MOORTHY ASSOCIATES(MOOVSEN)
Submitted ByMOORTHY OVSN
![Page 2: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/2.jpg)
• FIRE PROTECTION..... A Brief Overview• FIRE PROTECTION…. Survey, Design &
Execution• THERMAL POWER PLANT……Fire
Risks • TYPES OF PROTECTION
RECOMENDED
![Page 3: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/3.jpg)
SCEMATIC VIEW OF THERMAL POWER PLANT
![Page 4: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/4.jpg)
![Page 5: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/5.jpg)
• Fire Audit / Survey to be conducted.
• Fire Risk, Load and Hazard to be indentified.
• Recommended protection to be Identified through TAC/NBC/IS Guide Lines.
• Preparation of drawings, calculations, Quantities, Specifications and Estimates etc to be done.
FIRE PROTECTION..... A Brief Overview
![Page 6: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/6.jpg)
Coal yard High hazardous area :
Fire Risk : Class A Fire Best extinguishing agent is water.
Automatic Extinguishing is crit ical and expensive.
Manual Protection to be Instal led:
Water Hydrant system as per TAC/NBC to be Instal led .
![Page 7: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/7.jpg)
Coal Conveyor High hazardous area :Fire Risk : Class A Fire Best extinguishing agent is water.Automatic Extinguishing to be Installed:Manual Protection to be also to be Provided:High Velocity Water Spray system as per TAC/NBC to be Installed .Detection: LHS OR QUORTZOID BULBAtomization: Deluge / Electrical
COAL CONVEYOR
![Page 8: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/8.jpg)
Boiler medium hazardous area :Fire Risk : Class A Fire Best extinguishing agent is water.Automatic Extinguishing to be Installed:Manual Protection to be also to be Provided:High Velocity Water Spray system as per TAC/NBC to be Installed .Detection: LHS OR QUORTZOID BULBAtomization: Deluge / Electrical
![Page 9: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/9.jpg)
TG (TURBINE GENARATOR)
Turbine Medium hazardous area :Fire Risk : Class B and C Fire Best extinguishing agent is Foam / Co2 / PowderAutomatic Early warningSmoke detectionsystem to be Installed:Portable Equipment CO2 / DCP also to be Provided:Foam based Medium Velocity Water Spray system as per TAC/NBC to be Installed to lube oil tanks.Detection: QUORTZOID BULBAtomization: Deluge
![Page 10: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/10.jpg)
Cable Gallery Medium hazardous area :Fire Risk : Class B and C Fire Best extinguishing agent is Foam / Co2 / PowderAutomatic Early warningSmoke detectionsystem to be Installed:Portable Equipment CO2 / DCP also to be Provided:High Velocity Water Spray system as per TAC/NBC to be Installed to lube oil tanks.Detection: QUORTZOID BULBAtomization: Deluge
![Page 11: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/11.jpg)
Electrical Panel Medium hazardous area :
Fire Risk : Class B and C Fire Best extinguishing agent is Foam / Co2 / Powder
Automatic Early warningSmoke detectionsystem to be Installed:
Portable Equipment CO2 / DCP also to be Provided:
![Page 12: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/12.jpg)
Central Control Room Light hazardous area :
Fire Risk : Class A and C Fire Best extinguishing agent is Co2 / FM 200 / INERGEN
Automatic Early warningSmoke detectionsystem and Clean agent Gas suppression systems to be Installed:Detection: Smoke (Cross zone /addressable analogue )Atomization: Solenoid
Portable Equipment CO2 also to be Provided:
![Page 13: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/13.jpg)
TRANSFORMER hazardous area :Fire Risk : Class B and C Best extinguishing agent is High Velocity water.Automatic Extinguishing to be Installed:Manual Protection also to be Provided:High Velocity Water Spray system as per TAC/NBC to be Installed .Detection: LHS OR QUORTZOID BULBAtomization: Deluge / Electrical
![Page 14: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/14.jpg)
LDO High hazardous area :Fire Risk : Class B Best extinguishing agent is Foam / Co2 / PowderAutomatic Early warningDetection system to be Installed:Required Capacity Equipment FOAM / DCP also to be Provided:Foam based Medium Velocity Water Spray system as per TAC/NBC to be Installed to lube oil tanks.Detection: LHS / QUORTZOID BULBAtomization: Deluge
![Page 15: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/15.jpg)
TRANSFORMER hazardous area :Fire Risk : Class B and C Best extinguishing agent is High Velocity water.Automatic Extinguishing to be Installed:Water Hydrant System to be Provided for Switch yard:High Velocity Water Spray system as per TAC/NBC to be Installed for Transformer.Detection: LHS OR QUORTZOID BULBAtomization: Deluge / ElectricalPortable extinguishers to be provided
![Page 16: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/16.jpg)
COMMON FIRE PROTECTION FOR TOTAL PLANT:
EARLY WARNING MANUAL CALL POINT FIRE ALARM SYSTEM
PORTABLE EXTINGUISHERS
WATER HYDRANT SYSTEM
![Page 17: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/17.jpg)
![Page 18: Fire protection in thermal power station](https://reader035.vdocuments.mx/reader035/viewer/2022081323/559aa9491a28ab8a1c8b4685/html5/thumbnails/18.jpg)