RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS F4545.01 STC 62 IIC 53 CONSTRUCTION Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York PB Truss L/360 Open Web Truss @ 24" O.C. RSIC-1 Installed @ 24"x48" Clark Dietrich 087F125-18 Furring Channel @ 24" O.C. National Gypsum Gold Bond Fire-Shield C Gypsum Board STC 62 Test Number F4545.01 IIC 53 ©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710 RSIC® is a registered Trade Mark of PAC International, LLC. STC IIC 1 Hour See www.UL.com World Leader in Noise Control Solutions

Upload: others

Post on 23-Nov-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

RSIC ACOUSTIC ASSEMBLY

FLOOR CEILING ASSEMBLY

DIRECT FIX TO WOOD OPEN WEB TRUSS

F4545.01 STC 62 IIC 53

CONSTRUCTIONHacker Industries, Inc. Firm-Fill Gypsum ConcreteHacker Industries, Inc. Firm-Fill SCM-250 Sound Control MatOriented Strand Board SheathingGuardian Faces R-13 Fiberglass InsulationYork PB Truss L/360 Open Web Truss @ 24" O.C.RSIC-1 Installed @ 24"x48"Clark Dietrich 087F125-18 Furring Channel @ 24" O.C.National Gypsum Gold Bond Fire-Shield C Gypsum Board

STC 62Test Number F4545.01 IIC 53

©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710RSIC® is a registered Trade Mark of PAC International, LLC.

ST

C

IIC

1 HourSee www.UL.com

World Leader in Noise Control

Solutions

Page 2: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

53

F4545.01-113-11-R2

ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E 90 AND ASTM E 492

Rendered to

HACKER INDUSTRIES, INC.

Series/Model: FIRM-FILL® Brand Gypsum Concrete and FIRM-FILL® SCM-250

Sound Control Mat - Bare

Specimen Type: Open Web Truss - 457 mm

Overall Size: 3023 mm by 3632 mm

STC 62

IIC

Test Specimen Identification:

Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete

Subfloor Underlayment: 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat

Subfloor: 18.8 mm Oriented Strand Board Sheathing

Insulation: 88.9 mm Guardian Faced R-13 Fiberglass Insulation

Truss: 457.2 mm York PB Truss L/360 Open Web Truss

Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips

Ceiling Isolation: 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel

Ceiling: 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Reference should be made to Intertek-ATI Report F4545.01-113-11 for complete test specimen

description. This page alone is not a complete report.

130 Derry Courtaa

York, PA 17406aa

p. 717.764.7700

f. 717.764.4129www.archtest.com · www.intertek.com/building

Page 3: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

F4545.01-113-11-R2

Page 1 of 4

Acoustical Performance Test Report

HACKER INDUSTRIES, INC.

1600 Newport Center Drive, Suite 275

Newport Beach, California 92660

Report F4545.01-113-11

Test Date 02/02/16

Report Date 03/03/16

Revision Date 04/29/16

Project Scope

Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct

airborne sound transmission loss and impact sound transmission tests. The complete test data is

included as attachments to this report. The client provided the test specimen. The specimen was

constructed on the date of testing.

Test Methods

The acoustical tests were conducted in accordance with the following standards. The equipment

listed in the attachments meets the requirements of the following standards.

ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound

Transmission Loss of Building Partitions

ASTM E 413-10, Classification for Rating Sound Insulation

ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound

Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine

ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)

ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in

Sound Insulation Test Methods

Test Procedure

All testing was conducted in the VT test chambers at Intertek-ATI located in York,

Pennsylvania. The microphones were calibrated before conducting the tests.

The airborne transmission loss test was conducted in accordance with the ASTM E 90 test

method using the single direction method. Two background noise sound pressure level and five

sound absorption measurements were conducted at each of five microphone positions. Four

sound pressure level measurements were made simultaneously in both rooms, at each of five

microphone positions.

130 Derry Courtaa

York, PA 17406aa

p. 717.764.7700

f. 717.764.4129www.archtest.com · www.intertek.com/building

Page 4: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

F4545.01-113-11-R2

Page 2 of 4

Test Procedure (Continued)

The impact sound transmission test was conducted in accordance with the ASTM E 492 test

method. Two background noise sound pressure level, two sound pressure level measurements

with the tapping machine operating at each position specified by ASTM E 492, and five sound

absorption measurements were conducted at each of five microphone positions.

The air temperature and relative humidity conditions were monitored and recorded during all

measurements.

Test Conditions

Source Room Receive Room

Average Temperature 16.6°C Average Temperature 15.5°C

Average Relative Humidity 57% Average Relative Humidity 54%

Test Calculations

The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated

in accordance with ASTM E 413 and ASTM E 989, respectively.

Test Specimen Materials and Installation Details

MaterialDimensions

(mm)

Thickness

(mm)Manufacturer and Series Quantity

Average

Weight

Gypsum Concrete3632 by 3023 25.4

Hacker Industries, Inc. FIRM-

FILL® Brand10.98 m² 47.85 kg/m²

Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a

closed cell foam perimeter isolation. The product name was specified by client.

Sound Control Mat1219 by 3023 6.4

Hacker Industries, Inc. FIRM-

FILL® SCM-25010.98 m² 0.49 kg/m²

Note: The SCM was installed as per manufacturer's specifications with seams overlapping and taped.

Oriented Strand

Board Sheathing

1219 by 2438 18.8 N/A 10.98 m² 13.82 kg/m²

Note: The OSB was adhered to the trusses with Loctite PL 400 Subfloor adhesive. It was attached

with 9D nails on 203 mm centers along perimeter and 305 mm centers along trusses.

Fiberglass Insulation2962 by 584 88.9 Guardian Faced R-13 10.98 m² 1.33 kg/m²

Note: Installed in the cavity between trusses flush with the OSB. Hanger wire was used to keep

insulation secure on 305mm

Open Web Truss88.9 by 2933.7 457.2 York PB Truss L/360 7 m² 19.05 kg/m²

Note: Installed on 610 centers using JUS414 hanger brackets.

Isolation Clips76.9 by 35.6 28.0 PAC International RSIC-1 Classic 24 clips 0.06 kg/clip

Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.

Page 5: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

F4545.01-113-11-R2

Page 3 of 4

Test Specimen Materials and Installation Details (Continued)

MaterialDimensions

(mm)

Thickness

(mm)Manufacturer and Series Quantity

Average

Weight

Furring/Hat Channel3657.6 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m

Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center.

Gypsum Board1219 by 3023 15.9

National Gypsum Gold Bond®

Fire-Shield C™10.35 m² 10.74 kg/m²

Note: Fastened to furring channels on 305 mm centers with 25.4 mm type S screws. Seams finished

with joint compound. Perimeter sealed with acoustical caulk.

Comments

The total weight of the floor/ceiling assembly was 957.2 kg. Intertek-ATI will store samples of

the test specimen for four years. A drawing of the test specimen is included in the attachments.

Intertek-ATI will service this report for the entire test record retention period. Test records,

such as detailed drawings, datasheets, representative samples of test specimens, or other

pertinent project documentation, will be retained by Intertek-ATI for the entire test record

retention period. The test record retention period ends four years after the test date.

This report does not constitute certification of this product nor an opinion or endorsement by

this laboratory. It is the exclusive property of the client so named herein and relates only to the

specimen tested. This report is intended to help in the client’s quality assurance program, but it

does not represent a continuous or exhaustive evaluation of the specimen tested or of other

products or materials that were not evaluated. The statements and data provided herein do not

constitute approval, disapproval, certification, or acceptance of performance or materials.

This report may not be reproduced, except in full, without the written approval of

Intertek-ATI.

FOR INTERTEK-ATI:

David M. Dacheux Jordan Strybos

Technician II - Acoustical Testing Project Manager - Acoustical Testing

Attachments (6 Pages): This report is complete only when all attachments are included.

* Stated by Client/Manufacturer

N/A - Non Applicable

Page 6: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

F4545.01-113-11-R2

Page 4 of 4

Revision Log

Revision Date Page(s) Description

R0 03/03/16 N/A Original Report Issue

R1 03/10/16 Cover page "Bare" added to Series/Model listing

R2 04/29/16 Page 2 Clip spacing installation note corrected

This report produced from controlled document template ATI 00629(d), Revised 02/09/15.

Page 7: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

F4545.01-113-11-R2

Attachments

Instrumentation

Instrument Manufacturer Model ATI NumberDate of

Calibration

Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *

Microphone Calibrator Norsonic 1251 Y002919 07/15

Receive Room Microphone Scantek 378B20 63748 05/15

Receive Room Microphone PCB Piezotronics 378B20 63744 05/15

Receive Room Microphone PCB Piezotronics 378B20 63745 05/15

Receive Room Microphone PCB Piezotronics 378B20 63746 05/15

Receive Room Microphone PCB Piezotronics 378B20 63747 05/15

Receive Room Environmental

IndicatorComet T7510

63810

63811

10/15

10/15

Source Room Microphone PCB Piezotronics 378B20 63738 04/15

Source Room Microphone PCB Piezotronics 378B20 63739 04/15

Source Room Microphone PCB Piezotronics 378B20 63740 04/15

Source Room Microphone PCB Piezotronics 378B20 63742 04/15

Source Room Microphone Scantek 378B20 63741 04/15

Source Room Environmental

IndicatorComet T7510 63812 11/15

Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 11/15

* The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

Test Chambers

VT Receive Room Volume 155.77 m³

VT Source Room Volume 190 m³

Page 1 of 6

Page 8: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

F4545.01-113-11-R2

AIRBORNE SOUND TRANSMISSION LOSS

ASTM E 90

Test Date 02/02/16

Data File No. F4545.01

Client Hacker Industries, Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250

Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm

York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Specimen Area 10.98 m²

Technician David M. Dacheux

FreqBackground

AbsorptionSource Receive Specimen

TL

95% Number

SPL SPL SPL Confidence of

(Hz) (dB) (m²) (dB) (dB) (dB) Limit Deficiencies

50 43.5 26.8 100 66 32 4.60 -

63 43.9 23.0 100 64 35 3.60 -

80 51.8 17.4 109 68 40 4.80 -

100 38.7 12.6 106 67 40 2.10 -

125 39.3 9.6 106 67 41 1.30 5

160 28.2 9.0 108 65 44 1.50 5

200 24.8 10.1 105 58 49 1.20 3

250 27.6 10.6 104 53 53 1.00 2

315 24.1 10.3 106 54 54 0.70 4

400 21.4 8.2 105 50 57 0.50 4

500 23.6 7.7 105 48 60 0.40 2

630 22.3 7.4 106 47 63 0.40 0

800 22.4 7.3 105 45 63 0.20 1

1000 23.6 7.1 105 43 65 0.50 0

1250 23.1 7.2 105 41 67 0.40 0

1600 19.7 7.3 105 39 69 0.30 0

2000 12.1 8.6 104 39 68 0.40 0

2500 8.1 9.5 103 36 69 0.50 0

3150 7.3 10.8 104 33 72 0.40 0

4000 6.5 12.3 105 31 74 0.50 0

5000 6.2 14.9 104 28 76 0.50 -

6300 6.6 19.9 98 18 78 0.80 -

8000 7.5 25.9 97 14 81 0.80 -

10000 7.3 33.7 92 8 81 0.70 -

62

26

Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

ATI 00614 Revised 02/09/15 Page 2 of 6

Page 9: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

F4545.01-113-11-R2

AIRBORNE SOUND TRANSMISSION LOSS

ASTM E 90

Test Date 02/02/16

Data File No. F4545.01

Client Hacker Industries, Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250

Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm

York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Specimen Area 10.98 m²

Technician David M. Dacheux

ATI 00614 Revised 02/09/15 Page 3 of 6

0

10

20

30

40

50

60

70

80

90

100

63

125

250

500

100

0

200

0

400

0

800

0

Sou

nd

Tra

nsm

issi

on

Loss

(d

B)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL

Contour Curve

Page 10: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

IIC Rating (Impact Insulation Class)

Deficiencies (Sum of Deficiencies)

F4545.01-113-11-R2

IMPACT SOUND TRANSMISSION

ASTM E 492

Test Date 02/02/16

Data File No. F4545.01

Client Hacker Industries, Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250

Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm

York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Specimen Area 10.98 m²

Technician David M. Dacheux

Freq Background SPL AbsorptionNormalized Impact

SPL

95% Number

Confidence of

(Hz) (dB) (m²) (dB) Limit Deficiencies

50 51.3 28.4 71 2.5 -

63 47.7 26.4 64 2.5 -

80 50.7 17.7 62 2.4 -

100 42.2 11.9 60 1.6 1

125 40.8 10.0 56 1.3 0

160 32.4 9.0 59 1.0 0

200 27.5 10.3 58 1.2 0

250 29.6 10.4 57 0.8 0

315 24.6 10.1 59 0.3 0

400 23.3 8.4 58 1.3 0

500 25.0 7.5 58 0.2 1

630 25.5 7.5 59 0.5 3

800 23.3 7.2 58 0.2 3

1000 24.7 7.2 56 0.3 2

1250 25.8 7.1 52 0.0 1

1600 21.1 7.4 51 0.3 3

2000 13.9 8.6 51 0.2 6

2500 9.8 9.6 44 0.5 2

3150 10.2 10.7 36 0.4 0

4000 10.0 12.2 28 0.3 -

5000 8.0 15.1 21 0.4 -

6300 8.6 20.0 14 0.3 -

8000 9.4 26.1 12 0.4 -

10000 8.5 33.3 11 0.7 -

53

22

Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

ATI 00615 Revised 02/09/15 Page 4 of 6

Page 11: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

F4545.01-113-11-R2

IMPACT SOUND TRANSMISSION

ASTM E 492

Test Date 02/02/16

Data File No. F4545.01

Client Hacker Industries, Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250

Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm

York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Specimen Area 10.98 m²

Technician David M. Dacheux

ATI 00615 Revised 02/09/15 Page 5 of 6

10

20

30

40

50

60

70

80

90

100

1100

10

20

30

40

50

60

70

80

90

100

63

125

250

500

100

0

200

0

400

0

800

0

Imp

act

In

sula

tion

Cla

ss (

IIC

)

So

un

d P

ress

ure

Lev

el (

dB

)

Frequency (Hz)

Impact Sound Transmission

Normalized Impact SPL

Contour Curve

Page 12: FLOOR CEILING ASSEMBLY Solutions - PAC International, Inc. RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13

Drawing

F4545.01-113-11-R2

1-Subfloor Topping

2-Subfloor Underlayment

3-Subfloor

4-Insulation

5-Truss

6-Ceiling Isolation

7-Ceiling

Page 6 of 6