fw e3co star technical catalogue
TRANSCRIPT
-
7/28/2019 FW e3co Star Technical Catalogue
1/16
e3
CO - Star
Energy Recovery Unit > Technical Brochure
CFD Optimised Compact Design
Plate Heat Exchanger Efficiency up to 70%
Plug & Play Controls
Indoor or Outdoor Installation
Side-by-side Format
Up to 1.0 m3/s (3600 m3/h)
Full BMS Communication
EC Motors = Low SFP Values: 0.17 w/l/s
Very Low Noise Levels: 30 dBA Breakout*
Integrated Exchanger
-
7/28/2019 FW e3co Star Technical Catalogue
2/16
Description- Sel-supporting casing made o galvanised steel;
- Reduced height allows or easy installation into
ceiling voids;
- Side access or inspection and maintenance;
- Dierential pressure switches mounted on board (or
plug-n-play solution);
- Condensation drainage system, with side mounteddrain point to minimise height
Double Skin Sandwich Panels
- Steel panels thickness is 0.9mm/0.7mm (inner/
outer skins)
- Internal rockwool insulation thickness is 25mm.
Density is 60Kg/m3 - giving a low noise solution,
whilst optimising product weight
Exchanger
- Cross-low aluminium heat exchanger with a thermal
eiciency o up to 70%, has proven perormance asit is Eurovent certiied
Filters
- G4 class or exhaust air and resh air, but higher
ilter grades are available on request
Range
- 6 models rom 300m3/h (0.08 m3/s) up to
3600 m3/h (1.0 m3/s)
Available Configurations
Unit ormat:
Side-by-sidewithinternalby-passnoheater;
Integralpostheateroption;waterorelectric
Pre-heateroption(fittedexternally)
100% By-Pass via motorised Damper
The plate heat exchanger is complete with a bypass
damper which is itted with an actuator, giving a
100% by-pass capability - control is via our integrated
e3co Star control package.
Accessories available on request
Accessories or rost protection - Pre-Heater
ESFP round electric heater with electronic
regulation or duct mounting
Accessories or post-heating: HWLG temperate water coil (45/35 C) available
on request
Accessories or air iltration:
- F7 & F9 Optional ilter (media) is available on
request
Protective accessories:
ESWC Weather cowl c/w bird guard
ESWR External weather protective roo
1
Speciication
Application
High perormance sel regulating ventilation and energy recovery or oice and industrial applications
Thermalefficiencyupto70%(EN308),incompliancewithErP2009/125/ECdirective,usingaEuroventcertiied core.
Airfiltrationandtemperaturecontrolincluded.OndemandventilationisavailableviaPIRorCO2
sensors
Compact, plug n play units complete with integrated BMS communications (MODBUS) and touch screen HMI
Range
Available in 6 models, the e3co Star range covers low rates rom 300 to 3600 m3/h (0.08 to 1.00m3/s).e3co Star range is available in 3 variants:
e3ssential ERU with plate heat exchanger and ilters itted
e3
nhanced ERU with plate heat exchanger, ilters and post heater itted (water or electric)e3lite ERU with plate heat exchanger, ilters and post heater plus pre heater (electric)
A shining example of excellence
-
7/28/2019 FW e3co Star Technical Catalogue
3/162
Speciication
Integrated Exchanger
Fans and Motors
Completewithdirectdrivencentrifugalfans;singleordoubleinletwithforwardcurvedimpellerblades
DirectdrivenviaEC(ElectronicallyCommutated)motorswithhigh-performance,thermalprotectionandbuilt in speed control. EC technology is an ecological solution guaranteeing low energy consumption and
better management and control o the operating point (air lows can be controlled rom 30 to 100 %)
ControlsUserfriendlyinterface-colourtouchscreen
Fastandeasycommissioning-savingtimeonsite
Pre-configuredcontrols.VariableAirVolume,ConstantAirVolumeandConstantPressureoptions
Plugandplaysolution
FullBMScapabilityasstandard,usinganopentableversionoftheMODBUSprotocol-easytointegrate
controls
Heat Exchanger
Cross-flowheatexchangercorewithaluminiumplatesisEUROVENTcertified
Efficiencyuptothan70%(EN308)undertypicaloperatingconditionsasstatedbelow:
Fresh air : -5C/90 % RH Return air 20C/50 % RH
Automaticdefrostfunctionisincludedtoprotecttheheatexchangercorefromtheriskoffreezing.
An optional electric pre-heater (rost heater) is also available as part o rost protection strategy
Filters
Filtersareincludedtoprovideprotectiontoothercomponents(ie,exchanger/fans)Mediaismountedwithinrunnersforeasyfitting/removal
Thee3coStar unit is equipped with G4 grade ilter media itted to the resh air intake and return air
intake. F7 & F9 grade ilter media can be itted i desired and are available as optional accessories
Benefits and Features
IntegratedventilationcontrolcanbeaccessedviaourHMI(displaypanel),whichusestouchscreen
technology, BMS communication uses a MODBUS protocol is via an RS485 port. Alternatively, the built-in
Ethernet port can be used.
100%bypassviaintegraldamperisfittedwithservomotorscontrolledautomaticallybyourbuilt-in
controls, which can provide FREE-COOLING and NIGHT-COOLING unctions
WidechoiceofairflowcontrolscenariosareavailabletooptimiseenergyconsumptionTemperatureprobesareincludedtomonitorsupplyair,exhaustairandexternaltemperature
Anintegratedde-icingsensorisincludedtoprotectthehotwatercoil(whereheaterisfitted)
Electric heaters are complete with a manual reset saety thermostat to protect the electric heater elements
Programmableschedulerfunctionisincludedtoallowuserstocustomisetheirownoperatingschedule
Weekly,dateperiodorsingledatescheduleoptionsareavailable.Externaltimercontrolisalsoavailable
Airpressureswitchesmonitorfiltersandprovideadirtyfilteralarmfunction
Pressureswitchesareusedwithinthecontrolofairflowsforeachfan,andprovidefanfailalarms,both
locally (on the HMI) and to the BMS
Installation
Side-by-Sideformat-designedtobecompact
Lowprofile-suitableformountinginceilingvoids
Indoororoutdoor(whenweatherroofandweathercowlsaccessoriesarefitted)
-
7/28/2019 FW e3co Star Technical Catalogue
4/163
Applications
e3co Stare3co Star
OFFICES
Flkt Woods offer a highperformance product rangecovering all key elements of
the overall ventilation system.Our products are designedto secure the best overallperformance of the system as awhole, considering parameters
such as health and air quality,energy efficiency, noise, firesafety and ease of installation.
EDUCATION
High occupancy levelsduring teaching periodsrequire energy-efficient andcontrollable demand-based
management of air quality andtemperature. The comfort,health and alertness ofstaff and pupils is ensured
during the learning process,but operating costs can beminimised when these facilitiesare unoccupied.
GYMNASIUM/INDOOR SPORTS
Differing types of activityand occupancy mean abroad spectrum of functionalrequirements to ensure efficientremoval of used air and the
introduction of fresh supplies.
Systems need to contain andcontrol the periodic build upof high humidity levels andtemperature.
HEALTHCARE
For a hospital to operate atits maximum potential, it has tohave all systems workingat the optimum. This not
only applies to staff,communications and lifesupport systems, but alsoto pipework, cleaning andventilation systems.
RETAIL/SHOPPING AREAS
With high activity levelsduring the working week andweekends, its important to
make sure that all areas ofventilation are maintained andFlkt Woods has the systemsto achieve all requirements.
APARTMENTS
The purpose of ventilation is toprovide clean good quality airby removing the stale, pollutedair from our homes. The maintask is of course to ensure that
the indoor air is healthy and
safe to breathe. Ventilationtoday is also about energy andsaving energy costs by addingheat recovery to the ventilation
system.
INDUSTRY
Flkt Woods technologyis used widely in industrialprocessing plants and factoriesfor ventilation of work spaces,as vital components in high
tech manufacturing facilities,
and for maintaining delicateenvironments within hightolerance levels inpetrochemical andpharmaceutical plants.
A shining example
of excellence
-
7/28/2019 FW e3co Star Technical Catalogue
5/164
Legislation
Environmental Assessment SchemesIt is now very common for new build projects to be designed to achieve environmental standards such
as those set out in LEED and BREEAM programs. Flkt Woods, with its market leading knowledge and
products in energy recovery, has helped many projects achieve the very highest levels in both of these
schemes.
Energy Performance of Buildings Directive (EPBD)
TheCommissionoftheEuropeanUnionhasrecentlyproposedarevisionoftheEPBD(EnergyPerformance
in Buildings Directive, 2002/91/EC). The objective is to further strengthen the effectiveness and impact
of the existing Directive.
The background to this initiative is to optimise energy usage. It was noted that even in member states
where the existing Directive has been successfully implemented, the Commission still identified an untapped
potential for improvements that could further reduce the energy consumption and CO2
emissions from
buildings.
Building Regulations - Part L for New (A) and Existing Buildings (B)BuildingRegulationsPartLandFoutlinetheneedforahealthierworking/indoorenvironment,withthe
aim of decreasing CO2
emissions. The eco design of our e3co Star range will allow specifiers to create
designs which incorporate the necessary energy usage reductions, whilst still providing precise control of
mechanical ventilation.
European Energy Related Products Directive (ErP)
Directive2009/125/ECwasintroducedbytheEuropeanParliamentin2009withtheaimtoset
requirements for energy-related products being placed on the European Market. The intention is to
contribute to sustainable development by increasing the energy efficiency of those products having
significant environmental impact.
As a result, a series of implementing measures have been introduced and Regulation (EU) No 327/2011
applies to fans driven by electric motors with an electrical input power of between 125 W and 500 kW.
The fans installed in the e3co Star product benefit from EC technology and exceed the requirements of this
regulation.
Further measures relating more generally to domestic ventilation and non-domestic ventilation are yet tobe implemented. This will also have an impact on heat recovery units. The overall performance of the
e3co Star product has been developed with this in mind. In addition, at the heart of the product, its heat
exchanger is Eurovent certified, which provides reassurance that it will deliver performance that has been
independently confirmed.
LEGISLATION
In Europe, all countries now have to design their new buildings to meet energy targets that
are set out in the Energy Performance in Buildings Directive (EPBD). All Flkt Woods Energy
Performance of Buildings Directive solutions are designed to enable full compliance with this
and other directives regarding ventilation and air conditioning.
Being a global manufacturer and supplier makes meeting legislation easier for Flkt Woods. It means that
Flkt Woods must produce solutions at standards that equal the most stringent legislation and guidelines
around. Only by doing this can we ensure that we meet relevant standards within every market.
-
7/28/2019 FW e3co Star Technical Catalogue
6/165
Performance-CompositeCurves
Size 1 Size 2 Size 3 Size 4 Size 5 Size 6
Fan DataMaxInstalledPower:Wattsinput 175 x2 171 x2 465 x2 450 x2 750 x2 1000 x2
Nominal Running speed: rpm 2150 1740 1640 1085 1030 880
Fan Motor FLC: amps (note 1) 1.3 x 2 1.3 x 2 3.0 x 2 2.8 x 2 3.4 x 2 1.7 x 2
FanMotorIPrating 44 44 54 54 54 54
Motor Insulation class B B B B B B
Unit Data
Max Running temperature: C +40 +40 +40 +40 +40 +40
Min Running temperature: C (note 2) -10 -10 -10 -10 -10 -10
ElectricalSupply:V/Ph/Hz(note3) 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 415/3/50
ElectricalSupply:V/Ph/Hz(note4) 230/1/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50
Thermal Recovery Perormance
RecoveredThermalPower:kW(note5) 2.5 3.6 6.1 7.1 11.0 16.0
Air o temperature: C 9.9 10.0 8.2 8.3 9.3 9.4
Condensate rate: l/h 0.5 0.8 0.9 1.1 2.1 3.1
Filters
Supply / Exhaust Air Filter class (note 6) G4 G4 G4 G4 G4 G4
Note 1: Starting currents are the same as ull load currents as EC motors have a sot start unction
Note 2: BasedonPre-Heaterbeingfitted,theminimuminlettemperatureis-5C
Note 3: Electrical supply when no electric heater is itted ie, e3ssential variant
Note 4: Electrical supply when integral electric heater is itted ie, e3
nhanced and e3
lite variantsNote 5: Data relates to nominal airlow rates, which are a mid-curve duty point. Thermal recovery data is based on the ollowing conditions:
External air: -5C @ 90%RH ; Return air: 20C @ 50%RH ; Nominal airlow as deined above
Note 6: F7 and F9 grade ilter media is available as an optional extra. The extra pressure drop, when F7 grade ilter media is itted is approx 40Pa
-
7/28/2019 FW e3co Star Technical Catalogue
7/166
Technical Details
ESFP: Electric Pre-Heater Data (Frost Protection)
Note 7: NominalPowerbasedonnominalairflowperunitNote 8: Stated Unit Max current rating includes Fans FLC and Electric Pre-Heater ratingNote 9: Heater o temperature is based on air entering the pre-heater at -10C at nominal airlow
AirpressurelossforPre-Heaterisbetween2and5Pa
ESHE: Electric Post-Heater Data
Note 10: Stated Unit Max current rating includes Fans FLCandElectricPost-Heaterrating,butexcludestheElectricPre-HeaterratingNote 11: HeaterontemperatureisbasedairofftemperatureofPlateHeatExchangeratnominalairflow Note 12: Heater o temperatures are stated at nominal airlow
AirpressurelossforPre-Heaterisbetween2and5Pa
HWLP: Hot Water Coil (Post Heater) 82C / 71C
Heater o temperature is based on ollowing conditions: nominal air on value o 7C ; Nominal airlowValues reer to the ollowing conditions: Water Flow and Return temperatures o 82/71C; Nominal Airlow Reer to our sales oice (see backpage or contact numbers) or other design options such as alternative low and return temperatures or optional chilled water coil or heatpump system.
HWLG: Hot Water Coil (Post Heater) 45C / 35C
Heater o temperature is based on ollowing conditions: nominal air on value o 7C ; Nominal airlowValues reer to the ollowing conditions: Water Flow and Return temperatures o 45/35C; Nominal airlow
Electro Valve Kits
Actuator Motors used within all Electro Valve Kits are suitable or an electrical supply AC 24 V. Motors are designed to be controlled via aDC 010 V signal to provide proportional control. All actuator motors include an Actuator Return Spring
Size 1 Size 2 Size 3 Size 4 Size 5 Size 6NominalPower:kW(note7) 0.85 1.24 2.1 2.7 3.9 5.6
MaxRatedPower:kW 0.90 1.50 2.1 3.0 5.0 6.0Supply Voltage: V 230 230 230 400 400 400
SupplyPhasePh 1 1 1 3 3 3
ProportionalControl Yes Yes Yes Yes Yes Yes
Pre-Heater Absorbed Current: amps 3.9 6.52 9.13 7.5 12.5 8.64
Max Absorbed Current: amps (note 8) 6.5 9.12 15.13 13.1 19.3 12.04
Duct Connection Diameter 200 250 315 315 400 500
Heater o temperature: C (note 9) -5 -5 -5 -5 -5 -5
Size 1 Size 2 Size 3 Size 4 Size 5 Size 6NominalPower:kW 2.7 3.9 7.0 8.7 12.6 17.9
MaxRatedPower:kW 2.7 4.3 7.0 9.5 13.6 19.0Supply Voltage: V 230 415 415 415 415 415
SupplyPhasePh 1 3 3 3 3 3
ProportionalControl Yes Yes Yes Yes Yes Yes
Max Unit Absorbed Current: amps (note 10) 14.3 8.8 16.1 19.3 26.4 30.8
Heater on temperature: C (note 11) 9.9 10.0 8.2 8.3 9.3 9.4
Heater o temperature: C (note 12) 25 24.1 20.9 23.2 22.7 23.3
Size 1 Size 2 Size 3 Size 4 Size 5 Size 6Number o Rows 1 1 1 1 1 1
NominalPower:kW 2.8 4.7 8.1 9.6 14.1 22.8Heater o temperature: C 23.7 26.2 24.5 24.9 25.1 27.4
AirSidePressureloss:Pa 21 19 29 25 29 41
WaterSidePressureloss:KPa 1.0 5.0 15.0 4.0 9.0 5.0
Water Side Flow Rate : l/s 0.06 0.10 0.18 0.21 0.31 0.50
PipeConn.sizes:DN/inches 15 / 15 / 15 / 25 / 1 25 / 1 25 / 1
ProportionalControl Yes Yes Yes Yes Yes Yes
Size 1 Size 2 Size 3 Size 4 Size 5 Size 6
Valve Model : 1 row (82C / 71C) E SM PV A- 02 5 E SM PV A-0 40 E SM PV A- 10 0 E SM PV A-1 00 E SM PV A- 16 0 E SM PV A- 25 0
Kvs Value (m3/h) 0.25 0.4 1 1 1.6 2.5
PipeConn.sizes:DN 15 15 15 25 25 25
Valve Model : 2 row (45C / 35C) E SM PV A- 02 5 E SM PV A-0 40 E SM PV A- 10 0 E SM PV A-1 00 E SM PV A- 16 0 E SM PV A- 16 0Kvs Value (m3/h) 0.25 0.4 1 1 1.6 1.6
PipeConn.sizes:DN 15 15 25 25 25 25
Size 1 Size 2 Size 3 Size 4 Size 5 Size 6Number o Rows 2 2 2 2 2 2
NominalPower:kW 2.7 4.3 8.1 8.9 14.3 17.4Heater o temperature: C 22.8 24.8 24.6 23.7 25.3 22.6
AirSidePressureloss:Pa 41 37 64 48 65 71
WaterSidePressureloss:KPa 3.0 10.0 5.0 8.0 9.0 15.0
Water Side Flow Rate : l/s 0.06 0.10 0.19 0.21 0.34 0.42
PipeConn.sizes:DN/inches 15 / 15 / 25 / 1 25 / 1 25 / 1 25 / 1
ProportionalControl Yes Yes Yes Yes Yes Yes
-
7/28/2019 FW e3co Star Technical Catalogue
8/167
Sound Levels & Conigurations
ModelSpeeds
% oDuty
Inlet Sound Power Levels (LwA)*Breakout
dB(A)@ 3m
SFPPowerSaving
%
PowerSaving(Watts)
63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHzTotalLwA
Size 1
Boost Max 42 54 50 46 42 43 37 20 57 29 0.88 - -
75% 75% 42 53 48 43 41 40 34
-
7/28/2019 FW e3co Star Technical Catalogue
9/16
-
7/28/2019 FW e3co Star Technical Catalogue
10/169
IndividualPerformanceCurves
0
50
100
150
200
250
300
350
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
S
tatic
Pressure
(Pa)
Volume Flow (m /s)
Boost Mode
75%
60%
45%
Trickle Mode
3
0
50
100
150
200
250
300
350
400
0 0.05 0.1 0.15 0.2 0.25 0.3
Boost Mode
75%
60%
45%
Trickle Mode
Static
Pressure
(Pa)
Volume Flow (m /s)3
e3co Star - Size 1
e3co Star - Size 2
-
7/28/2019 FW e3co Star Technical Catalogue
11/1610
IndividualPerformanceCurves
0
50
100
150
200
250
300
350
400
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
S
tatic
Pressure
(Pa)
Volume Flow (m /s)
Boost Mode
75%
60%
45%
Trickle Mode
3
Boost Mode
75%
60%
45%
Trickle Mode
0
50
100
150
200
250
300
350
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Static
Pressure
(Pa)
Volume Flow (m /s)3
e3co Star - Size 3
e3co Star - Size 4
-
7/28/2019 FW e3co Star Technical Catalogue
12/161
IndividualPerformanceCurves
Boost Mode
75%
60%
45%
Trickle Mode
0
50
100
150
200
250
300
350
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Static
Pressure
(Pa)
Volume Flow (m /s)3
Boost Mode
75%
60%
45%
Trickle Mode
0
50
100
150
200
250
300
350
400
0 0.2 0.4 0.6 0.8 1 1.2
Static
Pressure
(Pa
)
Volume Flow (m /s)3
e3co Star - Size 5
e3co Star - Size 6
-
7/28/2019 FW e3co Star Technical Catalogue
13/1612
Control Solutions
Pa
HS air flow
LS air flow
Air flow
HS constant air flow
LS constant air flow
Air flow
Pa
CAVConstant Air Volume2 Constant Air low Options
VAVVariable Air Volume - Trickle & Boost Strategy2 Air low rates - Low Speed/High Speed
Pa HS air flow
LS air flow
Air flow
COPConstantPressureControl
VAV AQVariable Air Volume plus CO
2sensor
ProportionalairflowcontrolviaCO2sensor
The e3co Star unit has a factory-pre-set controller as standard, which can be used to configure how air flows can
be modulated:
Pa
Constant pressure
Air flow
HMI Screen OverviewAlarm indication, building parameters, operation mode,
temperature, on demand set points and alarm statuscan all be viewed and set via our touch screen HMI
-
7/28/2019 FW e3co Star Technical Catalogue
14/163
Accessories
Filter media upgrade
The Filter Media grade ftted to the supply air side, can be upgraded rom G4 to F7,
or enhanced protection.
Alternatively, The Filter Media grade or the supply air side can be upgraded rom
G4 to F9, or ultimate protection.
e3co-Star units can have a number o accessories ftted:
ESDC ESMPVA
Connectors 3-Port Valve + Actuator
BDER ESMF (set o 4)
Cylindrical Duct Silencers Mounting eet
HMI extension cables ESFP
10m ESC10 Optional
25m ESC25 Pre-Heater
ESPIR BDEP-46-024
PIR Occupancy Sensor Inlet damper
and actuator
e3co-Star units can be installed outside when a weather proo kit is ftted.
ESWR: Weather Roo
ESWC Weather Cowl / Bird GuardFit to inlet and discharge spigots
-
7/28/2019 FW e3co Star Technical Catalogue
15/1614
AccessoriesandProductCodes
1 2 3 4 5
e3co-Star 1 SS-R e3ssential Control optione3nhanced HW/HE
e3lite HW/HE
1 - Thermal Efficiency unit (up to 70%) - completewithautomaticcontrolandCrossFlowPlate Heat Exchanger
2 - Unit Model Code Examples:
1 Unitsize=1(0.12m3/s) e3co-Star 1 6 Unitsize=6(0.90m3/s) e3co-Star 6
3 - Unit Configuration Options:SS-R Side-by-Side format (access and controls on right side)SS-L Side-by-Side format (access and controls on left side)
4 - Unit Version Options:
e3ssential Unit with NO coils fittede3nhanced HW Hotwatercoil(POSTHeater)plusappropriatecontrolsfitted
e3nhanced HE Electricheater(POSTHeater)plusappropriatecontrolsfitted e3lite HW UnitwithElectricPRE-HeaterandhotwaterPOSTHeaterpluscontrols
e3
lite HE UnitwithElectricPRE-HeaterandElectricPOSTheaterpluscontrols
5 - Controls: VAV Variable Air Volume - Trickle and BoostVAV AQ Variable Air Volume - + Air Quality (CO
2) Sensor
CAV Constant Air VolumeCOP ConstantPressure
All motors are EC type
Dia A
Length
Dia B
BDER Silencer Information
Product Coding Guide
Dia A(mm) Length(mm) Dia B mm Code
Attenuation, dB
63Hz 125Hz 250Hz 500Hz 1KHz 2KHz 4KHz 8KHz
200 600 300 BDER-30-020-060 -1 -3 -7 -14 -20 -26 -15 -7
200 900 300 BDER-30-020-090 -2 -3 -9 -24 -30 -36 -20 -9
200 1200 300 BDER-30-020-120 -3 -5 -14 -30 -37 -46 -25 -12
250 600 355 BDER-30-025-060 0 -2 -7 -12 -18 -23 -10 -5
250 900 355 BDER-30-025-090 -2 -2 -8 -19 -25 -32 -12 -6
250 1200 355 BDER-30-025-120 -2 -4 -11 -25 -30 -39 -14 -10
315 600 415 BDER-30-031-060 0 -2 -7 -10 -15 -20 -7 -4
315 900 415 BDER-30-031-090 -1 -2 -7 -16 -22 -24 -10 -6
315 1200 415 BDER-30-031-120 -2 -4 -10 -22 -28 -30 -12 -9
400 900 500 BDER-30-040-090 -1 -2 -6 -13 -19 -16 -8 -6
400 1200 500 BDER-30-040-120 -2 -4 -8 -18 -25 -20 -10 -8
500 900 630 BDER-30-050-090 -1 -1 -5 -11 -14 -12 -9 -6
500 1200 630 BDER-30-050-120 -1 -3 -7 -16 -20 -15 -10 -7
-
7/28/2019 FW e3co Star Technical Catalogue
16/16
Flkt Woods Group - Ventilation Solutions
Flkt Woods LimitedAxial Way, ColchesterEssex, C04 5ZDUNITED KINGDOMTel: +44 (0)1206 222 555
Fax: +44 (0)1206 222 777E-mail: [email protected]
Flkt Woods OyKalevantie 39FI-20520TurkuFINLANDTel: +358 20 442 3000Fax: +358 20 442 3018E-mail: [email protected]
Flkt Woods OyHmeentie 23FI-37800ToijalaFINLANDTel: +358 20 442 3500Fax: +358 20 442 3502E-mail: [email protected]
Flkt Woods ABGesllgatan 17745 39EnkpingSWEDENTel: +46 36 19 30 00Fax: +46 171-240 97E-mail: [email protected]
Flkt Woods ABKung Hans vg12 192 68, SollentunaSwedenTel: +46 (0)771 26 26 26
Fax: +46 (0)8 626 73 10E-mail: [email protected]
Flkt Woods ABFlktvgen 2, Box 84153 22JrnaSWEDENTel: +46 8-551795 00Fax: +46 8-551744 80E-mail: [email protected]
Flkt Woods4 Avenue LaurentCELY-Batiment C - Etage 3Asnieres Sur Seine92600 FRANCETel: +33 1 80 21 07 00Fax: +33 1 80 21 07 00E-mail: [email protected]
Flkt Woods Ventilatoren GmbHAmSportplatz4DE-40882RatingenGERMANYTel: +49 2012 61038 11Fax: +49 2102 61038 18E-mail: [email protected]
Flkt Woods SpAViaPacinotti,28IT-20092, Cinisello BalsamoITALYTel: +39 02 6186 6091
Fax: +39 02 6186 0947E-mail: [email protected]
Flkt Bovent Sp. z o.o.PanattoniParkPruszkwIIul.Poudniowa2,Otarzew05-850OarwMazowieckiPOLANDTel: +48 22 392 43 43Fax: +48 22 392 43 44E-mail: [email protected]
LLC Flkt Industrial& Building Systems23,ul.ProfsojuznayaRU-117418 MoscowRUSSIATel: +7 (495) 589-31-08Fax: +7 (495) 589-31-74E-mail: [email protected]
The Flkt Woods Group is divided into three businesses:
Global Inrastructure and Industry (GII)A leader or Air Movement using ans to improve perormance o equipment and industrialprocesses
Air Climate Solutions (ACS)AworldwideHVACleaderrecognizedbyourcustomersasaproviderofsuperiorAirClimateSolutions combining Indoor Air Quality and Energy Efciency applied to specifed buildings
Ventilation Solutions (VS)A European Ventilation Specialist Servicing our customers with a complete range o
ventilation products ocused on Non residential buildings. For more specifc productinormation or Ventilation Solutions, please visit:
www.vsecatalogue.flaktwoods.com
VS/ESTB-ENG-02/0912
Flkt Woods Limited
Axial Way, Colchester, Essex, C04 5ZD
Tel 01206 222 555 Fax 01206 222 777