firecel general catalogue - 100_2 - light version

Upload: limcsiang99

Post on 04-Mar-2016

29 views

Category:

Documents


1 download

DESCRIPTION

Cable specification

TRANSCRIPT

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    1/36

    Conducting Value

    Fire

    ResistantCables

    100/2

    The Last Cable Standing

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    2/362

    Fire Resistant Cables

    CAVICEL 4

    Construction and General Information 6

    Construction 6

    Standards at a glance 8

    Standards 14

    Cable Selection 15

    Fire Resistant Cables 16

    SR 114H 16

    SR 114E 17

    SR 125 E30 18

    SR 125 RF1 19

    SR 125H 20

    SR 225 21

    SR 118 22SR 220 23

    SR 109 24

    SR 116H 25

    SR 112 26

    SR 206 27

    SR 106H 28

    SR 145 29

    SR 140 30

    SLO-FR / MLO-FR 31

    Fire Tests 32

    Recommendation for handling and storage 34

    Reference Installations 35

    ISO 9001:2008

    Certifcate No. 217

    ISO 14001:2004

    n. 9191.CVCL

    ISO 9001:2008

    n. 9125.CAVL

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    3/36Cavicel, Conducting Value 3

    Fire Resistant Cables

    The Last Cable Standing

    Fire: a serious problem

    Fires have ahigh costin terms of loss of

    human lifeand of damages to plants andstructures.

    About athirdof fires originateinside buildings.

    Research studies in this field state that the

    most commonly identified cause of deathfrom

    a fire accident is being overcome by gasor

    smoke(Department for Communities and Local

    Government - formerly ODPM - Fire Statistics,

    United Kingdom, 2005).

    Other influential sources have demonstratedthatfor the last 50 years, the average time

    from ignition of a fire to flashover has gone

    from 15 minutes to 3 minutes, thus seriously

    complicating the escapefrom fire. And this is

    due only to the increase of plastics in home and

    buildings.

    It has to be kept into consideration, then, that

    even the most sophisticated alarm systems

    or emergency systems can be uselessiftheir performances are compromisedby the

    destructionof the cables because of the fire. This

    is the reason why, over the last few years, the

    companies havestrongly invested in designand

    development of insulation material and of

    cables granting the best performancesin case of

    fire, while reducingfumes and acid gases emission

    and grantingthe circuit integrity even in

    case of fire.

    Cavicelhas been present for years onto the market

    with its own products and its own experience.

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    4/36

    CAVICEL

    When talking about safety, a particular care must be paid to your interlocutor.When you then have to choose products that must safeguard systems and human lives, you haveto make sure that your choice is the right one.The cables, for instance, that quite often cannot be seen, being hidden in walls or below the oor,but run for kilometres around us, must be chosen by a company you trust.

    Cavicel is present onto the market with a wide range of products, including the reresistant cables FIRECEL that are installed in over 30 countries.Buildings, skyscrapers, public buildings, chemical andpetrochemical plants, undergrounds, manifold applications thathave a common denominator: they require a safe use of cables.When selecting cables that should guarantee specicperformances in case of re, it is necessary to choose a reliablecompany, with a long experience and careful to technologyevolution.A reliable company, having a long experience that allows to gain themarket trust.

    The security of our cables during a fireCavicel has started designing and manufacturing re resistant cables

    in the rst 70s. Before that, it studied halogen free special compoundshaving very low fume development, when the relevant norms were notdened yet; Cavicel has then used these products in the manufacturingof its re resistant cables. In 1983 the rst patent covering an enhancedame resistant cable had been deposited and the manufacturing ofspecial products for specic requirements had been enlarged.Those have been more and more used with a wider and wider diffusion in many elds. The studyhas then included the optic bres and in 1999 Cavicel deposited a patent covering re resistantbre optic cables.To improve as much as possible the research and development activity, Cavicel has equippeditself since many years with a re test laboratory capable to carry out tests according to severalinternational standards. A bigger guarantee for our Customer.

    Why CAVICELWe have a long experience in designing and manufacturing special cables for over 50 years, andwe have always worked closed to our customers to understand the real needs.Our cables installed in more than 50 countries say that we have the right knowledge andexperience in approaching the market.We know the problems that a re could cause to the cables, in terms of both signal interruption andfume emission that could prevent the evacuation or the rescue.There are a lot of problems to handle, we know, and this is why we work together with ourcustomers to deepen all the problems.The right Partner is important to CAVICEL and this is why we put our experience at customersdisposal.

    4

    Fire Resistant Cables

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    5/36

    Where CAVICELOur cables are installed in the following countries:Algeria, Austria, Bangladesh, Belgium, Brunei, Bulgaria,Cyprus, Czech Republic, Denmark, Egypt, Estonia,

    Finland, France, Germany, Greece, Holland, Hong Kong,Hungary, India, Indonesia, Iran, Ireland, Italy, Japan,Jordan, Kuwait, Lebanon, Luxembourg, Malaysia,Maldive, Malta, Nigeria, Oman, Pakistan, Philippines,Poland, Portugal, Qatar, Romania, San Marino, SaudiArabia, Singapore, Spain, Sudan, Sweden, Syria,Taiwan, Turkey, United Arab Emirates, United Kingdom,Usa, Venezuela, Vietnam, Yemen.Many destinations, but only one origin: Italy

    Total QualityQuality means different things to different people.Quality is not only our approved Quality Systemaccording to ISO 9001 by CSQ Italy and LPCB UK.

    Quality is not only our full equipped test laboratory tocertied required characteristics of cables.For CAVICEL Quality simply means to satisfy customersnot only supplying them the required products, butworking together in a professional way to create a longlasting successfully relationship.Our growth and success stem from the quality of ourpromise and the certainty of delivering on promise.Quality also means respect for the environment and thisis why Cavicel is now ISO 14001 certied.

    Our ValueWe are cable manufacturer, but we do not only supplycables. We grant the satisfaction of the right solution incable application. And this means to have fully evaluatedall customers requirements, not only in term of cableperformance, but in term of service, knowledge, reliabilityin order to assure the best value for the customer. We tryto understand our partners situation and criticality. Thanwe just create a cable which lets your value ow free.This is CAVICEL: Conducting Value.

    Cavicel, Conducting Value 5

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    6/36

    Construction andGeneral Information

    CablingFire resistant cables generally can be laid-up inconcentric construction and in pairs.Twisting is important to reduce noise in circuits andalso the lay of twist in some constructions must becarefully considered.

    ScreeningScreens are often used in instrumentation cables to prevent or reducepossible interference in cables that can be caused by the followingreasons:

    Cross-talk from adjacent pairs or triples; Interference induced by external source such as electricalequipments, machinery, power line.

    The most popular screen is:

    Aluminium/polyester tapewith a tinned copper drain wireor earth conductor

    Following screens can also been used, when required:

    Copper/polyester tapewith a tinned copper drainwire, for a better screen effect

    Bare copper braidfor electromagneticinterference or when the cableis subject to movements

    Aluminium/polyester or copper/polyester tapes normally have a total thicknessfrom 25 to 100 m, according to standards and are wrapped with an overlap>125% to assure a full coverage even in case of bending.In continuous contact with metallic side there could be an earth tinnedconductor, same cross section of the other cores, or a drain wire, normally

    tinned copper, 0.5 sqmm, stranded or solid, according to cable specifications.Copper braid normally has a coverage from 80% to 95%. This type of

    screen presents a lower electrical resistance, a very good protection alsoto electromagnetic noises and a higher mechanical resistance compared to

    aluminium/polyester tape. It is suitable for mobile applications.

    6

    Insulation

    The most widespread technologies to guarantee theelectric cables connection integrity during a re arecurrently the following:

    ceramied silicone-rubber mica-glass tape and cross-linked polyolene

    The taping with mica tape is the most typical solution;it allows the use of several insulation materials sincethe re resistance is guaranteed by the tape.The silicone rubber is currently the most frequentlyused solution and simplies and speeds up theinstallation, thanks to the easy peeling and to the lackof tape.

    Mica-glass tape Silicone rubber

    ConductorsConductors can generally be according to EN 60288:

    class 1solid

    class 2stranded

    class 5exible

    Type of conductors are chosen according to electrical characteristics,required exibility, type of connection systems or specic installationconditions, for example:

    in presence of vibration or movement or reduced bending radius ispreferable class 5 exible conductor,

    class 1 solid conductor is preferable for permanent installation,crimping termination,

    in presence of corrosive atmosphere, high temperature or tofacilitate the soldering is preferable tinned conductor.

    Fire Resistant Cables

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    7/36

    SheathTo optimize the behaviour in case of re, best sheathis made of LSZH (Lows Smoke Zero Halogen)materials since, thanks to that, re would not bepropagated, toxic or corrosive gases would not bedeveloped and a minimum quantity of white fumesare emitted.Other materials can obviously be used in case ofspecic installation requirements, such as:PVC, for example, where a higher resistance to oilsand chemicals is required (this material containshalogens, so it emits acid gas and smoke).

    PE, when a higher resistance to water and moistureis required (this material is no anti-ame, though).

    Cavicel, Conducting Value 7

    Construction and General Information

    ArmouringMetallic armour are used when cables have to be installed direct buried,or if mechanical protection is required.Following points must be considered:

    Required tensile load

    Expected pressure on cable during service Protection against rodent Protection against accidental damage Minimum required bending radius.

    SWA: single layer of galvanized steelwires, with diameters according torelevant standards, coverage min.90%. This armour assures a very goodmechanical protection and tensilestrength. An additional counterspiraltape increases solidity, if required.

    GSWB: galvanized steel wire braid,diameter of wire: 0.20 - 0.25 -0.30 - 0.40 mm, with coverage of>80%. It assures a good mechanicalresistance, allowing a lower bendingradius compared to other armour. It ispreferable when there is movement orvibration.For special application is possible touse stainless steel, tinned copper orspecial alloy wires.

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    8/368

    Standards at a glanceA higher and higher care is paid towards safetyin many places and environments in general.Fire is considered one of the most frequent cause of disasters and human lives loss.The standards have tried more and more to face this problem under various aspects.Over the last few years, particularly, both national(BS, DIN, CEI) and international(EN, IEC) standardshave gone through a remarkable evolution.The evolution, though, is so fast that it is difcult to always have an updated picture.The purpose of this sectionis therefore to provide an overview on how the standards have faced

    the denition, the choice and the installation of the electric cables concerning the re risks.Reference is also made to outdated standards since they are still present in many specications.

    Fire Resistant Cables

    Fire resistance

    Fire resistance means that the cable or the installation where the cable is

    installed is capable tocontinue to operate even in case of refor aspecic period of time (from 30 to 180 minutes).

    To be more precise, it is possible to have two different denitions: Circuit Integrity (or Insulation Integrity)which indicates testsexclusively referred to cables;

    System Circuit Integrity is referred to tests on cables and systems

    (ladder, cable tray, clamps).

    In some countries, such as Germany or Belgium, the rst characteristics

    (Circuit Integrity) is often indicated by an abbreviation (FE180 in case the

    test lasts 180 min) and the second one (System Circuit Integrity) by the

    abbreviations E30, E60, E90 that indicate the cable resistance for 30, 60 and

    90 minutes according to a specic test and with different installation systems.

    Fire resistance - Circuit integrity - Reference Standards

    Fire resistance - Circuit Integrity

    Fire resistance - System CircuitIntegrity - Reference Standards

    Fire resistance - System Circuit Integrity Flame non propagation

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    9/36

    Standards at a glance

    Cavicel, Conducting Value 9

    Reaction to fire propagation

    Cables can be a critical vehicle for the re transmissionsince they run for long tracts, even in vertical ducts that couldbehave as chimneys and therefore propagate the re even inother areas.CAVICEL useshigh self-extinguishing materials andrealizes constructive solutions that contrast the amepropagation.Normally two characteristicsare checked: non propagation

    of ame on a single cable alike the wiring and the nonpropagation of ame on more cables assembled as a bunch,as generally happens for electric installations.

    Behaviour to the fire of the electric cables

    The behaviour of the electric cables in case of re can be evaluated according to various aspects:Fire resistance - Non propagation of re - Emission of fumes and acid gases

    The rst aspect can be considered as active since the cable continues to perform its main function:

    transmit power and signals even during the fire.

    The other characteristics can be dened as passive, but of primary importance,by limiting the fire

    propagationandby reducing fumes and gasesthat are developed by the combustion and that cause

    severe damages and human lives losses. It must be considered, in fact, that most commonly identied

    causes for death from a re incident are due to gas or smoke.

    Emission of fumes and acid gases

    CAVICELalways usesLSZH (Low Smoke Zero Halogen)sheaths for its FIRECELcables (unless when specicallyprescribed because of special working conditions). This term

    indicates materials that are properly formulated to guarantee,besides the high self-estinguishing characteristic, also a low

    emission of clear fumes, without halogens (corrosive gases)

    and that do not developtoxic gases in case of combustion.

    Other acronyms are used, some of which are registered; it

    is important though that the required performance are clear.

    A term which is not too clearis, for instance, the acronymLSF (Low Smoke and Fumes), that, not making any reference

    to halogens, could also be referred to PVC; in this case, the

    characteristics of corrosive gases absenceis missing.

    Non propagation of fire Smoke Density Acid Gas Emission

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    10/3610

    Fire Resistant Cables

    Fire resistance

    Fire resistance - Circuit Integrity

    The rst testson re resistance cables were only providing

    the presence of ame, for example for IEC 331 standards, for a

    period of 180 minutes at a temperature of 750C.

    Subsequentlythe test conditions have been extended, by

    changing the duration, by increasing the temperature of the

    ame and by adding mechanical stress and water sprays.These modications allowed to better simulatethe real re

    conditions, with mechanical stresses due to the fall of materials

    and with the presence of water for the putting out of the same.

    The standard BS 6387has been introduced by keeping that

    into consideration: it was providing three tests on three

    different cable samples: one only with the ame, up to 950C

    (cat. C), one with the ame and water spray (cat. W), one with

    the ame and mechanical stresses (cat. Z). This test is still used

    but its limit is to require three different tests on three different

    cable samples.

    BS EN 50200standard has solved this problem since the same

    cable sample is simultaneouslystressed by the ame action,

    by the mechanical shock and by water spray.

    Fire resistance - Circuit integrity - Reference Standards

    IEC 60331- Tests for electric cables under fire conditions - Circuit integrity. This is one of the rst tests that had been introduced to verify electric cables reresistance. Currently it is divided in more parts that describe the test modes, the conditions and the equipment to use. The test, originally carried out only inpresence of re, now also stresses the cable with mechanical shocks. In details, the standard is subdivided in several parts:IEC 60331-1 ed1.0 (2009-05)- Part 1: Test method for fire with shock at a temperature of at least 830 C for cables of rated voltage up to and including0,6/1,0 kV and with an overall diameter exceeding 20 mIEC 60331-2 ed1.0 (2009-05)- Part 2: Test method for fire with shock at a temperature of at least 830 C for cables of rated voltage up to and including0,6/1,0 kV and with an overall diameter not exceeding 20 mm IEC 60331-3 ed1.0 (2009-05)- Part 3: Test method for fire with shock at a temperature of at least 830 C for cables of rated voltage up to and including0,6/1,0 kV tested in a metal enclosureIEC 60331-11 ed1.1 Consol. with am1 (2009-07) - Part 11: Apparatus - Fire alone at a flame temperature of at least 750 C

    IEC 60331-21 ed1.0 (1999-04)- Part 21: Procedures and requirements Cables of rated voltage up to and including 0,6/1,0 kVIEC 60331-23 ed1.0 (1999-04)- Part 23: Procedures and requirements - Electric data cablesIEC 60331-25 ed1.0 (1999-04)- Part 25: Procedures and requirements - Optical fibre cables

    BS EN 50200:2006 - Method of test for resistance to fire of unprotected small cables for use in emergency circuits. The cable undergoes the action of the ameat 850C and mechanical shocks. The test duration is expressed in minutes and is recorded in the classication: PH 15 - PH 30 - PH 60 - PH 90 - PH 120.Annex E of the standard also foresees the water stress, as previously provided by BS 8434-1 standard.This test is equivalent to IEC 60331-2.

    BS EN 50362:2003 - Method of test for resistance to fire of larger unprotected power and control cables for use in emergency circuits. This standard providesthe same tests foreseen by IEC 60331-1 standards (Temperature of the ame 830C, with mechanical stresses)

    BS 6387:1994- Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.This can be dened as thehistorical standard for re resistance cables since in many countries it is still the most widespread one. It has been the rst to include also mechanical stress andwater action in the re resistance test of electric cables. The cables can be tested in different conditions, but most commonly required are:Cat C- test with ame at 950C for 180 minutes.Cat W- test with ame for 15 minutes and ame and water for further 15 minutes at 650C.Cat Z - test with ame and mechanical shocks for 15 minutes at 950C.Reference is also made to constructive standards, such as BS 7629 one.

    BS 8434-2:2003+A2:2009- Methods of test for assessment of the fire integrity of electric cables. Test for unprotected small cables for use in emergencycircuits. BS EN 50200 with a 930 flame and with water spray.This standard is foreseen by BS 5839-1:2002 standards and is an extension of the testconditions according to BS EN 50200 standards. The cable is stressed by the ame at 930C with mechanical shocks for 60 minutes and further 60 minuteswith the addition of water spray. Since it has not been included in the BS EN 50200 standard yet, it is still in force.

    BS 8491:2008 - Method for assessment of fire integrity of large diameter power cables for use as components for smoke and heat control systems and certainother active fire safety systems.This standard is related to cables included in BS 7346-6, and certain other active re safety systems. It is applicable to cablesof rated voltage not exceeding 600/1 000 V and of overall diameter greater than 20 mm. The test method in BS 8491:2008 includes subjecting the cable undertest to radiation via direct impingement corresponding to a constant temperature attack of 842 C, to direct mechanical impacts corresponding to a force ofapproximately 10 N, and to direct application of a water jet simulating a water re ghting jet. The test method given in this standard includes three different testdurations to allow testing of cables intended for different applications.

    BS 8434-1:2003 (SUPERSEDED)- Methods of test for assessment of the fire integrity of electric cables. Test for unprotected small cables for use inemergency circuits. BS EN 50200 with addition of water spray.This standard is no longer in force since it has been replaced by Annex E of the S EN 50200

    standard. Reference to it is made in BS 5839-1:2002 standard, in order to add a test with water. The cable is tested at 830C for 15 minutes in presence of

    ame and mechanical shocks and for 15 minutes with ame, mechanical shocks and water spray.

    NF C 32-070- Tests for classification of conductors and cables with respect to their fire behaviour.This test differs from the others since the cable is not directly

    in contact with the ame, but it is positioned in a steel conduit inside a circular oven. The oven reaches a temperature of 920C and this causes the cable

    combustion. Mechanical shocks are applied to the conduit containing the cable; furthermore, the cable is subjected to tensile strength.

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    11/36

    Standards at a glance

    Cavicel, Conducting Value 11

    Reaction to fire propagation

    Behaviour to the fire of the electric cables

    Emission of fumes and acid gases

    Fire resistance - System Circuit Integrity

    In this case it is required a re resistance verication onthe installed cables, as for instance according to DIN 4102standards, part 12, where the cables are tested in realinstallation conditions and the resistance is veried at 30, 60and 90 minutes (the cables are in fact classied E30, E60,E90).Another standard included in this category is NBN 731.020.

    Constructive standards

    BS 7629-1:2008- Electric cables. Specificationfor 300/500 V fire resistant screened cables havinglow emission of smoke and corrosive gases whenaffected by fire. Multicore and multipair cables.This standard includes the currently most commoncables onto the market of the re resistant cables.Those cables are used in re alarm and emergencylighting applications. They have a rated voltage of300/500 V.Generally, the cables are particularly exible and easyto be installed.These standards require that the cables get throughthe re resistance tests prescribed by BS 6387standards.

    BS 7846:2009- Electric cables. Thermosettinginsulated, armoured, fire-resistant cables of ratedvoltage 600/1000 V, having low emission ofsmoke and corrosive gases when affected by fire.Specification.

    This standard refers to the armoured cables withrated voltage 600/1000 V.The circuit integrity performance under re conditionsis assessed on the basis of various tests which eitherseparately measure resistance to re, resistance tore with water, and resistance to re with mechanicalshock, or in combination measure resistance to rewith mechanical shock and water.

    BS EN 60702-1:2002- Mineral insulated cables andtheir terminations with a rated voltage not exceeding750 V. Cables.These standards apply to mineral insulated cables.Those cables have an insulation completely differentfrom those seen so far: they are extremely resistant

    but rigid. Their installation is not handy and aparticular care has to be paid to the installation toprevent moisture absorption by the mineral oxide.

    Fire resistance - System CircuitIntegrity - Reference Standards

    DIN 4102-12- Fire behaviour of building materials and building

    components - Part 12: Circuit integrity maintenance of electric

    cable systems - Requirements and testing.This test foresees the

    installation of cables in specically dened conditions, on ladder,

    cable tray, ceiling installations, in a 3 meters long oven, for a period

    up to 90 minutes, with a ame temperature that reaches 1000C. In

    this case, the SYSTEM formed by cables and accessories is tested.

    NBN 713.020- Protection contre lincendie - Comportement au feu

    des matriaux et lments de construction - Rsistance au feu des

    lments de construction (avec addendum 1994)(Fire ghting - Fire

    performance of building materials and products - Fire resistance

    of building materials). The cables are installed in a 3 x 3 m testing

    room. They are installed on cable trays and undergo the ame

    action up to 1000C. The cables are classied according to their

    operating life.

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    12/3612

    Fire Resistant Cables

    Flame non propagation

    Code of practice and general standards

    BS 5839-1:2002+A2:2008- Fire detection and fire alarm systems for buildings. Code of practice for system design, installation, commissioning andmaintenance. BS 5839-1:2002+A2:2008 provides recommendations for the planning, design, installation, commissioning and maintenance of redetection and re alarm systems in and around buildings, other than dwellings. It does not recommend whether or not a re alarm system should beinstalled in any given premises. Recommendations for re detection and alarm systems in dwellings are given in BS 5839-6. Cables are describedin clause 26. This standard introduces two different levels of resistance of cables during a re (standard and enhanced type) and many prescriptionsregarding installations. The standard cable must withstand the ame at 830C for 30 minutes, the enhanced type at 930C for 120 minutes.Besides the EN 50200 test, the cable must also get through specic BS tests, such as the BS 8434, that, however, will be gradually absorbed by theEN standards. New re tests are described in this standard, based on EN 50200, modied to include exposure to water spray. Even if BS 6387 is notexpressively called up, for standard cross reference anyway this standard is still required. Other standards of the same series are:BS 5839-6:2004- Fire detection and fire alarm systems for buildings. Code of practice for the design, installation and maintenance of fire detection andfire alarm systems in dwellings.BS 5839-8:2008- Fire detection and fire alarm systems for buildings. Code of practice for the design, installation, commissioning and maintenance ofvoice alarm systems.BS 5839-9:2003- Fire detection and alarm systems for buildings. Code of practice for the design, installation, commissioning and maintenance ofemergency voice communication systems

    BS 5266-1:2005- Emergency lighting. Code of practice for the emergency lighting of premises.Cables installed for these systems have to withstand tore for at least 60 minutes according to BS EN 50200.

    BS 7346-6:2005 (SUPERSEDED)- Components for smoke and heat control systems. Specifications for cable systems.

    BS 8519:2010- Selection and installation of fire-resistant power and control cable systems for life safety and fire-fighting applications. Code of practice.BS 8519 gives guidance and recommendations on the selection and installation of power and control cable systems. It covers systems that arerequired to maintain their circuit integrity for life safety and re-ghting applications. It also gives specic recommendations for electrical system design

    for such applications, and recommended limits for survival times.

    Flame non propagation

    In this case, a single cable sampleundergoes the ame

    action of a bunsen burner. The test only lasts few minutes.

    BS EN 60332- Tests on electrical and optical cables under

    fire conditions.These stardards describe the test conditions

    for a single cable. The test lasts between 1 and 8 minutes,

    depending on the cable diameter.

    BS EN 60332-1-1:2004- Tests on electrical and optical cables

    under fire conditions. Test for a vertical flame propagation for

    a single insulated wire or cable. Apparatus.This test refers to

    cables having standard dimensions.

    BS EN 60332-2-1:2004- Tests on electrical and optical cables

    under fire conditions. Test for vertical flame propagation for a

    single small insulated wire or cable. Apparatus. This test applies

    to small dimensions cables.

    BS 4066-1 and 2 :1980 (SUPERSEDED)- Tests on electric

    cables under fire conditions. Method of test on a single vertical

    insulated wire or cable.This standard is no longer in force and is

    replaced by the BS EN 60332.

    BS EN 50265-1:1999 (SUPERSEDED)- Common test

    methods for cables under fire conditions. Test for resistance

    to vertical flame propagation for a single insulated conductor

    or cable. Apparatus.This standard is no longer in force and is

    replaced by the BS EN 60332 standard.

    Non propagation of fire

    These tests simulate the chimney effect in vertical installation ofbunch of cables.The tests differ for quantity of installed cables in the verticalstructure and for the duration of the ame application.

    BS EN 60332-3:2009- Common test methods for cablesunder fire conditions. Test for vertical flame spread of vertically-mounted bunched wires or cables.This test is the most

    common one to verify the behaviour of a cable vs the repropagation. The cables are installed on a vertical ladder insidea metal cabinet and undergo the action of a ribbon ame at

    750C.The standard is subdivided in several parts that differ one fromthe other for the quantity of cable to be installed, the installationmode and the ame application time.BS EN 60332-3-10:2009- Common test methods for cablesunder fire conditions. Test for vertical flame spread of vertically-mounted bunched wires or cables. ApparatusBS EN 60332-3-21:2009- Procedures. Category A F/R.Installation in two layers (front and rear). Test time: 40 minutes.

    The quantity of the installed cable is equal to 7 litres of insulatingmaterial per 1 meter installed cables.BS EN 60332-3-22:2009- Procedures. Category A.Installation in one layer (front). Test time: 40 minutes. Thequantity of the installed cable is equal to 7 litres of insulatingmaterial per 1 meter installed cables.BS EN 60332-3-23:2009- Procedures. Category B.Installation in one layer (front). Test time: 40 minutes. The

    quantity of the installed cable is equal to 3,5 litres of insulatingmaterial per 1 meter installed cables.BS EN 60332-3-24:2009- Procedures. Category C.Installation in one layer (front). Test time: 20 minutes. Thequantity of the installed cable is equal to 1,5 litres of insulatingmaterial per 1 meter installed cables.BS EN 60332-3-25:2009- Procedures. Small cables. Category DInstallation in one layer (front). Test time: 20 minutes. Thequantity of the installed cable is equal to 0,5 litres of insulating

    material per 1 meter installed cables.BS 4066-3:1994, IEC 60332-3:1992 (SUPERSEDED)- Tests

    on electric cables under fire conditions. Tests on bunched wiresor cables.This standard is no longer in force and is replaced bythe BS EN 60332-3:2009.

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    13/36

    Standards at a glance

    Cavicel, Conducting Value 13

    Reaction to fire propagation

    Behaviour to the fire of the electric cables

    Emission of fumes and acid gases

    Smoke Density

    The standards describe the modality to be followedtomeasure the visibilitydecay inside a closed area, throughthe measurement of a luminous beam, by burning a specicquantity of cables.

    BS EN 61034- Measurement of smoke density of cablesburning under defined conditions.The test is carried out in a3 x 3 m metal hood with a luminous beam that is transferred

    between two walls. The light decay due to the smoke thatdevelops should not exceed specic values.BS EN 61034-1:2005Test apparatusBS EN 61034-2:2005Measurement of smoke density ofcables burning under defined conditions. Test procedure andrequirements.The previous standards related to fume emission measurementwere:

    BS 7622-1:1993 (SUPERSEDED) - Measurement of smokedensity of electric cables burning under defined conditions.Test apparatus.This standard is no longer in force and wasreplaced by the BS EN 50268-1:2000, even though this too issuperseded by now.

    BS EN 50268-1:2000 (SUPERSEDED)- Common testmethods for cables under fire conditions. Measurement ofsmoke density of cables burning under defined conditions.Apparatus.This standard is no longer in force and is replacedby the BS EN 61034-1:2005.

    Acid Gas Emission

    The gases developed by the cables in case of re could be

    corrosive. A cause for their corrosivity can be the emissionof halogensthat can be present either in the polymers thatform the cable insulation or sheath (PVC for example) or addeddisguised as anti-ame products.

    There are mainly two systemsto measure how dangerousthey are. A system allows to measure the halogen contentsin the gas; the second one measures both the pHand the gasconductivity.

    BS EN 50267- Common test methods for cables underfire conditions. Tests on gases evolved during combustionof materials from cables.This test allows to determine the

    corrosivity of the acid gases, generally halogens, that developduring the electric cable combustion.BS EN 50267-1:1999Apparatus.

    BS EN 50267-2-1:1999Procedures. Determination of theamount of halogen acid gas.This part of the standard denes

    the method to measure the halogens quantity, by having thembubbling in a solution that is then titrated.

    BS EN 50267-2-2:1999Procedures. Determination ofdegree of acidity of gases for materials by measuring pH and

    conductivity.In this case the standard allows to measure thepH and the conductivity of a solution where are collected thegases developed by the combustion of the single materials

    (insulation and sheath).BS EN 50267-2-3:1999Procedures. Determination of degree

    of acidity of gases for cables by determination of the weightedaverage of pH and conductivity. In this case the standard allows

    to calculate a weighed average of the measured value of pH,conductivity of a solution where the gases developed by the

    combustion of the materials forming the cable are collected(normally insulation and sheaths).

    BS 6425-1:1990 (SUPERSEDED) - Test on gases evolvedduring the combustion of materials from cables. Method fordetermination of amount of halogen acid gas evolved during

    combustion of polymeric materials taken from cables.Thisstandard is no longer in force and is replaced by the BS EN

    50267 standard.

    BS 6425-2:1993 (SUPERSEDED)- Test on gases evolvedduring the combustion of materials from cables. Determination

    of degree of acidity (corrosivity) of gases by measuring pH andconductivity.This standard is no longer in force and is replaced

    by the BS EN 50267 standard.

    The contents of this section is an overview of the problems related

    to the state of the art behaviour of the electric and bre optic cables

    in case of re. The picture is quite complex, both for the problems

    critical state and for all the connections and prescriptions existing

    between the various standards.

    Deliberately we did not deepen this topic since this would require

    many more pages and it would be useless in this context.

    It is anyhow the position of Cavicel as far as the cable behaviour

    in case of re in industrial plants is concerned; more detailed

    technical information could be required any time at our Technical

    Department.

    (updated to March 2010)

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    14/3614

    Fire Resistant Cables

    StandardsBS British Standard Institution

    BS 5266-1Emergency lighting. Code of practice for the emergency

    lighting of premises

    BS 5839-1

    Fire detection and re alarm systems for buildings. Code

    of practice for system design, installation, commissioning

    and maintenance

    BS 5839-6

    Fire detection and re alarm systems for buildings. Code of

    practice for the design, installation and maintenance of re

    detection and re alarm systems in dwellings

    BS 5839-8

    Fire detection and re alarm systems for buildings. Code

    of practice for the design, installation, commissioning and

    maintenance of voice alarm systems

    BS 5839-9

    Fire detection and alarm systems for buildings. Code of

    practice for the design, installation, commissioning and

    maintenance of emergency voice communication systems

    BS 6387Specication for performance requirements for cables

    required to maintain circuit integrity under re conditions

    BS 7211

    Electric cables. Thermosetting insulated, non-armoured

    cables for voltages up to and including 450/750 V, for

    electric power, lighting and internal wiring, and having low

    emission of smoke and corrosive gases when affected

    by re

    BS 7346-6Components for smoke and heat control systems.

    Specications for cable systems

    BS 7629-1

    Electric cables. Specication for 300/500 V re resistant

    screened cables having low emission of smoke and

    corrosive gases when affected by re. Multicore and

    multipair cables

    BS 7846

    Electric cables. Thermosetting insulated, armoured, re-

    resistant cables of rated voltage 600/1000 V, having low

    emission of smoke and corrosive gases when affected by

    re. Specication

    BS 8434-2

    Methods of test for assessment of the re integrity of

    electric cables. Test for unprotected small cables for use in

    emergency circuits. BS EN 50200 with a 930 ame and

    with water spray

    BS 8491

    Method for assessment of re integrity of large diameter

    power cables for use as components for smoke andheat control systems and certain other active re safety

    systems

    BS 8519

    Selection and installation of re-resistant power and

    control cable systems for life safety and re-ghting

    applications. Code of practice.

    CEI Comitato Elettrotecnico Italiano

    CEI 20-11 /

    EN 50363

    Insulating, sheathing and covering materials for low voltage

    energy cables

    CEI 20-36/2-1

    Tests for electric cables under re conditions - Circuit

    integrity - Part 21: Procedures and requirements - Cables

    of rated voltage up to and including 0,6/1,0 kV

    CEI 20-45Fire resistant elastomeric insulated cables, halogen free

    (LSOH) with rated voltage Uo/U 0.6/1 kV

    DIN Deutsches Institut fur Normung

    DIN 4102Fire behaviour of building materials and buildingcomponents - Part 12: Circuit integrity maintenance of

    electric cable systems; requirements and testing

    EN European Norm

    EN 50200Methods of test for resistance to re of unprotected small

    cables for use in emergency circuit

    EN 50266Test for vertical ame spread of vertically-mounted

    bunched wires and cables

    EN 50267/2-1

    Method of determination of amount of halogen acid gas

    evolved during combustion of polymeric materials taken

    from cables

    EN 50267/2-2Determination of degree of acidity (corrosivity) of gases by

    measuring PH and conductivity

    EN 50288-7Sectional specication for instrumentation and control

    cables

    EN 50362Method of test for resistance to re of larger unprotected

    power and control cables for use in emergency circuits

    EN 50363Insulating, sheathing and covering materials for low

    voltage energy cables

    EN 60228 Conductors of insulated cables

    EN (continued)

    EN 60332-1Test for vertical ame propagation for a single insulated

    wire or cable

    EN 60332-2Test for vertical ame propagation for a single small

    insulated wire or cable

    EN 60332-3Test for vertical ame spread of vertically-mountedbunched wires or cables

    EN 61034Measurement of smoke density of cables burning under

    dened conditions

    IEC International Electrotechnical Commission

    IEC 60228Conductors of insulated cables - Guide to the dimensional

    limits of circular connectors

    IEC 60331Test for electrical cables under re conditions. Circuit

    integrity.

    IEC 60332-1

    Tests on electric and optical bre cables under re

    conditions -Test for vertical ame propagation for a single

    insulated wire or cable

    IEC 60332-3

    Test on electric cables under re conditions - Test for

    vertical ame spread of vertically-mounted bunched wires

    or cables

    IEC 60502-1

    Power cables with extruded insulation and theiraccessories for rated voltages from 1 kV (Um = 1,2 kV) up

    to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages

    of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)

    IEC 60754-1

    Method for determination of amount of halogen acid gas

    evolved during combustion of polymeric materials taken

    from cables

    IEC 60754-2Determination of degree of acidity (corrosivity) of gases by

    measuring pH and conducivity

    IEC 60793-1 Optical bres

    IEC 60794-1 Optical bre cables

    IEC 61034-2Measurement of smoke density of electric cables burning

    under dened conditions (LT)

    NBN Norme Belge

    NBN C 30-004Fire resistance of electical cables - Classication and test

    methodsNBN 713-020 Fire resistance of building materials

    NF Norme Franaise

    NF-C-32-070

    Insulated cables and exible cords for installations -

    Classication tests on cables and cords with respect to

    their behaviour to re

    SS Singapore Standard

    SS 299 part 1

    Fire resistant cables - Performance requirements for

    cables required to maintain circuit integrity under re

    conditions

    VDEVerband der Elektrotechnik Elektronik

    Informationstechnik

    VDE 0815

    Wiring cables for telecommunication and data processing

    systems

    part 814 - Testing of cables, wires and exible cords

    Continuance of insulation effect under re conditions

    VDE 0482

    part 267 - Common test methods for cables under re

    conditions - Test on gases evolved during combustion of

    materials from cables

    part 1034 - Measurement of smoke density of cables

    burning under dened conditions

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    15/36Cavicel, Conducting Value 15

    Standards / Cable Selection

    protectionsbasic design standards fre resistant standards

    insulation

    coppercable

    fbre

    optic

    cable

    voltagerating

    silicone

    mica/XLcompound

    shield

    armour

    BS7211

    BS7629-1

    BS7846

    CEI20-45

    VDE0815

    IEC60502-1

    EN50288-7

    BS5839

    BS8519

    BS6387C-W-Z

    EN50200

    IEC60331-21

    IEC60331-23

    IEC60331-25

    CEI20-36

    NBNC30-004

    NBN713-020

    VDE0472

    DIN4102-12

    SS299part1

    page

    SR 114H 300/500 V standard standard PH30/PH60 16

    SR 114E 300/500 V enhanced enhanced PH120 17

    SR 125 E30 225 V 18

    SR 125 RF1 300 V PH90 19

    SR 125H 300/500 V PH90 20

    SR 225 300/500 V 21

    SR 118 300/500 V PH90 22

    SR 220 300/500 V 23

    SR 109 450/750 V PH120 24

    SR 116H 450/750 V PH90 25

    SR 112 450/750 V

    0,6/1 kV 26

    SR 206 0,6/1 kV 27

    SR 106H 0,6/1 kV PH90 28

    SR 145 0,6/1 kV PH90 29

    SR 140 0,6/1 kV PH60/PH90 30

    SLO-FRMLO-FR 31

    = on request.

    Cable Selection MatrixAll cables comply with following standards:

    EN/IEC 60332, EN 50266, EN 50267, IEC 60754, EN/IEC 61034.

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    16/3616

    Fire Resistant Cables

    FIRECEL SR 114HSilicone Insulation

    Overall Screen

    Standard Cable

    BS 5839-1:2002 Clause 26.2d

    EN 50200 PH 30 (PH 60)830C - 30 min. (60 min.)re and mechanical shocks

    EN 50200 Annex E830C - 15 min. re andmechanical shocks + 15 min. re mechanicalshocks and water spray

    SR 114H solid conductor 300/500 V SR 114H-R stranded conductor300/500 V

    Cables up to 4 coresapproved by LPCB,

    certificate N 217f

    ApplicationsFIRECEL SR 114H are primarily intended for generalapplication.Typical applications are:

    BS 5839-1for standardre resistant cables in redetection and re alarm systems for building

    BS 5839-8for voice alarm systems BS 5839-9for emergency voice communicationsystems.

    BS 5266-1for emergency lighting of premises(PH60)

    BS 8519for re-resistant control cable systems forlife safety and re-ghting application - Category 1

    Operating temperature-40C to +90C

    Minimum bending radius6 times the outer diameter.

    N of cond. x cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    1 mm2solid SR 114H2x1.0 7.1 70

    3x1.0 7.6 85

    4x1.0 8.3 110

    7x1.0 10.0 165

    12x1.0 12.5 255

    19x1.0 15.0 380

    1.5 mm2solid SR 114H2x1.5 8.0 95

    3x1.5 8.5 115

    4x1.5 9.4 1407x1.5 11.3 225

    12x1.5 14.5 340

    19x1.5 17.0 520

    1.5 mm2stranded SR 114H-R2x1.5 8.4 100

    3x1.5 8.9 125

    4x1.5 9.8 155

    2.5 mm2 solid SR 114H2x2.5 9.4 130

    3x2.5 10.0 170

    4x2.5 11.0 210

    2.5 mm2stranded SR 114H-R2x2.5 9.9 145

    3x2.5 10.3 180

    4x2.5 11.7 2304 mm2 stranded SR 114H-R2x4 11.5 200

    3x4 12.2 260

    4x4 13.5 330

    approximate values

    Cable construction

    ConductorsPlain annealed copper wire, solid class 1 or stranded class 2 according toEN 60228.

    InsulationHigh performance re resistant silicone rubber type EI2 to BS EN 50363-1.

    CablingInsulated cores are cabled together.

    Overall screenAluminium/polyester tape.

    Circuit protective conductor or drain wireUninsulated tinned copper conductor of the same section and class as theinsulated conductors in the 2-, 3- and 4-core cables. Drain wire of 0.5 mm2tinnedcopper conductor is provided in cables with more than 4 conductors.

    Outer sheathLSZH thermoplastic material type LTS3 to BS 7655-6.1.Colour red or white (other colours on request).

    Colour code up to 4 cores to HD 3082 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey

    7 cores centre: brown1st layer: brown - black - 4 cores white

    12 cores centre: brown - black - white 1st layer: brown - black - 7 cores white19 cores centre: brown

    1st layer: brown - black - 4 cores white 2nd layer: brown - black - 10 cores white(on request the cores can be one colour only, identified by printed numbers)

    Applicable StandardsBasic design BS 7629-1Fire resistant BS 6387 (cat. C-W-Z) EN 50200 (class PH30 and PH60)

    EN 50200 annex E (re, mechanical shock and water spray)Flame retardant EN 60332-1-2Acid gas emission EN 50267-2-1Smoke density EN 61034-2

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    17/36

    N of cond. x cross section

    (mm2)

    Outer diameter

    (mm)

    Weight

    (kg/km)

    1 mm2solid SR 114E2x1.0 7.9 85

    3x1.0 8.4 105

    4x1.0 9.3 125

    7x1.0 10.9 175

    12x1.0 14.5 300

    19x1.0 17.0 470

    1.5 mm2solid SR 114E2x1.5 8.8 105

    3x1.5 9.3 130

    4x1.5 10.3 1657x1.5 12.1 230

    12x1.5 16.0 380

    19x1.5 19.0 590

    1.5 mm2stranded SR 114E-R2x1.5 9.2 110

    3x1.5 9.7 135

    4x1.5 10.5 170

    2.5 mm2 solid SR 114E2x2.5 10.2 150

    3x2.5 10.8 190

    4x2.5 12.0 240

    2.5 mm2stranded SR 114E-R2x2.5 10.6 155

    3x2.5 11.3 190

    4x2.5 12.5 2504 mm2 stranded SR 114E-R2x4 12.2 220

    3x4 13.0 280

    4x4 14.4 350

    approximate values

    Cavicel, Conducting Value 17

    Fire Resistant Cables

    FIRECEL SR 114EMica/Silicone Insulation

    Overall Screen

    Enhanced Cable

    BS 5839-1:2002Clause 26.2e + A2:2008

    EN 50200 PH 120830C - 120 min. re andmechanical shocks

    BS 8434-2:2003 +A2:2010930C - 60 min. reand mechanical shocks + 60 min. re mechanicalshocks and water spray

    SR 114E solid conductor 300/500 V SR 114E-R stranded conductor300/500 V

    Cables up to 4 coresapproved by LPCB,

    certicate N 217g

    ApplicationsFIRECEL SR 114Eare primarily intended for use inre detection and re alarm systems, emergencylighting circuits or if cables need to properlyoperate when re resistance improvement isrequired.Typical applications are:

    BS 5839-1for enhancedre resistant cables inre detection and re alarm systems for building

    BS 5839-8 for voice alarm systems BS 5839-9for emergency voice communication

    systems. BS 8519for re-resistant control cable systems forlife safety and re-ghting application - Category 2

    Operating temperature-40C to +90C

    Minimum bending radius6 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, solid class 1 or stranded class 2 according toEN 60228.

    InsulationMica/Glass re resistant tape covered by high performance re resistant siliconerubber type EI2 to BS EN 50363-1.

    CablingInsulated cores are cabled together.

    Overall screenAluminium/polyester tape.

    Circuit protective conductorUninsulated tinned copper conductor of the same section and class as theinsulated conductors in the 2-, 3- and 4-core cables. Drain wire of 0.5 mm2tinnedcopper conductor is provided in cables with more than 4 conductors.

    Outer sheathLSZH thermoplastic material type LTS3 to BS 7655-6.1.Colour red or white (other colours on request)

    Colour code up to 4 cores to HD 3082 cores blue - brown3 cores brown - black - grey

    4 cores blue - brown - black - grey7 cores centre: brown

    1st layer: brown - black - 4 cores white12 cores centre: brown - black - white 1st layer: brown - black - 7 cores white19 cores centre: brown

    1st layer: brown - black - 4 cores white 2nd layer: brown - black - 10 cores white(on request the cores can be one colour only, identified by printed numbers)

    Applicable StandardsBasic design BS 7629-1Fire resistant BS 6387 (cat. C-W-Z) EN 50200 (class PH120)

    BS 8434-2 (120 min)Flame retardant EN 60332-1-2Acid gas emission EN 50267-2-1Smoke density EN 61034-2

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    18/36

    FIRECEL SR 125 E30Silicone Insulation

    Overall Screen

    JE-H(St)H FE180/E30

    JE-H(St)H Bd Z FE180/E30 U-SR/OS/LSZH 225 V

    Approved by VDEReg. No 7549

    ApplicationsFIRECEL SR 125 E30 are wiring cables for

    telecommunication and information processing

    systems where absence of halogen and

    improved properties in case of re and specied

    continuance of insulation effect when exposedto ame.

    For xed installation in dry and humid premises,

    may be embedded in plaster, not for power

    supply, external use or underground laying.

    Operating temperature-40C to +90C

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsSolid plain annealed copper wire.

    InsulationHigh performance re resistant silicone rubber compound type HJ1.

    Cable elementsInsulated cores are twisted to form pairs.

    Two-pair cable had four cores laid in quad formation.CablingPairs are cabled together.In cables with 8 pairs or more 4 pairs are assembled to form a bunch, thebunches are cabled together.

    Flame barrierSpecial re proof tape.

    Overall screenAluminium/polyester tape with copper drain wire.

    Outer sheathLSZH thermoplastic material type HM2.Colour orange or red with printed BRANDMELDEKABEL for re alarms.

    Colour codeEach bunch blue - red / grey - yellow / green - brown / white - blackBunch identication plastic numbered tape

    Applicable StandardsBasic design VDE 0815Fire resistant VDE 0472-814 (FE180) / IEC 60331-23Functionality of cabling system DIN 4102 Part 12 (E30)Fire retardant VDE 0472 Part 804 (test C) /

    EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Flame retardant EN 60332-1-2 / IEC 60332-1-2Acid gas emission VDE 0482-267 / EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density VDE 0482-1034 / EN 61034-2 /

    IEC 61034-2

    N of pairs x conductor diameter

    Outer diameter

    (mm)

    Weight

    (kg/km)

    section 0.5 mm2solid JE-H(St)H FE180/E30

    1x2x0.8 mm 6.1 52

    2x2x0.8 mm (quad cabled) 7.5 77

    4x2x0.8 mm 10.5 133

    section 0.5 mm2solid JE-H(St)H Bd Z FE180/E30

    8x2x0.8 mm 17.4 296

    12x2x0.8 mm 18.9 368

    16x2x0.8 mm 20.7 442

    20x2x0.8 mm 22.7 508

    32x2x0.8 mm 24.5 772

    40x2x0.8 mm 26.5 946

    52x2x0.8 mm 28.0 1016

    approximate values

    18

    Fire Resistant Cables

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    19/36

    N of pairs x conductor diameterOuter diameter

    (mm)Weight(kg/km)

    section 0.65 mm2solid U-SR/OS/LSZH

    1x2x0.9 mm 6.5 60

    2x2x0.9 mm (quad cabled) 7.4 85

    3x2x0.9 mm 10.9 145

    approximate values

    FIRECEL SR 125 RF1Silicone InsulationOverall Screen

    U-SR/OS/LSZH 300 V

    Approved by ISIB(Institut de SecuriteIncendie - Belgium)

    ApplicationsFIRECEL SR 125 RF1are designed, manufacturedand tested as data transmission cables foremergency services. These are used for data andvoice transmission when high frequency signal has tobe assured also in the event of a re.

    Operating temperature-40C to +90C

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsSolid plain annealed copper wire.

    InsulationHigh performance re resistant silicone rubber.

    Cable elementsInsulated cores are twisted to form pairs.

    Two-pair cable had four cores laid in quad formation.CablingThree pairs are cabled together.

    Flame barrierGlass tape.

    Overall screenAluminium/polyester tape with tinned copper drain wire.

    Outer sheathLSZH thermoplastic material.Colour orange (other colours on request).

    Colour codeSingle pair white - blue

    Multipair white - blue numbered

    Applicable StandardsFire resistant NBN C 30-004 (cat. F3) / NBN 713-020 (RF1) /

    EN 50200 (PH90) / IEC 60331-23Fire retardant NBN C 30-004 (cat. F2) / EN 50266-2-4 (cat. C) /

    IEC 60332-3-24 (cat. C)Flame retardant NBN C 30-004 (cat. F1) / EN 60332-1-2 / IEC 60332-1-2Acid gas emission EN 50267-2-1 / IEC 60754-1

    EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    Cavicel, Conducting Value 19

    Fire Resistant Cables

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    20/36

    N of pairs x cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    0.5 mm2solid U-SR/OS/LSZH

    1x2x0.5 6.5 56

    2x2x0.5 9.5 94

    3x2x0.5 10.5 118

    5x2x0.5 12.0 167

    6x2x0.5 13.0 197

    10x2x0.5 16.5 273

    15x2x0.5 20.5 410

    20x2x0.5 22.6 520

    1 mm2stranded R-SR/OS/LSZH

    1x2x1 7.4 77

    2x2x1 10.6 130

    3x2x2 11.2 196

    5x2x1 13.7 245

    6x2x1 14.8 300

    10x2x1 18.9 378

    15x2x1 23.2 567

    20x2x1 26.2 831

    1.5 mm2stranded R-SR/OS/LSZH

    1x2x1.5 8.7 100

    2x2x1.5 10.2 188

    3x2x1.5 12.9 223

    5x2x1.5 16.7 346

    6x2x1.5 17.5 426

    10x2x1.5 23.4 541

    15x2x1.5 28.9 892

    20x2x1.5 32.5 1182

    approximate values

    FIRECEL SR 125HSilicone Insulation

    Overall Screen

    U-SR/OS/LSZH 300/500 V

    R-SR/OS/LSZH 300/500 V

    ApplicationsFIRECEL SR 125H are designed, manufactured andtested as data transmission cables for emergencyservices. These are used for data and voicetransmission when high frequency signal has to beassured also in the event of a re.

    Operating temperature-40C to +90C

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, solid class 1 or stranded class 2 according toEN 60228.

    InsulationHigh performance re resistant silicone rubber.

    Cable elements

    Insulated cores are twisted to form pairs.CablingPairs are cabled together.

    Overall screenAluminium/polyester tape with copper drain wire.

    Outer sheathLSZH thermoplastic materialColour red (other colours on request).

    Colour codeCables up to 6 pairs black-red / black-blue / red-blue / yellow-black /

    yellow-red / yellow-blueCables above 6 pairs all pairs black-red numbered on black conductors

    Applicable StandardsBasic design BS 7629Fire resistant EN 50200 (PH90) / EN 50362 (PH90) / IEC 60331-21 /

    BS 6387(cat. C-W-Z) / SS 299 part 1Flame retardant EN 60332-1-2 / IEC 60332-1-2Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    Fire Resistant Cables

    20

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    21/36

    FIRECEL SR 225HMica/XLPE Insulation

    Overall Screen

    R-mXLPE/OS/LSZH 300/500 V

    ApplicationsFIRECEL SR 225Hare designed, manufactured andtested as data transmission cables for emergencyservices. These are used for data and voicetransmission when high frequency signal has to beassured also in the event of a re.

    Operating temperature-40C to +90C

    Minimum bending radius

    10 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, stranded according to EN 60228 class 2.

    InsulationMica/Glass re resistant tape covered by extruded cross-linked XLPE compound.

    Cable elementsInsulated cores are twisted to form pairs.

    CablingPairs are cabled together.

    Overall screenAluminium/polyester tape with copper drain wire.

    Outer sheathLSZH thermoplastic material.Colour red (other colours on request).

    Colour codeAccording to IEC 60189-2 (other colour code on request).

    Applicable StandardsFire resistant IEC 60331-23

    Flame retardant EN 60332-1-2 / IEC 60332-1-2Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    N of pairs x cross section(mm2)

    Outer diam.(mm)

    Weight(kg/km)

    0.75 mm2stranded R-mXLPE/OS/LSZH

    1x2x0.75 7.8 64

    2x2x0.75 10.7 118

    5x2x0.75 14.8 218

    10x2x0.75 20.1 380

    15x2x0.75 24.9 535

    20x2x0.75 28.2 680

    1 mm2stranded R-mXLPE/OS/LSZH

    1x2x1 8.4 73

    2x2x1 11.5 136

    5x2x1 15.7 266

    10x2x1 21.3 455

    15x2x1 26.5 646

    20x2x1 30.2 839

    1.5 mm2stranded R-mXLPE/OS/LSZH

    1x2x1.5 9.3 87

    2x2x1.5 13.0 165

    5x2x1.5 18.1 342

    10x2x1.5 24.8 606

    15x2x1.5 30.8 862

    20x2x1.5 34.9 1121

    approximate values

    Fire Resistant Cables

    Cavicel, Conducting Value 21

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    22/36

    N of cond. x cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    1.5 mm2solid U-SR/LSZH

    2x1.5 7.4 70

    3x1.5 7.9 93

    4x1.5 8.8 122

    2.5 mm2solid U-SR/LSZH

    2x2.5 8.8 105

    3x2.5 9.4 141

    4x2.5 10.4 183

    approximate values

    FIRECEL SR 118Silicone Insulation

    U-SR/LSZH 300/500 V

    Approved by ISIB(Institut de SecuriteIncendie - Belgium)

    ApplicationsFIRECEL SR 118are designed, manufactured andtested as control cable for emergency services andre circuit control.

    Operating temperature-40C to +90C(for insulated conductors only: max 200C).

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, solid according to EN 60228 class 1.

    InsulationHigh performance re resistant silicone rubber type EI2.

    CablingInsulated cores are cabled together.

    Outer sheathLSZH thermoplastic material type HM2.Colour orange (other colours on request).

    Colour codeWithout earth conductor2 cores black - blue3 cores black - blue - brown4 cores black - blue - brown - blackWith earth conductor3 cores black - blue - yellow/green4 cores black - blue - brown - yellow/green

    Applicable StandardsFire resistant NBN C 30-004 (cat. F3) NBN 713-020 (RF1 for section 1,5 mm2,

    RF1.5 for section 2,5 mm2) EN 50200 (PH90) / IEC 60331-21Flame retardant NBN C 30-004 (cat. F1) / EN 60332-1-2 / IEC 60332-1-2Fire retardant NBN C 30-004 (cat. F2) / EN 50266-2-4 (cat. C) /

    IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1

    EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    Fire Resistant Cables

    22

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    23/36

    N of cond. x cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    0.75 mm2stranded R-mXLPE/LSZH

    2x0.75 7.3 68

    3x0.75 8.0 83

    4x0.75 8.7 100

    1 mm2stranded R-mXLPE/LSZH

    2x1 7.9 82

    3x1 8.4 96

    4x1 9.4 121

    7x1 11.3 174

    12x1 15.1 282

    19x1 18.0 424

    1.5 mm2stranded R-mXLPE/LSZH

    2x1.5 8.5 1003x1.5 9.3 126

    4x1.5 10.1 150

    7x1.5 12.2 220

    12x1.5 16.5 365

    19x1.5 19.5 544

    2.5 mm2stranded R-mXLPE/LSZH

    2x2.5 9.7 139

    3x2.5 10.4 168

    4x2.5 11.5 206

    7x2.5 14.0 310

    12x2.5 18.8 514

    19x2.5 22.4 782

    approximate values

    FIRECEL SR 220Mica/XLPE Insulation

    R-mXLPE/LSZH 300/500 V

    ApplicationsFIRECEL SR 220are designed, manufactured andtested for general application.

    Operating temperature-40C to +90C

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, stranded according to EN 60228 class 2.

    InsulationMica/Glass re resistant tape covered by extruded cross-linked XLPE compound.

    CablingInsulated cores cabled together.

    Outer sheathLSZH thermoplastic material.Colour orange or white (other colours on request)

    Colour code to HD 308Without earth conductor2 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey5 cores blue - brown - black - grey - blackAbove 5 cores black numberedWith earth conductor3 cores yellow/green - blue - brown4 cores yellow/green - brown - black - grey

    5 cores yellow/green - blue - brown - black - greyAbove 5 cores yellow/green - black numbered

    Applicable StandardsBasic design EN 50288-7Fire resistant IEC 60331-21Flame retardant EN 60332-1-2 / IEC 60332-1-2Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    Fire Resistant Cables

    Cavicel, Conducting Value 23

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    24/36

    FIRECEL SR 109FlexibleSilicone InsulationOverall Screen

    F-SR/OS/LSZH 450/750 V

    ApplicationsFIRECEL SR 109are designed, manufactured andtested for general application in power and signalwiring, for emergency circuit and re circuit controlwhere high rejection to electrostatic noise is needed.

    Operating temperature-40C to +90C

    Minimum bending radius8 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, exible according to EN 60228 class 5.

    InsulationHigh performance re resistant silicone rubber.

    CablingInsulated cores are cabled together.

    Overall screenAluminium/polyester tape with tinned copper drain wire.

    Outer sheathLSZH thermoplastic material.Colour red (other colours on request).

    Colour code to HD 308Without earth conductor2 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey7 cores and above black numberedWith earth conductor3 cores yellow/green - blue - brown

    4 cores yellow/green - brown - black - grey5 cores yellow/green - blue - brown - black - grey7 cores and above yellow/green - black numbered

    Applicable StandardsFire resistant CEI 20-36/2-1 / EN 50200 (PH120) / IEC 60331-21Flame retardant EN 60332-1-2 / IEC 60332-1-2Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    N of cond. x cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    0.75 mm2flexible F-SR/OS/LSZH

    2x0.75 7.6 69

    3x0.75 8.0 84

    4x0.75 8.7 103

    1 mm2flexible F-SR/OS/LSZH

    2x1 8.0 78

    3x1 8.2 86

    4x1 8.9 110

    7x1 10.8 176

    12x1 13.9 275

    19x1 16.4 408

    1.5 mm2flexible F-SR/OS/LSZH

    2x1.5 8.3 883x1.5 8.8 112

    4x1.5 9.8 141

    7x1.5 11.7 218

    12x1.5 15.3 352

    19x1.5 18.2 535

    2.5 mm2flexible F-SR/OS/LSZH

    2x2.5 9.8 123

    3x2.5 10.4 159

    4x2.5 11.4 196

    7x2.5 13.4 305

    12x2.5 17.9 505

    19x2.5 21.1 760

    approximate values

    Fire Resistant Cables

    24

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    25/36

    FIRECEL SR 116HSilicone Insulation

    R-SR/LSZH 450/750 V

    ApplicationsFIRECEL SR 116Hare designed, manufactured

    and tested for general application in power

    supply and signal wiring, for emergency circuit

    and re circuit control.

    Operating temperature-40C to +90C(for insulated conductors only: max 200C).

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, stranded according to EN 60228 class 2.

    InsulationHigh performance re resistant silicone rubber.

    CablingInsulated cores are cabled together.

    Outer sheathLSZH thermoplastic material.Colour red (other colours on request).

    Colour code to HD 308Without earth conductor2 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey5 cores blue - brown - black - grey - blackWith earth conductor3 cores yellow/green - blue - brown4 cores yellow/green - brown - black - grey5 cores yellow/green - blue - brown - black - grey

    Applicable StandardsFire resistant CEI 20-36/2-1 / EN 50200 (PH90) / IEC 60331-21Flame retardant EN 60332-1-2 / IEC 60332-1-2Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    N of cond. x cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    1.5 mm2stranded R-SR/LSZH

    2x1.5 7.8 96

    3x1.5 8.3 116

    4x1.5 9.3 147

    5x1.5 10.5 180

    2.5 mm2stranded R-SR/LSZH

    2x2.5 9.2 138

    3x2.5 9.8 169

    4x2.5 11.3 222

    5x2.5 12.3 259

    4 mm2stranded R-SR/LSZH

    2x4 10.5 189

    3x4 11.6 2464x4 12.5 299

    5x4 14.0 359

    approximate values

    Fire Resistant Cables

    Cavicel, Conducting Value 25

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    26/36

    FIRECEL SR 112Single CoreMica/XLPE Insulation

    FIRECEL SR 112XTwin Core

    Mica/XLPE Insulation

    R-mXLSZH 450/750 V

    (600/1000 V for protected

    installation)

    Single coreapproved by LPCB,certificate N 217d

    ApplicationsFIRECEL SR 112are designed, manufactured andtested as cable xed or protected installation forpower supply, lighting and control gear.

    Operating temperature-40C to +90C

    Minimum bending radius6 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, stranded according to EN 60228 class 2.

    InsulationMica/Glass re resistant tape covered by extruded cross-linked compoundtype EI5.

    Twisting

    Only for FIRECEL SR 112X two conductors are twisted.

    ColoursSingle core Red - black - blue - brown (other colours on request)Twin core Red - black (other colours on request)

    Applicable StandardsBasic design BS 7211Fire resistant BS 6387 (cat.C-W-Z tested in steel conduit)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    Cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    SR 112

    single core R-mXLSZH

    1.5 3.4 26

    2.5 4.0 38

    4 4.7 60

    6 5.3 84

    10 6.6 128

    16 7.6 190

    25 9.4 294

    SR 112X

    twin core R-mXLSZH

    2x1.5 6.8 52

    2x2.5 8.0 762x4 9.4 120

    2x6 10.6 168

    2x10 13.2 256

    2x16 15.2 380

    2x25 18.8 588

    approximate values

    Fire Resistant Cables

    26

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    27/36

    FIRECEL SR 206Mica/XLPE Insulation

    R-mXLPE/LSZH 0.6/1 kV

    ApplicationsPower supply and signals trasmission, indoors oroutdoors even wet environment.For xed laying in free air, in pipe or conduit, onmasonry and metal structures or suspended.In places where in case of re people are exposedto serious risks for emission of smoke, toxic andcorrosive gases and where you want to avoiddamage to facilities, equipment, goods.Suitable for feeding of: emergency exits, alarmsignals, warning of smoke or gas, escalators.Suitable for laying underground direct or indirect.

    Operating temperature-40C to +90C

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, stranded according to EN 60228 class 2.

    InsulationMica/Glass re resistant tape covered by extruded cross-linked XLPE compound.

    CablingInsulated cores are cabled together.

    Outer sheathLSZH thermoplastic material type ST8.Colour red (other colours on request).

    Colour code to HD 308Without earth conductor2 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey5 cores blue - brown - black - grey - blackWith earth conductor3 cores yellow/green - blue - brown4 cores yellow/green - brown - black - grey5 cores yellow/green - blue - brown - black - grey

    Applicable StandardsBasic design IEC 60502-1Fire resistant IEC 60331-21Flame retardant IEC 60332-1-2Fire retardant IEC 60332-3-24 (cat. C)Acid gas emission IEC 60754-1Smoke density IEC 61034-2

    N of cond. x cross section

    (mm2)

    Outer diam.

    (mm)

    Weight

    (kg/km)

    1.5 mm2stranded R-mXLPE/LSZH

    2x1.5 10.4 1453x1.5 10.9 167

    4x1.5 11.8 196

    5x1.5 12.9 226

    2.5 mm2stranded R-mXLPE/LSZH

    2x2.5 11.2 180

    3x2.5 11.8 209

    4x2.5 12.8 250

    5x2.5 14.0 289

    4 mm2stranded R-mXLPE/LSZH

    2x4 12.3 230

    3x4 13.0 275

    4x4 14.1 331

    5x4 15.5 387

    6 mm2stranded R-mXLPE/LSZH

    2x6 14.6 329

    3x6 15.5 397

    4x6 16.9 482

    5x6 18.6 565

    10 mm2stranded R-mXLPE/LSZH

    2x10 16.4 450

    3x10 17.4 554

    4x10 19.1 682

    5x10 21.0 805

    16 mm2stranded R-mXLPE/LSZH

    2x16 18.5 619

    3x16 19.7 777

    4x16 20.3 1050

    5x16 23.9 1208

    25 mm2stranded R-mXLPE/LSZH2x25 22.0 914

    3x25 23.5 1161

    4x25 26.0 1500

    5x25 28.7 1700

    approximate values

    Fire Resistant Cables

    Cavicel, Conducting Value 27

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    28/36

    FIRECEL SR 106HSilicone Insulation

    R-SR/LSZH 0.6/1 kV F-SR/LSZH 0.6/1 kV

    ApplicationsPower supply and signals trasmission, indoor oroutdoor even wet environment.For xed laying in free air, in pipe or conduit, onmasonry and metal structures or suspended.In places where in case of re people are exposedto serious risks for emission of smoke, toxic andcorrosive gases and where you want to avoiddamage to facilities, equipment, goods.Suitable for feeding of: emergency exits, alarmsignals, warning of smoke or gas, escalators.Suitable for laying underground direct or indirect.

    Operating temperature-40C to +90C(for insulated conductors only: max 200C).

    Minimum bending radius10 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, stranded class 2 for section up to 10 mm2or exibleclass 5 for section above 10 mm2according to EN 60228.

    InsulationHigh performance re resistant silicone rubber.

    Cabling

    Insulated cores are cabled together.Outer sheathExtruded LSZH thermoplastic material.Colour red (other colours on request).

    Colour code to HD 308Without earth conductor2 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey5 cores blue - brown - black - grey - blackWith earth conductor3 cores yellow/green - blue - brown4 cores yellow/green - brown - black - grey

    5 cores yellow/green - blue - brown - black - grey

    Applicable StandardsFire resistant EN 50200 (PH90) / EN 50362 (PH90) / IEC 60331-21 /

    BS 6387 (cat. C-W-Z) / SS 299 part 1Flame retardant EN 60332-1-2 / IEC 60332-1-2Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    N of cond. x cross section(mm2)

    Outer diameter(mm)

    Weight(kg/km)

    1.5 mm2stranded R-SR/LSZH

    2x1.5 9.2 124

    3x1.5 9.8 148

    4x1.5 10.6 176

    5x1.5 11.5 214

    2.5 mm2stranded R-SR/LSZH

    2x2.5 10.0 155

    3x2.5 10.6 188

    4x2.5 11.5 228

    5x2.5 12.6 266

    4 mm2stranded R-SR/LSZH

    2x4 11.2 207

    3x4 12.1 2634x4 13.6 332

    5x4 14.5 399

    6 mm2stranded R-SR/LSZH

    2x6 13.1 298

    3x6 14.4 372

    4x6 15.8 463

    5x6 17.6 576

    10 mm2stranded R-SR/LSZH

    2x10 15.9 441

    3x10 16.8 541

    4x10 18.5 680

    5x10 20.5 850

    16 mm2flexible F-SR/LSZH

    2x16 17.4 602

    3x16 19.4 777

    4x16 21.2 973

    5x16 23.3 1202

    approximate values

    Fire Resistant Cables

    28

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    29/36

    N of cond. x cross section

    (mm2)

    Outer diameter

    (mm)

    Weight

    (kg/km)1.5 mm2flexible F-mG10/LSZH1x1.5 6.7 782x1.5 11.4 1683x1.5 12.0 1934x1.5 13.0 2275x1.5 13.7 260

    7x1.5 16.3 34012x1.5 19.4 51019x1.5 23.9 76024x1.5 26.5 9102.5 mm2flexible F-mG10/LSZH1x2.5 7.3 902x2.5 12.3 2043x2.5 13.0 2384x2.5 14.1 2835x2.5 15.4 3587x2.5 17.7 41412x2.5 21.4 66519x2.5 26.2 96924x2.5 29.8 12004 mm2flexible F-mG10/LSZH1x4 7.7 982x4 13.4 2553x4 14.2 3024x4 15.5 363

    5x4 17.1 4826 mm2flexible F-mG10/LSZH1x6 8.5 1232x6 15.0 3413x6 15.9 4124x6 17.4 5025x6 19.3 62010 mm2flexible F-mG10/LSZH1x10 10.5 1982x10 18.3 5103x10 19.5 6204x10 21.4 8595x10 24.3 109216 mm2flexible F-mG10/LSZH1x16 11.8 2732x16 21.5 7293x16 22.9 8974x16 25.2 1107

    5x16 28.1 130125 mm2flexible F-mG10/LSZH1x25 13.7 3852x25 25.4 11203x25 27.2 13214x25 30.2 14755x25 33.5 2073

    approximate values

    FIRECEL SR 145FlexibleMica/G10 Insulation

    FTG10OM1 0.6/1 kV

    (F-mG10/LSZH 0.6/1 kV)

    ApplicationsPower supply and signals trasmission, indoors oroutdoors even wet environment.For xed laying in free air, in pipe or conduit, onmasonry and metal structures or suspended.In places where in case of re people are exposedto serious risks for emission of smoke, toxic andcorrosive gases and where you want to avoiddamage to facilities, equipment, goods.Suitable for feeding of: emergency exits, alarmsignals, warning of smoke or gas, escalators.Suitable for laying underground direct or indirect.

    Operating temperature-40C to +90C

    Minimum bending radius10 times the outer diameter.

    Cable constructionConductorsPlain annealed copper wire, exible according to EN 60228 class 5.

    InsulationMica/Glass re resistant tape covered by extruded cross-linked compound type G10.

    CablingInsulated cores are cabled together.

    Outer sheath

    LSZH thermoplastic compound type M1.Colour blue (other colours on request).

    Colour code to HD 308Without earth conductor2 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey5 cores blue - brown - black - grey - blackAbove 5 cores black numberedWith earth conductor3 cores yellow/green - blue - brown4 cores yellow/green - brown - black - grey5 cores yellow/green - blue - brown - black - greyAbove 5 cores yellow/green - black numbered

    Applicable StandardsBasic design CEI 20-45Fire resistant EN 50200 (PH90) / EN 50362 (PH90) / IEC 60331-21Flame retardant EN 60332-1-2Fire retardant EN 50266-2-4 (cat. C)Acid gas emission EN 50267-2-1Smoke density EN 61034-2Toxicity CEI 20-37/4-0

    Fire Resistant Cables

    Cavicel, Conducting Value 29

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    30/36

    FIRECEL SR 140Mica/XLPE Insulation

    Armoured

    R-mXLPE/LSZH/SWA/LSZH

    0.6/1 kV

    ApplicationsPower supply and signals trasmission, indoors

    or outdoors even wet environment.

    For xed laying in free air, in pipe or conduit, on

    masonry and metal structures or suspended.

    In places where in case of re people are

    exposed to serious risks for emission of smoke,

    toxic and corrosive gases and where you want

    to avoid damage to facilities, equipment, goods.

    Suitable for feeding of: emergency exits, alarm

    signals, warning of smoke or gas, escalators.Suitable for laying underground direct or

    indirect.

    Operating temperature-40C to +90C

    Minimum bending radius12 times the outer diameter.

    Cable construction

    ConductorsPlain annealed copper wire, stranded according to EN 60228 class 2.

    InsulationMica/Glass re resistant tape covered by extruded cross-linked XLPE compound.

    CablingInsulated cores are cabled together.

    BeddingLSZH thermoplastic material.

    ArmourSingle layer of galvanized steel wires (SWA).

    Outer sheathLSZH thermoplastic material.Colour black (other colours on request).

    Colour code to HD 3082 cores blue - brown3 cores brown - black - grey4 cores blue - brown - black - grey7 cores and above white numbered

    Applicable StandardsBasic design BS 7846Fire resistant BS 7846 (cat. F2) / BS 6387 (cat. C-W-Z) /

    EN 50200 (PH60)Flame retardant EN 60332-1-2Fire retardant EN 50266-2-4 (cat. C)Acid gas emission EN 50267-2-1Smoke density EN 61034-2

    N of cond. x cross section

    (mm2)

    Diameter under

    armour (mm)

    Outer diameter

    (mm)

    Weight

    (kg/km)

    1.5 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x1.5 8.8 13.8 364

    3x1.5 9.8 14.8 418

    4x1.5 10.6 15.6 460

    7x1.5 12.8 18.2 607

    12x1.5 16.8 23.1 98819x1.5 19.4 26.4 1390

    27x1.5 23.3 30.5 1760

    37x1.5 26.4 34.0 2175

    2.5 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x2.5 9.6 14.6 416

    3x2.5 10.7 15.7 480

    4x2.5 11.2 16.2 514

    7x2.5 13.8 19.9 818

    12x2.5 18.2 25.4 1312

    19x2.5 21.4 28.8 1705

    27x2.5 25.8 33.4 2180

    37x2.5 29.2 37.8 2950

    4 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x4 11.1 16.1 510

    3x4 11.8 16.8 570

    4x4 12.9 17.9 649

    7x4 15.6 21.7 1004

    12x4 20.9 28.1 1642

    6 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x6 12.3 17.3 600

    3x6 13.1 18.1 680

    4x6 14.4 20.5 927

    10 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x10 14.9 19.9 800

    3x10 16.1 22.2 1078

    4x10 17.7 23.8 1256

    16 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x16 17.1 22.5 1034

    3x16 18.3 24.4 1354

    4x16 20.2 26.5 1625

    25 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x25 20.3 26.6 1530

    3x25 21.8 28.8 19724x25 24.1 31.3 2355

    35 mm2stranded R-mXLPE/LSZH/SWA/LSZH2x35 22.7 29.9 2055

    3x35 24.3 31.7 2450

    4x35 27.0 34.4 2943

    approximate values

    Fire Resistant Cables

    30

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    31/36

    SLO-FR

    -A5

    SLO - MLOLoose Buffered Cables

    Single Tube SLO-000-**-M1-A5-FR

    SLO-000-**-M1-A1-FR

    Multi Tube

    MLO-000-**-M1-A5-FR MLO-000-**-M1-A3-FR MLO-000-**-M1-A1-FR (DNV-QFCI)

    ApplicationsThese cables are mainly used inside buildings,tunnels or closed areas in general, are designed andmanufactured to guarantee the signal transmissioneven in case of re, thus safeguarding the operationof the safety systems or of particularly critical and

    high speed connections.

    Temperature range-40C to +90C

    Minimum bending radius10 times the outer diameter.

    Cable construction

    FibresSinglemode and multimode bres, with loose technology coating.

    Structure For type SLO-FR the jelly lled tube containing the bres is reinforced with glassyarns and is wound with a ame resistant tape.

    For type MLO-FR the jelly lled tubes containing the bres are individuallywound with a mica tape and are cabled around a central steel or FRP(breglass reinforced plastic) element. When necessary glass yarn is the tractionelement. A ame resistant tape improves re resistance.

    Inner sheath (only for A1 and A3 armoured cables)LSZH thermoplastic compound.

    ArmouringA1 Galvanized steel wire braidA3 Corrugated steel tapeA5 Anti-rodent glass yarns

    Outer sheathLSZH thermoplastic compound.Colour orange (other colours on request).

    Applicable Standards

    Optical fibre characteristics IEC 60793-1 / IEC 60794-1Fire resistant IEC 60331-25Flame retardant EN 60332-1-2 / IEC 60332-1-2Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)Acid gas emission EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2Smoke density EN 61034-2 / IEC 61034-2

    Available upon request Armouring:A7 - Steel wire armour

    Fire ResistantFibre Optic Cables

    Cavicel, Conducting Value 31

    Tube diameter (mm)Outer diameter

    (mm)Weight(kg/km)

    -**- number of fibres SLO-000-**-M1-A5-FR

    2 12 2.7 8.0 70

    16 24 3.5 9.0 80

    -**- number of fibres SLO-000-**-M1-A1-FR

    2 12 2.7 11.5 160

    16 24 3.5 12.0 180

    -**- max number of fibres MLO-000-**(n)-M1-A5-FR

    72 2.0 15.0 230

    96 2.0 16.5 250

    144 2.0 20.5 280

    -**- max number of fibres MLO-000-**(n)-M1-A3-FR

    72 2.0 15.0 280

    96 2.0 17.5 310144 2.0 21.5 350

    -**- number of fibres MLO-000-**(n)-M1-A1-FR (DNV-QFCI)

    4 24 2.5 13.5 230

    36 48 3.0 14.5 250

    approximate values

    SLO-FR

    -A1

    MLO-FR

    -A5

    MLO-F

    R-A

    1(DNV-Q

    FCI)

    MLO-FR

    -A3

    Test Report

    WARRES N. L18679

    Approved by:

    NEK 606DNV Certicate

    N. E-9136

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    32/3632

    BS 6387

    Following tests are carried out to verify if a cable is capable of maintainingcircuit integrity under re condition, re with water, and re with mechanicalshocks.During the tests the cables are maintained at their rated voltage.

    Fire Resistance (Cat. A B C S)The cable is exposed to re at thespecied temperature and time.

    Fire and Water Resistance(Cat. W)

    The cable is exposed for 15 minutesto ame at 650C and for additional15 minutes to re and water spray.

    Fire Resistance with MechanicalShocks (Cat. X Y Z)

    The cable is mounted on a verticalpanel and shocked with a steel barfor 15 minutes while submitted tothe action of a ame.

    Performance Table

    Test Category

    Fire Resistance

    650 C for 3 hours A

    750 C for 3 hours B

    950 C for 3 hours C

    950 C for 20 minutes S

    Resistance to Fire and Water

    650 C W

    Resistance to Fire with Mechanical Shock

    650 C X

    750 C Y

    950 C Z

    BS EN 50200

    Fire ResistanceThis test is carried out to verify thecircuit integrity of cables exposed

    to re at 830C and mechanicalshocks.

    Classification

    PH 15 ame exposure for 15 min

    PH 30 ame exposure for 30 min

    PH 60 ame exposure for 60 min

    PH 90 ame exposure for 90 min

    PH 120 ame exposure for 120 min

    BS EN 50200 Annex E(Standard Cable - BS 5839-1 - Clause 26.2d)

    Fire ResistanceThis test is carried out to verify circuitintegrity during a re. The cable isexposed to a ame at 830C andmechanical shocks for 15 minutesand additional 15 minutes to ame,mechanical shocks and water spray.

    BS 8434-2

    (Enhanced Cable - BS 5839-1 - Clause 26.2e)Fire Resistance

    This test is carried out to verify circuitintegrity during a re. The cable isexposed to a ame at 930C andmechanical shocks for 60 minutesand additional 60 minutes to ame,mechanical shocks and water spray.

    Fire TestsCables have to be properlydesigned, manufactured and also tested.

    Many tests are carried out during manufacturing or as nal inspections.

    Many of them are attended by customers or third part inspectors.

    The tests are part of R&D, an extremely strategic activity for a Company

    and this is the reason why CAVICEL has invested in this eld.

    You can nd here the maintests concerning the behaviour of cables

    under re conditions, and our main test equipments.

    It is important to verify all required performances and give the customers

    the full compliance to the requirements.

    CAVICEL is proud of its own laboratories and customersare always

    welcome to visit them.

    Fire Resistant Cables

  • 7/21/2019 Firecel General Catalogue - 100_2 - Light Version

    33/36Cavicel, Conducting Value 33

    IEC 60331, CEI 20-36

    Fire ResistanceThis test is carried out to verify circuitintegrity even during a re. A sampleof cable is held on a ame at about750C for a period of minimum 90min, under rated voltage. No breakor short circuit should occur. The

    test can also be performed in moresevere conditions, up to 1100 C.Fibre optic cables can be tested insame conditions, monitoring theattenuation of the signal of one ormore bres.

    ClassificationCEI 20-36/2-1 IEC 60331-21 Electrical cables up to 0,6/1 kVCEI 20-36/2-3 IEC 60331-23 Data cablesCEI 20-36/2-5 IEC 60331-25 Fibre optic cables

    NF C 32-070

    Fire ResistanceThis test is carried out to verify circuitintegrity during a re. The cable isinto a tubular oven with graduallyincreasing of temperature up to920C. The cable is stressed bymechanical shocks and subjected totensile strength.

    BS EN 60332-3, IEC 60332-3, CEI 20-22/3

    Fire Propagation Test on BunchedCablesSamples of cables 3,5 m long inquantities required by standard areinstalled on a ladder inside a metalliccabinet. They are subjected to theaction of a ame at 750C for a

    specic time (20 or 40 minutes).Cables must not burn for more than2,5 m.

    BS EN 60332-1, IEC 60332-1, CEI 20-35/1BS EN 60332-2, IEC 60332-2, CEI 20-35/2, for smalldiameter cables

    Flame Propagation Test on aSingle Cable

    A 60 cm long sample of cable isvertically xed with two clampsinside a small cabin, open on thefront. The cable is subjected to theaction of a ame produced by acalibrated Bunsen burner.

    The application time of the ame isaccording to the cable diameter(60-480 seconds). At the end of thetest the burnt portion of cable mustnot be 50 mm close to the higherclamp.

    BS EN 50267-2-1, IEC 6