foundation fieldbus

26
Foundation Fieldbus Protocol

Upload: sharadonlinemails

Post on 28-Jan-2015

1.403 views

Category:

Education


86 download

DESCRIPTION

foundation fieldbus details, LAS algorithm, HSE fieldbus

TRANSCRIPT

Page 1: Foundation fieldbus

Foundation Fieldbus Protocol

Page 2: Foundation fieldbus

2

Family of industrial computer network protocols

Multiple instruments- Single cable Used for real-time distributed control

What is fieldbus?

IEC 61158Standard

Page 3: Foundation fieldbus

3

Traditional 4-20mA field wiring

Rat’s nest of wires, cables and terminators

Page 4: Foundation fieldbus

4

Trunk Power conditioner Terminators Device couplers

Fieldbus configuration

Page 5: Foundation fieldbus

5

Carries both digital signal and DC power Connects up to 32 field devices to DCS Interface at DCS is called H1 card for FF Wiring and power requirement

◦Minimum device operating voltage : 9V◦Maximum bus voltage : 32V◦Maximum cable length (trunk + spur) : 1900m

Maximum distance◦9500m with 4 repeaters

Trunk

Page 6: Foundation fieldbus

6

Components of Fieldbus power supply.◦Isolation◦Power conditioning◦Current limiting

Fieldbus power supply

24VDC350 mA

Page 7: Foundation fieldbus

7

Two terminators are required on each segment

One at the control room end of cable

Other is in the junctionbox in the field

An extra terminator cause 300 mV drop in signal level

Terminator

Page 8: Foundation fieldbus

8

One or more fieldbus devices can connect tothe segment at one location

Short-circuit protection

Device couplers

Page 9: Foundation fieldbus

9

All communications andpower depend on singletwisted pair wire

If the trunk cable fails it can “take down” all the segments at one time

MooreHawke’s Fault- Tolerant fieldbus system

Redundant fieldbuses

Page 10: Foundation fieldbus

10

Fieldbus topologies

Page 11: Foundation fieldbus

11

System architecture

Page 12: Foundation fieldbus

12

Each layer addsa portion of themessage that istransmitted onthe fieldbus.

System architecture

Page 13: Foundation fieldbus

13

Converts received messages into physicalsignals and vice-versa.

Add, removepreamble, and

delimiters Signals are

encoded usingManchester code

Physical layer

Page 14: Foundation fieldbus

14

31.25 kbps fieldbus signaling◦Device delivers ±10 mA at 31.25 kbps ◦1.0 volt peak-to-peak voltage modulated on top of

the DC supply voltage

Physical layer

Page 15: Foundation fieldbus

15

DLL◦Controls transmission of messages◦Manages access to the fieldbus through LAS◦LAS is a deterministic

centralized bus scheduler

◦Basic device andLink master

Data link layer

Page 16: Foundation fieldbus

16

Scheduled communication◦LAS schedules publisher/subscriber communication◦Scheduled data transfers are done

deterministically.

Data link layer

Page 17: Foundation fieldbus

17

LASAlgorithm

Data link layer

Page 18: Foundation fieldbus

18

Fieldbus access sublayer Communication Relationships

Page 19: Foundation fieldbus

19

FMS services allows user applications to send messages to each other across the fieldbus

FMS describes◦Communication

services◦Message formats◦Protocol behavior

Fieldbus Message Spec.

Page 20: Foundation fieldbus

20

Types of blocks used in user application◦Resource block◦Transducer block◦Function block

User layer

Page 21: Foundation fieldbus

21

Resource block◦It describes characteristics of device.◦Used to configure devices

Function block◦Control system behavior◦FF has sets of standard function blocks.

Transducer blocks◦Calibration date, sensor type

User layer

Page 22: Foundation fieldbus

22

Functionblock

User layer

Page 23: Foundation fieldbus

23

Connecthigherlevel devices

Foundation HSE

Page 24: Foundation fieldbus

24

Wiring ◦98 % reduction in homerun

Control room◦84% reduction in terminations freed up

two third of cabinet space Cost saving

◦Lowers CAPEX and OPEX Commissioning

◦Easy to diagnose equipment problems◦Cut maintenance cost

Justifying fieldbus

Page 25: Foundation fieldbus

25

Questions?

Page 26: Foundation fieldbus

26

Nested messages in HSE