flow measurement with primary element
TRANSCRIPT
![Page 1: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/1.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Flow measurement with primary element
15/05/2018 Primary element flowrate measurement
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 2: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/2.jpg)
Flow measurement with DP transmitter
2
Measurement of a differential pressure: upstream and downstream of a primary element
Qv = V1S1 = V2S2
• Increase the speed (Qv)
• Increase the dynamical pressure
• Decrease of the static pressure
15/05/2018 Primary element flowrate measurement
![Page 3: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/3.jpg)
C = pressure lost coefficient determined by experimental test
E = approach coefficient 𝐸 = 1/ 1 − 𝑏4
ε = expansion coefficient
d = internal primary element diameter
D = Internal pipe diameter
Primary Element
3
Volumetric flowrate is depending of the differential pressure square root made by the primary element
15/05/2018 Primary element flowrate measurement
HP LP
![Page 4: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/4.jpg)
Flow type
4
LAMINAIRE TURBULENT
So it is necessary to ensure to have the right straight length
15/05/2018 Primary element flowrate measurement
Laminar Turbulent
![Page 5: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/5.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
What are the Primary Element ?
15/05/2018 Primary element flowrate measurement
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 6: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/6.jpg)
Primary elements
15/05/2018 Primary element flowrate measurement6
Pitot Tube
Diaphragm
Venturi and micro-venturi Nozzles
V-ConeWedges
Orifice plate
![Page 7: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/7.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Pitot Tube
15/05/2018 Pitot tube
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 8: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/8.jpg)
Principle
15/05/2018 Pitot Tube 8
Low cost solution for measurement in large diameter pipes or ducts
❖ Low permanent pressure lost – energy lost use is minimal
❖ Robust construction – long service life and virtually impossible to wear out
❖ Negligible wear – long term stability with Zero drift or degradation
Negative pressurePositive pressure
Flow direction
Average point for the
speed
Pitot tubes generates a differential pressure proportional
to the dynamic pressure
![Page 9: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/9.jpg)
Pitot Tube
15/05/2018 Pitot Tube9
Single point 5 RB
Average 5RD
Pitot Tubes with FKC
for Flow measurement and corrected Flowrate (Nm3/h)
![Page 10: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/10.jpg)
Pitot tube characteristics
• Rangeability: 10 : 1
• Accuracy ± 1 % of real flow rate
• Maxi Temperature: 500°c
• DN50 to DN1500
• 316 L
• Be careful with loaded fluids➔ fooling !
15/05/2018 Pitot Tube10
![Page 11: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/11.jpg)
❖ 5RD Average
16/09/2015 Pitot Tube 11
What kind of fluids?
Water Gas Steam
❖ 5RD Single point
Gas
![Page 12: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/12.jpg)
16/09/2015 Pitot Tube 12
What kind of pipe?
Circular pipe Rectangular pipe
To know the internal diameter
and the thickness of the pipeTo know the internal length, height and
thickness of the duct
IMPORTANT: Specify the pitot tube
localization: in the length or height
Be careful if the pipe has a thermal protection !!!
![Page 13: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/13.jpg)
Pitot tube accuracy with the flowrate
15/05/2018 Pitot Tube13
Pitot tube only
Be careful to the minimal flowrate !!!
FKC11 and 22 Accuracy50-100% of output 0,10% span20-50 % of output 0,25% span10-20% of output 0,50% span
Pressure transmitter only
![Page 14: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/14.jpg)
Straight length
15/05/2018 Pitot tube14
No straight length, degraded accuracy !!!
5RB pitot tube is more
sensitive ot the straight lenght
than 5RD pitot tube !! !
![Page 15: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/15.jpg)
URV transmitter : 1,74
FKC11 et FKC22Flowrate DP Transmitter accuracy Measurement accuracy
T/h or m3/h mbar % Span mbar %1200 1,74 0,1 0,00174 0,1
900 0,98 0,1 0,00174 0,2
800 0,77 0,25 0,00435 0,6600 0,44 0,25 0,00435 1,0500 0,3 0,5 0,0087 2,9400 0,19 0,5 0,0087 4,6
300 0,11 0,5 0,0087 7,9200 0,05 0,5 0,0087 17,4
100 0,01 0,5 0,0087 87,0
Exemple of accuracy
15/05/2018 15
Accuracy = Transmitter + Pitot + all element of the measurement chain
: Imprecision (Pitot (2%) + transmitter) : 10 % around at 300 m3/h
Pitot Tube
![Page 16: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/16.jpg)
Application
• Biogaz
• Boiler
• Incineration plant
• Cogeneration plant
15/05/2018 Pitot Tube 16
• Compressor and HVAC
• Flow gas or atmospheric emission flue gas measurement
• Oxygenation of water treatment plant’s aerating tank
![Page 17: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/17.jpg)
Measurement of steam flowrate with a pitot tube
17
Condensat
chamber
Pitot Tube
Pitot Tube 15/05/2018
![Page 18: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/18.jpg)
Pitot tube with remote transmitter
18
Pitot tube with a remote
erection
Pressure transmitter
Differential pressure transmitter
15/05/2018 Pitot Tube
![Page 19: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/19.jpg)
15/05/2018 Primary element flowrate measurement 19
Absolute
pressure XTR
Temperature
measurement
Differential
pressure XTR
Pitot tube
Biogaz flow measurement with Pitot tube
![Page 20: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/20.jpg)
Automatic unclogging cabinet system – Pitot tube
15/05/2018 Pitot tube20
Air injection with programming time in the 5RD and 5RB pitot tubes
For loaded fluids
![Page 21: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/21.jpg)
Velocity profile
15/05/2018 Pitot Tube21
Can be made by FEF
Standard NF X10-112
To determine the velocity profile
inside the pipe
Check and/or verify the
precise localization of the
pitot tube inside the pipe …
![Page 22: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/22.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
V-Cone
15/05/2018 V-Cone
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 23: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/23.jpg)
Technical datasheet – V-Cone
15/05/2018 V-Cone23
❖ Liquid, gas and steam measurement
for high loaded and high viscosity
fluid. For example: waste water, oil…
❖ Straight length very low (3D/1D)
❖ Flow profile very stable, High accuracy
(< 1% of the flow) and reputability: 10:1
❖ No corrosion of the cone by abrasion
❖Many FCX working for « subsea »
flowrate measurement (oil&gas
application)
❖Measurement in 2 ways
![Page 24: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/24.jpg)
Performance
15/05/2018 V-Cone24
• Accuracy: to +/- 0.5% of rate
• Turndown: from 10:1
• Repeatability: +/- 0.1%
![Page 25: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/25.jpg)
Accuracy
15/05/2018 V-Cone25
❖ All and each V-Cones are supplied with standard water calibration.
❖ +/-0.5% Accuracy for all V-Cones calibrated over the total Re Range
of the application for a 10:1 turndown.
❖ +/-1.0% Accuracy for all V-Cones operated above 20,000 Re but not
calibrated over the total Re application range.
❖Meters operated below Re 8,000 may require a high viscosity
calibration.
❖ Stated accuracy is valid through all the Turndown of the meter.
![Page 26: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/26.jpg)
Wafer-Cone
15/05/2018 V-Cone26
![Page 27: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/27.jpg)
V-Cone
15/05/2018 V-Cone27
![Page 28: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/28.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Orifice plate
15/05/2018 Orifice plate
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 29: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/29.jpg)
Technical specification: Orifice plate
15/05/2018 Orifice plate29
• Accuracy: 1,5 % or flow (ISO 5167)• Rangeability: 6 : 1• Excellent repeatability
• Connection clogging because of high loaded fluid
• High pressure lost
![Page 30: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/30.jpg)
Integrated orifice
• Measurement of low flowrate (liquid or gas)
• Assembly with flange upon request
Orifice plate3015/05/2018
![Page 31: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/31.jpg)
Orifice plate3115/05/2018
Steam flowrate with orifice plate
![Page 32: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/32.jpg)
Corrected steam flowrate with orifice plate
15/05/2018 Orifice plate32
Be careful to the straight length !
![Page 33: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/33.jpg)
Straight length: Orifice plate
15/05/2018 Orifice plate33
Straight length according to ISO 5167
![Page 34: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/34.jpg)
34
Diaphragm installation
Orifice plate15/05/2018
![Page 35: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/35.jpg)
Diaphragm installation
15/05/2018 Diaphragm35
![Page 36: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/36.jpg)
Exemple of installation
36 Diaphragm15/05/2018
![Page 37: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/37.jpg)
Exemple of installation
37 Diaphragm15/05/2018
![Page 38: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/38.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Venturi and micro venturi
15/05/2018 Venturi and micro venturi
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 39: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/39.jpg)
Venturi & Micro-venturi, the difference
15/05/2018 Venturi and micro venturi39
Venturi Micro venturi
![Page 40: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/40.jpg)
Technical datasheet - Venturi
15/05/2018 Venturi and micro venturi40
• Accuracy: 1,5% of maximal flow
• Rangeability: 6 : 1
• Low pressure lost
• Recommended for high viscosity and high loaded fluid
![Page 41: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/41.jpg)
Straight length – Venturi
15/05/2018 Venturi and micro venturi41
Straight length according to ISO 5167
![Page 42: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/42.jpg)
Technical datasheet - Micro venturi
• Rangeability: 6 : 1
• Accuracy: 1,5 % of flow
• Low pressure lost
15/05/2018 Venturi and micro venturi42
![Page 43: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/43.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Nozzle
15/05/2018 Nozzle
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 44: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/44.jpg)
Technical datasheet - Nozzle
15/05/2018 Nozzle44
❖ Recommanded for high Reynolds number > 50000, for exemple : steam with
high temperature. DO NOT USE THIS PRIMARY ELEMENT FOR SLUDGE
❖ Accuracy: 1,5 % of flow (ISO 5167)
❖ Rangeability: 6 : 1
![Page 45: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/45.jpg)
Straight length - Nozzle
15/05/2018 Nozzle45
Straight length according to ISO 5167
![Page 46: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/46.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Wedges
15/05/2018 Wedges
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 47: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/47.jpg)
Flowrate measurement with a wedges
15/05/2018 Wedges47
Measurement for high viscosity or high loaded fluid
![Page 48: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/48.jpg)
Technical datasheet - Wedges
15/05/2018 Wedges48
❖ Accuracy: < 1% of maximal flow
❖ Repeatability: ± 0,2%
❖ Correct measurement with a low
Reynolds (<300)
❖ Low pressure lost
❖ Measurement for fluid with high
viscosity
❖ Dual measurement
Oil&Gas application
![Page 49: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/49.jpg)
Straight length – Wedges
15/05/2018 Wedges49
![Page 50: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/50.jpg)
Exemple of measurement with a wedges
15/05/2018 Wedges50
![Page 51: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/51.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Conclusion
15/05/2018 Primary element flowrate measurement
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com
![Page 52: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/52.jpg)
Some advises…
• DP transmitter must be in square root or the PLC
Do not put the square root function on both
• The range of the pressure transmitter is according to the primary element calculation so to the flowrate
The URV is link to the maximum flowrate calculated
• Caution during the installation of the primary element (for example not in the right direction)
• BE careful to the clogging of the primary element
5215/05/2018 Primary element flowrate measurement
![Page 53: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/53.jpg)
53
Primary element comparison
DIAPHRAGM VENTURI NOZZLE PITOT
Pressure lost High pressure lost Low pressure lost Low pressure lost Low pressure lost
Accuracy According to a standard According to a standard According to a standardNo standard. Accuracy at 1,5%
(ISO 5167) arround 1,5% (ISO 5167) arround1,5% (ISO 5167) around 1,5%Very dependant of the flow
ErectionNeed to cut the pipe and weld the flange
Need to cut the pipe and weld the flange
Need to cut the pipe and weld the flange
Easy. No big works: No weld etc..
DN limitsAccording to the standard: DN> 50mm
According to the standard: DN between 200 mm and 1200 mm
According to the standard: DN between 50 mm and 630 mm
According to the standard: DN between 25mm and 6000 mm
Conclusion Frequent use due to its priceMedian use because of the cost of the erection
Rare. Very expensive for erection
Very often. Erection and price very interesting
Primary element flowrate measurement 15/05/2018
![Page 54: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/54.jpg)
Primary element flowrate measurement 54
Nozzle Orifice plate (single hole)
Orifice plate (multi hole)
V-Cone Pitot Micro-venturi
Venturi
Price +++ ++ + ++++ + +++ +++
Efficiency on loaded fluid
+ + + +++ + ++ ++
Straight length +++ ++++ + + ++ + +++
High viscosity + + + ++++ + ++ +++
Erection parameters
++ ++ ++ ++ + +++ ++
Primary element comparison
+ Low
++++ High
15/05/2018
![Page 55: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/55.jpg)
Straight length - Comparison
15/05/2018 Primary element flowrate measurement 55
Example: Pipe with 1 elbow downstream and upstreamBeta : 0,50
Primary Element
Pitot * Orifice plateSingle hole
Orifice plateMulti hole *
Venturi Micro venturi *
Nozzle Wedge V-Cone
Straightlength
7D/4D 22D/6D 2D/2D 9D/3,5D 3D/2D 14D/6D 12D/4D 3D/1D0D/0D1
* Not included to ISO51671 According to manufacturer McCrometer
![Page 56: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/56.jpg)
Important technical point !!
• Technical information datasheet
• Minimum required technical data:
❖Internal diameter, thickness, thermal protection or other
❖Nominal Pressure
❖Nominal temperature
❖Fluid type
❖Maximal REAL flowrate !
❖Density if non standard
• Check straight length
• Check connection and erection
• DP pitot tube calculation note15/05/2018 Primary element flowrate measurement 56
![Page 57: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/57.jpg)
15/05/2018 Primary element flowrate measurement 57
Selection table – Primary element
New table to be filled and
sent to FEF
![Page 58: Flow measurement with primary element](https://reader031.vdocuments.mx/reader031/viewer/2022012013/6158d9275da7646d961ba76f/html5/thumbnails/58.jpg)
Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet
63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99
WEB www.fujielectric.fr - Email [email protected]
Thank You
15/05/2018 Primary element flowrate measurement
Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ
(732) 560-9410
americas.fujielectric.com