fire pump design and testing
TRANSCRIPT
![Page 1: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/1.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 1/74
Fire Pump Design & Testing
TS 300
‐1‐1
Friday 9:00am‐12:00pm
Greg Trombold
![Page 2: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/2.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 2/74
By: Greg Trombold
![Page 3: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/3.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 3/74
Code books used during presentation
Terms and definitions Water supply
Pressure calculation
Flow calculation xamp es Pump selection Code issues Avoiding trouble Contractors point of view on pump selection
![Page 4: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/4.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 4/74
–
Fire Protection NFPA 13 – Installation of S rinkler S stems
NFPA 14 – Installation of Standpipe and hose
s stems
NFPA 22 – Water tanks for Private FireProtection
![Page 5: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/5.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 5/74
NPSH – net positive suction head (32 feet at sea
level) Rotation – direction that a pump shaft spins – –
of vertical head, friction loss, and other losses due
to heat or elevation –at a specific point on a pump curve
Locked rotor current – maximum amp draw for a
mo or e s a s e n a oc e pos on Service entrance rated – a device that is rated to
handle direct feed from the utility
![Page 6: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/6.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 6/74
–
level that a vertical turbine fire pump willoperate to its design parameters
Static pressure – pressure reading at no flow
Residual ressure – ressure at a s ecific flow
Churn pressure – pressure that a pumpproduces at no flow
AHJ – Authority having jurisdiction
![Page 7: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/7.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 7/74
–
75 feet in height. Where the building ismeasured from the lowest level of firedepartment vehicle access to the floor of the
highest occupiable story.
![Page 8: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/8.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 8/74
when sizing a fire pump is water supply The first uestion one needs to ask is “does the
municipal supply provide enough volume to
meet the system demand” For example if a city water test is 75 static, 50
residual at 1350 flowing
pump
Answer: Yes – the maximum you test a 750 GPM firepump to is 1125 GPM or 150% of rated flow
![Page 9: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/9.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 9/74
Does this same water supply provide enough waterfor a 1500 GPM fire pump
nswer : may e – you p o a ow curve ou you
could have the flow required for the 100% flow point(1500 GPM) *see curve
However this can be misleading there is a couple ofrules that I follow when talking about a municipal
water supply.1. Make sure the test is recent – within a year
2. Make sure the residual flow is at least the 100% flowratin of the um
3. Avoid winter tests versus summer tests – flow tests donein the winter are always better than flow tests done inthe summer
![Page 10: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/10.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 10/74
![Page 11: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/11.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 11/74
![Page 12: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/12.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 12/74
If the water su l does not su l enou h
volume what are your options Gravity feed tank – a ground level storage tank
sprinkler demand
30 of system demand for light hazard 60 min for ordinary hazard
90 min for extra hazard
Below round tank – usuall limited to 50 k ofsupply
Lake or reservoir – leads to some system-
![Page 13: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/13.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 13/74
![Page 14: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/14.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 14/74
City water test 82 static, 45 residual with 1941flowing
Test date February 2011
Main size 8” ystem eman at psi
Pump size 2500 GPM at 80 psi
you have enough water at 2500 GPM or 100%
![Page 15: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/15.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 15/74
![Page 16: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/16.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 16/74
![Page 17: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/17.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 17/74
should have been looked at when engineeringthis job
1. The water test was done in the winter
2. The main size is 8” when the main is tapped thecoupon a s appe n e p pe s roug y .
3. The city water test was only run to 1941 GPM – notfull flow of the fire um
Actual flow when pump was tested in August2011
![Page 18: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/18.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 18/74
![Page 19: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/19.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 19/74
Horizontal split case pumps Inline fire pumps
End suction pumps
Vertical turbine fire pumps
![Page 20: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/20.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 20/74
–
a double suction fire pump because the waterpathways direct water to both sides of theimpeller. It is also the most common fire pump
on the market partly because of the ratingsava a e n s s y e o pumpthrough 5000 GPM
fire protection systems
![Page 21: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/21.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 21/74
![Page 22: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/22.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 22/74
![Page 23: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/23.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 23/74
–
expanded in use in the last five years forseveral reasons
Space savings
Increase in ratings allowable by NFPA 20 from maxo , en o , o o ay w c sunlimited rating. The largest currently available is1500 GPM
Cost of installation – these are typically lessexpensive to install because there is no base plate
![Page 24: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/24.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 24/74
![Page 25: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/25.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 25/74
![Page 26: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/26.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 26/74
–
mostly because they are limited in size percode
They are also slightly more expensive than in
line pumps The one pump application where it is used is
small diesel driven applications 500 GPM or
ess
![Page 27: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/27.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 27/74
![Page 28: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/28.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 28/74
![Page 29: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/29.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 29/74
–
water supplies that are below the suctionflange of a fire pump
NFPA 20 states that you have to have a positive suctionpressure to a fire pump #
![Page 30: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/30.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 30/74
![Page 31: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/31.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 31/74
![Page 32: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/32.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 32/74
The first thin we should talk about when
discussing pressure is height of the building If a building is more than 75 feet tall the building
will have stand pipes. The pressure required at thetop most outlet is required to be 100 psi at a given
Does this mean that the AHJ will not require 100PSI on buildin less than 75 feet tall that have
standpipes The answer is maybe different AHJ’s have different
requ remen s
![Page 33: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/33.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 33/74
building is not classified as a high rise thestandpipes installed can be classified as manualdry, or manual wet.
These types of standpipes do not require 100psi at the top most outlet.
If that is the case then you simply need end
ea pressure at t e top o t e structure orstandard heads this number is usually around
![Page 34: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/34.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 34/74
the city flow test. Unless we are using a groundlevel storage tank or reservoir.
Once we have gathered that info most of the
industry would have a form like the one on thefollowing page to compile the data and comeup with your pressure
![Page 35: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/35.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 35/74
![Page 36: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/36.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 36/74
In both examples we will assume that the citywater test is ri ht at the 100% ratin of um
1. Height of building is 212 feet. City water test is
45 si static, residual is 35 si with 1250 GPMflowing
2. Height of the building is 70 feet. City water
test is 95 psi static with 30 residual with 750flowing
![Page 37: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/37.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 37/74
![Page 38: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/38.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 38/74
![Page 39: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/39.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 39/74
examples in example one the pressure is above175 psi.
Since you are no longer allowed to use main
relief valves to control system pressure youhave to install pressure reducing valves onsprinkler lines and pressure restricting valves
high enough in building where the pressure
![Page 40: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/40.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 40/74
that the pump will discharge much higherpressure at churn than at the design point
Per NFPA 20 fire pumps are allowed to have a
40% rise in pressure from rated flow to churn This is almost never the case but different
pumps and speeds affect the churn pressure so
you s ou a ways oo at a curve to eterminethe shut off pressure. (see attached)
![Page 41: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/41.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 41/74
![Page 42: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/42.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 42/74
130 psi The shut off head is 390 feet or 168 si
This calculates to 29% rise from rated point to
shut off head This pump is a newer design and is 3500 rpm
both contribute to the higher percentage
![Page 43: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/43.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 43/74
The static pressure is 45 psi plus the churn pressureof 211 psi for a total of 255 psi.
If the floors are 12 feet apart we would needpressure reducing valves and pressure restricting
.
255 psi – 175 psi = 80 psi / 12 = 15.4
![Page 44: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/44.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 44/74
calculation sheet and I want you all to try thefollowing example:
Building height 160 feet
City water test done 1-5-09, 60 static, 38 residualw ow ng
Lets assume the pump is 10 feet below grade in abasement
Assume backflow, water meter, and friction insuction piping are constant
![Page 45: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/45.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 45/74
![Page 46: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/46.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 46/74
Area calculation Standpipe calculation
We will start with the standpipe calculation
NFPA 14 states that the GPM re uired for thefirst standpipe is 500 GPM
Each additional stand i e re uires 250 GPM
with a maximum GPM of 1000 GPM
![Page 47: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/47.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 47/74
combining GPM with sprinkler systemrequirements
Since most area calculations for building with
standpipes come up to be less than 500 GPMthe Fire pump GPM is generally equal to thestand calc
![Page 48: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/48.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 48/74
would be 750 GPM 500 GPM for the first and 250 for the second
If a building has 3 standpipes the pump GPM
would be 1000 GPM 500 GPM , 250 for the second, and 250 for the third
Any building with more standpipes would be
1000 GPM as that is the maximum allowable bycode
![Page 49: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/49.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 49/74
number of factors that come into play. The first is the type of hazard you are protecting
there are 5
Light hazard
Ordinary hazard group 2
Extra hazard rou 1
Extra hazard group 2 The density associated with the hazard
![Page 50: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/50.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 50/74
S uare foota e of area associated with hazard
Hose allowance We are not oin to discuss how to choose a
hazard as that is a different topic
We are also not going to talk about storagedesign approaches. These are for warehousetype facilities and generally require soft ware
o e erm ne pump . ese ypes osystems are better to be left to sprinkler.
![Page 51: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/51.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 51/74
use the chart on the following page from NFPA13.
The density is multiplied by 1500 for light and
ordinary and 2500 for extra hazard The 1500 and 2500 are the most remote square
footage
You then add in the hose allowance from thechart on the next page to get your pump GPM
![Page 52: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/52.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 52/74
![Page 53: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/53.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 53/74
![Page 54: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/54.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 54/74
Buildin with multi le t es of hazards oucalculate each area and take the worst of thetwo to determine your pump GPM
T ere are a unc o exceptions in NFPA 13which we will only talk about so that you
the examples
Make sure the insurance company is consulted
because they can change the density andsquare footage requirement depending on the.
![Page 55: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/55.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 55/74
Density for light hazard .1 Hose stream for light hazard 100 GPM
Calculation 1500 x .1 = 150 + 100 = 250
Pump GPM 250 GPM
Building is 24,000 square feet, ordinary group 1
.
Hose stream for light hazard is 250 GPM
Calculation 1500 x .15 = 225 + 250 = 475 GPM
![Page 56: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/56.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 56/74
either building had standpipes why thestandpipe calculation would be the primarycalculation.
If standpipes are present there is always at least twow c ma es e pump w c s ar grea erthan the area calculation.
![Page 57: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/57.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 57/74
22,200 square feet is light hazard and 800square feet is extra hazard (group 1)
We will calculate the two areas separately
1500 x .1 = 150
x . =
As you can see the extra hazard is a greater GPM eventhough the area is much smaller
Pump GPM would be 240 + 500 (hose) = 740 GPM
![Page 58: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/58.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 58/74
building on a blank piece of paper Building is 35,000 square feet
All but 500 square feet is light hazard
Balance is ordinary group 2
![Page 59: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/59.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 59/74
![Page 60: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/60.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 60/74
Then select the type of driver Electric motor
Diesel engine
Wh would ou select one over the other If you do not have or an electrical feed would be
costly to install to the location
If the AHJ has deemed that the power in an are isunreliable
![Page 61: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/61.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 61/74
Across the line Part winding
Primary reactor
Wye delta open transition
Wye delta closed transition
Auto transformer
r mary res s ance
Soft start
![Page 62: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/62.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 62/74
’
purpose of a reduced voltage start is to save onthe size of your generator
If a soft start is used the inrush current goes
from 600% to roughly 400% this reduction incurrent can be taken off the generator size
![Page 63: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/63.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 63/74
Take the GPM required for job and determineappropriate pump
NFPA 20 states that you can use up to 150% of the rated GPMfor the system demand but they don’t recommend using more
This makes selecting the pump much more difficult
For example if you are using a 1250 GPM pump for
1450 GPM s stem demand ou have to o to the curveand pick the GPM and pressure required for thesystem and then slide back on the curve to the ULrated point of 1250 GPM to determine rated pressure.
See attached We will assume system pressure required is 121 PSI or
280 feet
![Page 64: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/64.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 64/74
![Page 65: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/65.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 65/74
selection tables (see attached) Then thin s like RPM and horse ower come
into play when selecting the pump
![Page 66: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/66.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 66/74
![Page 67: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/67.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 67/74
![Page 68: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/68.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 68/74
you select the best pump for the job A lot of times the will know which um s
have lower churn pressures and which are
more cost effective
![Page 69: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/69.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 69/74
pumps that should factor into selection andsystem design
Horizontal elbows or tees upstream of a fire pumphave to be ten pipe diameters from the suction
Pump rooms require a floor drain
Pum rooms have to be two hour fire rated if no
sprinklers are present and a one hour fire rating ifsprinklered
![Page 70: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/70.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 70/74
pressure at the suction flange
Electrical feeds to fire um controllers have tohave a two hour fire rating
Fire um s can’t be used as ressuremaintenance pumps
Variable speed pumps are now allowed by the
code
![Page 71: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/71.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 71/74
a problem things like horizontal elbows and 4’of clearance in front of a 480 volt maincontroller are things that need to be looked at.
Make sure the electrical engineer knows whathe is doing and follows NEC article 695. themajority of field issues stem from electrical
Do your homework with the AHJ and the
![Page 72: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/72.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 72/74
S ecial re uirements some urisdictions re uiredifferent things New York City requires a manual round rotor fire
Ohio EPA requires suction control valves on every
fire pump to prevent going below 20 psi in the main Insurance companies like FM require things
above and beyond the code ese ue an s are o e ou e wa an ave a
spill basin Every pump room has a low pump room temp alarm
![Page 73: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/73.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 73/74
of pressure in a system that they can.
Reason smaller pipe and lower installation costs
For what ever reason they don’t like packagedsystems they think they can do it cheaper anddon’t like to over pay for things
Contractors will try to use inline pumps up tot eir maximum ow ratings ecause t ey on thave to poor a pad
![Page 74: Fire Pump Design and Testing](https://reader034.vdocuments.mx/reader034/viewer/2022052319/577cb5451a28aba7118d0687/html5/thumbnails/74.jpg)
8/9/2019 Fire Pump Design and Testing
http://slidepdf.com/reader/full/fire-pump-design-and-testing 74/74