made with 4 nos. MS Rod 20 mm dia,electrodes (black) of 3 Mtr. Length to be driven in earth by mechanical means and jointing through transformers body, 11 KV neutral ,LT neutral & LA with MS flat 40x5 mm ( black 32 mtr.) .The MS Flat will be welded at the top of the electrode.

Per.Trans.

Excavation of pit in soil (ordinary) to erect various supports and stay sets including stacking of excavated soil from the edge of excavation.

(A) Height of poles/R.S.Joist/M.S. Rail Size of pit

2.1.1

8 Mtr/R.S.Joist/M.S. Rail 1.2mx0.6mx1.35 m deep Pit

70.76 20 1415.2

5.2

342.48 40 13699.2

(C)Stay set/Depth of pit

2.1.7

6'x 5/8" -0.75x0.5x1.35 m Pit

Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the paymentwill be made at the prevailing Discom store issue rates.

(B) IN RURAL AREA

5.2.5

PCC Poles 8 Mtr. Long (200Kg) Nos.

5.4

267.44 20 5348.8

6.3

19.24 40 769.6

Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire

5.4.2

6"x5/8" with 7/10 SWG stay wire Nos.

Fixing of LT brackets with clamp on erected support as per design. The nuts &bolts will be supplied by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates.

b 2' long Nos.

6.12 11.00 20 220

6.15 6.87 40 274.8

7.6

2,291.21 4.5 10310.45

Total 35906.44G Shedule of Safe Carriage Part -D

3.1

256.81 10 2568.1

78.90 10 789

Fixing of shackle insulator with hardware. Nos.

Fixing of L T pin insulator with pins. Nos.

Drawing of overhead ABC conductor (Areal bunched cable)on existing erected pole/support including laying. Jointing,stringing complete in all respect.

a1cX25 + 25 Sq mm Km

Safe carriage of PCC poles including loading / un-loading

a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole

3.1.1Within 10 Kms. Pole

3.1.2

Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

Pole

b) 8 Mtr. Long PCC pole

174.67 260 45414.2

78.90 260 20514

3.2

360.89 10 3608.9

76.65 10 766.5

3.1.4Within 10 Kms. Pole

3.1.5

Above 10 Kms. & upto 30 Kms. Add for each Km. or part thereof.

Pole

Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site

3.2.1Within 10 Kms. M.T.

3.2.2

Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

M.T.

3.3

432.53 6 2595.18

92.40 6 554.4

3.6

217.77

5 1088.85

3.6.2

92.40

5 462

Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc.

3.3.1Within 10 Kms. M.T.

3.3.2

Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

M.T.

Safe Carriage of 6.35/0.24 KV Single phase distribution transformer including loading /unloading from store to site.

16/25 KVA

3.6.1Within 10 Kms. Nos.

Above 10 Kms. & upto 30 Kms Add for each Km.or part thereof.

Nos.

4.3

61.06 5 305.3

Total 78666.43G Shedule of Dismentling Part -E

6.2

13.74 484 6650.16

6.14 11.00 484 5324

Total 11974.16Dismentling 60% of Erection 7184.496

Total Of Part A+Part B+Part C+Part D+Part E456524.623

Safe unloading of steel fabricated/ unfabricated conductor drum &other line material.

M.T.

(c ) 6.35/0.24 KV Transformer

4.3.11 25KVA Nos.

Fixing of top hampers with clamp on erected support as per design. The nuts &bolts will be supplied by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates.

6.2.211 KV Top Hampers Nos.

Fixing of 11 KV pin insulator with pins. Nos.

Juniour Engineer(Rural) Assistant Engineer(O&M)JdVVNL,Pilibangan JdVVNL,Pilibangan