fire and smoke update]

40
Technical Databook Fire & Smoke Actuators Spring-Return and Non-Spring-Return Version 1 Belimo Asia Pacific

Upload: shweta-rawal-vij

Post on 31-Aug-2014

68 views

Category:

Documents


9 download

TRANSCRIPT

Technical Databook

Fire & Smoke ActuatorsSpring-Return and Non-Spring-Return

Version 1

Belimo Asia Pacific

2 Sub

ject

to te

chni

cal c

hang

es.

Spring-Return18Nm/12Nm F11Nm/8.5Nm FG6Nm/4Nm* LF

Angle Rotation max. 95° Blank

Power SupplyAC/DC 24V 24AC/DC 24...48V 24...48 (only for BR..)AC 230V 230

* Torque of BLF24-SR is 4Nm/4Nm.

* FSAF24(-S) US power supply is AC/DC 24V.

Fire & Smoke Actuator Standard Type Naming

max. 180° G

Open/Close BlankModulating DC 2(0)...10V control -SRThermal trip -T

Product Naming

Fire and Smoke Actuator (CE Certification) B

Non-Spring-Return40Nm E24Nm15Nm

SBS(E) system connection -ST

EGLE / R

Spring-Return15Nm AF7.9Nm NF3.5Nm LF

Power Supply

AC 24V* 24AC 230V 230

Spring-Return

Products meet the America sales and applications standard

Open/Close BlankModulating DC 2(0)...10V control -SRAuxiliary Switch -S

Product Naming FS LF 24 -S US

Fire and Smoke Actuator (UL555/UL555S) FS

B F G 24 -SR

Sub

ject

to te

chni

cal c

hang

es.

3

Contents

Note:

The modification and mounting of the actuator to the fire damper is made by the manufacturer of the damper.

For this reason, the Fire & Smoke Actuator is supplied directly to fire damper manufacturers. The manufacturer then bears over all responsi-bility for a proper function of the damper.

The enclosure of the actuator equipment may only be opened by the manufacturer. It contains no components which the user can replace or repair.

BLF24(-T)(-ST)6BLF24-SR7

Fire and Smoke Spring-Return Actuators, 6/4Nm

BLF230(-T)

8BF24(-T)(-ST)9

Fire and Smoke Spring-Return Actuators, 18/12Nm

BF230(-T)BF24-SR(-T)

10

11BFG24(-T)(-ST)12

Fire and Smoke Spring-Return Actuators, 11/8.5Nm

BFG230(-T)

FSLF24(-S) US 13FSLF230(-S) US 14

FSNF230(-S) US 16

Fire and Smoke Spring-Return Actuators, 3.5Nm

FSNF24(-S) US 15

Fire and Smoke Spring-Return Actuators, 7.9Nm

FSAF24(-S) US 17FSAF230(-S) US 18

Fire and Smoke Spring-Return Actuators, 15Nm

5

4

Control and monitoring, power unit

SBS(E)-Control system overview

Connections and display devices /

34

35

Block diagram

B..E../BR.. series 29

Accessories

Wiring diagrams

BAE72B (-S) 32

33

Application information

30

ZTPC600-B

28FS..US series 26B..F.. series

B..F../FS..US series B..E.. series 31

BE24(-12)(-ST) 23

Smoke Control Non-Spring-Return Actuators, 40Nm

BE230(-12) 24

BEG230 22BEG24(-ST) 21

Smoke Control Non-Spring-Return Actuators, 24Nm

BLE24(-ST) 19

Smoke Control Non-Spring-Return Actuators, 15Nm

BLE230 20

BR24-48-F-ST 25

Smoke Control Non-Spring-Return Actuators, 15Nm

Product overviewB..F..

FS.. US

B..E..

BR..

* For BLF24-SR, the motor torque is 4Nm and the spring return torque is 4Nm, motor running time is 150s.** BLF24-SR has 1 SPDT auxiliary switch built-in.***BLF24-SR has no manual override function.

Fire and Smoke protection Spring-Return Actuator BLF.. BF.. BFG.. FSLF..US FSNF..US FSAF..USAgency listing

Torque -Motor 6Nm 18Nm 11Nm

Open/Close

-Spring return 4Nm 12Nm 8.5Nm

AC 24V 50/60Hz, DC 24V BLF24 BF24 BFG24 FSAF24 US

AC 24V 50/60Hz, DC 24V with thermal trip (72oC) BLF24-T BF24-T BFG24-T

AC/DC 24V with plug connect to BKN230-24 BLF24-ST BF24-ST BFG24-ST

AC 24V 50/60Hz, DC 24V with thermal trip andplug connect to BKN230-24 BLF24-T-ST BF24-T-ST BFG24-T-ST

AC 24V 50/60Hz FSLF24 US FSNF24 US

AC 230V 50/60Hz BLF230 BF230 BFG230 FSLF230 US FSNF230 US FSAF230 US

AC 230V 50/60Hz with thermal trip BLF230-T BF230-T BFG230-T

Modulating (AC 24V 50/60Hz, DC 24V)

Feedback signal DC 2...10VControl signal DC 2(0)...10V

BLF24-SR* BF24-SR(-T) FSAF24-SR(-S) US

Running time -Motor 40..75s 140s 140s 15s 15s 75s-Spring return 20s 16s 20s 15s 15s 20s

Built-in 2 SPDT auxiliary switch FSNF24-S USFSNF230-S US

Built-in 2 SPST auxiliary switch FSLF24-S USFSLF230-S US

FSAF24-S USFSAF230-S US

Form-fit 10x10mm

Clamp

Manual override function Yes

Angle of rotation Max.180°

Direction of rotation selectable by L/R mounting

Max. 95° Max. 95°

CE certification UL555 and UL555S

Yes

12x12mm,(10x10mm with adapter)

3.5Nm 7.9Nm 15Nm

Built-in**

Yes***

Smoke control Non-Spring-Return Actuator BLE.. BE.. BEG.. BR..Agency listing

Torque 15Nm 40Nm 24Nm 15Nm

Open/Close

AC 24V 50/60Hz, DC 24V BLE24 BE24 BEG24

AC/DC 24V with plug connect to BKNE230-24 BLE24-ST BE24-ST BEG24-ST

AC 24...48V compatible with control unit for pulse triggering BSIA24-48(-R) BR24-48-F-ST

AC 230V 50/60Hz BLE230 BE230 BEG230

Running time 30s 60s 60s 30s

Form-fit 12x12mm

Yes

BE24-12BE24-12-STBE230-12 Yes Yes

Form-fit 14x14mm YesAngle of rotation Max. 180° Max. 105°

Direction of rotation selectable by L/R mountingBuilt-in 2 SPDT auxiliary switch

Manual override function Yes

CE certification

Yes

Yes

Max. 95°

12.7...20mm 12.7...26mm

4 Sub

ject

to te

chni

cal c

hang

es.

Fire and Smoke Damper Actuator product overview

Sub

ject

to te

chni

cal c

hang

es.

5

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V

Power consumption 5W @ running / 2.5W @ holding

Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V

Wire sizing 7VA (Imax 5.8A @ 5ms)

Connection cable -Motor 1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 6Nm Min. 4Nm

Direction of rotation Selectable by L/R installation

Angle of rotation

Running time - Motor

Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)

40...75s (0...6Nm)~20s @ -20...+50°C/max. 60s @ -30°C

Position indication Mechanical with pointerService life >60,000 cycles

Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54

Ambient temperature - Normal duty -30...+50°C

- Safety duty

Non-operation temperature -40...+50°C (-40...+80°C without thermal trip)Humidity test 95%RH, non condensingMaintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 185x98x57.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight BLF24 (-ST) Approximately 1540g

BLF24-T(-ST) Approximately 1630g

Fire and Smoke Spring-Return Actuator BLF24(-T)(-ST)

- Spring return

- Spring return

Thermal trip (-T: BAE72B-S)

EMC CE according to 2004/108/EC

Dimensions [mm]

BLF24-ST

( ..-ST with plug connectors, suitable for BKN230-24)

Safe position will be attained up to max. 75°C

BAE72B-S: see page 32

• For control of Fire and Smoke Dampers • in HVAC systems • Torque: 6/4Nm • Nominal voltage: AC/DC 24V • Manual override function• Control: Open/Close

-Auxiliary switch

Mode of operation Type 1.AA.B

Auxiliary switch-Switching points fixed at 5° , 80°

Max. 95° (incl. 5° spring pretensioning) 57

.657

185

155

93 18

8012.249

6.5

10 25

120

98

2 SPDT, 1mA...3(0.5)A, DC 5V...AC 250V

Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)

when initiated by a thermal trip

6 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V

Power consumption 2.5W @ running / 1W @ holding

Nominal voltage range AC 19.2 ... 28.8V, DC 21.6...28.8V

Wire sizing 5VA (Imax 5.8A @ 5ms)

Connection cable -Motor 1m, 4x0.75mm2 (halogen-free)1m, 3x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 4Nm Min. 4Nm

Direction of rotation -Motor-Spring return

Selectable by L/R switchSelectable by L/R installation

Angle of rotation Max. 95°Running time - Motor

Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)

150s~20s (@ tamb=20°C)

Position indication Mechanical with pointer

Control signal DC 2 (0) ...10V (input impedance 100kΩ)Feedback signal DC 2...10V

Service life >60,000 cyclesWorking conditions Protection class III (safety extra-low voltage)

Degree of protection IP54EMC CE according to 2004/108/ECMode of operation Type 1.AA.BAmbient temperature - Normal duty -30...+50°C

- Safety duty Safe position will be attained up to max. 75°C

Non-operation temperature -40...+80°CHumidity test 95%RH, non condensingMaintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 185x98x57.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight Approximately 1630g

Fire and Smoke Spring-Return Actuator BLF24-SR

- Spring return

- Spring return

Dimensions [mm]

• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 4/4Nm• Nominal voltage: AC/DC 24V• Control signal: DC 2(0)...10V• Position feedback: DC 2...10V

Auxiliary switch 1 SPDT, 1mA...3(0.5)A, AC 250Vfixed at 5°

57.657

185

155

93 18

8012.249

6.5

10 25

120

98

-Auxiliary Switch

Sub

ject

to te

chni

cal c

hang

es.

7

Technical data

Electrical data Nominal voltage AC 230V 50/60Hz

Power consumption 6W @ running/3W @ holding

Nominal voltage range AC 198 ... 264V

Wire sizing 7VA (Imax. 150mA @ 10ms)

Connection cable -Motor 1m, 2x0.75mm2 (halogen-free)

1m, 6x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 6Nm

Min. 4Nm

Direction of rotation Selectable by L/R installationAngle of rotation Max. 95°Running time - Motor

Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)

40...75s (0...6Nm)

Position indication Mechanical with pointerService life >60,000 cycles

Working conditions Protection class II (all insulated)Degree of protection IP54

Ambient temperature - Normal duty -30...+50°C- Safety duty Safe position will be attained up to max. 75°C

when initiated by a thermal trip

Non-operation temperature

Humidity test 95%RH, non condensingMaintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 185x98x57.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight Approximately 1730g

Fire and Smoke Spring-Return Actuator BLF230(-T)

- Spring return

- Spring return

Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)

EMC CE according to 2004/108/EC

Dimensions [mm]

185

155

93 18

57.657

8012.249

6.5

10 25

120

98

BAE72B-S: see page 32

• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 6/4Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close

-Auxiliary switch

Auxiliary switch 2 SPDT, 1mA...3(0.5)A, DC 5V...AC 250Vfixed at 5° , 80°-Switching points

(incl. 5° spring pretensioning)

-40...+50°C (-40...+80°C without thermal trip)

Type 1.AA.B Mode of operation

~20s @-20...+50°C/max. 60s @ -30°C

8 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V

Power consumption 7W @ running / 2W @ holding

Nominal voltage range AC 19.2...28.8V, DC 21.6 ... 28.8V

Wire sizing 10VA (Imax 8.3A @ 5ms)

Connection cable - Motor - Auxiliary Switch

1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 18Nm Min. 12Nm

Direction of rotation Selectable by L/R installation

Angle of rotation Max. 95°

Running time - Motor

Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)

140s~16s (@tamb=20°C)

Position indication Mechanical with pointerService life >60,000 cycles

Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54

Ambient temperature - Normal duty -30...+50°C- Safety duty Safe position will be attained up to max. 75°C

when initiated by a thermal trip

Non-operation temperatureHumidity test 95%RH, non condensingMaintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 248x98x58.6mm

Shaft diameter Form-fit 12x12mm (10mm with adapter supplied)

Weight Approximately 2800g

Fire and Smoke Spring-Return Actuator BF24(-T)(-ST)

- Spring return

- Spring return

(..-T..) operating temperaturethermal trips BAE72B-S

Tf1: duct outside temperature 72°C *Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)

Dimensions [mm]

L

40

6.5

18850 10

ø5.2

248

175.6

27.2

4040

8098

1717

5.1

1

12.2

58.6

BF24-ST

BAE72B-S: see page 32

( ..-ST with plug connectors, suitable for BKN230-24)

• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 18/12Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close

Auxiliary switch 2 SPDT, 1mA...6(3)A, DC 5V...AC 250V-Switching points fixed at 5° , 80°

Mode of operation Type 1.AA.B

-40...+50°C (-40...+80°C without thermal trip)

(incl. 5° spring pretensioning)

EMC CE according to 2004/108/EC

Sub

ject

to te

chni

cal c

hang

es.

9

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V

Power consumption 7W @ running / 2W @ holding

Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V

Wire sizing 10VA (Imax 8.3A @ 5ms)

Connection cable -Motor -Auxiliary switch

1m, 4x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 18Nm Min. 12Nm

Direction of rotation Selectable by L/R installation

Angle of rotation Max. 95°

Auxiliary switch- Switching points

2 SPDT, 1mA...6(3)A, DC 5V...AC 250Vfixed at 5° , 80°

Running time - Motor

Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)

150s~16s (@tamb=20°C)

Position indication Mechanical with pointer

Control signal DC 2 (0)...10V (input impedance 100k Ω)Feedback signal DC 2...10V

Service life >60,000 cycles

Working conditions Protection class III (safety extra-low voltage)

Degree of protection IP54

EMC CE according to 2004/108/EC

Ambient temperature - Normal duty -30...+50°C- Safety duty -30...+75°C (24hr)

Non-operation temperatureHumidity test 95%RH, non condensingMaintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 248x98x58.6mmShaft diameter Form-fit 12x12mm (10mm with adapter supplied)Weight Approximately 2800g

Fire and Smoke Spring-Return Actuator BF24-SR(-T)

- Spring return

- Spring return

Dimensions [mm]

L

40

6.5

18850 10

Ø5.2

248

175.6

27.2

4040

8098

1717

5.1

1

12.2

58.6

Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)

BAE72B-S see page 32

• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 18/12Nm • Nominal voltage: AC/DC 24V• Manual override function• Control signal: DC 2 (0)...10V • Position feedback: DC 2...10V

-40...+50°C

Mode of operation Type 1.AA.B

10 Sub

ject

to te

chni

cal c

hang

es.

fixed at 5° , 80°

Technical data

Electrical data Nominal voltage AC 230V 50/60Hz

Power consumption 8W @ running/3W @ holding

Nominal voltage range AC 198...264V

Wire sizing 12.5VA (Imax 500mA @ 5ms)

Connection cable -Motor -Auxiliary switch

1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 18Nm Min. 12Nm

Direction of rotation Selectable by L/R installation

Angle of rotation Max. 95° (incl. 5° spring pretensioning)

Auxiliary switch 2 SPDT, 1mA...6(3)A, DC 5V...250V

Running time - Motor

Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)

140s~16s (tamb=20°C)

Position indication Mechanical with pointer

Service life >60,000 cycles

Working conditions Protection class II (all insulated)Degree of protection IP54

Ambient temperature - Normal duty -30...+50°C- Safety duty

Non-operation temperature

Humidity test 95%RH, non condensing

Maintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 248x98x58.6mm

Shaft diameter Form-fit 12x12mm (10mm with adapter supplied)

Weight Approximately 3100g

Fire and Smoke Spring-Return Actuator BF230(-T)

• For control of Fire and Smoke Dampers • in HVAC systems• Torque: 18/12Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close

- Spring return

- Spring return

Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)

EMC CE according to 2004/108/EC

Mode of operation Type 1.AA.B

Dimensions [mm]

L

40

6.5

18850 10

ø5.2

248

175.6

27.2

4040

8098

1717

5.1

1

12.2

58.6

Safe position will be attained up to max. 75°Cwhen initiated by a thermal trip

-Switching points

BAE72B-S see page 32

-40...+50°C (-40...+80°C without thermal trip)

Sub

ject

to te

chni

cal c

hang

es.

11

25° , 145° (angles of rotation of damper: 5° , 80° )

Technical data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V

Power consumption 7W @ running / 2W @ holding

Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V

Wire sizing 10VA (Imax 8.3A @ 5ms) / (..T type: Imax 5.8A @ 5ms)

Connection cable - Motor - Auxiliary switch

1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 11Nm Min. 8.5Nm

Direction of rotation Selectable by L/R installation

Auxiliary switch 2 SPDT, 1mA...6(3)A, DC 5V...AC 250V

Running time - Motor

Sound power level Motor max. 45d(A), Spring return approximately 62dB(A)

140s~20s (tamb=20°C)

Position indication Mechanical with pointerService life >50,000 cycles

Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54EMCMode of operationAmbient temperature - Normal duty

- Safety duty

Non-operation temperature

Humidity test 95%RH, non condensing

Maintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 248x98x58.6mm

Shaft diameter Form-fit 10x10mm

Weight Approximately 2800g

Fire and Smoke Spring-Return Actuator BFG24(-T)(-ST)

• For control of Fire and Smoke Dampers in HVAC systems• Torque motor: 11/8.5Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close

- Spring return

- Spring return

Dimensions [mm]

Angle of rotation Max. 180°

BFG24-ST

Thermal trip (-T: BAE72B-S)

-30...+50°C

Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)

(..ST with plug connectors, suitable for BKN230-24)

Safe position will be attained up to max. 75°Cwhen initiated by a thermal trip

L

40

6.5

18850 10

ø5.2

248

175.6

27.2

4040

8098

1717

5.1

1

10.2

58.6BAE72B-S: see page 32

-Switching points

CE according to 2004/108/ECType 1.AA.B

-40...+50°C (-40...+80°C without thermal trip)

12 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data Nominal voltage AC 230V 50/60Hz

Power consumption 8W @ running / 3W @ holding

Nominal voltage range AC 198...264V

Wire sizing 12.5VA (Imax 500mA @ 5ms )

Connection cable - Motor - Auxiliary switch

1m, 2x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque - Motor Min. 11Nm Min. 8.5Nm

Direction of rotation Selectable by L/R installation

Auxiliary switch

Running time - Motor

Sound power level Motor max. 45dB(A), Spring return approximately 62dB(A)

140s~20s ( tamb=20°C)

Position indication Mechanical with pointerService life >50,000 cycles

Working conditions Protection class II (all insulated)Degree of protection IP54EMC

Ambient temperature - Normal duty -30...+50°C- Safety duty Safe position will be attained up to max. 75°C

when initiated by a thermal tripNon-operation temperatureHumidity test 95%RH, non condensingMaintenance Maintenance-free

Dimensions / weight Dimensions (L x W x H) 248x98x58.6mmShaft diameter Form-fit 10x10mm Weight Approximately 3100g

• For control of Fire and Smoke Dampers• in HVAC systems • Torque: 11/8.5Nm•• Nominal voltage: AC 230V• Manual override function• Control: Open/Close

- Spring return

- Spring return

Dimensions [mm]

Angle of rotation Max. 180°

Thermal trip (-T: BAE72B-S) Tf1: duct outside temperature 72°C Tf2/Tf3: duct inside temperature 72°C *(Art. Nr. ZBAE72)

-Switching points

L

40

6.5

18850 10

ø5.2

248

175.6

27.2

4040

8098

1717

5.1

1

10.2

58.6

CE according to 2004/108/ECMode of operation

BAE72B-S: see page 32

Fire and Smoke Spring-Return Actuator BFG230(-T)

2 SPDT, 1mA...6(3) A, DC 5V...AC 250V25° , 145° (angles of rotation of damper: 5° , 80° )

-40...+50°C (-40...+80°C without thermal trip)

Type 1.AA.B

Class 2 supply

Sub

ject

to te

chni

cal c

hang

es.

13

Technical data

Electrical data AC 24V 50/60Hz

Power consumption 5VA @ running / 3.5VA @ holding

Power supply

5VA (Class 2 power supply)

Connection cable -Motor 1m, 18ga, 2 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector

Functional data

Working conditions

Dimensions / weight

Torque Min. 3.5Nm

Direction of rotation Selectable by CW/CCW installation

Angle of rotation Max. 95°

Auxiliary switch (-S) 2 SPST, 1mA @ DC 5V, 3(0.5)A, 120/250Vfixed at 10° and 85°

Running time - Motor <15s at rated voltage and torque<15s

Position indication Mechanical

Protection class

Degree of protection IP 30 / Enclosure type 1

Mode of operation Type 1.AA.B

Agency listed UL60730-1, UL60730-2-14 and CAN/CSA E60730-1:02

Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C

Non-operation temperature -40...+80°C

Humidity test 5...95%RH, non condensing

Maintenance Maintenance-free

179x98x82mm

Shaft diameter 12.7...20mm

Weight Approximately 1700g

Fire and Smoke Spring-Return Actuator FSLF24(-S) US

• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 3.5Nm• Running time: 15s• Control: Open/Close•

- Spring return

Transformer sizing

Dimensions (L x W x H)

Dimensions [mm]

12.7...20

Nominal voltage range AC 21.6...26.4V

19 [0.75"]

6 [0.24"]

[2.24"]

179[7.03"]173

[6.81"]11[0.45"] 28

[1.1"]

min 12.7[0.5"]

max 20[0.79"]

98[3.86"]

138[5.42"]

60[2.37"]

5[0.2"]

57

-Auxiliary switch (-S)

14 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data AC 230V 50/60Hz

Power consumption 17VA @ running / 8VA @ holding (50Hz)17VA @ running / 6VA @ holding (60Hz)

Power supply

5VA

Connection cable - Motor 1m, 18ga, 3 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector

Functional data

Working conditions

Dimensions / weight

Torque Min. 3.5Nm

Direction of rotation Selectable by CW/CCW installation

Angle of rotation Max. 95°

Auxiliary switch (-S) 2 SPST, 1mA@ DC 5V, 3(0.5)A, 120/250Vfixed at 10° and 85°

Running time - Motor <15s at rated voltage and torque<15s

Position indication Mechanical

Protection class

Degree of protection IP30 / Enclosure type 1

Mode of operation Type 1. AA. B

Agency listed UL60730-1, UL60730-2-14 and CAN/CSA E60730-1:02

Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C

Non-operation temperature -40...+80°CHumidity test 5...95%RH, non condensing

Maintenance Maintenance-free179x98x82mm

Shaft diameter 12.7...20mmWeight Approximately 1700g

Fire and Smoke Spring-Return Actuator FSLF230(-S) US

• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 3.5Nm• Running time: 15s• Control: Open/Close•• 1 wire control

- Spring return

Transformer sizing

Dimensions (L x W x H)

Dimensions [mm]

12.7...20

Nominal voltage range AC 207...253V

Grounded enclosure

19 [0.75"]

6 [0.24"]

[2.24"]

179[7.03"]173

[6.81"]11 [0.45"] 28

[1.1"]

min 12.7[0.5"]

max 20[0.79"]

98[3.86"]

138[5.42"]

60[2.37"]

5[0.2"]

57

- Auxiliary switch (-S)

Technical data

Electrical data AC 24V 50/60Hz

Power consumption

Power supply

27VA Class 2 power supply

Connection cable - Motor 1m, 18ga, 2 color coded leads1m, 18ga, 6 appliance leads1/2" conduit connector

Functional data

Working conditions

Dimensions / weight

Torque Min. 7.9Nm

Direction of rotation Selectable by CW/CCW installation

Angle of rotation Max. 95°

Auxiliary switch (-S) 2 SPDT, 7(2.5)A @ AC 125/250Vfixed at 5° and 85°

Running time - Motor <15s at rated voltage and torque<15s

Position indication Mechanical

Protection class

Degree of protection NEMA type 1

Agency listed UL 873 and CAN / CSA C22.2 No.24

Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C

Non-operation temperature -40...+80°C

Humidity test 5...95%RH, non condensing

Maintenance Maintenance-free

259x98x78mm

Shaft diameter 12.7...20mm (10...20mm optional)

Weight Approximately 2750g

• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 7.9Nm• Running time: 15s • Control: Open/Close

- Spring return

Transformer sizing

Dimensions (L x W x H)

Dimensions [mm]

Nominal voltage range AC 19.2...28.8V

27VA @ running / 10VA @ holding

50

80 [3

.15"

]

98 [3

.86"

]78

[3.1

0"]

57[2

.24"

]

5 [0

.19"

]

[1.97"]

49

[1.9

3"]

73.5

[2.8

9"]

67[2.64"]

6.5 [0.26"]148.5 [5.85"]

259 [10.20"]

9 [0.35"]

10 [0.39"]

16.5 [0.65"]

5 [0.19"]

[Ø41.2]Ø1.62"

[7.54"]

191.6

-S models only

Standard:12.7 to 26 mm[1/2" to 1.05"]

Optional*10 to 20mm[3/8" to 3/4"]

*with K4 US clamp

Shaft Size

Class 2 supply

Sub

ject

to te

chni

cal c

hang

es.

15

Fire and Smoke Spring-Return Actuator FSNF24(-S) US

- Auxiliary switch (-S)

16 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data

Power consumption

Power supply

27VA

Connection cable -Motor -Auxiliary switch (-S)

Functional data

Working conditions

Dimensions /weight

Torque Min. 7.9Nm

Direction of rotation Selectable by CW/CCW installation

Angle of rotation Max. 95°

Auxiliary switch (-S) 2 SPDT, 7(2.5)A @ AC 125/250Vfixed at 5° and 85°

Running time - Motor <15s at rated voltage and torque<15s

Position indication Mechanical

Protection class

Degree of protection NEMA type 1

Agency listed UL 873 and CAN/ CSA C22.2 No. 24

Ambient temperature - Normal duty 0...+50°C- Safety duty 3 Open/Close cycles after 1/2hr @ 177°C

Non-operation temperature -40...+80°CHumidity test 5...95%RH, non condensing Maintenance Maintenance-free

259x98x78mmShaft diameter 12.7...20mm (10...20mm optional ) Weight Approximately 2750g

Fire and Smoke Spring-Return Actuator FSNF230(-S) US

• UL555/UL555S rated Fire and Smoke dampers in HVAC systems• Torque: 7.9Nm• Running time: 15s • Control: Open/Close

- Spring return

Transformer sizing

Dimensions (L x W x H)

Dimensions [mm]

Nominal voltage range

AC 230V 50/60Hz

1m, 18ga, 3 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector

AC 207...253V

50

80 [3

.15"

]

98 [3

.86"

]78

[3.1

0"]

57[2

.24"

]

5 [0

.19"

]

[1.97"]

49[1

.93"

]73

.5[2

.89"

]

67[2.64"] 6.5 [0.26"]

148.5 [5.85"]259 [10.20"]

9 [0.35"]

10 [0.39"]

16.5 [0.65"]

5 [0.19"]

[Ø41.2]Ø1.62"

[7.54"]

191.6

-S models only

Standard:12.7 to 26 mm[1/2" to 1.05"]

Optional*10 to 20mm[3/8" to 3/4"]

*with K4 US clamp

Shaft Size

Grounded enclosure

27VA @ running / 10VA @ holding (50Hz)17VA @ running / 6VA @ holding (60Hz)

Sub

ject

to te

chni

cal c

hang

es.

17

Technical data

Electrical data AC 24V 50/60Hz, DC 24V

Power consumption 7.5W @ running / 2W @ holding

Nominal voltage

10VA (Class 2 power supply)

Connection cable - Motor - Auxiliary switch (-S)

1m, 18ga, 2 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector

Functional data

Working conditions

Dimensions / weight

Torque Min. 15Nm

Direction of rotation Selectable by CW/CCW installation

Angle of rotation Max. 95°

Auxiliary switch (-S) 2 SPST, 7(2.5)A @ AC 120/250Vone fixed at 10° and one is adjustable from 30° to 90°

Running time - Motor <75s at rated voltage and torque<20s

Position indication Mechanical

Sound power level Motor max. 45dB(A), Spring approximately 62dB(A)

Protection class

Degree of protection NEMA type 1

Agency listed UL 873 and CAN/CSA C22.2 No.24-93, CE.Ambient temperature - Normal duty -30°C...+50°C

- Safety duty 3 Open/Close cycles after 1/2hr @ 121°C

Non-operation temperature -40°C...+80°C

Humidity test 5...95%RH, non condensing Maintenance Maintenance-free

259x98x78mmShaft diameter 12.7...20mm (10...20mm optional ) Weight Approximately 2700g

Fire and Smoke Spring-Return Actuator FSAF24(-S) US

• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Running time: motor 75s, spring return 20s• Manual override function• Control: Open/Close

- Spring return

Transformer sizing

Dimensions (L x W x H)

Dimensions [mm]

Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V

Class 2 supply

1.97"

3.15

" [80

]

3.86

" [98

]3.

10" [

78]

2.24

"[5

7]

[50]

1.93

"[4

9]

2.64"[67]

0.26" [6.5]5.85" [148.5]

10.59" [269]

0.35" [9]

0.39" [10]

0.65" [16.5]

0.19" [5]

Standard:1/2" to 1.05"

Optional* 3/8" to 3/4"

3/8" to 5/8"

*with K4 US clamp

18 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data

Power consumption

Nominal voltage

10VA

Connection cable - Motor 1m, 18ga, 2 color coded leads1m, 18ga, 4 appliance leads1/2" conduit connector

Functional data

Working conditions

Dimensions / weight

Torque Min. 15Nm

Direction of rotation Selectable by CW/CCW installation

Angle of rotation Max. 95°

Auxiliary switch (-S) 2 SPST, 7(2.5)A @ AC 120/250Vone fixed at 10° and one is adjustable from 30° to 90°

Running time - Motor <75s at rated voltage and torque<20s

Position indication Mechanical

Protection class

Degree of protection NEMA type 1

Agency listed UL 873 and CAN/CSA C22.2 No.24-93

Ambient temperature - Normal duty -30°C...+50°C- Safety duty 3 ON/OFF cycles after 1/2hr @ 121°C

Non-operation temperature -40°C...+80°C

Humidity test 5...95%RH, non condensing

Maintenance Maintenance-free

259x98x78mm

Shaft diameter 12.7...20mm (10...20mm optional)

Weight Approximately 3100g

Fire and Smoke Spring-Return Actuator FSAF230(-S) US

• UL555/UL555S rated Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Running time: motor 75s, spring return 20s• Manual override function• Control: Open/Close

- Spring return

Transformer sizing

Dimensions (L x W x H)

Dimensions [mm]

Nominal voltage range

AC 230V 50/60Hz

11W @ running / 3.5W @ holding

AC 197.8...262.2V

Double insulated

Sound power level Motor max. 45dB(A), Spring approximately 62dB(A)

1.97"

3.15

" [80

]

3.86

" [98

]3.

10" [

78]

2.24

"[5

7]

[50]

1.93

"[4

9]

2.64"[67]

0.26" [6.5]5.85" [148.5]

10.59" [269]

0.35" [9]

0.39" [10]

0.65" [16.5]

0.19" [5]

Standard:1/2" to 1.05"

Optional* 3/8" to 3/4"

3/8" to 5/8"

*with K4 US clamp

- Auxiliary switch (-S)

Sub

ject

to te

chni

cal c

hang

es.

19

(referred to 0...90° )

Non-Spring-Return Smoke Control Actuator BLE24(-ST)

Technical Data

Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V

Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V

Power consumption 7.5W @ running / 0.5W @ holdingWire sizing 9 VA (Imax. 2.7A @ 5ms)

Auxiliary switch- Switching points

2 SPDT, 1mA...3A, DC 5V...AC 250V3° , 87°

Connection cable - Motor- Auxiliary switch

1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)(..-ST with plug connectors, suitable for BKNE230-24)

Functional data Torque (nominal torque) Min. 15Nm

Blocking torque - Dynamic - Steady-state

Min. 15NmMin. 20Nm

Direction of rotation Selected by L/R installationAngle of rotation Max. 105° (incl. mechanical overrun on each side)Running time 30s/90°Sound power level Max. 62dB(A)Service life >10’000 cycles

Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54EMCLow voltage directive

CE according to 2004/108/ECCE according to 2006/95/EC

Mode of operation Type 1.B Ambient temperature - Normal duty

- Safety duty–30...+50°CSee “Safety function” on page 31

Non-operating temperature –40...+80°CHumidity test 95%RH, non condensing Maintenance Maintenance-free

Dimensions / weight Dimensions ( L x W x H ) 185x98x57.6mmShaft diameter Form-fit 12x12mmWeight Approximately 1680g

Dimensions [mm]

.756

57

185

155

93 18

80

212

.

49

6. 5

10 25

120

89

• For control of Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Nominal voltage: AC/DC 24V• Manual override function • Control: Open/Close

BFG24-ST

20 Sub

ject

to te

chni

cal c

hang

es.

(referred to 0...90° )

Non-Spring-Return Smoke Control Actuator BLE230

Technical Data

Electrical data Nominal voltage AC 230V 50/60HzNominal voltage range AC 198...264V

Power consumption

Wire sizing5W @ running / 1W @ holding

12VA (Imax, 6A @ 5ms)

Auxiliary switch-Switching points

2 SPDT, 1mA...3A, DC 5V...AC 250V 3° , 87°

Connecting cable - Motor - Auxiliary switch

1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque (nominal torque) Min. 15Nm

Blocking torque - Dynamic - Steady-state

Min. 15NmMin. 20Nm

Direction of rotation Selected by L/R installation

Angle of rotation Max. 105° (incl. mechanical overrun on each side)Running time 30s/90°

Sound power level Max. 62dB(A)

Position indication Mechanical with pointerService life >10‘000 cycles

Working conditions Protection class II (totally insulated) Degree of protection IP54

EMCLow voltage directive

CE according to 2004/108/ECCE according to 2006/95/EC

Mode of operation Type 1.B

Ambient temperature - Normal duty - Safety duty

–30...+50°CSee “Safety function” on page 31

Non-operating temperature –40...+80°C

Ambient humidity range 95%RH, non condensingMaintenance Maintenance-free

Dimensions / weight Dimensions ( L x W x H ) 185x98x57.6mm

Weight Approximately 1680gShaft diameter Form-fit 12x12mm

Dimensions [mm]

657

.57

185

155

93 18

0812.294

6.5

10 25

120

89

• For control of Fire and Smoke Dampers in HVAC systems• Torque: 15Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close

Sub

ject

to te

chni

cal c

hang

es.

21

Technical data

Electrical data Nominal voltage

Power consumption

Nominal voltage range

Wire sizing

Connection cable -Motor-Auxiliary switch

Functional data Torque

Direction of rotation

Angle of rotation

Auxiliary switch

Running time

Sound power level

Position indication

Service life

Working conditions Protection class

Degree of protection

Ambient temperature - Normal duty- Safety duty

Non-operationing temperature

Humidity test

MaintenanceDimensions / weight Dimensions (L x W x H)

Shaft diameter

EMC

Dimensions [mm]

-Switching points

Blocking torque - Dynamic- Steady-state

AC 24V 50/60Hz, DC 24V

13W @ running / 0.5W @ holding

AC 19.2...28.8V, DC 21.6...28.8V

18VA (Imax 8.2A @ 5ms )

1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Min. 24Nm

Selectable by L/R installation

Max. 180°

2 SPDT, 1mA...6A, DC 5V...AC 250V5° , 175° (referred to 0...90° )

Max. 62dB(A)

<60s

Mechanical with pointer

>10,000 cycles

III (safety extra-low voltage)

IP54

-30...+50°C

-40...+80°C

Mode of operation Type 1.B

95%RH, non condensing

Maintenance-free

248x98x71mm

Form-fit 12x12mm

Weight Approximately 2700g

CE according to 2004/108/EC

Min. 24NmMin. 30Nm

40

6.5

18850 10

248

175.6

27.2

4040

5.1

71

98

1

12.2

Non-Spring-Return Smoke Control Actuator BEG24(-ST)

• For control of Fire and Smoke Dampers in HVAC systems • Torque: 24Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close

(..-ST with plug connectors, suitable for BKNE230-24)

See “Safety function” on page 31

BFG24-ST

22 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data Nominal voltage

Power consumption 8W @ running / 0.5W @ holding

Nominal voltage range

Wire sizing

Connection cable - Motor- Auxiliary switch

1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Functional data Torque

Direction of rotation

Angle of rotation

Auxiliary switch

Running time

Sound power level

<60s

Position indication

Service lifeWorking conditions Protection class II (totally insulated)

Degree of protection

Ambient temperature -Normal duty-Safety duty

Storage temperature

Humidity test

Maintenance

Dimensions / weight Dimensions (L x W x H)

Weight

Shaft diameter

EMCLow-voltage directive

CE according to 2004/108/ECCE according to 2006/95/EC

Dimensions [mm]

- Switching points

Blocking torque - Dynamic- Steady-state

40

6.5

18850 10

248

175.6

27.2

4040

5.1

71

98

1

12.2

Non-Spring-Return Smoke Control Actuator BEG230

• For control of Fire and Smoke Dampers • in HVAC systems • Torque: 24Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close

5° , 175° ( referred to 0...90° )

Mode of operation

AC 230V 50/60Hz

AC 198...264V

15VA ( Imax 7.9A @ 5ms )

Min. 24Nm

Min. 24NmMin. 30Nm

Selectable by L/R installation

Max. 180°

2 SPDT, 1mA...6A, DC 5V...AC 250V

Max. 62dB(A)

Mechanical with pointer

>10,000 cycles

IP54

-30...+50°C

-40...+80°C

95%RH, non condensing

Maintenance-free

248x98x71mm

Approximately 2700g

Form-fit 12X12mm

Type 1.B

See “Safety function” on page 31

Technical data

Electrical data Nominal voltage

Power consumption

Nominal voltage range

Wire sizing

Connection cable - Motor- Auxiliary switch

Functional data Torque

Direction of rotation

Angle of rotation

Auxiliary switch

Running time

Sound power level

Shaft diameter BE24(-ST) BE24-12(-ST)

Position indication

Service life

Working conditions Protection class

Degree of protection

Ambient temperature - Normal duty- Safety duty

Storage temperature

Humidity test

Maintenance

Dimensions / weight Dimensions (L x W x H)

Weight

EMC

Dimensions [mm]

-Switching points

Blocking torque - Dynamic - Steady-state

• For control of fire and smoke dampers in HVAC systems• Torque: 40Nm• Nominal voltage: AC/DC 24V• Manual override function• Control: Open/Close

AC 24V 50/60Hz, DC 24V

12W @ running / 0.5W @ holding

AC 19.2...28.8V, DC 21.6...28.8V

18VA (Imax 8.2A @ 5ms)

1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Min. 40Nm

Selectable by L/R installation

100° (including 5° mechanical overrun at the ends)

2 SPDT, 1mA...6A, DC 5V...AC 250V

3° , 87° (referred to 0...90° )

Max. 62dB(A)

Form-fit 14x14mmForm-fit 12x12mm

<60s for 90°

Mechanical with pointer

>10,000 cycles

III (safety extra-low voltage)

IP54

-30...+50°C

-40...+80°C

95%RH, non condensing

Maintenance-free

248x98x71mm

Approximately 2700g

CE according to 2004/108/EC

Min. 40NmMin. 50Nm

(..-ST with plug connectors, suitable for BKNE230-24)

Mode of operation Type 1.B

BE24(-12)-ST

*Type Damper driverBE24

BE24-12

Form-fit 14.2mm

Form-fit 12.2mm

17

1

40

188 5010

248

175.6

27.2

04

08

04

895°

*

5°90°

See “Safety function” on page 31

Non-Spring-Return Smoke Control Actuator BE24(-12)(-ST)

6.5

5.1

Sub

ject

to te

chni

cal c

hang

es.

23

Technical data

Electrical data Nominal voltage

Power consumption

Nominal voltage range

Wire sizing

Connection cable -Motor-Auxiliary switch

Functional data Torque

Direction of rotation

Angle of rotation

Auxiliary switch

Running time

Shaft diameter BE230 BE230-12

Position indication

Service life

Working conditions Protection class

Degree of protection

Ambient temperature -Normal duty-Safety duty

Non-operation temperature

Humidity test

MaintenanceDimensions / weight Dimensions (L x W x H)

Weight

EMCLow-voltage directive

Dimensions [mm]

-Switching points

Blocking torque - Dynamic -steady-state

AC 230V 50/60Hz

8W @ running / 0.5W @ holding

AC 198...26 V

15VA (Imax 7.9A @ 5ms)

1m, 3x0.75mm2 (halogen-free)1m, 6x0.75mm2 (halogen-free)

Min. 40Nm

Selectable by L/R installation

Max. 100° (including 5° mechanical overrun on each side)

2 SPDT, 1mA...6A, DC 5V...AC 250V3° , 87° (referred to 0...90° )

Form-fit 14x14mmForm-fit 12x12mm

< 60s for 90°

Sound power level Max. 62dB(A)

Mechanical with pointer

>10,000 cycles

II (all insulated)

IP54

-30...+50°C

-40...+80°C

95%RH, non condensing

Maintenance-free

248x98x71mm

Approximately 2700g

CE according to 2004/108/ECCE according to 2006/95/EC

Mode of operation Type 1.B

Min. 40NmMin. 50Nm

• For control of Fire and Smoke Dampers in HVAC systems • Torque: 40Nm• Nominal voltage: AC 230V• Manual override function• Control: Open/Close

* Type Damper driver

BE230 Form-fit 14.2mm

BE230-12 Form-fit 12.2mm

17

1

40

188 5010

248

175.6

27.2

04

08

04

5.1

895°

*

5°90°

See “Safety function” on page 31

6.5

24 Sub

ject

to te

chni

cal c

hang

es.

Non-Spring-Return Smoke Control Actuator BE230(-12)

Sub

ject

to te

chni

cal c

hang

es.

25

Technical data

Electrical data Nominal voltage

Power consumption

Nominal voltage range

Wire sizing

Connection cable - Motor

Functional data Torque

Direction of rotation

Angle of rotation

Auxiliary switch

Running time

Sound power level

Position indication

Service life

Working conditions Protection class

Degree of protection

Ambient temperature - Nomal duty

Humidity test

Maintenance

Dimensions / weight Dimensions (L x W x H)

Shaft diameter

Weight

EMC

Dimensions [mm]

-Switching points

- Safety duty

• For control of Fire and Smoke Dampers in HVAC system• Torque: 15Nm• Nominal voltage: AC/DC 24...48V• Manual override function • Control: Open/Close• Compatible with the control unit for pulse triggering BSIA24-48(-R)

Non-Spring-Return Smoke Control Actuator BR24-48-F-ST

- Steady-state

Non-operation temperature

AC 24...48V 50/60Hz, DC 24...48V

AC/DC 20.4...57.6V

15...30VA

C2 cable 1m, 3x0.75mm2 (with 3-pole plug)C2 cable 1m, 6x0.75mm2 (with 3-pole plug)

Min. 15Nm

Selectable by L/R installation

Max. 95°

2 SPDT 6(3)A, AC 250V5° , 80°

Max. 60dB(A)

< 30s

Mechanical with pointer

>10,000 cycles

III (safety extra-low voltage)

IP54

-30...+50°C

95%RH, non condensing

Maintenance-free

248x98x58mm

Form-fit 12x12mm

Approximately 2200g

CE according to 2004/108/EC

-30...+70°C (24hr guaranteed safety)

Min. 30Nm Blocking torque - Dynamic Min. 15Nm

-40...+80°C

L

40

6.5

18850 10

ø 5.2

248

175.6

27.2

4040

8058

98

1717

5.1

1

12.2

- Auxiliary switch

12...24W @ running / 1.5...3W @ holding

26 Sub

ject

to te

chni

cal c

hang

es.

Wiring diagram: B..F.. series Spring-Return Open/Close Actuators

1 2

BLF24, BLF230M

~

- +

T

AC 24V DC 24V

S1 S2 S3 S4 S5 S6

< 80°< 5°

N L1 AC 230V (for BCF230, BF230)

Notes: • Parallel connection of several actuators is possible.

• Power consumption must be observed.

Wiring diagrams — B..F.. series Spring-Return Open/Close Actuators

1 2

BLF24-T, BLF230-TM

AC 24VDC 24V

S1 S2 S3 S4 S5 S6

< 80°< 5°

N L1 AC 230V (for BLF230-T, BF230-T)

1 2

BFG24BFG230

M

AC 24VDC 24V

S1 S2 S3 S4 S5 S6

< 145° < 25°

N L1 AC 230V (for BFG230)

1 2

M

~

- +

T

AC 24VDC 24V

S1 S2 S3 S4 S5 S6

< 145° < 25°

N L1 AC 230V (for BFG230-T)

BFG24-TBFG230-T

Tf2Tf1 Tf3 LEDBAE72B-S

Tf2Tf1 Tf3 LEDBAE72B-S

Tf2Tf1 Tf3 LEDBAE72B-S

BF24, BF230

BF24-T, BF230-T

Application with the SBS-Controldamper control and monitoring system

Connecting lead with plugs for linking to the communication and power units

S1 S2 S3 S4 S5 S6

<5° <80°

21

T ~

BLF24-T-STBF24-T-ST

Application with the SBS-Controldamper control and monitoring system

Connecting lead with plugs for linking to the communication and power units

S1 S2 S3 S4 S5 S6

<5° <80°

21

T ~

BLF24-STBF24-ST

Application with the SBS-Controldamper control and monitoring system

Connecting lead with plugs for linking to the communication and power units

S1 S2 S3 S4 S5 S6

<25° <145°

21

T ~

BFG24-T-ST

Application with the SBS-Controldamper control and monitoring system

Connecting lead with plugs for linking to the communication and power units

S1 S2 S3 S4 S5 S6

<25° <145°

21

T ~

BFG24-ST

Tf2Tf1 Tf3 LEDBAE72B-S

Connect via safetyisolating transformer

Connect via safetyisolating transformer

Connect via safetyisolating transformer!

!

!

!

Connect via safetyisolating transformer

~

- +

T

~

- +

T

Sub

ject

to te

chni

cal c

hang

es.

27

Notes: • Parallel connection of several actuator is possible.

• Power consumption must be observed.

Wiring diagrams — B..F.. series Modulating Actuators

!

1 2 3 5

AC 24VDC 24V

BLF24-SR

S1 S2 S3

< 5°

Y DC 2(0)...10V

U DC 2...10VL

0.2

.4

.6

.8

1

R0

.2

.4

.6

.8

1

Y = 0 Y = 0 Y = 0 Y = 0

R L R L

Revisible switch

Installation

!

1 2 3 5

AC 24VDC 24V

BF24-SR

S1 S2 S3 S4 S5 S6

< 80°< 5°

Y DC 2(0)..10V

U DC 2..10V

!

1 2 3 5

AC 24VDC 24V

BF24-SR-T

S1 S2 S3 S4 S5 S6

< 80°< 5°

Y DC 2(0)..10V

U DC 2..10V

Tf2Tf1 Tf3 LEDBAE72B-S

Wiring diagram: B..F.. series Spring-Return Modulating(-SR) Actuators

Connect via safetyisolating transformer

Connect via safetyisolating transformer

Connect via safetyisolating transformer

~

- +

T

~

- +

T

~

- +

T

28 Sub

ject

to te

chni

cal c

hang

es.

Wiring diagram: FS.. series Spring-Return Open/Close Actuators

• Parallel connection of several actuators is possible. • Power consumption must be observed.

Wiring diagrams — FS.. US series Spring-Return Open/Close Actuators

1 2

FSAF230 USFSAF24 US

AC 24V

M

~

- +

T

AC 24VDC 24V

1 2

FSAF24-S USFSAF230-S US

M

~

- +

T AC 230V (for FSAF230-S US)

DC 24V

30...90° 10°

!

1 2 3

1 2 3

FSLF24 USFSLF230 US

M

1 2 3

1 2 3

FSLF24-S USFSLF230-S US

MNO

S1 S2 S4 S6

NC

NO

S1 S2 S4 S6

NC

85°10°

Ground

T

AC 24V

FSNF24 USFSNF230 US

FSNF24-S USFSNF230-S US

M

S1 S2 S3 S4 S5 S6

< 85°< 5°

• No ground on 24V models.

• Provide overload protection and disconnect as required.

! • No ground on 24V models.

• Provide overload protection and disconnect as required.

! • No ground connection is required, doubled insulated.• Provide overload protection and disconnect as required.

~T

AC 24V

~T

AC 24V

AC 230V (for FSNF230 US) N L1

AC 230V (for FSAF230 US) N L1

AC 230V (for FSLF230 US)N L1 AC 230V (for FSLF230-S US)N L1

M

~ ~T

AC 24VAC 230V (for FSNF230-S US)N L1

N L1

Ground

Ground Ground

Sub

ject

to te

chni

cal c

hang

es.

29

Wiring diagram: B..E.. series Non-Spring-Return Actuators

Wiring diagrams--B..E..BR.. series Non-Spring-Return Open/Close Actuators

BE24(-12)-ST < 3 < 87

Application with theSBSE-Control

damper control and monitoring system

T ~

AC 24V

S1 S2 S3 S4 S5 S6

S1 S2 S3 S4 S5 S6

3221

~

Connecting lead with plugs for linking to theBKNE230-24 communication and power unit

BEG24-ST < 5 < 175

Application with theSBSE-Control

damper control and monitoring system

T ~

AC 24V

1 2 3

~

Connecting lead with plugs for linking to theBKNE230-24 communication and power unit

BE24(-12), BE230(-12)

S1 S2 S3 S4 S5 S6

< 3 < 87

1 2

1 2

3

3

2-wire control

AC 24VDC 24V Connect via safety

isolating transformer!

!

BEG24

S1 S2 S3 S4 S5 S6

< 5 < 175

2-wire control

AC 24VDC 24V Connect via safety

isolating transformer

BLE24(-12)-ST

AC 230V (BLE230, BE230(-12))N L

BLE24, BLE230

AC 230V (BEG230)N L

BEG230

Notes: • Parallel connection of several actuators is possible.

• Power consumption and switching thresholds must be observed.

BR24-48-F-ST

AC 24...48VDC 24...48V

1 2 3 S1 S2 S3 S4 S5 S6

<5 <80

Connect via safety islolating transformer!

~

- +

T

~

- +

T

~

- +

T

30 Sub

ject

to te

chni

cal c

hang

es.

B..F../FS..US series technical information

The typical US Fire and Smoke Damper requires 5-15 in-lb torqueper square ft. [6-17 Nm per square meter] at 171°C under dynamic load (2400 fpm [12 m/s] velocity).

Some of multiple actuators application are shown below.

Single sectionfor one actuator

Two sections for two actuators

Maximum areafor one actuator

Maximum areafor two actuators

Large multi-section assemblies

Use of blank-offs between damper sections to provide space for actuator mounting.

Blank-offChannel

Multi-section damper assemblies - typical applications

Product features

mounting

Mode of operation

High function reliability The actuator is overload-proof, needs no limit switches and halts automatically at the end stops.

Internal Aux. switch B..F.. & FS..-S US series: Actuator has two (one for BLF24-SR) internal auxiliary switches.

Manual override function

B..F.. series: Square shaft mounting - mounting the actuator on the damper spindle through a sqaure shaft adaptor. The square shaft adaptor maintains a perfect connection. An anti-rotation device has to be installed by the fire damper manufacturer, or order an anti-rotation strip device separately.

B..F.. & FSAF.. series: Damper can be operated manually and fixed in any required position. Release of the locking mechanism can be achieved manually or automatically by applying the supply voltage.

Thermal tripping device BAE72B-S

Connection to SBS-Control

B..F..-T series: Thermal trip Tf1 operates if the ambient temperature exceeds 72°C. Replaceable thermal trip Tf2/Tf3 operates if the temperature inside the duct exceeds 72°C. Both trips cause the power supply to be interrupted permanently, so that it cannot be uncancelled.

B..F..-ST series: Available with plug connectors fitted to their connecting leads. This allows the actuator to be incorporated into the SBS-Control damper monitoring system via the type BKN230-24 communication and power supply unit.

FS.. series: Direct mounting on the damper spindle by a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The special designed clamp will not crush hollow shafts. An anti-rotation device is supplied.

The actuator moves the damper to its normal working position while tensions the return spring at the same time. If the power supply is interrupted, the energy stored in the spring moves the damper back to its safe position.

Sub

ject

to te

chni

cal c

hang

es.

31

B..E.. series technical information

B.. E.. product features

Mode of operation Open/Close control is effected by means of a 2-wire system. The actuator is overload-proof and therefore remain energised while stationary at the end stops.

Signalling Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions. The position of the damper blade can be read off on a mechanical position indicator.

Manual operation The crank handle supplied with the actuator allows it to be operated manually. It also allows a functional test of the damper to be performed very easily.

Standards and specifications The design of the actuator is based on the following standards and specifications:

• Draft DIN 18232, Part 6, Sept. 1992–Fire protection in industrial buildings–Smoke and heat extraction systems

• Preliminary standard ÖNORM H 6029, May 1997–Ventilation systems–Fire smoke extraction systems

• Extracts from:–CEN/TC191, 1996–pr EN12101-8 (Smoke and heat control systems-specifications for smoke control dampers)

Safety function The safety function is guaranteed within the temperature range shown in the diagram below which is based on standard ÖNORM H 6029 and DIN 18232.

°C

0

50

100

–10 20100

Safety notes

!

TimeMin.

Test temperature acc. to standard temperature-time curve

Temperature on the BE24-ST actuator(protected by thermic isolating)

Temperature

30

• The actuator is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• The actuator is adapted and mounted to the fire and smoke damper by the damper manufacturer. For this reason, the actuator is supplied directly to safety damper manufacturers. The manufacturer then bears full responsibility for the proper functioning of the damper.

• Since very high values of torque are exerted on the damper spindle, it is advisable to use steel of at least grade St50.

• The device may only be opened at the manufacturer‘s site. It does not contain any parts which can be replaced or repaired by the user.

• The device contains electronic and electrical components and may not be disposed with the household waste. Observe local regulations and valid laws.

32 Sub

ject

to te

chni

cal c

hang

es.

Technical data

Electrical data

Functional data

Working conditions

Dimensions / weight

Thermoelectric tripping device BAE72B(-S)

Wiring diagram

Maintenance Maintenance-free

EMC CE according to 89/336/EEC

Ambient temperature range –30…+50°C

Non operation temperature –40…+50°C

Humidity test To EN 60730-1

Degree of protection IP54

Protection class III (safety extra-low voltage)

– CNPP Centre National de Prévention et Protection, F-Vernon, to NF S61-937

Testing – VdS Verband der Sachversicherer, D-Köln, to DIN 4102, Part 06

Operating temperature Tf1: duct outside temperature 72°Cthermal trips Tf2, Tf3: duct inside temperature 72°C (replaceable)

Connection Cable 1.2m long, 2×0.5 mm2, BETA flam 145(interchangeable wires)

Through resistance

Rated current Max. 3A

Rated voltage AC/DC 24V

Weight Approx. 85g

(..-S) with test button For function check

Light when- there is a supply voltage

- the test switch is not pressed- the temperature fuses are ok

Dimensions (L x W x H) See “Dimensions”

LED

1 2

M 5° 80 °

Tf1BAE72B-S

Tf2

1 2

- +

T ~

AC 24VDC 24V

Connect via safetyisolating transformer!

BLF24, BF(G)24BLF...-STBF...-ST

1 2 3 4 5 76*

Remove factory fitted jumper!*

BKN230-24...

M 5° 80 °

Tf1BAE72B-S

Tf2

1 2

Tf3

Tf3

ø 9.0 65

27

98

ø 55 40

ø 3.0 ø 3.0

ø 9.5…11

20 20

6

Dimensions [mm]

• Thermoelectric tripping device• BAE72-S, without LED (order separately)• BAE72B-S, with LED (not available for order• separately, only integrated with actuator)

Spare parts:

Thermal trip Tf2/Tf3 ZBAE72Thermal trip Tf2/95°C ZBAE95

Sub

ject

to te

chni

cal c

hang

es.

33

Dimensions [mm]

ZTPC600-B thermal protection case

Witnessed by Lloyds

Note: Cable glands and terminal blocks are not provided. Belimo does not recommend the use of brass fittings at temperatures over 300°C.

Material specification

• The ZTPC600-B thermal case is for the protection of•?Belimo safety actuators operating in an environment of • 300°C for 1 hour • 600°C for 30 minutes.

Tested with the BF actuator in accordance with EN 1210/1999 Part 3 under dynamic load conditions. Protection times quoted are at the rated temperature for the full test time. All tests where witnessed by TUV ( copies of the report available upon request) .

Protection class

Degree of protection IP42Operating temperature range 250°C (90 minutes)

300°C (1 hour)600°C (30 minutes)

MaintenanceWeightColourFlammability

Maintenance-freeLid 2.3kg, Base 2kg (without actuator)GreySelf extinguishing

Application

Principle of operation

Note

The modification and mounting of the thermal case to the fire damper is made by the manufac-turer of the damper. For this reason the thermal case is only supplied directly to the damper manufacturer. The manufacturer then takes overall responsibility for the performance of the damper.

The thermal case consists of three layers: Two intumescence and one insulation. The ZTPC600-B uses the principal of intumescence as the main form of protection. As the fire makes contact with the surface, the outer layer will intumesce or swell by a factor of four or five. A hard forms, that in turn reflects the heat back into the fire. When the first layer has expanded, the next layer intumesces.

The thermal case is designed to allow the BF range of actuators to operate in ambient tempera-tures above their specified rating. The case gives a high degree of mechanical protection and allows for the installation of 2 x M20 cable connectors to facilitate connection of fire proof cable/conduit to the case, and termination of cable to an internal connection block. The fixing of the top shell is done with screws.

439

142

215

110

30

O = 21

A

B

B

Block diagram

1 2 3 4 5 6 7

13 14 15 16 17 18

Fault12

3 54 6

a1................ a6 b1...b6

Input 1

AC 24V

Equipment cubicle

8 9 10 11 12

AC 24V

s0

yaleD

s06

yaleD

NE

PO

DE

SOL

C

tluaF

Input 2

Smoke extraction damper 6

BKNE230-24a b

M

BE(G)24-ST

Smoke extraction damper 1

BKNE230-24a b

M

BE(G)24-ST

SMOKE EXTRACTIONAUTO

CEASE SMOKE EXTRACTION

Firebrigadecontrolpanel

Fire alarm system

BKSE24-6

AC 230V

+

Service pushbutton

SMOKE EXTRACTIONAUTOCEASE SMOKE EXTRACTION

~

~

-

The b-conductors must belinked to the equipment cubicle

A tip:The signal from the Delay 0 soutput can be used as feedbackfor the smoke extraction/cease smoke extraction command.

Power supply AC 230V

Plugging connections for Belimo actuator 24V

Terminal strip, 7-pole

Cable entry for Belimo actuator

Cable entry for 2-wire conductor

LED green (damper position: CLOSED)

LED yellow (damper position: OPEN)

1

7

6

5

4

3

2

2

4

1

7

4

5

6

3

2

Retaining clip

Labelling field (zone/floor)

Labelling fields (dampers)

LED red (fault)

PRG pushbutton

LED yellow (damper position: OPEN)

LED green (damper position: CLOSED)

SET/INIT pushbutton

Plug-in/Screw terminals

1

2

3

4

5

6

7

8

9

1

7

4

5

6

3

2

8

9

Communication and control unit (BKSE24-6)

Communication and Power unit (BKNE230-24)

1 2 3 4 5 6 7 1 2 3 4 5 6

34 Sub

ject

to te

chni

cal c

hang

es.

7

Displays and operating controls / Block diagram (example)

Actuators

BLF BF BFG FSLF FSAFAuxiliary Switch1 SPDT

ZSN-BF Bracket for auxiliary switch SN1, SN2

ZA11-BF Insert square shaft 12mm/11mm

ZA18-BF Adapter insert from form-fit to round spindles Ø 20mm

ZA8-BF Insert square shaft 12mm/8mm

ZK-BF Shaft adapter

BAE72(-S) Thermoelectrical tripping device 72°C

ZG-AF Crankarm adapter kit

K4 US

K4-1 US Universal clamp for up to 1.05’’ dia.jackshaft

FSNF

ZBAE95/72

SN2 Auxiliary Switch2 SPDT

ZSN-BLF Bracket for auxiliary switch SN1, SN2

• •

Accessories

SN1

IND-AF2

ZDB-AF2

Thermoelectrical tripping device 95°C/72°C

Damper position indicator

Universal clamp for 3/8’’ to 3/4’’ shafts

Angle of rotation limiter

Sub

ject

to te

chni

cal c

hang

es.

35

Markets Asia Pacific

ASIA PACIFIC HEADQUARTERSBelimo Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2 Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]

Belimo AUSTRALIAMelbourne Office: Belimo Actuators Pty. Ltd.12 Enterprise Court Mulgrave Business Park Mulgrave, VIC 3170, Australia Tel: +61 (0)3 9545 0844 Fax: +61 (0)3 9545 0855 E-mail: [email protected]

Sydney Office: Belimo Actuators Pty. Ltd. Suite 2.20, 32 Delhi RoadNorth Ryde, NSW 2113Australia Tel: +61 (0)2 9805 1777Fax: +61 (0)2 9805 1722E-mail: [email protected]

Belimo CHINA Shanghai Office:Belimo Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2 Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]

Beijing Office:Belimo Actuators Ltd.Room 605, Hai Chang Edifice44 Liang Ma Qiao RoadBeijing 100016, P.R. ChinaTel: +86 10 6462 1382Fax: +86 10 6462 1383E-mail: [email protected] Chongqing Office:Belimo Actuators Ltd.Room 4, 9th floor, Unit 7, Luoma Jiari GardenNo. 36, QingLong Road, Nan'an District Chongqing 400060, P.R. ChinaTel: +86 23 6275 3155Fax: +86 23 6280 3380 *519E-mail: [email protected] Guangzhou Office:Belimo Actuators Ltd.Room 1202, Skyline Plaza644 Tong Fu East Road, Haizhu AreaGuangzhou 510240, P.R. ChinaTel: +86 20 3435 1860Fax: +86 20 3435 1870 E-mail: [email protected]

Belimo HONG KONGHong Kong Office:Belimo Actuators Ltd.Room 207, 2/F, New Commerce Center19 On Sum Street, Shatin, N.T., Hong KongTel: +852 2687 1716Fax: +852 2687 1795E-mail: [email protected]

Japan Office:Belimo Actuators Ltd. 7th Floor, Honjo-Azumabashi DJ Building 4-19-3, Honjo, Sumida-kuTokyo 130-0004, Japan Tel: +81 3 6823 6961 Fax: +81 3 3626 3911 E-mail: [email protected]

Malaysia Office:Belimo Actuators Ltd.12-1, Jalan PJS 10/2, Subang Indah46000 Petaling Jaya Selangor, MalaysiaTel: +603 5631 2188Fax: +603 5638 2189E-mail: [email protected]

Singapore Office: Belimo Actuators Ltd.1 Tannery Road #08-04, One TannerySingapore 347719Tel: +65 6842 1626Fax: +65 6842 1630 E-mail: [email protected]

Taiwan Office:Belimo Actuators Ltd. 7F-2, No. 343, Jhonghe Road, Yonghe CityTaipei County 234, Taiwan Tel: +886 2 2922 8805 Fax: +886 2 2922 8806 E-mail: [email protected]

Thailand Office:Belimo Actuators Ltd.90/2 Pensiri PlaceSoi Phaholyothin 32, Phaholyothin RoadChandrakasem, JatujakBangkok 10900, ThailandTel: +662 9415582-3Fax: +662 9415584E-mail: [email protected]

Belimo INDIAMumbai Office:Belimo Actuators India Pvt. Ltd. 204 Jaisingh Business Center, Parsiwada Sahar Road, Andheri (East) Mumbai 400099, India Tel: +91 22 6733 2525 / 6733 2501 Fax: +91 22 2822 2643 E-mail: [email protected]

Bangalore Office:Belimo Actuators India Pvt. Ltd. 60/1, 1st Floor, Coles Road, Frazer TownBangalore 560005, India Tel: +91 80 2558 0421 / 6565 6978 Fax: +91 80 2558 0422 E-mail: [email protected]

New Delhi Office:BELIMO Actuators India Pvt. Ltd.Flat No. 516, DLF Tower – B, Jasola Distt. Centre, Jasola, New Delhi – 110025Phone: +91 11 41078501 to 41078507 Fax:� +91 11 41078508E-mail: [email protected]

Innovation, Quality and Consultancy:A partnership for motorising HVAC Actuators

BELIMO Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]

BELIMO Aircontrol (USA), Inc.43 Old Ridgebury RoadDanbury, CT 06813-2928, USATel: +800 543-9038 / 203 791-9915Fax: +800 228-8283 / 203 791-9919

BELIMO Automation AGBrunnenbachstrasse 18340 Hinwil, SwitzerlandTel: +41 43 843 61 11Fax: +41 43 843 62 68E-mail: [email protected]