Heat Exchange“The Alphabet Boys” Group K1
Colin Hannahan, Nerses Haroutunian, Jon Gigas, Adam Haidari
1
![Page 2: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/2.jpg)
Table of ContentsCalibration of flow rates with pneumatic valves………………………….……...3
Heat transfer coefficients compared with Reynolds # …………….……….….11
Heat Loss and Fouling Analysis ….………………………………………..……18
Conclusions and recommendations…………………………………..…………22
2
![Page 3: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/3.jpg)
Calibrating Flow
3
![Page 4: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/4.jpg)
Pneumatic valve setting corresponds to pressure (psig)
Measure flows by measuring mass of water over a given time (lbs/sec)
Calibrating Flowrates: Methods
4
Figure 1. A fully closed pneumatic valve. Figure 2. A partially opened pneumatic valve.
![Page 5: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/5.jpg)
Calibrating Flowrates: Methods
5
Valves
Calibrating Operation Mode Steam Cooling Water
Process Water
Cooling Water Co-Current Closed Variable Constant
Cooling Water Counter-Current Closed Variable Constant
Process Water Counter-Current Closed Constant Variable
Figure 3. LabView dials for pneumatic valve of process and cooling waters.
Figure 4. View of apparatus outlining direction of flows.
![Page 6: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/6.jpg)
Calibrating Flowrates: Calibration Curves
6Figure 5. Calibration curve for cooling water in co-current operation.
![Page 7: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/7.jpg)
Calibrating Flowrates: Calibration Curves
7
Figure 6. Calibration curve for cooling water in counter-current operation.
![Page 8: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/8.jpg)
Calibrating Flowrates: Calibration Curves
8Figure 7. Calibration curve for process water, independent of operation mode.
![Page 9: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/9.jpg)
Flowmeter Error AnalysisFlowmeter readings were compared to values from valve correlation on all data logs.
Figure 8. Flowmeter error of process water at various flowrates. Figure 9. Flowmeter error of cooling water at various flowrates. 9
![Page 10: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/10.jpg)
Calibrating Flowrates: Suggestions1. Cooling water flowrate undetermined under 6 psig.
2. First open each valve fully, then reduce to setpoint.
3. Redundancy moving between different operating method.
10
![Page 11: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/11.jpg)
Calculating Heat Transfer Coefficients
11
ho and hi
![Page 12: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/12.jpg)
12
ho and hi
Figure 10. Cooling-process water heat exchanger
Figure 11. Steam heat exchanger.
![Page 13: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/13.jpg)
hi vs Reynolds Number
13
Figure 12. Comparing calculated Reynolds number to heat transfer coefficient for process water
Source: Bergman et al. (2007)
![Page 14: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/14.jpg)
ho vs Reynolds Number
14Figure 13. Comparing calculated Reynolds number to heat transfer coefficient for cooling water in co-current operation mode.
Source: Bergman et al. (2007)
![Page 15: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/15.jpg)
ho vs Reynolds Number
15Figure 14. Comparing calculated Reynolds number to heat transfer coefficient for cooling water in counter-current operation mode.
Source: Bergman et al. (2007)
ho,steam=11.7 kW/(m^2*s)
![Page 16: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/16.jpg)
Reynolds Number Calculation
16
Figure 15. Kinematic viscosity of water decreases with increasing temperature.
![Page 17: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/17.jpg)
Calculating hi, ho
17
![Page 18: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/18.jpg)
Heat Loss and Fouling Analysis
18
![Page 19: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/19.jpg)
Heat Loss: Methodology● Adjusted valve W2 to maintain constant liquid level in the sight glass
● Measured condensate flowrate and performed energy balance on the overall system
Balance:
19
![Page 20: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/20.jpg)
Heat Loss: Results● Average total heat loss: 4.3 kW
● Average loss as a percentage of total heat transferred from steam: 9.9%
● Most loss likely due to radiation from steam piping.
20
![Page 21: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/21.jpg)
Fouling Analysis● Observed rust in cooling water stream, but not in process water steam
● Significantly higher values of hi vs ho for cooling water at the same
Reynolds number
● Assumed differences due to fouling on outer surface of pipe
21
![Page 22: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/22.jpg)
Conclusions● Flowrate valve correlations were developed based on pneumatic valve pressure
○ Flowrate range (0.2 - 1.35 lbs/sec)
● h vs Reynolds number consistent with correlation
● Fouling in cooling water heat exchanger
● Overall heat loss: 4 kW
○ ~ 10 % of total heat transferred
22
![Page 23: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/23.jpg)
Recommendations● Valve C7 is very sticky
● Low cooling water valve settings are inaccurate
● Open valves fully (17 psig) to start before adjusting to desired flow
● Ensure that no steam flows out of apparatus
23
![Page 24: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/24.jpg)
ReferencesDelta T Heat Exchangers. Fouling in Heat Exchangers. http://deltathx.com/uploadsdocs/foulingfactors.pdf (accessed October 4, 2015).
Engel, Y. A.; Boles, M. A. Thermodynamics: An Engineering Approach; Seventh.; McGraw-Hill: New York, NY, 2011; pp. 868–870.
Kestin, Joseph; Sokolov, Mordechai; Wakeham, William A. Viscosity of Liquid Water in the Range -8 °C to 150 °C. Journal of Physical and Chemical Reference Data. 1978, 7, 941-948.
Pipe and Hose. American National Pipe - NPT/NPS | Pipe and Hose. http://pipeandhouse.com/node/19 (accessed October 4, 2015).
24
![Page 25: Final Presentation- Heat Exchange](https://reader030.vdocuments.mx/reader030/viewer/2022020119/58eed9921a28ab5e3a8b45d9/html5/thumbnails/25.jpg)
Process Flow Diagram
25