FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS

Assured Automation19 Walnut Avenue | Clark, NJ 07066Tel: 800-899-0553assuredautomation.com

Meets API 607 Edition 3 and 4,Factory Mutual FM 7440

Page 2: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

Order Your Fire-Safe Thermal andElectro-Thermal Shutoff Valves Online!Assured Automation Makes it Easy to Configure, Price, and

Buy at www.fmfiresafe.com

It’s that easy. Get your quote today.

FM Fire-Safe Thermal and Electro-Thermal Shutoff Valves:

Fire-Safe Thermal Shutoff Valves provide automatic emergencyshutdown to stop the flow of flammable or hazardous mediaduring a fire or emergency. The complete ball valve and butterflyvalve assemblies are Factory Mutual (FM) approved. Heat actuated,UL listed thermal links automatically shut off or open the valve atpredetermined temperatures. A unique, removable handle allowsthe valve to be manually operated without affecting the fusiblelinks. The Fire-Safe Shutoff Valve is completely self-contained anduses a spring return so no external electrical power or pneumaticpressure is required for operation.

Two FM/UL-listed links are offered: a thermal and EA electrothermalto connect with a fire alarm panel for remote operation.

Typical Safety Installation Sites:

1. Installed where fuel supply enters a building from an outsidestorage tank. The Fire-Safe can be alarm activated to stop theflow of fuel into the building whenever a fire occurs withinthe building.

2. Installed inside a firewall and alarm activated to pressurize waterinto sprinkler pipes to extinguish fire when the fire occursoutside a building.

Select Ball Valve, Flanged BallValve or Butterfly Valve Body1

Select Size and Material:Carbon Steel or Stainless Steel2

Select Thermal Link andFire Actuation Options3

Save, Print, EmailQuote and Checkout4

Page 3: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

TABLE OF CONTENTS

Fire-Safe Ball Valve Assemblies Thermal.........................................................1Fire-Safe Ball Valve Assemblies Electro-thermal...............................................2 Fire-Safe Butterfly Valve Assemblies Thermal...................................................3Fire-Safe Butterfly Valve Assemblies Electro-thermal.......................................4Multi-Port Ball Valve Assemblies 3-Way............................................................5Spring-Return Handles........................................................................................6Custom Fire-Safe Valve Actuators.....................................................................7Fire-Safe Valves Equipment Uses......................................................................8

FM Fire-Safe valve assemblies and actuators in this catalogue are manufactured by Essex™ Industries

Page 4: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

1 assuredautomation.com

FIRE-SAFE BALL VALVE ASSEMBLIES THERMAL

Thermal Fire-Safe Ball Valve Assemblies are Factory Mutual (FM) approved and combine the characteristics of a manual ball valve with the added safety of an automatic shut-off. Heat actuated, U.L. listed thermal links automatically shut off or open the valve at predetermined temperatures. A unique, removable handle allows the valve to be manually operated without affecting the fusible links.

The thermal fire-safe ball valve assembly, ranging in size from 1/4” to 4”, is available in a variety of metals, including stainless steel, carbon steel, monel, Inconel, hastelloy B & C, alloy 20, copper and brass.

All thermal links are U.L. listed and are available in the following temperatures: 165° F (74º C), 212° F (100º C), 286° F (141º C), 360° F (182º C) and 500° F (260º C).

Fire-Safe Ball Valve Assemblies are available with the following connection configurations: threaded; socket-weld; butt-weld; and flanged.

Drawing Shown: Jamesbury 4000 Series 2” Threaded Thermal Link

Thermal Link Assemblies

"C"

"D""B"

"A""E"

90°

"G"

"F"

A B C D E F G

½” 6.9 1.1 4.3 3.4 7.8 3.3 4.8

¾” 7.0 1.3 4.3 3.9 7.8 3.3 4.8

1” 7.4 1.7 5.0 4.3 7.8 3.3 4.8

1 ½” 10.0 2.1 6.6 5.0 10.0 4.3 5.3

2” 10.2 2.3 7.0 6.0 10.0 4.3 5.3

3” 12.1 3.5 8.0 7.5 10.0 4.3 5.3

4” 12.6 4.0 9.0 9.0 18.0 4.3 5.3

A B D E F G

½” 6.9 1.1 2.1 7.8 3.3 4.8

¾” 7.1 1.3 2.3 7.8 3.3 4.8

1” 7.5 1.7 2.6 7.8 3.3 4.8

1 ¼” 9.7 1.8 2.9 10.0 4.3 5.3

1 ½” 10.0 2.1 3.4 10.0 4.3 5.3

2” 10.2 2.3 3.7 10.0 4.3 5.3

C-TS C-BW

2.6 2.4

3.3 3.4

3.7 4.0

4.3 4.6

4.6 5.5

5.2 6.0

Flanged

Threaded / Socket & Butt-Weld

Page 5: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

2assuredautomation.com

FIRE-SAFE BALL VALVE ASSEMBLIES ELECTRO-THERMAL

"B"

"A"

"C"

"D"

"G""E"

"F"

Electro-thermal Link AssembliesElectro-thermal Fire-Safe Ball Valve Assemblies are Factory Mutual (FM) approved at 165° F (74º C) and are equipped with an electro-thermal linkthat reacts when subjected to heat or to a low-power electrical impulse.

Sizes range from 1/4” to 4”, and are available in a variety of metals, including stainless steel, carbon steel, monel, Inconel, hastelloy B & C, alloy 20, copper and brass.

The operating range is 6-30 VDC or VAC. Requiring less than 0.2 amps of power, .5 ms at 24 V, the unit may be used with similar circuitry such as electrical signaling systems which are activated by heat, smoke, gas, flame-energy, maximum temperature or rate of temperature rise. Units are also available at 212° F (100º C) or 255° F (124º C) that are not U.L. listed.

Fire-Safe Ball Valve Assemblies are available with the following connection configurations: threaded; socket-weld; butt-weld; and flanged.

Drawing Shown: Jamesbury 7000 Series 3” & 4” Flanged Electro-thermal Link

A B C D E F G

½” 6.9 1.1 4.3 3.4 7.8 3.3 4.8

¾” 7.0 1.3 4.3 3.9 7.8 3.3 4.8

1” 7.4 1.7 5.0 4.3 7.8 3.3 4.8

1 ½” 10.0 2.1 6.6 5.0 10.0 4.3 5.3

2” 10.2 2.3 7.0 6.0 10.0 4.3 5.3

3” 12.1 3.5 8.0 7.5 10.0 4.3 5.3

4” 12.6 4.0 9.0 9.0 18.0 4.3 5.3

A B D E F G

½” 6.9 1.1 2.1 7.8 3.3 4.8

¾” 7.1 1.3 2.3 7.8 3.3 4.8

1” 7.5 1.7 2.6 7.8 3.3 4.8

1 ¼” 9.7 1.8 2.9 10.0 4.3 5.3

1 ½” 10.0 2.1 3.4 10.0 4.3 5.3

2” 10.2 2.3 3.7 10.0 4.3 5.3

C-TS C-BW

2.6 2.4

3.3 3.4

3.7 4.0

4.3 4.6

4.6 5.5

5.2 6.0

Flanged

Threaded / Socket & Butt-Weld

Page 6: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

3 assuredautomation.com

A B C D E

3” 14.6 7.5 1.9 2.9 13.0

4” 15.1 9.0 2.1 3.8 13.0

"E"

"C"

"D"

"A"

"B"Drawing Shown: Jamesbury 8” F815L Butterfly Valve Thermal Link

Thermal Fire-Safe Shut-off Butterfly Valve Assemblies include an FM approved actuator on a fire-safe butterfly valve. They are designed to meet the requirements for plant applications where flammable fluids are piped and controlled, such as in the petroleum or process industries. When used in conjunction with high performance butterfly valves having a resilient/metallic seating arrangement, the patented Thermal Actuator (TA Series) has the ability to shut-off in the event of fire or a hazardous situation.

Note: Butterfly Valves cannot be manually operated without removing the spring-loaded canister

Valve Construction Materials:

Body: Carbon Steel or 316 Stainless SteelDisc: 316 Stainless SteelShaft: 17.4 PH or 316 Stainless SteelSeal: TFE/316 Stainless SteelShaft Seal: Graphite

*Other body, disc shaft and seat materials are available.

FIRE-SAFE BUTTERFLY VALVE ASSEMBLIES THERMAL

Approximate Dimensions (inches)

Cv Values (gpm)

Valve Positions

22-½° 45° 67-½° 90°

3” 13.2 36.3 82.5 165

4” 88 200 40032

Page 7: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

4assuredautomation.com

A B C D E

3” 14.6 7.5 1.9 2.9 13.0

4” 15.1 9.0 2.1 3.8 13.0

FIRE-SAFE BUTTERFLY VALVE ASSEMBLIES ELECTRO-THERMAL

"E"

"C"

"D"

"A"

"B"Drawing Shown: Jamesbury 8” F815L Butterfly Valve Thermal Link

Electro-thermal Fire-Safe Shut-off Butterfly Valve Assemblies include an FM approved actuator with an electro-thermal link added to the list of features of the thermal version. The electro-thermal link provides for a means of remote actuation typically achieved using a gas or smoke detector.

Spare actuators can be purchased separately.Assembly and disassembly manuals are available upon request.

Note: Butterfly Valves cannot be manually operated without removing the spring-loaded canister

Valve Construction Materials:Body: Carbon Steel or 316 Stainless SteelDisc: 316 Stainless SteelShaft: 17.4 PH or 316 Stainless SteelSeal: TFE/316 Stainless SteelShaft Seal: Graphite

*Other body, disc shaft and seat materials are available.

Approximate Dimensions (inches)

Cv Values (gpm)

Valve Positions

22-½° 45° 67-½° 90°

3” 13.2 36.3 82.5 165

4” 88 200 40032

Page 8: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

5 assuredautomation.com

MULTI-PORT BALL VALVE ASSEMBLIES 3-WAY

3-Way Multi-port Ball Valve Assemblies are fusiblelink actuators designed for use on 3-way multi-port ballvalves. Capable of reacting to heat, smoke or gas leaks,this system will shut off and vent the air supply to apneumatic spring return actuator allowing it to close largerfire-safe valves.

Choose from one of the flow plans below or call for alternative patterns to meet specific application needs.

Available valve sizes:

1/4”, 3/8”, 1/2”, 3/4”, 1”, 1 1/4”, 1 1/2” and 2”.

Features

• All stainless steel valve construction• 800 WOG rating• Threaded ends• Standard port• Closing temperatures - 165°F (74°C),

212°F (100°C) and 286°F (141°C)

L-Port 90°, FLOW PLAN A

POSITION 1 POSITION 2(OPEN) (FAIL)

T-Port 90°, FLOW PLAN B

POSITION 1 POSITION 2(OPEN) (FAIL)

T-Port 90°, FLOW PLAN C

POSITION 1 POSITION 2(OPEN) (FAIL)

Page 9: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

6assuredautomation.com

SPRING-RETURN HANDLES

Spring-Return Handles provides reliable automatic closing/opening of manual ball valves. The handles may be held in the operating position and the spring will automatically return the valve to the fail position upon release. They can be mounted for either spring-to-close or spring-to-open operation. The spring is housed in a steel enclosure and provides quick cycling of the valve to the fail position upon release of the handle. Sizes range from ¼” to 4” and are available in Threaded, Socket-Weld, Butt-Weld, and Flanged.

SA0001X ¼”-1”

SA0002 1¼”-2”

SA0003X 2½”-4”*

* 4” Valve not available inFull Port configurations.

Available Valve Sizes

Page 10: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

7 assuredautomation.com

CUSTOM FIRE-SAFE VALVE ACTUATORS

Custom Fire-Safe Valve Actuators are available using customer supplied fire-safe valves*. The actuators retain FM approval and can be purchased as an accessory to the fire-safe valve. This maintains equipment consistency throughout the application.

* Valve must be soft seated and either API607 or FM fire rated.**Actuator sizing and price determined by valve torque.***Butterfly valves priced by torque.

Call for more information. Examples shown are for informational purposes only.

Thermal Electro-thermal Applications Ball TA0001X EA0001X ¼”-1”**Ball TA0002X EA0002X 1¼”-2”**Ball TA0003X EA0003X 2½”-4”**

Butterfly TA0003XBF EA0003XBF 2”- 4”***

Page 11: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

8assuredautomation.com

FIRE-SAFE VALVES EQUIPMENT USES

Fire-safe valves and emergency breathing equipment prove useful throughout industrial applications. From process to production, this equipment protects people and products during emergency situations.

Boiler valve/utility room. For prevention of fuel flow from boiler to furnace during an emergency.

Structure Entry. Valve used in two positions to stop flammables from entering structure during emergency.

Interim Storage Tanks. Can be dumped to another location to prevent an explosion.

Off-load Truck. Prevent flammables from being dumped from process lines to the environment.

Plant. Use on process lines to help prevent local damage and loss of equipment.

Page 12: FM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS · PDF fileFM FIRE-SAFE VALVE ASSEMBLIES & ACTUATORS Assured Automation 19 Walnut Avenue | Clark, NJ 07066 ... Meets API 607 Edition 3 and

"C"

"D""B"

"A""E"

90°

"G"

"F"

"B"

"A"

"C"

"D"

"G""E"

"F"

"E"

"C"

"D"

"A"

Assured Automation19 Walnut Avenue | Clark, NJ 07066Tel: 800-899-0553 "B" assuredautomation.com