PROJECT LOCATION/TYPE FIXTURE SENSORS & CONTROLS www.wattstopper.com 800.879.8585 FS-305/FS-355 Low and Line Voltage Indoor/Outdoor Fixture Integrated Occupancy Sensors Multiple lens choices Low-profile fixture-integrated sensor Product Overview Features IP65 rated for indoor and outdoor wet locations Line and low voltage models Adjustable time delay from 30 seconds to 30 minutes Fixed sensitivity optimized for FS-LxW lens coverages RoHS compliant Light level daylighting feature from 10-120 fc The FS-305 and FS-355 are PIR occupancy sensors that turn lighting on and off automatically based on occupancy. The models are slim, low-profile devices designed for installation inside the bottom of either an indoor or outdoor lighting fixture body. The FS-305 is a low voltage model, while the FS-355 is a line voltage model. Operation Wet Location Rating The FS-305/FS-355 sensors feature the IP65, UL244A and UL508 ratings for indoor or outdoor wet locations when fully assembled and installed with FS-LxW lenses. To obtain this rating, the sensor underwent extremely rigorous testing. The IP65 rating means the sensors are totally protected against dust and low-pressure jets from all directions when installed in an IP65 lighting fixture. Description IP65 and UL 244A and 508 rated (when fully assembled and installed with FS-L2W, FS-L3W, or FS-L4W lenses) Four interchangeable lenses (FS-L2W, FS-L3W, FS-L4W, FS-L6) for mounting between 8’ and 40’ (ordered separately) The FS-305/FS-355 consist of two components, a sensor and a lens. Four lens choices provide flexibility for varying mounting heights. When occupancy is detected within the sensor’s coverage area, the sensor signals lighting to turn on automatically. When occupancy is no longer detected and the time delay has elapsed, lighting automatically turns off. Either model can be wired to control all loads in a fixture, or to provide hi/low control of LED arrays. Both models provide a light level daylighting feature. In the FS-305, the light level feature holds lights off, while in the FS-355, the feature turns lights off if the load is already turned on and adequate daylight exists. Applications FS-305/FS-355 sensors are ideal for damp or wet indoor or outdoor locations. They are suitable for use in parking garages, parking lot luminaires, as well as any outdoor application when installed in a UL-rated outdoor fixture. Adjustable time delay Daylighting light level feature

Upload: nguyenmien

Post on 19-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

PROJECT

LOCATION/TYPE

FIx

tu

re

Se

nS

or

S &

Co

nt

ro

lS

www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5 e30e29 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5 e30

FS-305/FS-355 Low and Line Voltage Indoor/Outdoor Fixture Integrated Occupancy Sensors

Multiple lens choices

Low-profile fixture-integrated sensor

Product Overview

Features

IP65 rated for indoor and outdoor wet locations

Line and low voltage models

• Adjustabletimedelayfrom30secondsto30minutes

• FixedsensitivityoptimizedforFS-LxWlenscoverages

• RoHScompliant

• Lightleveldaylightingfeaturefrom10-120fc

TheFS-305andFS-355arePIRoccupancysensorsthatturnlightingonandoffautomaticallybasedonoccupancy.Themodelsareslim,low-profiledevicesdesignedforinstallationinsidethebottomofeitheranindoororoutdoorlightingfixturebody.TheFS-305isalowvoltagemodel,whiletheFS-355isalinevoltagemodel.

Operation

Wet Location Rating

TheFS-305/FS-355sensorsfeaturetheIP65,UL244AandUL508ratingsforindoororoutdoorwetlocationswhenfullyassembledandinstalledwithFS-LxWlenses.Toobtainthisrating,thesensorunderwentextremelyrigoroustesting.TheIP65ratingmeansthesensorsaretotallyprotectedagainstdustandlow-pressurejetsfromalldirectionswheninstalledinanIP65lightingfixture.

Description

• IP65andUL244Aand508rated(whenfullyassembledandinstalledwithFS-L2W,FS-L3W,orFS-L4Wlenses)

• Fourinterchangeablelenses(FS-L2W,FS-L3W,FS-L4W,FS-L6)formountingbetween8’and40’(orderedseparately)

TheFS-305/FS-355consistoftwocomponents,asensorandalens.Fourlenschoicesprovideflexibilityforvaryingmountingheights.Whenoccupancyisdetectedwithinthesensor’scoveragearea,thesensorsignalslightingtoturnonautomatically.Whenoccupancyisnolongerdetectedandthetimedelayhaselapsed,lightingautomaticallyturnsoff.Eithermodelcanbewiredtocontrolallloadsinafixture,ortoprovidehi/lowcontrolofLEDarrays.Bothmodelsprovidealightleveldaylightingfeature.IntheFS-305,thelightlevelfeatureholdslightsoff,whileintheFS-355,thefeatureturnslightsoffiftheloadisalreadyturnedonandadequatedaylightexists.

Applications

FS-305/FS-355sensorsareidealfordamporwetindoororoutdoorlocations.Theyaresuitableforuseinparkinggarages,parkinglotluminaires,aswellasanyoutdoorapplicationwheninstalledinaUL-ratedoutdoorfixture.

Adjustable time delayDaylighting light level feature

e29 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5 e30

FIx

tu

re

Se

nS

or

S &

Co

nt

ro

lS

e29 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5

Settings, Dimensions &

Mounting

Specifications • FS-355-120-277VAC;60HzLoad@120VAC0-800Wballastorincandescent-Load@277VAC0-1200Wballast

• FS-305-12-24VDC(requiresFS-PPpowerpackforoperation)

• Lightleveldaylightingfeature(10fc-120fc)• Operatingtemperature:-40-131°F(-40-55°C)

• Storagetemperature:-40-176°F(-40-80°C)• OperatingHumidity:20-90%• Weight:1.5oz(42.52grams)• Fiveyearwarranty• IP65,UL244AandUL508rated• ULandcULlisted

Dimensions and Settings

LoadBallastLoad

Line/HotNeutral

FS-355 Line Voltage Wiring

Wiring & Connections

FS-L4Wlens

FS-3x5body

FS-305 Wiring

11524r2

FS-305

Passive Infrared Sensor24V

DC

Connect to Watt Stopper

Class 2 Power Packs

Mod

el#:

Santa C

lara, CA

800.879.8585

Control (BLU)

+24V (RED)

Com (BLK)

N/CGrey

ComViolet

0-10VDC

0-10VDCDimming Ballast

Line VoltageInputs to Ballast

Outputsto Lamps

Com

N/O

RJ45 Plug from FS sensor

Hot

120 - 277 Volts AC

Neutral

Ground

Green OperationLED

Santa Clara, CA800.879.8585

GROUND

NEUTRAL

HOT

COM

N/O

N/C

03500r1

ISO

LA

TE

D R

EL

AY

OU

TP

UT

ST

O L

OA

D

RJ45

TO

SE

NS

OR

Hot

120 - 277 Volts AC

Neutral

Ground

Santa Clara, CA800.879.8585

FS-PP GROUND

NEUTRAL

HOT

COM

N/O

N/C

03500r1

ISO

LA

TE

D R

EL

AY

OU

TP

UT

ST

O L

OA

D

RJ45

TO

SE

NS

OR

LightingLoad

FS-PP

RJ45 Plug from FS sensor

88T9ApplianceControlLISTED

C US

Fixture Sensor Power Pack120-277VAC, 60Hz@120VAC 5A (N/0) 3A (N/C)@277VAC 4.3A (N/0) 2.5A (N/C)

Str

ip G

auge

12-1

8AW

GC

U w

ire o

nly

120-

277V

AC

Inp

ut

88T9ApplianceControlLISTED

C US

Fixture Sensor Power Pack120-277VAC, 60Hz@120VAC 5A (N/0) 3A (N/C)@277VAC 4.3A (N/0) 2.5A (N/C)

Str

ip G

auge

12-1

8AW

GC

U w

ire o

nly

120-

277V

AC

Inp

ut

Neutral

11524r2

FS-305

Passive Infrared Sensor24V

DC

Connect to Watt Stopper

Class 2 Power Packs

Mod

el#:

Santa C

lara, CA

800.879.8585

Control (YEL)

+24V (RED)

Com (BLK)

Ordering Information

1.28” 1.14”

1.38”

2.35”

.88”

Light Level

Time Delay

Mounting

Pub.No.35501rev.10/2010

1.28” 1.14”

1.38”

2.35”

.88”

Light Level

Time Delay

CatalogNo.ColorDescription InputVoltage

FS-305

FS-305-RC

FS-355

FS-355E

FS-PPv2

FS-C2

White

White

White

White

White

White

Fixturemount,passiveinfraredoccupancysensor

Fixturemount,passiveinfraredoccupancysensorwithRJ45connection

Fixturemount,passiveinfraredoccupancysensor

Fixturemount,passiveinfraredoccupancysensor

PowerPack,120/277/347VAC;60Hz

Connectorcable,6”cablewith3flyingleadsatoneendandashieldedRJ45maleconnectoronotherend

12-24VDC

12-24VDC

120/277VAC,60Hz

230VAC,50Hz

PROJECT

LOCATION/TYPE

FIx

tu

re

Se

nS

or

S &

Co

nt

ro

lS

www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5 e30e29 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5 e30

FSP-211 Digital High/Low Passive Infrared Fixture Integrated Outdoor Sensor

Designed for LED fixtures; rated for extreme temperatures and up to 200,000 on/off cycles

Fully adjustable high and low dimmed light levels

Product Overview

Features

Adjustable via handheld wireless configuration tool

Hold off setpoint with automatic calibration option for convenience and added energy savings

• ProvideslinevoltageOn/Offswitchingand0-10VDCdimmingcontrol

• WorkswithballastsorLEDdrivers

• Highandlowmodesfullyadjustablefrom0to10V

• Timedelayfrom5to30minutes

• Optionalcutoffdelay

• Adjustablerampupandfadedowntimes

TheFSP-211mountsinanoutdoorlightingfixtureandprovidesmulti-levelcontrolbasedonmotion.Thesensoralsoincludesaphotocelltomeasuretheambientlightlevel.Itcontrols0-10VDCLEDdriversordimmingballasts,aswellasnon-dimmingballastsand,withanFSP-LxLens,isratedforwetandcoldlocations.Allcontrolparametersareadjustableviaawirelessconfigurationtoolcapableofstoringandtransmittingsensorprofiles.

Operation

Wireless Handheld Configuration Tool

Initialsetupandsubsequentsensoradjustmentsaremadeusingahandheldconfigurationtool(FSIR-100).Thistoolenablesadjustmentofparametersincludinghighandlowmodes,sensitivity,timedelay,cutoffandmore.TheFSIR-100isalsousedtoinitiateautomaticcalibrationoftheFSP-211ambientlightlevelsetpoint.Thesetpointisusedtoholdthecontrolledlightingofforatlowlevelwhenthereissufficientdaylight.Thewirelesstoolstoresuptofivesensorparameterprofilestospeedconfigurationofmultiplesensors.

Description

• Optionaldaylightingsetpointfeaturesautomaticcalibration,orpermitsmanualadjustment

• Configurationtoolstoresfivesensorprofilesforquicksetupandadjustmentofmultiplesensors

• Polycarbonateconstruction;flameretardant,UVresistant,impactresistant,recyclable

• UL244AandUL508;IP66rated(whenfullyassembledandinstalled)foruseinwetlocations

ThesensorrampslightingOntotheselectedHighmodelevelwhenmotionisfirstdetectedandtheambientlightlevelisbelowtheholdoffsetpoint.Afterthesensorstopsdetectingmovementandthetimedelayelapses,lightsfadetotheLowmodelevel.Ifthereisnomotionduringthesubsequentcutofftimedelay,thelightswillturnOff.IfthesensordetectsmotionbeforethelightsturnOff,itrampsthelightlevelbacktoHigh,unlessthedaylightcontributionissufficienttoholdlightingatLow.

Applications

Theslim,low-profileFSP-211isdesignedforinstallationinsidethebottomofalightfixturebody.WhenfullyassembledandinstalledinanIP66-ratedfixture,thesensorandFSP-LxlensesareIP66outdoorrated.Thesensorisidealforareassuchasparkingfacilities,gasstations,pedestrianpathwaysandwarehouses.Achoiceoffourlensesensurescompletecoverageformountingheightsupto40’.

IP66 rated with choice of lenses for wet and outdoor locations, and mounting heights from 8’ to 40’

Adjustable time delay and cut off delay

e29 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5 e30

FIx

tu

re

Se

nS

or

S &

Co

nt

ro

lS

e29 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5www.wattstopper.com8 0 0 . 8 7 9 . 8 5 8 5

Dimensions & Mounting

Specifications • 120/277VAC,50/60Hz -Load@120VAC0-800Wballastorincandescent -Load@277VAC0-1200Wballast• 230VAC,50Hz;Load0-300Wballast• Relayliferating:200,000cycles(120/277VAC);

50,000cycles(230VAC)• Highmode:0-10V;default10V• Lowmode:Off,0-9.8V;default1V• Timedelay:30sec.,5-30min.;default5min.• Cutoffdelay:none,1-60min.1-5hrs.;default1hr.

• Sensitivity:none,low,med,max;defaultmax• Setpoint:none,1-250fc,auto;default4fc• Rampuptime:none,1-60sec.;defaultnone• Fadedowntime:none,1-60sec.;defaultnone• Operatingtemperature:-40-167°F(-40-75°C)• OperatingHumidity:20-90%• Weight:2.8oz(80grams)• IP66,CEcompliant• TUV,ULandcULlisted• Fiveyearwarranty

Sensor Mounting

Wiring Dimming Wiring Diagram

Ordering Information

Sensor Dimensions

Pub.No.38801rev.12/2011

1.63”41.28mm

1.29”32.77mm

1.66”42.18mm

0.9”22.86mm

.65”16.48mm

3.79”96.27mm

1.38”35.05mm

0.9”22.86mm

.65”16.48mm

3.79”96.27mm

1.38”35.05mm

DimmingDriver

LIN

EN

EU

TRA

L

NEUTRAL

GROUND

GRAY (-)

VIOLET (+)

LOAD

Occupancy Sensor

5E4

800.879.8585www.wattstopper.com

1519

5r1

LOA

D

LIN

E

NEU

T(v

iole

t)

(gre

y)

Class 2 Wiring Only18-20 AWG Solid CU Wire Only

230 VAC, 50 Hz1200W max ballast

FSP-211

GRN

D

DIM

-

DIM

+

14-18 AWG Solid CU Wire Only

High/Low PIR

Non-DimmingDriver

LIN

EN

EU

TRA

L

NEUTRAL

LOAD

* GROUND

Occupancy Sensor

5E4

800.879.8585www.wattstopper.com

1519

5r1

LOA

D

LIN

E

NEU

T(v

iole

t)

(gre

y)

Class 2 Wiring Only18-20 AWG Solid CU Wire Only

230 VAC, 50 Hz1200W max ballast

FSP-211

GRN

D

DIM

-

DIM

+

14-18 AWG Solid CU Wire Only

High/Low PIR

Non-Dimming Wiring Diagram

Tightening Nut

FSP-211LEDController

Lens Assembly

TighteningNut

TighteningNut Fixture

Wall

Lens Assembly

0.2” (minimum)FSP-211

Outside Fixture Wall

Inside FixtureWall

RubberGasket

RubberGasket

Tightening Nut

FSP-211LEDController

Lens Assembly

TighteningNut

TighteningNut Fixture

Wall

Lens Assembly

0.2” (minimum)FSP-211

Outside Fixture Wall

Inside FixtureWall

RubberGasket

RubberGasket

*TheFSP-211mustbeproperlygrounded.

TheFSP-211accommodatesfixturewallthicknessupto0.125”(3.18mm).

CatalogNo.ColorDescription InputVoltage

FSP-211

FSIR-100

White

Black

120/277V,50/60Hzor230V,50Hz

(3)1.5VAAAalkalinebatteries

Fixturemount,passiveinfraredmotionsensor

Remotehandheldconfigurationtool