fire retardant non corrosive cables for nuclear power plants
TRANSCRIPT
Bratislava – September 27, 20061
Tristan CEROSKY / Lukas VON LAUE
Fire Retardant Non Corrosive Cables for Nuclear Power Plants
Introduction
� At the beginning, PVC & Hypalon®
were used in Nuclear Power Plant
� At that time Fire properties were
acceptable
Bratislava – September 27, 20062
� But corrosivity, toxicity, and smoke were tremendous
Fire Retardant Non Corrosive (FRNC) Cables
Bratislava – September 27, 20063
� NC means Non Corrosive
(or Halogen Free)
� FR means Fire Retardant
40 years experience for 1E & non 1E …
� 1980’: First generation of FRNC cables in France
� 1990’: Openning of Central & East Europe market with supplyof Temelin, Bohunice, Dukovany, Kozloduy
Improvement of Fire Performances versus Special painting on existing cables
2000’: Aecl, Minatom & General Electric now use FRNC Nexans cables
Bratislava – September 27, 20064
� 2000’: Aecl, Minatom & General Electric now use FRNC Nexans cables
� Today: FRNC cables are available for 60 years lifetime requested for EPR
reactor (Areva)
During all these years, close partnership between Nexans and EDF (Electricité de France)
Flame Retardancy - IEC 60332-1
� Single burner (IEC 695-2-4/1)
� Sample of 600 ± 25 mm
� Temperature : ± 400 °C
� Test duration : according to the cable
diameter (60 to 480 seconds)
Bratislava – September 27, 20065
� Results: after test the cable should
stop burning and the burnt length
should not reach 50 mm under the A mark
Fire Retardancy - IEC 60332-3
• Test on bunched cables
• High performances of FRNC (Fire
Retardant Non Corrosive) Cables
• Temperature: 800 °C 22 (A) : 7l/m of burning material
23 (B) : 3.5l/m
24 (C) : 1.5l/m
Bratislava – September 27, 20066
24 (C) : 1.5l/m
• Test duration22 (A) : 40 mn
23 (B) : 40 mn
24 (C) : 20 mn
� Results: no burning over 2.5m height
from the burner.
Smoke - Opacity - IEC 61034
� Smoke opacity measurement in a
27m3 room, during the burning of a
cable sample (25 min), and 40 min after burning is completed
Bratislava – September 27, 20067
- To simulate the cables qualified life- Arrhenius methodology(IEEE 383 par. 1.3.5.2)
Thermal Aging1
- To simulate the cables qualified lifenormal and accident irradiation(IEEE 383 par. 1.3.5.2)
Radiation Aging2
- To simulate the most severe postulated3
IEEE Standard 383 for Type Test of Class 1E Electric cables
Bratislava – September 27, 20068
- To simulate the most severe postulatedconditions of a design basis event andspecified conditions of installation(IEEE 383 par. 1.3.5.3)
Test design Basis event3
The type testing for design basis event conditions shall involve both aged and non aged
samples (IEEE 383 par. 1.3.5.2)
2 scenariis because the design basis event
may occur at any time (IEEE 383 par. 1.3.5.1)
+ +
+
1 2 3
2 3
Gamma radiation Aging
Bratislava – September 27, 20069
Nexans Cable
Gamma radiation Aging
(from Cobalt 60)
To simulate the cable qualified life
normal and accident irradiation
CIS bio intern./ LABRA (CEA
Saclay Facilities)
Accident Simulation
Bratislava – September 27, 200610
To simulate the most severe
postulated conditions of a design
basis event - thermo dynamical
shocks)
CIS bio intern./LABRA
(CEA Saclay Facilities)
Nexans cable after
Accident Simulation test
(DBA or LOCA)
Medium Voltage CablesExamples of cable constructions and Standards references
Medium Voltage
1. Conductor
IEC 60228
ASTME B3, B8
2. Non Corrosive Medium Voltage Insulation
IEC 60502 - 2 types EPR & HEPR
IEC 60092-351 type HF EPR
ICEA S-68-516 type EPR
Bratislava – September 27, 200611
ICEA S-68-516 type EPR
ICEA S-94-649 / AEIC CS 6/8
4. Medium Voltage semi conducting &
metallic screens
IEC 60502
ICEA S-94-649 / AEIC CS 6/8
6. Fire Retardant Non Corrosive
Inner Sheath
7. Fire Retardant Non Corrosive
Outer Sheath:
IEC 60092-359 type SH F1 EPR
ICEA T-33-65 types thermoset I & II
CSA 22.2 n°38
BTS 74 C 068
12467
Low Voltage CablesExamples of cable constructions and Standards references
Low Voltage
1. Conductor
IEC 60228
ASTME B3, B8
3. Non Corrosive Low Voltage Insulation
IEC 60502 - 1 types EPR & HEPR
IEC 60502 - 1 types XLPE
Bratislava – September 27, 200612
IEC 60502 - 1 types XLPE
IEC 60092-351 type HF EPR
6. Fire Retardant Non Corrosive Inner Sheath
7. Fire Retardant Non Corrosive Outer Sheath:
IEC 60092-359 type SH F1 EPR
ICEA T-33-65 types thermoset I & II
CSA 22.2 n°38
BTS 74 C 068
7 6 3 1
Control & Instrumentation Cables:Examples of cable constructions and Standards references
Control & Instrumentation
1. Conductor
IEC 60228
ASTME B3, B8
3. Non Corrosive Low Voltage Insulation
IEC 60502 - 1 types EPR & HEPR
IEC 60502 - 1 types XLPE
IEC 60092-351 type HF EPR
Bratislava – September 27, 200613
IEC 60092-351 type HF EPR
5. Instrumentation cable Screen
6. Fire Retardant Non Corrosive Inner Sheath
7. Fire Retardant Non Corrosive Outer Sheath:
IEC 60092-359 type SH F1 EPR
ICEA T-33-65 types thermoset I & II
CSA 22.2 n°38
BTS 74 C 068
7 5 3 165
Success Stories Since 1975
Nexans Supplier
� France : all NPPs
� Slovaquia : Bohunice
� Czech Republic : Temelin & Dukovany
� Romania : Cernavoda
Bratislava – September 27, 200614
� Ukraine : Khmelnitsky, Zaporozhe & South-Ukraine
� Bulgaria : Kozloduy
� Russia : Kalinine
� China : Tianwan, Qinshan phase 3, Ling Ao & Daya Bay
� India : Kudankulam
Slovaquia, Bohunice
Nexans Expertise
� Used Inside and Outside NPP’s
containment
� Fitted to 60 years life time
Fire Retardant Non Corrosive
� High quality and performance of electrical cables for Nuclear
installation
� Broad experience all over the World
for many types of reactors:
Nexans FRNC cables 1E & non1E Nexans choice
Bratislava – September 27, 200615
� Fire Retardant Non Corrosive
� Nuclear Qualification according to
many standards
� Radiation resistance up to 2.106 Gy
(200 Mrads)
for many types of reactors:
PWR, VVER, Candu & BWR reactors
� Tailor made
� Efficient Service & Reliability
Global expert in cables and cabling systems
Thank you for your attention