![Page 1: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/1.jpg)
![Page 2: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/2.jpg)
Fire Safety of Staircases in Multi-Story Buildings
The Results of Measurements in Buildings and Simulations
Grzegorz Kubicki Ph.D. Department of Environmental Engineering,
Warsaw University of Technology
Izabela Tekielak – Skałka M.Sc. Eng.Head of Research and CFD Simulations
Department, SMAY LLC
![Page 3: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/3.jpg)
50 Pa
t inn = t out
h [m]
∆p [Pa]
AssumptionsStaircase protected by pressure differential system
Pressure differential system
Pressure~50 Pa
Air velocity throughan open door
The force to open the door
![Page 4: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/4.jpg)
50 Pa
t inn > t out
h [m]
∆p [Pa]
Problem with pressuredistribution in winter
European standard EN 12101-6 advises:
„if stack effect is the problem, then the system should be
activated at last 1 hourbefore the test”
![Page 5: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/5.jpg)
Real Scale Testingbuilding was adapted as a test rig:
- the 23-storey building
- building total height ~ 92 m
-reinforced concrete staircase
- located in Cracow
![Page 6: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/6.jpg)
Fire Safety in Staircase – Schema of the Ventilation System
vertical duct
![Page 7: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/7.jpg)
The Measuring System
pressure differential sensor
temperature sensor
![Page 8: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/8.jpg)
Measuring Data
Stack effect in the staircase due to temperature change
![Page 9: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/9.jpg)
Measuring Data
Stack effect in the staircase due to temperature change
![Page 10: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/10.jpg)
CFD Simulation
![Page 11: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/11.jpg)
Real Test
h [m]
∆p [Pa]
+5 Pa
- 5 Pa
h [m]
∆p [Pa]
+38 Pa
+99 Pa
setting of the pressure controllers:
Storey +23: 40 PaStorey +1: 100 Pa
![Page 12: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/12.jpg)
Test in Real Building – Sky Tower in Wroclaw50 storey building
212 m height
FIRE SAFETY SYSTEM
Staircase protected by the pressure differentia systemNo pressure relief damper in staircase
Supply air injection point to fire-fighting lobby
2 staircase
Air exhaust inside the corridor
![Page 13: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/13.jpg)
Test in Real Building – Sky Tower in Wroclaw
![Page 14: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/14.jpg)
Measure of Pressure
![Page 15: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/15.jpg)
∆𝑝𝑝𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠_𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑠𝑠𝑠𝑠= 𝜌𝜌𝑒𝑒 − 𝜌𝜌𝑖𝑖 � 𝑔𝑔 � ℎ � 𝑐𝑐 𝑃𝑃𝑃𝑃
𝑐𝑐 ∈ 0,5 ÷ 0,9 𝑃𝑃𝑃𝑃
![Page 16: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/16.jpg)
storey ∆p staircase - corridor(volume flow)
+50+60 Pa
(out 23 200 m3/h)(supply 7 700 m3/h)
+27 +48 Pa(supply 8 000 m3/h)
+17 +54 Pa(supply 8 000 m3/h)
+3 +53 Pa(supply 40 000 m3/h)
Smoke Control System
storey ∆p staircase - corridor ∆p staircase - outside
+50 +21 +82
+27 -
+17 -
+3 -6 -54
Initial distribution of pressure Pressure differentia system
Staircase
inside temperature = +10 ÷ 17 oCexternal temperature = - 4 oC
![Page 17: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/17.jpg)
PPU KSK
Test in Real Building - Riviera22 storey building
66 m height
FIRE SAFETY SYSTEMStaircase protected by multi-point
air injection system
Pressure relief damper inside the staircase
2 staircase
Supply air injection point to fire-fighting lobby
Air exhaust inside the corridor
![Page 18: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/18.jpg)
Pressure Differential
and Temperature Measurement
Point
![Page 19: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/19.jpg)
Pressure and Temperature Measurement
Data
![Page 20: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/20.jpg)
CFD Simulation Software: Ansys Fluent 13.0Model include: staircase Fire-fighting lobbies corridor Air leakage pressure differential
system
![Page 21: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/21.jpg)
-10
0
10
20
30
40
50
60
70
-50 -40 -30 -20 -10 0 10 20 30 40 50 60
H, m
∆p, Pa
winter periodStack Effect
![Page 22: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/22.jpg)
-10
0
10
20
30
40
50
60
70
-10 0 10 20 30 40 50 60 70
H, m
∆p, Paprzedsionki ppoż. klatka schodowa
winter period
![Page 23: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/23.jpg)
-10
0
10
20
30
40
50
60
70
-10 0 10 20 30 40 50 60 70
H, m
∆p, Paprzedsionki ppoż. klatka schodowa
winter period
![Page 24: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/24.jpg)
-10
0
10
20
30
40
50
60
70
-10 0 10 20 30 40 50 60 70
H, m
∆p, Paprzedsionki ppoż. klatka schodowa
warm period
![Page 25: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/25.jpg)
Fan with a frequency inverter
Pressure controller
![Page 26: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/26.jpg)
∆𝑝𝑝𝑖𝑖= 𝐾𝐾𝑠𝑠𝑠𝑠 �ℎ𝐷𝐷ℎ
�𝜌𝜌 � �𝑤𝑤2
2
( ) chgρρ=Δp ext ⋅⋅⋅− int
SummaryThe main idea of system
h [m]
∆p [Pa]
![Page 27: Fire Safety of Staircases in Multi-Story...Fire Safety of Staircases in Multi-Story Buildings The Results of Measurements in Buildings and Simulations Grzegorz Kubicki Ph.D. Department](https://reader034.vdocuments.mx/reader034/viewer/2022042916/5f5569dc63bfa65472132334/html5/thumbnails/27.jpg)
Thank You for Your Attention
Grzegorz Kubicki Ph. D. Izabela Tekielak – Skałka M.Sc. [email protected] [email protected]