flow rate indicator / totalizer displays … 1 gd eex ia iic t4 t100°c. ... indication and...
TRANSCRIPT
Features• Displays instantaneous flow rate, total and
accumulated total.• Large 17mm (0.67") digit selection for flow
rate or total.• Selectable on-screen engineering units.• Ability to process all types of flowmeter
signals.• Auto backup of settings and running totals.• Operational temperature -40°C up to +80°C
(-40°F up to 178°F).• Very compact design for panel mount, wall
mount or field mount applications.• Rugged aluminum field mount enclosure
IP67/NEMA4X.• Intrinsically Safe
II 1 GD EEx ia IIC T4 T100°C.• Explosion/flame proof II 2 GD EEx d IIB T5.• Easy configuration with clear alphanumerical
display.• LED backlight option.• Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.• Sensor supply 3.2 - 8.2 - 12 - 24V DC.
Signal inputFlow• Reed-switch.• NAMUR.• NPN/PNP pulse.• Sine wave (coil).• Active pulse signals.• (0)4 - 20mA.• 0 - 10V DC.
Applications• Flow measurement where a local flow rate
indication and totalizer function is requiredwithout re-transmission functionality.Alternative basic models F010 and F011 ormore advanced F013 - F014 - F016 - F110and higher.
FLOW RATE INDICATOR / TOTALIZERDISPLAYS FLOW RATE AND TOTAL
SIMULTANEOUSLY
DA
TAS
HE
ET
F01
2 -
FLO
W R
ATE
IN
DIC
ATO
R /
TO
TALI
ZE
R
1
General informationIntroductionThe F012 is a local indicator to display theactual flow rate, total and accumulated total.The total can be reset to zero by pressing theCLEAR button twice. The eleven digitaccumulated total however can not be reset tozero. A wide selection of options further enhancethis models capabilities, including IntrinsicSafety for hazardous area applications.
DisplayThe display has large 17mm (0.67”) and 8mm(0.31”) digits which can be set to show flow rateand / or totals. On-screen engineering units areeasily configured from a comprehensiveselection. The accumulated total can register upto 11 digits and is backed-up in EEPROMmemory every minute, just as the running total.As the F012 has been designed for fieldmounted applications, a smart display updatefunction has been incorporated. Related to thelower temperatures, the update frequency of theLCD is tuned automatically to achieve areadable display even at -40°C / -40°F.
BacklightFor those applications where readability duringday and night is an issue, a bi-color backlight isavailable. The background color can be set togreen or amber and the intensity can beadjusted from the keyboard. The display is atransflective type, which means that a highcontrast reading is guaranteed in full sunlightas well as during the night. This backlightoption is also available Intrinsically Safe.
ConfigurationAll configuration settings are accessed via asimple operator menu which can be pass-codeprotected. Each setting is clearly indicated withan alphanumerical description, thereforeavoiding confusing abbreviations and bafflingcodes. Once familiar with one F-series product,you will be able to program all models in theseries without a manual. All settings are safelystored in EEPROM memory in the event ofsudden power failure.
Signal inputThe F012 will accept most pulse and analoginput signals for flow or mass flow measurement.The input signal type can be selected by theuser in the configuration menu without havingto adjust any sensitive mechanical dip-switches,jumpers or trimmers. The analog input versionis even available as 4 - 20mA input looppowered display.
Power supplySeveral power supply options are available topower the F012 and sensor. Most popular is ourbattery powered version with a long life lithiumbattery which will last up to five years. Foranalog sensors, a 4 - 20mA loop poweredversion is available as well. A real sensor supplyis offered with the 24V AC/DC or 115 - 230V ACpower supply option.
Hazardous areasFor hazardous area applications, this modelhas been ATEX certified Intrinsically Safe
II 1 GD EEx ia IIC T4 T100°C with anallowed operational temperature of -40°C to+70°C (-40°F to +158°F). IEC, CSA and FMcertification is expected to be available inMay 2006. A flame proof enclosure withATEX certification offers the rating
II 2 GD EEx d IIB T5.
EnclosuresVarious types of enclosures can be selected, allATEX approved. As standard the F012 issupplied in an GRP panel mount enclosure,which can be converted to an IP67 / NEMA 4XGRP field mount enclosure by the addition of aback case. Most popular is our aluminum fieldmount enclosure with IP67 / NEMA 4X rating.Both European or U.S. cable gland entry threadsare available.
Overview application F012
Flowmeterinput
F0122
Dimensions enclosuresAluminum & GRP panel mount enclosure
Aluminum & GRP field / wall mount enclosures
Terminal connections power supply PB/PC - PD - PL - PX
Terminal connections power supply PF - PM
F012 3
P: reed switch / NPN
P: coil
P: namur
P: PNP
A: (0)4 - 20mA
P: active signal
U: 0 - 10V
-
POWER SUPPLY
2 3
FLOWMETER INPUT
1
+
+
-
+
4 5
+I
+U
PB / PC: battery powered(PX is also available: if an external supply is connected, the battery supply will be switched off / on automatically.)
6
BACKLIGHT
+
ZB: 20 - 30V DC
9 10
PL: input loop powered.
Sensor supply:For pulse input
(type P): 8.2V DC
A - PL: 4 - 20mA
+I
+
PD: 16 - 30V DC
PX: 8 - 30V DC
+
For analog input (type A): voltage as
connected to terminal 5.
For analog input (type U): voltage as
connected to terminal 5.
+
P: reed switch / NPN
P: coil
P: namur
P: PNP
A: (0)4 - 20mA
P: active signal
U: 0 - 10V
-
1 2
POWER SUPPLY
GND
- +
PF: 24V AC
PM: 115 - 230V AC
PF: 24V DC
3 4 6 7
FLOWMETER INPUT
5
+
+
- +
+
+
+
+
+
130 mm (5.12")
120
mm
(4.7
2")
31 mm(1.22")
29 mm(1.14")
115 (4.53")
98
(3.8
6")
panel cut-outHB & HC enclosures
75 mm (2.95")
130 mm (5.12")
112 mm (4.40")
60 m
m (2
.36"
)
120
mm
(4.7
2")
M20 x 1,5PG9 PG9
30mm 30mm
22,5
0mm
M20 x 1,5M16 x 1,5 M16 x 1,5
30mm 30mm
22,5
0mm
M20 x 1,5
22,5
0mm
M20 x 1,5 M20 x 1,5
25mm 25mm
22,5
0mm
1/2"NPT
0.9"
1/2"NPT1/2"NPT 1/2"NPT
1.18" 1.18"
0.9"
HA
HM
HN
HO
HD
HP
HE
HT
HF
HU
HG
HZ
HH6 x M12
12mm 12mm
24mm24mm36mm36mm
14m
m17
mm
Ø12
12mm 12mm
24mm24mm36mm36mm
14m
m17
mm
22,5
0mm
30mm 30mm
Ø16 Ø16Ø20
0.9"
Ø22 (0.866")
22,5
0mm
25mm 25mm
Ø20 Ø20
Aluminum GRP
Typical wiring diagram F012-P-PB-(PX)-(ZB)
Typical wiring diagram F012-A-PL-ZB
Typical wiring diagram F012-A-PX-ZB
Typical wiring diagram F012-P-PD-ZB
12
45
Common ground
Signal
TERMINAL CONNECTORSF0 - series
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
8 - 30V DC
+
-Common ground
* Sensor supply voltage for pulse flowmeter type P:Terminal 3: 1.2 - 3.2V DC.
* Sensor supply voltage for analog flowmeter type A / U:Terminal 3: not available.
Type PX:BASIC 8 - 30V DC POWER SUPPLY
(STANDARD)
Main supply
910
Common ground
Backlight supply
Power supply type PX: 8 - 30V DC
Backlight option: type ZB20 - 30V DC
Flowmeter input type A:(0)4 - 20mA
12
34
65
Common ground
Signal
Supply *
TERMINAL CONNECTORSF0 - series
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
16 - 30V DC
+
-Common ground
Supply *
* Sensor supply voltage for pulse flowmeter type P:Terminal 3: 1.2 - 3.2V DC. Terminal 6 with type PD: 8.2V DC.
* Sensor supply voltage for analog flowmeter type A / U:Terminal 3: not available. Terminal 6 with type PD: voltage as connected to terminal 5 (internally linked).
Flowmeter input type P:pulse
Type PD:16 - 30V DC POWER SUPPLY
Main supply
910
Common ground
Backlight supply
Power supply type PD: 16 - 30V DC
Backlight option: type ZB20 - 30V DC
12
34
5
Common ground
Signal
Supply *
TERMINAL CONNECTORSF0 - series
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Common ground
* Sensor supply voltage for pulse flowmeter type P:Terminal 3: 1.2 - 3.2V DC.
* Sensor supply voltage for analog flowmeter type A / U:Terminal 3: not available.
Flowmeter input type P:pulse
Type PB:BATTERY POWERED
Main supply
910
Common ground
Backlight supply Backlight option: type ZB20 - 30V DC
(not used in this example)
Power supply type PX: 8 - 30V DC
(not used in this example)
12
Common ground
Signal
TERMINAL CONNECTORSF0 - series
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Type PL:INPUT LOOP POWERED
910 20 - 30V DC
+
-Common ground
Backlight supply
+
-
8 - 30V DC
Backlight option: type ZB
Flowmeter input type A - PL:Input loop powered 4 - 20mA
Sensor supply: sensor is externally powered.
F0124
Typical wiring diagram F012-P-PF-ZB
Typical wiring diagram F012-A-PM-ZB
Typical wiring diagram F012-A-PF-ZB
Typical wiring diagram F012-P-PM-ZB
01
25
67
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Common ground
Main supply
Flowmeter input type P:pulse
TERMINAL CONNECTORSF0 - series
Type PF:24V AC / DC POWER SUPPLY
Backlight option: type ZBInternally powered.
* Sensor supply voltage for pulse flowmeter type P:Terminal 7: 1.2 - 3.2 - 8.2 - 12 - 24V DC.
* Sensor supply voltage for analog flowmeter type A / U:Terminal 7: 8.2 - 12 - 24V DC.
24V AC
Earth
Power supply type PF: 8 - 24V AC / DC
01
25
67
Common ground
Signal
Supply *
24V DC
+
-
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Common ground
Main supply
TERMINAL CONNECTORSF0 - series
Type PF:24V AC / DC POWER SUPPLY
* Sensor supply voltage for pulse flowmeter type P:Terminal 7: 1.2 - 3.2 - 8.2 - 12 - 24V DC.
* Sensor supply voltage for analog flowmeter type A / U:Terminal 7: 8.2 - 12 - 24V DC.
Backlight option: type ZBInternally powered.
Flowmeter input type A:(0)4 - 20mA
Power supply type PF: 8 - 24V AC / DC
01
25
67
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Common ground
Main supply
TERMINAL CONNECTORSF0 - series
Type PM:115 - 230V AC POWER SUPPLY
* Sensor supply voltage for pulse flowmeter type P:Terminal 7: 1.2 - 3.2 - 8.2 - 12 - 24V DC.
* Sensor supply voltage for analog flowmeter type A / U:Terminal 7: 8.2 - 12 - 24V DC.
Flowmeter input type A:(0)4 - 20mA
N
Earth
Power supply type PM:115 - 230V AC
L1
Backlight option: type ZBInternally powered.
01
25
67
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Common ground
Main supply
TERMINAL CONNECTORSF0 - series
Type PM:115 - 230V AC POWER SUPPLY
* Sensor supply voltage for pulse flowmeter type P:Terminal 7: 1.2 - 3.2 - 8.2 - 12 - 24V DC.
* Sensor supply voltage for analog flowmeter type A / U:Terminal 7: 8.2 - 12 - 24V DC.
N
Earth
Power supply type PM:115 - 230V AC
L1
Flowmeter input type P:pulse
Backlight option: type ZBInternally powered.
F012 5
Hazardous area applicationsThe F012-XI has been ATEX approved byKEMA for use in Intrinsically Safe applications.It is approved according to II 1 GD EEx iaIIC T4 T100°C for gas and dust applicationswith an operational temperature range of -40°C to +70°C (-40°F to +158°F). IEC, CSAand FM approvals are expected to becomeavailable in May 2006. It is allowed to connectup to three I.S. power supplies to power theunit, sensor and backlight. The F012-PD-XIoffers a 8.2V DC sensor supply to power e.g.a Namur sensor or the input voltage topower an analog sensor. An ATEX approvedflame proof enclosure with rating II 2 GDEEx d IIB T5 is available as well. Pleasecontact your supplier for further details.
Certificate of conformity KEMA 05ATEX1168 X
* Sensor supply voltage for pulse flowmeter type P : Terminal 3: 1.2 - 3.2V DC. Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.
HAZARDOUS AREA SAFE AREA
I.S. flowmeter input type: P
pulse
Basic power supply type PX:8 - 30V DC
(not used in this example).
Backlight option: type ZB(not used in this example).
TERMINAL CONNECTORSF0 - series
12
3
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
45
Common ground
Main supply
910
Common ground
Supply backlight
F0126
Configuration example IIA - IIB and IIC F012-P-PC-(PX)-XI-(ZB) - Battery powered unit
Configuration example IIA - IIB and IIC - F012-P-PX-XI-(ZB) - Basic power supply 8 - 30V DC
Configuration example IIA - IIB and IIC - F012-P-PX-XI-ZB - Basic power supply 8 - 30V DC
I.S. flowmeter input type: P
pulse
Backlight option: type ZB(not used in this example).
TERMINAL CONNECTORSF0 - series
12
3
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
45
Common ground
Main supply
910
Common ground
Supply backlight
HAZARDOUS AREA SAFE AREA
+
-
Power supply
For example MTL5025
= max. 30V
= max. 200mA
= max. 1,2W
Uo
Io
Po
Note: above values are safety values. Consult the technical specification for operational values.
Power supply type PX: 8 - 30V DC
* Sensor supply voltage for pulse type P: Terminal 3: 1.2V - 3.2V DC.Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.
I.S. flowmeterinput type: P
pulse
TERMINAL CONNECTORSF0 - series
12
3
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
45
Common ground
Main supply
910
Common ground
Supply backlight
HAZARDOUS AREA SAFE AREA
+
-
Power supply
For example MTL5025
+
-
Power supply
For example MTL5025
= max. 30V
= max. 200mA
= max. 1,2W
Uo
Io
Po
= max. 30V
= max. 200mA
= max. 0,75W
Uo
Io
Po
Note: above values are safety values. Consult the technical specification for operational values.
+
-
Power supply
For example MTL5025
Uo
Io
Po
Power supply type PX: 8 - 30V DC
Backlight option: type ZB
* Sensor supply voltage for pulse type P: Terminal 3: 1.2V - 3.2V DC.Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.
= max. 30V
= max. 150mA
= max. 0,92W
F012 7
F0128
Configuration example IIA - IIB and IIC - F012-P-PD-XI-ZB - Power supply 16 - 30V DC
Configuration example IIA - IIB and IIC - F012-A-PD-XI-ZB - Power supply 16 - 30V DC
I.S. flowmeterinput type: P
pulse
TERMINAL CONNECTORSF0 - series
12
3
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
64
5
Common ground
Main supply
Supply *
910
Common ground
Supply backlight
HAZARDOUS AREA SAFE AREA
+
-
Power supply
For example MTL5025
+
-
Power supply
For example MTL5025
= max. 30V
= max. 200mA
= max. 1,2W
Uo
Io
Po
= max. 30V
= max. 200mA
= max. 0,75W
Uo
Io
Po
Note: above values are safety values. Consult the technical specification for operational values.
Power supply type PD: 16 - 30V DC
Backlight option: type ZB
* Sensor supply voltage for pulse type P: Terminal 3: 1.2V - 3.2V DC. Terminal 6: 8.2V DC.Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.
TERMINAL CONNECTORSF0 - series
HAZARDOUS AREA SAFE AREA
* Sensor supply voltage for analog flowmeter type A / U: Terminal 6: as input voltage terminal 5 (internally linked).Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.
12
Common ground
Signal
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
64
5
Common ground
Main supply
Supply *
910
Common ground
Supply backlight
Power supply type PD: 16 - 30V DC
I.S. flowmeter input - type A: (0)4 - 20mA
Backlight option: type ZB
+
-
Power supply
For example MTL5025
+
-
Power supply
For example MTL5025
= max. 30V
= max. 200mA
= max. 1,2W
Uo
Io
Po
= max. 30V
= max. 200mA
= max. 0,75W
Uo
Io
Po
Note: above values are safety values. Consult the technical specification for operational values.
F012 9
Configuration example IIA - IIB and IIC - F012-A-PL-XI-ZB - Input loop powered
Configuration example IIA - IIB and IIC - F012-A-PX-XI-ZB - Basic power supply 8 - 30V DC
TERMINAL CONNECTORSF0 - series
12
Common ground
Signal
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
910
Common ground
Supply backlight
HAZARDOUS AREA SAFE AREA
+
-
Power supply
For example MTL5025
= max. 30V
= max. 200mA
= max. 0,75W
Uo
Io
Po
Note: above values are safety values. Consult the technical specification for operational values.
+
-
Power supply
For example MTL5025
= max. 30V
= max. 93mA
= max. 0,92W
Uo
Io
Po
I.S. flowmeter input - type A-PL: 4 - 20mA input loop powered.
Backlight option: type ZB
Sensor supply is not available: unit is input loop powered (type PL).Please note: type PL may be used in combination with the battery (type PC). PL will power the unit; the battery will be disabled automatically till power is disconnected.
TERMINAL CONNECTORSF0 - series
12
Common ground
Signal
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
45
Common ground
Main supply
910
Common ground
Supply backlight
HAZARDOUS AREA SAFE AREA
+
-
Power supply
For example MTL5025
+
-
Power supply
For example MTL5025
= max. 30V
= max. 200mA
= max. 1,2W
Uo
Io
Po
= max. 30V
= max. 200mA
= max. 0,75W
Uo
Io
Po
Note: above values are safety values. Consult the technical specification for operational values.
+
-
Power supply
For example MTL5025
= max. 30V
= max. 150mA
= max. 0,92W
Uo
Io
Po
Power supply type PX: 8 - 30V DC
I.S. flowmeter input - type A: (0)4 - 20mA
Backlight option: type ZB
* Sensor supply voltage for analog flowmeter type A / U: not available in this example.Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.
F012
Technical specificationGeneral
DisplayType High intensity reflective numeric and
alphanumeric LCD, UV-resistant.Dimensions 90 x 40mm (3.5" x 1.6").Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits.
Various symbols and measuring units.Refresh rate User definable: 8 times/sec. - 30 secs - off.Option ZB Transflective LCD with bi-color LED-backlight;
green / amber. Intensitiy and color selected trough the keyboard. Good readings in full sunlight and darkness. Also available Intrinsically Safe.
Operating temperatureStandard unit -40°C to +80°C (-40°F to +178°F).Intrinsically Safe -40°C to +70°C (-40°F to +158°F).
Power requirementsType PB Long life Lithium battery - life-time depends upon
settings and configuration - up to 5 years.Type PC Intrinsically Safe long life lithium battery - life-time
depends upon settings and configuration - up to 5 years.
Type PD 16 - 30V DC. Power consumption max. 1 Watt.Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt.Type PL Input loop powered from sensor signal 4 - 20mA
(type A).Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt.Type PX 8 - 30V DC. Power consumption max. 0.3 Watt.Type ZB 20 - 30V DC. Power consumption max. 1 Watt.
With type PF / PM: internally powered.Note PB/PF/PM Not available Intrinsically Safe.Note PF/PM The total consumption of the sensor and backlight
type ZB may not exceed 400mA @ 24V DC.Note For Intrinsically Safe applications, consult the safety
values in the certificate.
Sensor excitationType PB/PC/PX 3.2V DC for pulse signals and 1.2V DC for coil
pick-up.Note This is not a real sensor supply. Only suitable for
sensors with a very low power consumption like coils(sine wave) and reed-switches.
Type PD for pulse signals: 1.2 - 3.2 - 8.2V DC - max. [email protected] DC. For analog signals, the sensor supply voltage is according to the power supply voltage connected.
Type PF / PM With pulse input: 1.2 - 3.2 - 8.2 - 12 and 24V DC - max. 400mA @ 24V DC.With analog input: 8.2 - 12 and 24V DC - max. 400mA @ 24V DC.
Terminal connectionsType Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.
Data protectionType EEPROM backup of all settings. Backup of running
totals every minute. Data retention at least 10 years.Pass-code Configuration settings can be pass-code protected.
CasingGeneralWindow Polycarbonate window.Sealing Silicone.Control keys Three industrial micro-switch keys. UV-resistant
silicone keypad. Option ZS Silicone free ABS enclosure with EPDM and PE
sealings. UV-resisitant polyester keypad. Note This option comes with type HD only.
Aluminum wall / field mount enclosuresGeneral Die-cast aluminum wall/field mount enclosure IP67 /
NEMA 4X with 2-component UV-resistant coating.Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 1064 gr.
Type HA Cable entry: 2 x PG9 and 1 x M20. Type HM Cable entry: 2 x M16 and 1 x M20. Type HN Cable entry: 1 x M20. Type HO Cable entry: 2 x M20. Type HP Cable entry: 6 x M12. Type HT Cable entry: 1 x 1/2" NPT.Type HU Cable entry: 3 x 1/2" NPT.Type HZ Cable entry: no holes.
GRP wall / field mount enclosuresGeneral GRP wall/field mount enclosure IP67 / NEMA 4X,
UV-resistant and flame retardant. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 566 gr.
Type HD Cable entry: no holes.Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.Type HF Cable entry: 1 x Ø 22mm (0.866").Type HG Cable entry: 2 x Ø 20mm. Type HH Cable entry: 6 x Ø 12mm.
Panel mount enclosuresDimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.Panel cut-out 115 x 98mm (4.53" x 3.86") L x H.
Type HB Die-cast aluminum panel mount enclosure IP65 / NEMA 4.
Weight 570 gr.Type HC GRP panel mount enclosure IP65 / NEMA 4,
UV-resistant and flame retardant.Weight 422 gr.
10
F012
Hazardous areaIntrinsically Safe ATEX certification
II 1 GD EEx ia IIC T4 T100°C
CSA C-US/IECEx IEC, CSA and FM approvals are expected to become certification available in May 2006.Ambient -40°C to +70°C / -40° to +158°F.
Explosion proofATEX certification II 2 GD EEx d IIB T5.Type XF Dimensions of enclosure: 300 x 250 x 200mm
(11.8" x 9.9" x 7.9") L x H x D.Weight Appr. 15kg.
EnvironmentElectromagnetic Compliant ref: EN 61326 (1997), EN 61010-1 (1993).compatibility
Signal inputFlowmeter sensorType P Coil / sine wave (minimum 20mVpp or 80mVpp -
sensitivity selectable), NPN/PNP, open collector, reed-switch, Namur, active pulse signals 8 - 12 and 24V DC.
Frequency Minimum 0Hz - maximum 7kHz for total and flow rate. Maximum frequency depends on signal type and internal low-pass filter. E.g. reed switch with low-pass filter: max. frequency 120Hz.
K-Factor 0.000010 - 9,999,999 with variable decimal position.Low-pass filter Available for all pulse signals.Option ZF coil sensitivity 10mVpp.Option ZG coil sensitivity 5mVpp.
Type A (0)4 - 20mA. Analog input signal can be scaled to anydesired range within 0 - 20mA.
Type U 0 - 10V DC. Analog input signal can be scaled to any desired range within 0 - 10V DC.
Accuracy Resolution: 16 bit. Error < 0.01mA / ± 0.05% FS. Low level cut-off programmable.
Span 0.001 / 999,999 with variable decimal position.Update time Four times per second.Voltage drop Type A: max. 2V DC @ 20mA.Voltage drop Type A - PL (loop powered): max. 2.6V DC @ 20mA.Load impedance Type U: 3kΩ.Relationship Linear and square root calculation.Note For signal type A and U: external power to sensor is
required; e.g. type PD.
OperationalOperator functionsDisplayed • Flow rate and / or total.functions • Total and accumulated total.
• Total can be reset to zero by pressing the CLEAR-key twice.
TotalDigits 7 digits.Units L, m3, GAL, USGAL, KG, lb, bbl, no unit.Decimals 0 - 1 - 2 or 3. Note Total can be reset to zero.
Accumulated totalDigits 11 digits.Units / decimals According to selection for total.Note Can not be reset to zero.
Flow rateDigits 7 digits.Units mL, L, m3, Gallons, KG, Ton, lb, bl, cf, RND, ft3, scf,
Nm3, Nl, igal - no units.Decimals 0 - 1 - 2 or 3.Time units /sec - /min - /hr - /day.
Display example - 90 x 40mm (3.5" x 1.6")
11
Specifications are subject to change without notice.
Ordering informationStandard configuration: F012-P-HC-PX-XX-ZX.ordering information: F012 -_ -H _ -P _ -X _ -Z _Flowmeter Sensor input signalA (0)4 - 20mA input.P Pulse input: coil, npn, pnp, namur, reed-switch.U 0 - 10V DC input.Panel mount enclosures - IP65 / NEMA4HB Aluminum enclosure.HC GRP enclosure.GRP field / wall mount enclosures - IP67 / NEMA4XHD Cable entry: no holes.HE Cable entry: 2 x 16mm + 1 x 20mm.HF Cable entry: 1 x 22mm (0.866”).HG Cable entry: 2 x 20mm.HH Cable entry: 6 x 12mm.Aluminum field / wall mount enclosures - IP67 / NEMA4XHA Cable entry: 2 x PG9 + 1 x M20.HM Cable entry: 2 x M16 + 1 x M20.HN Cable entry: 1 x M20.HO Cable entry: 2 x M20.HP Cable entry: 6 x M12.HT Cable entry: 1 x 1/2”NPT.HU Cable entry: 3 x 1/2”NPT.HZ Cable entry: no holes.Power supplyPB Lithium battery powered.PC Lithium battery powered - Intrinsically Safe.PD 16 - 30V DC + sensor supply.PF 24V AC / DC + sensor supply.PL Input loop powered from sensor signal 4 - 20mA (type A).PM 115 - 230V AC + sensor supply.PX Basic power supply 8 - 30V DC (no real sensor supply).Hazardous areaXI Intrinsically Safe.XF EExd enclosure - 3 keys.XX Safe area only.Other optionsZB Backlight. ZF Coil input 10mVpp.ZG Coil input 5mVpp.ZS Silicone free ABS enclosure with EPDM and PE sealings (type HD only).ZX No options.
The bold marked text contains the standard configuration.
Available Intrinsically Safe.
FLUIDWELL bvP.O. Box 65460 AA - Veghel - The NetherlandsTel.: +31 (0)413 343786Fax.: +31 (0)413 [email protected] Internet: www.fluidwell.com C
opyr
ight
: Flu
idw
ell b
v -
2006
- F
WD
SF01
2-12
06-E
N