© Dipl.-Ing. Volker Rühle FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS

Upload: others

Post on 19-Jun-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

© Dipl.-Ing. Volker Rühle

FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS

Page 2: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

2

25 % of all daily news are about natural disasters, saving energy and the necessity of reducing our carbon

footprint

HOWEVER: WHAT WE ARE DOING IN REALITY?

DEFINITELY NOT ENOUGH!!!

Page 3: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

3

Industrial Solar Fresnel collectors are designed to generate heat at 130 - 400 °C

250 - 450 °C

130 - 220 °C

90 - 130 °C

40 - 80 °C

„Process Heat“

Large PTC

and Fresnel

Small PTC

and Fresnel

Vacuum tube

CPC collectors

Flat plate collectors

Utility scale power generation

industrial process heat

Industrial process heat solar cooling

commercial water heating

distributed power generation

Solar cooling (single stage)

Low temperature process heat

Domestic water heating, space heating

TECHNOLOGY INTRODUCTION

Page 4: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

4

TECHNOLOGY BASIC PRINCIPLE

Page 5: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

5

Development since 1999

Set up of international subsidiaries, JVs

and cooperations for

• Sales

• Installation

• Assembly

• Procurement

PSE AG

• Spin off from Fraunhofer ISE, Freiburg, founded 1999, staff 68

• CEO Dr. Andreas Häberle, member of ESTTP (European Solar Thermal Technology Panel), DSTTP (German Solar Thermal Technology Platform) and expert for European Commission on CSP related research

• Business units: Solar test stands, solar consulting, solar conferences

• Board: Prof. V. Wittwer, Prof. E. Weber, Prof. J. Luther

Pilot-Experience since 2005 Commercialization since 2007

HISTORY FROM PSE TO MIROXX

Page 6: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

6

Width 7.5 m

Length of one module 4.06 m

Height 4.5 m

11 rows of primary mirrors

1 2 3 4

11 10

6 5

9 8 7

TECHNOLOGY BASIC PRINCIPLE

Page 7: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

7

• Low wind load

• Good weight-spread

• High ground usage factor

• No north-south alignment necessary compared to non-concentrating collectors

Best suited for rooftop installation

ADVANTAGES I FRESNEL VS. PARABOLIC SMALL SIZE

Page 8: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

8

ADVANTAGES I FRESNEL VS. PARABOLIC SMALL SIZE

Page 9: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

9

THERMAL FRESNEL PTC FRESNEL VS. PTC

PEAK POWER GROUND AREA

GROUND AREA GROUND USAGE FACTOR RATIO

88 kWth 264 m2 458 m2 1,73

176 kWth 528 m2 869 m2 1,65

500 kWth 1.500 m2 2.462 m2 1,64

1.0 MWth 3.000 m2 4.923 m2 1,64

10.0 MWth 30.000 m2 48.574 m2 1,62

ADVANTAGES I FRESNEL VS. PARABOLIC SMALL SIZE

Page 10: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

10

• Primary mirrors made of flat glass vs. aluminum (durability, reflectivity)

• Precise temperature and power control

• Less absorber tube per m² allows high quality 70 mm vacuum absorber tube (industrial standard)

• Remote control and monitoring via LAN and internet

Meets industry requirements

ADVANTAGES II

Page 11: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

11

Date: 2008/07/16

0

20

40

60

80

100

120

140

160

180

200

8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00

Time (GMT +1h)

Tem

pera

ture

[°C

]

Po

wer

[kW

]

0

100

200

300

400

500

600

700

800

900

1000

<T>in-collector [°C] <T>out-collector [°C]

<T>ambient [°C] Collector Power [kW]

DNI (right axis) [W/m²]

Precise temperature control

ADVANTAGES II

Page 12: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

12

• Stationary receiver, no twisting of flexible connections

• Concentrated sunlight hits absorber tube always from below

Best suited for direct steam generation

Fresnel

Parabolic

ADVANTAGES III

Page 13: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

13

• Easy cleaning (flat glass/ good access)

• Low water demand for cleaning

• Reliable components

Low O&M

ADVANTAGES IV

Page 14: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

14

• Low wind load

• Good weight-spread

• High ground usage factor

• No north-south alignment necessary

• Stationary receiver, no flexivle connections

• Concentrated sunlight hits absorber tube always from below

Rooftop installation

Industry

Steam

• Easy cleaning (flat glass / good access)

• Low water demand for cleaning

• Reliable components (mirror/tube/drives)

Low O&M

• Primary mirrors made of flat glass vs. aluminum (durability, reflectivity)

• Precise temperature and power control

• Less absorber tube per m² allows high quality 70 mm vacuum absorber tube (industrial standard)

• Remote control and monitoring via LAN and internet

SUMMARY ADVANTAGES

Page 15: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

15

• Heat transfer fluid

– Pressurized water

– Steam

– Thermal oil

• Receiver SCHOTT PTR® 70

– Maximum pressure up to 120 bar (different versions 40, 60, 120 bar)

– Maximum temperature up to 380 °C with thermal oil up to 330 °C with saturated steam or pressurized water

– Thermal loss per m² of primary reflector u1 = 0.00043 W/(m²K²) (according to DLR)

FATCS & FIGURES

Page 16: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

16

Process Heat

Steam

Process heat

Cooling

Absorption Chillers

ORC-Turbines Steam Engines

Process Heat

Low temperature app.

Poly-Generation

APPLICATIONS

Page 17: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

17

MARKET

Page 18: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

18

• Peak load of electricity is already determined by air-conditioning demand in some areas

• At the same time, high solar gains may be utilised

Source: Fraunhofer ISE

MOTIVATION FOR SOLAR COOLING

Page 19: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

19

• Savings in primary energy consumption

• Reduction in peak electricity power demand

• Reduction in CO2 emissions

• Refrigerants without global warming potential; favorable: water

• All-season use of the solar thermal system: heating, cooling, domestic hot water

MOTIVATION FOR SOLAR COOLING

Page 20: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

20

Source: Henning, Fraunhofer ISE

SOLAR COOLING TECHNOLOGY

Page 21: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

21

Double effect

H2O/LiBr

Triple effect

H2O/LiBr

Single effect

NH3/H2O

Temperature lift (max)

25 K 25 K 55 K

Temperature of Cold 5-20°C 5-20°C -20°-20°C

Driving temperature 140-180°C 230-270°C 160-180°C

Max. COP 1,1-1,4 1,6-2,1 0,6-0,7

ABSORPTION CHILLERS

Page 22: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

22

fan

coils

absorpt.

chiller

ice

storage

dry

cooling

SOLAR COOLING WITH NH3-H2O CHILLER

Page 23: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

23

SOLAR COOLING WITH NH3-H2O CHILLER

Page 24: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

24

Collector

•16 modules, 352m² aperture area

•Pressurized water circuit at 16 bar

•Operating temperature 180 °C

Absorption chiller

• 2E water-LiBr

• Cooling capacity 174 kW

SOLAR COOLING WITH 2E WATER-LiBr

Page 25: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

25

• Built in 2007

• Aperture area 352 m²

• Pressurized water circuit at 16 bar

• Outlet temperature 180°C

• Double effect absorption chiller with 50 TR / 174 kW cooling capacity

SOLAR COOLING SYSTEM AT ESI IN SEVILLA

Page 26: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

26

Collector

• 64 modules, 1408m² aperture area

• Pressurized water circuit at 16 bar

• Operating temperature 180 °C

Absorption chiller

• 2E water-LiBr

• Cooling capacity 650 kW

SOLAR COOLING WITH 2E WATER-LiBr

Page 27: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

27

COMBINATION WITH RADIANT COOLING

Page 28: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

28

COMBINATION WITH RADIANT COOLING

0

20

40

60

80

100

120

17 19 21 23 25 27 29 31 33 35

Operative (feeling) temperatur, °C

Lab

ou

r p

rod

ucti

vit

y,

%

Labour productivity as a function of operative (room) temperature

source:

Hettinger, Th.,

Kaminsky, G. ,

Schmale, H.:

Ergonomy at the work place

… which directly influences their labour efficiency

Page 29: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

29

COMBINATION WITH RADIANT COOLING

We all spend 90 % of the day time indoors: at work, commuting and at home

BUT:

WHAT IS COMFORT FOR US?

Page 30: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

30

COMBINATION WITH RADIANT COOLING

Reem Emirates Aluminum HQ, Abu Dhabi, UAE

•Radiant floor cooling 5 000m² •Central Air Handling Unit

Page 31: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

31

COMBINATION WITH RADIANT COOLING

Page 32: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

32

COMBINATION WITH RADIANT COOLING

Page 33: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

33

COMBINATION WITH RADIANT COOLING

GARDENS BY THE BAY SINGAPORE

Page 34: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

34

COMBINATION WITH RADIANT COOLING

Page 35: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

35

COMBINATION WITH RADIANT COOLING

Page 36: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

36

Page 37: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

37

Why radiant cooling with solar cooling • We can use chilled water temperature

above 12 °C • PERFECT FOR ABSORPTION CHILLERS as the

capacity increase with higher chilled water leaving temperature (30 -50 % more capacity)

• Higher comfort, less O&M cost

• SUNTAINABILITY. LETS TAKE THIS RESPONSIBILITY.

COMBINATION WITH RADIANT COOLING

Page 38: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

38

COMBINATION WITH RADIANT COOLING

Page 39: FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS · 2018-12-09 · FRESNEL COLLECTORS FOR SOLAR THERMAL COOLING APPLICATIONS . 2 ... MARKET . 18 • Peak load of electricity

© Dipl.-Ing. Volker Rühle

AL HAWAI TOWER 904 | SHEIKH ZAYED ROAD | P.O.BOX: 29717 DUBAI – UAE | T: +971 4 343 4004 | F: +971 4 321 4530

[email protected] | www. centrogulf.ae

Thank you for your attention.

Dipl.-Ing. Volker Rühle, Director Centrogulf LLC.