geokiss.comgeokiss.com/software/tideload10v1.xls · xls file · web view · 2010-01-26cooling...

50
ta can be copied & pasted from Weather Tab belo Outdoor Temps. Heating (F) tdoor Temps Max Dry Bulb Cooling (º Temps at Max Wet Bulb Temps at Max Hum Ratio Location LatitudelevationFeet TodbHeat DRangeHtg TodbCool TowbCool DailyRange DBatMaxWB Max WB DailyRange DBatMaxHR WBatMaxH DailyRange Tuscaloosa, AL 33 171 20 20 96 76 20 90 80 16 84 79 12 Indoor Temperatures TidbHeat DelTHeat TidbCool TiwbCool DelTCool Tmean CLTDcor Windoor InGrains Woutdoor OutGrains DelW Daytime 70 50 75 63 21 86 4 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! TidbHeatUnoc DelTHeatUnocTidbCoolUnoc TiwbCoolUnocDelTCoolUnoc TmeanUnoc CLTDcorUnoc WindoorUnoc DelWUnoc Evening and Night 60 40 80 67 16 86 -1 #VALUE! #VALUE! #VALUE! Enter percentage of requirement to max requirement in each time period. 8 am - Noon Noon- 4 pm 4 pm - 8 pm 8 pm - 8 am Occupancy 100% 100% 0% 0% Input Cells Ventilation Air 100% 100% 10% 10% Lighting Load 100% 100% 10% 10% Floor Plan of Example Building Internal Load 100% 100% 0% 0% Number of Days/Week Occupied 5 Output Cells - Do Not Type in these Heating & Cooling Load Calculation Program - CLTD/CLF/SCL Method Input values in Yellow Cells. Values in blue cells are calculated. Building description data input and heating/cooling load output results are in "Zones" Worksheets. Supplemental data can be found in other worksheets and can be cut and pasted into Zone Worksheets. - References: ASHRAE Handbook of Fundamentals (1997), HVAC Simplified (2006), and ACCA Manual N, 4th Ed. 1988. School Addition in Tuscaloosa 10 Classroom Zones with 2 Restrooms (Zone 11) No heat recovery units (HRUs). Loads done at Max. dry bulb condition - check for loads at Max. wet bulb and Max. humidity ratio conditions (See Plan Below) Click on Weather worksheet here for data for 25 cities. See ASHRAE Fundamentals Handbook (Climatic Data Chapter) for additional sites. Note 2: If Macro security level is set at high, this program will result in errors in the cells [NAME?]. To reset the security level, 1. Close the program. 2. Click on "Tools" on the main tool bar, select "Macro", select "Security. 3. Reset security level to Medium (recommended) or Low 4. Exit Excel 5. Re-Open Excel 6. Run program R es tro o m C la ss ro o m 1 75 ' 5 4 2 3 1 6 0' 1 1 1 0 9 8 7 6

Upload: truonglien

Post on 08-Apr-2018

215 views

Category:

Documents


2 download

TRANSCRIPT

Data can be copied & pasted from Weather Tab below. Outdoor Temps. Heating (F) Outdoor Temps Max Dry Bulb Cooling (ºF) Temps at Max Wet Bulb Temps at Max Hum RatioLocation Latitude ElevationFeet TodbHeat DRangeHtg TodbCool TowbCool DailyRange DBatMaxWB Max WB DailyRange DBatMaxHR WBatMax DailyRange

Tuscaloosa, AL 33 171 20 20 96 76 20 90 80 16 84 79 12

Indoor Temperatures TidbHeat DelTHeat TidbCool TiwbCool DelTCool Tmean CLTDcor Windoor InGrains Woutdoor OutGrains DelWDaytime 70 50 75 63 21 86 4 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

TidbHeatUnocDelTHeatUnoc TidbCoolUnoc TiwbCoolUnoc DelTCoolUnoc TmeanUnoc CLTDcorUnoc WindoorUnoc DelWUnocEvening and Night 60 40 80 67 16 86 -1 #VALUE! #VALUE! #VALUE!

Enter percentage of requirement to max requirement in each time period.8 am - Noon Noon- 4 pm 4 pm - 8 pm 8 pm - 8 am

Occupancy 100% 100% 0% 0% Input CellsVentilation Air 100% 100% 10% 10%Lighting Load 100% 100% 10% 10% Floor Plan of Example BuildingInternal Load 100% 100% 0% 0%

Number of Days/Week Occupied 5

Output Cells - Do Not Type in these

Heating & Cooling Load Calculation Program - CLTD/CLF/SCL Method

Input values in Yellow Cells. Values in blue cells are calculated. Building description data input and heating/cooling load output results are in "Zones" Worksheets. Supplemental data can be found in other worksheets and can be cut and pasted into Zone Worksheets. - References: ASHRAE Handbook of Fundamentals (1997), HVAC Simplified (2006), and ACCA Manual N, 4th Ed. 1988.

School Addition in Tuscaloosa 10 Classroom Zones with 2 Restrooms (Zone 11) No heat recovery units (HRUs). Loads done at Max. dry bulb condition - check for loads at Max. wet bulb and Max. humidity ratio conditions (See Plan Below)

Click on Weather worksheet here for data for 25 cities. See ASHRAE Fundamentals Handbook (Climatic Data Chapter) for additional sites.

Note 2: If Macro security level is set at high, this program will result in errors in the cells [NAME?]. To reset the security level,1. Close the program.2. Click on "Tools" on the main tool bar, select "Macro", select "Security.3. Reset security level to Medium (recommended) or Low4. Exit Excel5. Re-Open Excel 6. Run program

R e s t r o o m

C l a s s r o o m

1 7 5 '

5

4

2

3

1

6 0 '

1 1

1 0

9

8

7

6

Zone 1 to 1 Zone 2 to 5 Zone 6 to 6 Zone 7 to 10 Zone 11 to 11 Zone to Zone to Zone toArea Morning Afternoon Morning Area Morning Afternoon Morning Area Morning Afternoon Morning Area Morning Afternoon Morning Area Morning Afternoon Morning Area Morning Afternoon Morning Area Morning Afternoon Morning Morning Afternoon Morning

960 Cooling Cooling Heating 960 Cooling Cooling Heating 960 Cooling Cooling Heating 960 Cooling Cooling Heating 900 Cooling Cooling Heating Cooling Cooling Heating Cooling Cooling Heating Cooling Cooling HeatingSolar Shade Coeff. SCL (am) SCL (pm) qc (am) qc(pm) qh qc (am) qc(pm) qh qc (am) qc(pm) qh qc (am) qc(pm) qh qc (am) qc(pm) qh qc (am) qc(pm) qh qc (am) qc(pm) qh qc (am) qc(pm) qhWindows (N) 0.55 35 35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Windows (E) 0.55 142 48 90 7.03 2.38 90 7.03 2.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Windows (S) 0.55 43 48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Windows (W) 0.55 32 140 0.00 0.00 0.00 0.00 90 1.58 6.93 90 1.58 6.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Conduction CLTD(am) CLTD(pm)Windows (N) 0.5 4 14 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Windows (E) 0.5 4 14 50 90 0.36 0.81 2.25 90 0.36 0.81 2.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Windows (S) 0.5 4 14 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Windows (W) 0.5 4 14 50 0.00 0.00 0.00 0.00 0.00 0.00 90 0.36 0.81 2.25 90 0.36 0.81 2.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Conduction CLTD(am) CLTD(pm)Walls (N) 0.05 6 13 50 280 0.14 0.24 0.70 0.00 0.00 0.00 280 0.14 0.24 0.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Walls (E) 0.05 15 34 50 230 0.22 0.44 0.58 230 0.22 0.44 0.58 230 0.22 0.44 0.58 230 0.22 0.44 0.58 150 0.14 0.29 0.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Walls (S) 0.05 5 17 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Walls (W) 0.05 8 14 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 150 0.09 0.14 0.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Conduction CLTD(am) CLTD(pm)Doors (N) 0.4 10 25 50 20 0.11 0.23 0.40 0.00 0.00 0.00 20 0.11 0.23 0.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Doors (E) 0.4 45 38 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Doors (S) 0.4 6 39 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Doors (W) 0.4 5 33 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Roof/Ceiling CLTD(am) CLTD(pm)Type A 0.03333333 7 67 50 960 0.35 2.27 1.60 960 0.35 2.27 1.60 960 0.35 2.27 1.60 960 0.35 2.27 1.60 900 0.33 2.13 1.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00Type B 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Floor50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Slab/Basemt Ins. Position Insulation UP Perim.-ft Perim.-ft Perim.-ft Perim.-ft Perim.-ft Perim.-ft Perim.-ft Perim.-ftVertical R5 x 48 in #VALUE! 50 62 ### 32 ### 62 ### 32 ### 30 ### ### ### ###

Ventilation cfm cfm cfm cfm cfm cfm cfm cfm Sensible 1.1 13 21 50 350 5.01 8.09 19.25 350 5.01 8.09 19.25 350 5.01 8.09 19.25 350 5.01 8.09 19.25 100 1.43 2.31 5.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Latent 4840 #VALUE! #VALUE! 350 ### ### 350 ### ### 350 ### ### 350 ### ### 100 ### ### 0 ### ### 0 ### ### 0 ### ###

InfiltrationVent Air Fan TSP = 1 in. wtr. 74 0.25 0.25 74 0.25 0.25 74 0.25 0.25 74 0.25 0.25 21 0.07 0.07 0 0.00 0.00 0 0.00 0.00 0 0.00 0.00

People Btu/person CLF(am) CLF(pm) People People People People People People People People Sensible 245 0.68 0.91 25 4.17 5.57 25 4.17 5.57 25 4.17 5.57 25 4.17 5.57 8 1.33 1.78 0.00 0.00 0.00 0.00 0.00 0.00 Latent 155 1 1 25 3.88 3.88 25 3.88 3.88 25 3.88 3.88 25 3.88 3.88 8 1.24 1.24 0 0.00 0.00 0 0.00 0.00 0 0.00 0.00Internal CLF(am) CLF(pm) Watts Watts Watts Watts Watts Watts Watts Sensible 3.412 0.68 0.91 700 1.62 2.17 700 1.62 2.17 700 1.62 2.17 700 1.62 2.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Latent 1 1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

CLF(am) CLF(pm) Watts Watts Watts Watts Watts Watts Watts WattsLighting 3.412 0.87 0.95 1 1248 3.70 4.05 1248 3.70 4.05 1248 3.70 4.05 1248 3.70 4.05 720 2.14 2.33 0 0.00 0.00 0 0.00 0.00 0.00 0.00

### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ###Ductwork Insulation Leakage Location Location Location Location Location Location Location LocationSensible R8 Sealed S-Ext ### ### ### S-Ext ### ### ### S-Ext ### ### ### S-Ext ### ### ### S-Ext ### ### ### S-Ext ### ### ### S-Ext ### ### ### S-Ext ### ### ###Latent ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ###

Entire Building Totals No. of Zones like this = 1 No. of Zones like this = 4 No. of Zones like this = 1 No. of Zones like this = 4 No. of Zones like this = 1 No. of Zones like this = 0 No. of Zones like this = 0 No. of Zones like this = 0Afternoon Vent Air 3600 cfm #VALUE! 350 cfm ### 350 cfm ### 350 cfm ### 350 cfm ### 100 cfm ### 0 cfm ### 0 cfm ### 0 cfm ###Total Sensible (MBtu/h) #VALUE! #VALUE! Sens. ### ### Sens. ### ### Sens. ### ### Sens. ### ### Sens. ### ### Sens. ### ### Sens. ### ### Sens. ### ###Total Latent (MBtu/h) #VALUE! #VALUE! Lat. ### ### Lat. ### ### Lat. ### ### Lat. ### ### Lat. ### ### Lat. ### ### Lat. ### ### Lat. ### ###Total Gain (MBtu/h) #VALUE! #VALUE! TotGain ### ### TotGain ### ### TotGain ### ### TotGain ### ### TotGain ### ### TotGain ### ### TotGain ### ### TotGain ### ###

SHR #VALUE! #VALUE! SHR ### ### SHR ### ### SHR ### ### SHR ### ### SHR ### ### SHR ### ### SHR ### ### SHR ### ###Total Loss (MBtu/h) #VALUE! NetLoss #VALUE! TotLoss ### NetLoss ### TotLoss ### NetLoss ### TotLoss ### NetLoss ### TotLoss ### NetLoss ### TotLoss ### NetLoss ### TotLoss ### NetLoss ### TotLoss ### NetLoss ### TotLoss ### NetLoss ###

Total Area 10500.0

Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2

U (Btu/hr-ft2-F) DT Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT(flr) Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2 Area-ft2

DT(slab)

DT(am) DT(pm) DT

ERU Eff. (sen.) = DW DW

ERU Eff. (lat.) =

F(ballast)

Net Sen.w/o duct

Enter CLTDs directly from Tables. Program will correct for temperatures.

See other sheets for CLTD, CLF, SCL & U-values.

For Printout of 8 zones - Use Legal Paper

Zone 1 to 1 Zone Area Night Evening Evening Area

960 Cooling Cooling Heating 960Solar Shade Coeff. SCL (ngt) SCL (eve) qc(nite) qc(eve) qh(eve)Windows (N) 0.55 0 35 0 0.00 0.00 0Windows (E) 0.55 0 16 90 0.00 0.79 90Windows (S) 0.55 0 17 0 0.00 0.00 0Windows (W) 0.55 0 142 0 0.00 0.00 0Other 0 0 0.00 0.00 0

Conduction CLTD(ngt) CLTD(eve)Windows (N) 0.5 0 12 28 0 0.00 0.00 0.00 0Windows (E) 0.5 0 12 28 90 -0.05 0.50 1.26 90Windows (S) 0.5 0 12 28 0 0.00 0.00 0.00 0Windows (W) 0.5 0 12 28 0 0.00 0.00 0.00 0Other 0 0 0.00 0.00 0.00 0Other 0 0 0.00 0.00 0.00 0Conduction CLTD(ngt) CLTD(eve)Walls (N) 0.05 12 20 28 280 0.15 0.27 0.39 0Walls (E) 0.05 14 34 28 230 0.15 0.38 0.32 230Walls (S) 0.05 14 28 28 0 0.00 0.00 0.00 0Walls (W) 0.05 45 40 28 0 0.00 0.00 0.00 0Other 0 0 0.00 0.00 0.00 0Other 0 0 0.00 0.00 0.00 0Conduction CLTD(ngt) CLTD(eve)Doors (N) 0.4 3 29 28 20 0.02 0.22 0.22 0Doors (E) 0.4 3 30 28 0 0.00 0.00 0.00 0Doors (S) 0.4 3 35 28 0 0.00 0.00 0.00 0Doors (W) 0.4 5 69 28 0 0.00 0.00 0.00 0Other 0 0 0.00 0.00 0.00 0Other 0 0 0.00 0.00 0.00 0Roof/Ceiling CLTD(ngt) CLTD(eve)Type A 0.03333333 11 79 28 960 0.32 2.50 0.90 960Type B 0 28 0 0.00 0.00 0.00 0

Floor0 28 0 0.00 0

Slab/Basemt Ins. Position Insulation UP Perim.-ft Perim.-ftVertical R5 x 48 in #VALUE! 28 62 ### 32

Ventilation 28 cfm cfm Sensible 1.1 15 5 28 350 0.58 0.19 1.08 350

0 Latent 4840 #VALUE! #VALUE! 350 ### ### 350

00%

Vent Air Fan TSP = 1 in. wtr. 74 0.25 0.25 74

People Btu/person CLF(am) CLF(pm) People People Sensible 245 0.04 0.31 25 0.00 0.00 25 Latent 155 1 1 25 0.00 0.00 25

Area-ft2 Area-ft2

U (Btu/hr-ft2-F) DT(eve) Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT(eve) Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT(eve) Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT(eve) Area-ft2 Area-ft2

U(Btu/hr-ft2-F) DT(flr) Area-ft2 Area-ft2

DT(slab)

DT(eve) DT(ngt)

HRU Eff. (sen.) = DW DW

HRU Eff. (lat.) =Infil (% of Vent)

Enter CLTDs directly from Tables. Program will correct for temperatures.

See other sheets for CLTD, CLF, SCL & U-values.

For Printout of 8 zones - Use Legal Paper

Internal CLF(am) CLF(pm) Watts Watts Sensible 3.412 0.04 0.31 700 0.10 0.74 700

Btu/h Btu/h Latent 1 1 0 0.00 0.00 0

CLF(am) CLF(pm) Watts WattsLighting 3.412 0.02 0.12 1 1000 0.07 0.41 1248

### ### ###Ductwork Insulation Leakage Location LocationSensible R3 NoWrap-Unsealed S-Ext ### ### ### S-ExtLatent ### ###

Entire Building Totals No. of Zones like this = 1 No. of Zones like this =Night Vent Air 360 cfm #VALUE! 35 cfm ###Total Sensible (MBtu/h) #VALUE! #VALUE! Sens. ### ### Sens.Total Latent (MBtu/h) #VALUE! #VALUE! Lat. ### ### Lat.Total Gain (MBtu/h) #VALUE! #VALUE! TotGain ### ### TotGain

SHR #VALUE! #VALUE! SHR ### ### SHRTotal Loss (MBtu/h) #VALUE! NetLoss #VALUE! TotLoss ### NetLoss ### TotLoss

Total Area 10500.0sqft/ClgTon #VALUE! ###ClLoad/sqft #VALUE! ###HtLoad/sqft #VALUE! ###People/sqft 10.3 26.0

F(ballast)

Net Sen.w/o duct

ft2/Ton ft2/ton ft2/tonBtu/hr·ft2 Btu/hr·ft2 Btu/hr·ft2

Btu/hr·ft2 Btu/hr·ft2 Btu/hr·ft2

Occupancy/1000ft2= P/Mft2= P/Mft2=

2 to 5 Zone 6 to 6 Zone 7 to 10 Zone Night Evening Evening Area Night Evening Evening Area Night Evening Evening Area

Cooling Cooling Heating 960 Cooling Cooling Heating 960 Cooling Cooling Heating 900qc(nite) qc(eve) qh(eve) qc(nite) qc(eve) qh(eve) qc(nite) qc(eve) qh(eve)

0.00 0.00 0 0.00 0.00 0 0.00 0.00 00.00 0.79 0 0.00 0.00 0 0.00 0.00 00.00 0.00 0 0.00 0.00 0 0.00 0.00 00.00 0.00 90 0.00 7.03 90 0.00 7.03 00.00 0.00 0 0.00 0.00 0 0.00 0.00 0

0.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.18 0.72 1.26 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 90 0.18 0.72 1.26 90 0.18 0.72 1.26 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.00 0.00 0.00 280 0.22 0.34 0.39 0 0.00 0.00 0.00 00.21 0.44 0.32 230 0.21 0.44 0.32 230 0.21 0.44 0.32 1500.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 1500.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.00 0.00 0.00 20 0.06 0.26 0.22 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.48 2.66 0.90 960 0.48 2.66 0.90 960 0.48 2.66 0.90 9000.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.00 0 0.00 0 0.00 0Perim.-ft Perim.-ft Perim.-ft Perim.-ft

### 62 ### 32 ### 30cfm cfm cfm

0.58 0.19 1.08 350 0.58 0.19 1.08 350 0.58 0.19 1.08 100

### ### 350 ### ### 350 ### ### 100

0.25 0.25 74 0.25 0.25 74 0.25 0.25 21

People People People0.00 0.00 25 0.00 0.00 25 0.00 0.00 80.00 0.00 25 0.00 0.00 25 0.00 0.00 8

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Watts Watts0.10 0.74 700 0.10 0.74 700 0.10 0.74 0

Btu/h Btu/h Btu/h0.00 0.00 0 0.00 0.00 0 0.00 0.00 0

Watts Watts Watts0.09 0.51 1248 0.09 0.51 1248 0.09 0.51 720### ### ### ### ### ### ### ### ###

Location Location Location Location### ### ### S-Ext ### ### ### S-Ext ### ### ### S-Ext### ### ### ### ### ###

No. of Zones like this = 4 No. of Zones like this = 1 No. of Zones like this = 4 No. of Zones like this =35 cfm ### 35 cfm ### 35 cfm ###

### ### Sens. ### ### Sens. ### ### Sens.### ### Lat. ### ### Lat. ### ### Lat.### ### TotGain ### ### TotGain ### ### TotGain### ### SHR ### ### SHR ### ### SHR### NetLoss ### TotLoss ### NetLoss ### TotLoss ### NetLoss ### TotLoss

### ### ###### ### ###### ### ###

26.0 26.0 26.0

ft2/ton ft2/ton ft2/tonBtu/hr·ft2 Btu/hr·ft2 Btu/hr·ft2

Btu/hr·ft2 Btu/hr·ft2 Btu/hr·ft2

P/Mft2= P/Mft2= P/Mft2=

11 to 11 Zone to Zone to Zone Night Evening Evening Area Night Evening Evening Area Night Evening Evening Area

Cooling Cooling Heating 0 Cooling Cooling Heating 0 Cooling Cooling Heating 0qc(nite) qc(eve) qh(eve) qc(nite) qc(eve) qh(eve) qc(nite) qc(eve) qh(eve)

0.00 0.00 0 0.00 0.00 0 0.00 0.00 00.00 0.00 0 0.00 0.00 0 0.00 0.00 00.00 0.00 0 0.00 0.00 0 0.00 0.00 00.00 0.00 0 0.00 0.00 0 0.00 0.00 00.00 0.00 0 0.00 0.00 0 0.00 0.00 0

0.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.14 0.29 0.21 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.37 0.33 0.21 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.45 2.49 0.84 0 0.00 0.00 0.00 0 0.00 0.00 0.00 00.00 0.00 0.00 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

0.00 0 0.00 0 0.00 0Perim.-ft Perim.-ft Perim.-ft Perim.-ft

### 0 #VALUE! 0 ### 0cfm cfm cfm

0.17 0.06 0.31 0 0.00 0.00 0.00 0 0.00 0.00 0.00 0

### ### 0 ### ### 0 ### ### 0

0.07 0.07 0 0.00 0.00 0 0.00 0.00 0

People People People0.00 0.00 0 0.00 0.00 0 0.00 0.00 00.00 0.00 0 0.00 0.00 0 0.00 0.00 0

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Area-ft2 Area-ft2 Area-ft2

Watts Watts Watts0.00 0.00 0 0.00 0.00 0 0.00 0.00 0

Btu/h Btu/h Btu/h0.00 0.00 0 0.00 0.00 0 0.00 0.00 0

Watts Watts Watts0.05 0.29 0 0.00 0.00 0 0.00 0.00 0### ### ### ### ### #VALUE! ### ### ###

Location Location Location Location### ### ### S-Ext ### ### #VALUE! S-Ext ### ### ### S-Ext### ### ### ### ### ###

No. of Zones like this = 1 No. of Zones like this = 0 No. of Zones like this = 0 No. of Zones like this =10 cfm ### 0 cfm #VALUE! 0 cfm ###

### ### Sens. ### ### Sens. ### ### Sens.### ### Lat. ### ### Lat. ### ### Lat.### ### TotGain ### ### TotGain ### ### TotGain### ### SHR ### ### SHR ### ### SHR### NetLoss ### TotLoss ### NetLoss #VALUE! TotLoss ### NetLoss ### TotLoss

### ### ###### ### ###### ### ###8.9 #DIV/0! #DIV/0!

ft2/ton ft2/ton ft2/tonBtu/hr·ft2 Btu/hr·ft2 Btu/hr·ft2

Btu/hr·ft2 Btu/hr·ft2 Btu/hr·ft2

P/Mft2= P/Mft2= P/Mft2=

toNight Evening Evening

Cooling Cooling Heatingqc(nite) qc(eve) qh(eve)

0.00 0.000.00 0.000.00 0.000.00 0.000.00 0.00

0.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.00

0.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.00

0.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.000.00 0.00 0.00

0.00 0.00 0.000.00 0.00 0.00

0.00Perim.-ft

###

0.00 0.00 0.00

### ###

0.00 0.00

0.00 0.000.00 0.00

0.00 0.00

0.00 0.00

0.00 0.00### ### ###

Location### ### ###### ###

No. of Zones like this = 00 cfm ###

### ###### ###### ###### ###### NetLoss ###

#########

#DIV/0!

A B C D E F

Location Lat. Elev. Heating-99.60% -0.40% -0.40%

D.Range DB MWB D.Range MDBCity/State °N Ft. °F °F °F °F °F °F

Albuquerque, NM 35 5320 13 22 96 60 25 83Atlanta, GA 34 1033 18 17 93 75 17 88Baltimore, MD 39 154 11 15 93 75 19 88Birmingham, AL 34 630 18 19 94 75 19 89Boise, ID 44 2870 2 13 96 63 30 90Boston, MA 42 30 7 13 91 73 15 87Brownsville, TX 26 20 36 18 95 78 17 89Chicago, IL 42 673 -6 14 91 74 20 88Cleveland, OH 41 804 1 13 89 73 19 85Dallas, TX 33 597 17 18 100 74 20 92Denver, CO 40 5330 -3 24 93 60 27 81Lake Charles, LA 30 33 29 17 93 78 16 88Los Angeles, CA 34 105 43 15 85 64 11 78Madison, WI 43 860 -10 16 90 74 21 86Miami, FL 26 13 46 15 91 77 11 87Minneapolis, MN 45 837 -16 16 91 73 19 88Nashville, TN 36 590 10 17 94 76 19 89Omaha, NE 41 1332 -8 18 95 75 20 90Oklahoma City 35 1300 9 19 99 74 21 91Phoenix, AZ 34 1089 34 22 110 70 23 97Raleigh, NC 36 440 16 19 93 76 19 88Sacramento, CA 39 23 31 15 100 69 33 96St. Louis, MO 39 564 2 15 95 76 18 90Salt Lake, UT 41 4230 6 14 96 62 28 85Seattle, WA 47 450 23 9 85 65 18 83Tallahassee, FL 30 69 25 23 95 77 19 89Tuscaloosa, AL 33 171 20 20 96 76 20 90

Cooling 1 Evaporation2

1This design conditions typically result in the highest sensible cooling load and highest total load when ventilation requirements and infiltration are low.2These design conditions will result in higher total cooling loads when the ventilation air requirements and infiltration are high in humid and moderate climates.3These design conditions typically result cooling loads with the lowest sensible heat ratio (SHRLoad).4 Gr = Grains of moisture (7000 Grains = 1 lb)

The Table below provides only a few of the sites listed in electronic format in the 2005 ASHRAE Fundamentals Handbook. The 2001 version of the Handbook (Chapter 27) contains tablular climatic data for over 1200 locations in the USA and Canada and 1700 international locations.

F G

-0.40% -0.40%WB D.Range DB WB D.Range DP HR°F °F °F °F °F °F65 12 68 63 5 61 9877 14 82 76 10 74 13378 15 83 77 10 75 13278 14 83 77 10 75 13566 24 72 63 5 58 7975 14 80 74 8 72 11980 16 83 79 10 78 14677 17 84 77 20 74 13076 19 82 75 10 73 12578 13 82 77 8 75 13265 15 69 63 5 60 9680 12 84 80 10 78 14870 8 75 70 6 67 9977 17 83 76 12 74 12980 9 83 79 8 78 14476 16 83 76 11 73 12478 14 83 77 10 75 13478 15 85 77 11 75 13677 14 83 76 11 73 12976 17 82 74 13 71 11878 14 82 77 10 75 13472 29 82 69 12 62 8479 15 85 78 13 76 13866 18 73 64 5 60 9266 16 71 64 5 60 7880 15 83 79 11 77 14280 16 84 79 12 77 142

Evaporation2 Dehumidification3

Gr4

1This design conditions typically result in the highest sensible cooling load and highest total load when ventilation requirements and infiltration are low.2These design conditions will result in higher total cooling loads when the ventilation air requirements and infiltration are high in humid and moderate climates.3These design conditions typically result cooling loads with the lowest sensible heat ratio (SHRLoad).4 Gr = Grains of moisture (7000 Grains = 1 lb)

The Table below provides only a few of the sites listed in electronic format in the 2005 ASHRAE Fundamentals Handbook. The 2001 version of the Handbook (Chapter 27) contains tablular climatic data for over 1200 locations in the USA and Canada and 1700 international locations.

Air (Heat Flow▲▼) Btu Insulation BtuExt. Surface (7½ mph) 0.25 3½ inch Fiberglass 11Ext. Surface (15 mph) 0.17 w/ 20% wood framing 9.6Inside Surface 0.68 3½ inch Fiberglass 131 in. Vertical Air Gap 0.8-1.6 w/ 20% wood framing 10.54 in. Vertical Air Gap 0.9-1.5 5½ inch Fiberglass 191 in. Horizontal Air Gap 0.8▲-1.7▼ w/ 10% wood framing 17.34 in. Horizontal Air Gap 0.8▲-2.2▼ w/ 20% wood framing 15.2

7¼ inch Fiberglass 25Exterior Materials w/ 10% wood framing 21U-Values in Btu /hr-°F-ft24 inch Face Brick 0.45 9¼ inch Fiberglass 30Steel siding 0 w/ 10% wood framing 26Vinyl Siding (0.06 in.) 0.06 11¼ inch Fiberglass 381 inch Stucco 0.21 w/ 10% wood framing 32.53/4 inch Plywood 0.93 Cellulose 3.7/in.1/2 inch Plywood 0.62 w/ 10% wood framing 3.1/in.5/8 inch Hardboard 0.85 w/ 20% wood framing 2.7/in.3/8 inch Hardboard 0.5 Panel-3½"beadbrd.+OSB 12.81/2 in. Veg. (Black) Board 1.32 Panel-3½"extr.poly+OSB 17Roof Stone/Slag 0.1/in. 1 inch Duct Liner/Wrap 4Building Wrap, Felt ~ 0 2 inch Duct Liner/Wrap 87/16" OSB 0.5 Expanded Polysty (beads) 3.5/in.Interior Extruded Polystyrene 5.0/in.1/2 inch Gypsum Board 0.45 Polyisocyanurate 6.0/in.5/8 inch Gypsum Board 0.56 Polyurethane foam 6.0/in.1/2 inch Acoustical Tile 1.79

hr-°F-ft 2 hr-°F-ft 2Table 7.1 R-Values for Building Materials and Structural Units

Out. Surface Face brick 2" extr,polyStructural Btu R(Total)= 0.25 0.45 108 inch LW block 2 R(Total)= 12.12 with perlite cores 5.5 U (Overall)= 0.08312 inch LW block 2.4 with perlite cores 7.212 inch HW block 1.11 R(Total)= 13Concrete 0.14/in. U (Overall)= 0.077Softwood 1.25/in.Hardwood 0.9/in.

% Total Area Out. Surface Face BrickR-Insul. Path = 85 0.25 0.45R-Wood Path = 15 0.25 0.45

Windows R / USgl. Pane Alum. frame 0.79/1.27 U (Overall)= 0.061Dbl. Pane Alum. frame 1.20/0.83 R(Total)= 16.39Dbl. Vinyl/Alum. frame 1.75/0.57Dbl. Wood/Vinyl frame 1.82/0.55Triple Vinyl/Al. frame 2.30/0.43 R per Inch InchesDoors 1.25 3.51-¾ inch Solid Wood 2.50/0.40 R(Total)= 4.375 with storm door 3.80/0.26 U (Overall)= 0.2291-¾ inch Panel 1.85/0.54 with storm door 2.80//0.361-¾ inch Insul. Metal 2.50/0.40 with storm door 3.80/0.262-¼ inch Solid Wood 3.7/0.27 with storm door 5.0/0.20

hr-°F-ft 2

hr-ft2-F/BtuBtu/hr-ft2-F

hr-ft2-F/BtuBtu/hr-ft2-F

R-Values in hr-°F-ft2/BtuU-Values in Btu/hr-°F-ft2

Btu/hr-ft2-Fhr-ft2-F/Btu

hr-ft2-F/BtuBtu/hr-ft2-F

R-Value Calculator

R-to-U Inverter

U-Value Calculator for Wood Frame Walls

R-per-Inch to R-Value Calculator

Table 7.1 R-Values for Building Materials and Structural Units

In su la tio n P a th F ram in g P a thP a ra lle l H ea t F lo w P a th s

Jo is t

C eil in g

A ttic S p ace

R o o f

R afters

In su la tio nB etw een Jo is t

In su la tio nA b o ve Jo is t

W a ll

R oo f-C eiling

In su la tio nB etw een W o o d F ram e W o o d (o r S tee l)

F ram e

E x te rio r F in ish

8" HWblock other other In. Surf. Σ R0.74 0.68 12.12

Insulation Air gap 1/2" Gyp. In. Surface R-Path Total13 2.5 1.2 0.45 0.68 18.53

4.375 2.5 1.2 0.45 0.68 9.905

3½"wood½" extr,poly

U-Value Calculator for Wood Frame Walls

In su la tio n P ath F ram in g P a thP a ra l le l H eat F lo w P a th s

Jo is t

C ei l in g

A tt ic S p ace

R o o f

R afters

In su la t io nB etw een Jo is t

In su la tio nA b o ve Jo is t

W a ll

R oof-C eiling

In su la tio nB etw een W o o d F ram e W o o d (o r S tee l)

F ram e

E x te rio r F in ish

Window and Glass Door Cooling Load Temperature Difference (ºF)All Hr = 10 Hr = 15 Hr = 2

Directions 4 14 0

Wall Cooling Load Temperature Difference (ºF)Wall Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N

1 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10N 18 30 17 30 16 30 15 30 14E 63 31 63 31 64 31 64 31 64S 12 31 13 35 15 39 17 43 18W 13 59 13 59 13 59 13 59 13

Wall Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N2 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10

N 12 25 12 25 11 25 10 25 9E 42 38 43 38 44 38 45 38 46S 4 27 4 31 5 35 6 39 6W 5 33 5 33 5 33 5 33 5

Wall Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N5 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10

N 7 19 7 19 7 18 7 18 6E 22 37 23 37 24 37 25 38 25S 3 18 3 20 4 23 4 25 4W 4 20 4 20 5 20 5 20 5

Wall Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N6 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10

N 8 17 8 17 8 17 8 17 7E 22 34 23 34 24 35 25 35 25S 4 16 4 18 5 21 5 23 5W 7 20 7 20 7 20 7 20 7

Wall Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N10 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10

N 8 14 8 14 7 13 6 13 5E 15 30 15 31 15 33 15 34 14S 5 12 5 13 5 15 5 17 4W 11 15 10 15 9 14 8 14 7

Wall Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N16 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10

N 8 11 8 11 8 11 8 11 7E 11 26 11 26 12 27 12 28 12S 6 8 6 9 7 10 7 12 7W 12 11 12 11 13 12 13 12 13

Roof Cooling Load Temperature Difference (ºF)Roof Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N

Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 33 Deg. N 33 Deg. N Hr = 101 44 92 45 92 45 91 45 91 452 30 90 31 90 31 89 32 89 323 22 74 22 74 23 74 24 74 244 5 67 6 67 6 67 7 67 75 10 61 11 61 11 61 12 61 128 14 59 15 57 15 54 15 52 159 5 46 6 46 6 46 7 46 710 8 37 9 43 9 48 9 43 913 16 38 17 38 17 38 17 38 1714 19 36 20 36 20 36 20 36 20

Window and Glass Door Cooling Load Temperature Difference (ºF)Hr = 18

12

Wall Cooling Load Temperature Difference (ºF)36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

29 14 29 14 29 14 29 13 2831 64 31 64 31 64 31 64 3046 21 50 23 53 25 56 28 5959 13 59 13 59 13 59 13 58

36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. N Wall TypeHr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 2

24 9 24 9 24 9 24 9 24 N38 46 38 47 38 48 38 49 38 E42 7 45 8 49 8 52 9 55 S33 5 33 6 33 6 33 6 32 W

36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

17 6 17 6 17 6 17 6 1738 25 38 27 39 27 39 28 3927 4 29 5 32 5 34 6 3720 5 20 6 20 6 20 6 20

36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

16 7 16 7 16 7 16 7 1635 28 35 31 36 29 36 27 3625 6 27 7 30 7 32 8 3420 7 20 8 20 8 20 8 20

36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. N Wall TypeHr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 10

12 5 12 6 12 6 12 6 12 N35 14 35 15 36 15 36 16 36 E18 4 19 5 21 5 22 5 24 S13 7 13 8 13 8 13 8 13 W

36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. N Wall TypeHr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 16

10 7 10 8 10 8 10 8 10 N28 12 28 13 29 13 29 14 29 E12 8 13 10 15 10 16 10 17 S12 13 12 14 12 14 12 14 12 W

Roof Cooling Load Temperature Difference (ºF)36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. N Roof TypeHr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

90 45 89 45 87 45 85 44 83 188 32 87 32 85 32 84 32 82 273 24 72 24 71 24 70 24 68 366 7 65 8 64 8 63 8 62 461 12 60 13 59 13 58 13 57 549 15 49 16 48 16 47 16 46 846 7 46 8 45 8 44 8 43 938 9 38 10 37 10 37 10 36 1038 17 38 18 38 18 38 18 37 1336 20 36 20 36 20 36 20 35 14

24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

3 32 3 31 3 30 3 29 3 283 30 3 30 3 30 3 30 3 303 28 3 31 3 33 3 35 3 375 69 5 69 5 69 5 69 5 69

24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

3 32 6 28 9 25 12 20 15 193 30 7 32 10 33 14 34 17 353 28 7 28 10 28 14 28 17 285 69 11 60 17 50 45 40 30 30

24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

16 20 16 19 16 18 17 17 17 1617 34 19 34 20 33 22 33 23 3214 19 16 20 17 21 19 22 20 2328 30 30 29 31 27 32 26 33 25

24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

-2 58 -2 59 -2 60 -2 60 -2 600 70 0 70 0 70 0 70 0 708 68 8 68 8 68 8 68 8 68

11 80 11 80 11 79 11 79 11 7916 70 16 70 16 70 16 70 16 7024 58 25 58 25 58 25 58 25 5825 65 26 65 26 64 26 64 26 6431 56 32 56 32 56 32 56 32 5631 49 31 49 31 49 31 49 31 4932 45 32 45 32 45 32 45 32 45

39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

3 28 3 28 3 28 3 273 30 3 30 3 30 3 293 40 4 42 4 45 4 475 69 6 69 6 69 6 69

39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

15 19 15 19 15 19 15 1817 35 17 35 18 35 18 3518 31 19 33 26 35 21 3731 30 31 30 32 30 32 30

39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

17 16 17 15 17 15 17 1423 32 23 32 23 32 23 3222 24 23 25 25 27 26 2834 24 34 22 35 21 35 20

39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

-2 60 -2 60 -2 60 -2 590 70 0 69 0 69 0 688 68 8 67 8 66 8 65

11 78 11 77 12 76 12 7416 69 16 68 16 67 16 6625 58 25 57 25 56 24 5526 63 26 62 26 61 26 6032 56 32 55 32 54 31 5331 49 31 48 31 48 30 4732 45 32 44 32 44 32 43

Shade Coefficients (SC) for Unshaded Windows Shade Coefficients (SC) for Windows with Interior ShadesFor NFRC rated windows, SC = SHGC/0.87

Glass Alum Wood Vinyl BLINDSGlass Type Gap Only Frame Frame Frame # of Panes Win. Tint

Sgl.-⅛"Clear ─ 1 0.86 0.72 0.72 Single ClearSgl.-¼"Acryl ─ 0.93 0.82 0.69 0.69 Double ClearDbl.-⅛"Clear 0.87 0.76 0.63 0.63 Double e=0.2Dbl.-⅛"Clear 0.87 0.76 0.63 0.63 DRAPES

0.7 0.66 0.55 0.55 # of Panes Win. Tint0.7 0.66 0.55 0.55 Single Clear

Trpl-⅛"Clear 0.71 0.68 0.59 0.59 Double ClearTrpl-⅛"Clear 0.71 0.68 0.59 0.59 Double e=0.2

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. NA Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

N 38 38 37 38 36 37 36 36E 154 40 154 40 155 40 155 40S 35 37 39 41 44 45 49 48W 35 160 35 160 35 160 35 160

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. NB Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

N 35 37 35 36 34 35 35 35E 141 48 142 48 142 48 142 48S 31 36 35 40 39 44 43 48W 32 141 32 141 32 140 32 140

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. NC Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

N 32 34 32 34 32 33 32 33E 123 47 123 47 124 47 124 47S 29 32 33 36 37 39 41 42W 34 132 34 132 34 132 34 132

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. ND Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

N 29 33 29 33 28 32 28 32E 108 52 108 52 109 53 109 53S 25 30 28 33 32 37 35 40W 32 112 32 112 33 112 33 112

¼" air½"argon

Dbl-⅛"ε=0.2 ¼" airDbl-⅛"ε=0.2 ½"argon

¼" air½"argon

SCL - Solar Cooling Loads (Btu/hr-ft2) Note: Go to "Wall" worksheet to determine Zone Type

Shade Coefficients (SC) for Windows with Interior Shades

Med. Blind Lt. Blind Med. Blind Lt. Blind Dark RollerWhite Rollerat 45° at 45° Closed Closed Closed Closed

0.74 0.67 0.63 0.58 0.81 0.390.62 0.58 0.63 0.58 0.71 0.350.39 0.36 - - 0.4 0.22

Drape Color / Weave Lt./Open Med./OpenDk./Open Lt./Closed Med./CloseDk./Closed

0.69 0.74 0.82 0.69 0.59 0.390.63 0.65 0.71 0.63 0.53 0.350.36 0.37 0.37 0.36 0.32 0.22

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

37 36 36 36 35 36 35 36 34 35155 39 155 39 154 39 153 39 153 38

53 52 63 61 72 70 81 79 90 8835 159 35 159 35 159 35 158 34 156

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

36 35 35 35 34 35 33 35 32 34143 48 143 48 143 48 143 48 143 47

47 52 55 67 63 81 70 95 78 10932 140 32 140 32 139 32 138 31 137

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

31 32 31 32 31 32 31 31 30 31124 47 124 47 124 47 124 47 124 47

45 45 53 53 60 61 67 68 75 7634 132 34 131 34 131 34 131 33 130

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15

27 31 27 31 27 31 27 31 27 30110 53 110 53 111 53 111 53 111 53

39 43 45 50 52 58 58 65 64 7233 112 33 111 33 111 33 110 33 110

2) Note: Go to "Wall" worksheet to determine Zone Type

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. NA Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

N 0 32 0 33 0 34 0 35E 0 14 0 15 0 15 0 16S 0 14 0 15 0 16 0 17

W 0 118 0 126 0 134 0 142

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. NB Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

N 2 33 2 34 2 34 2 35E 2 22 2 23 2 23 2 24S 1 17 2 19 2 20 2 22

W 6 115 6 122 6 128 6 135

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. NC Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

N 5 31 5 32 5 33 5 34E 9 16 9 20 8 23 8 26S 4 15 5 17 5 19 6 21

W 15 97 15 104 15 110 15 116

Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. ND Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

N 8 30 8 31 8 31 8 32E 14 33 14 34 14 34 14 35S 6 26 7 26 7 26 8 26

W 23 53 23 68 23 82 23 97

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

0 36 0 36 0 35 0 35 0 340 17 0 18 0 18 0 19 0 190 18 0 20 0 21 0 23 0 240 149 0 154 0 158 0 163 0 167

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

2 35 2 35 2 35 2 35 2 342 25 2 37 2 48 2 38 2 272 24 2 53 2 81 2 58 2 346 141 7 140 7 139 7 148 7 156

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

5 34 5 34 5 33 5 33 5 338 29 8 30 8 30 9 31 9 316 22 7 25 7 27 9 30 9 32

15 122 15 126 15 130 16 134 16 138

36 Deg. N 36 Deg. N 39 Deg. N 39 Deg. N 42 Deg. N 42 Deg. N 45 Deg. N 45 Deg. N 48 Deg. N 48 Deg. NHr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18 Hr = 2 Hr = 18

7 32 7 32 7 32 7 32 7 3113 36 13 37 13 37 14 38 14 389 26 10 30 11 33 13 36 14 39

22 111 23 114 23 117 24 120 24 123

Sensible Latent TotalActivity Level Heat Gain Heat Gain Heat GainSeated at Rest 245 105 350Seated Light work 245 155 400

Office work Moderate 250 200 450Standing Walking 250 250 500

Light Bench work 275 475 750Nightclub Dancing 305 545 850

Heavy Work 580 870 1450

Heat Gain From Occupants - Btu/hr person

Heat Gain From Lighting - Watts (For incandescent fixtures, Bulb Watts = Fixture Watts)

Power Consumption of Selected Lighting TypesSource (2001 ASHRAE Handbook of Fundamentals, Chp. 29, Table 2)

Fluorescent Bulbs and Ballasts Magnetic Ballast Electronic Ballast

Length (in.)

Dia. LampWattage

Ballast Factor

Net Wattage

Ballast Factor

NetWattage

18 T8 15 1.27 19 - -18 T12 15 1.27 19 - -24 T8 17 1.41 24 .94 1624 T12 20 1.4 28 - -36 T8 25 - - .96 2436 T12 30 1.35 40 - -48 T8 32 1.1 35 .97 3148 T12 34 1.18 40 .92 3160 T8 40 - - .90 3660 T12 50 1.26 63 .90 4572 T12 55 1.2 66 1.07 5996 T8 59 - - .94 5596 T12 60 1.15 70 .92 55

Other Nonincandescent LightingCompact Flour. HP Sodium Merc. Vapor Metal HalideRatedWatts

Actual(w/bal)

RatedWatts

Actual(w/bal)

RatedWatts

Actual(w/bal)

RatedWatts

Actual(w/bal)

13 17 50 66 50 74 50 7218 23 70 95 75 93 100 12822 24 100 138 100 125 175 215

Heat Gain From Office Equipment

Power Consumption of Selected Lighting TypesSource (2001 ASHRAE Handbook of Fundamentals, Chp. 29, Table 2)

Fluorescent Bulbs and Ballasts Magnetic Ballast Electronic Ballast

Length (in.)

Dia. LampWattage

Ballast Factor

Net Wattage

Ballast Factor

NetWattage

18 T8 15 1.27 19 - -18 T12 15 1.27 19 - -24 T8 17 1.41 24 .94 1624 T12 20 1.4 28 - -36 T8 25 - - .96 2436 T12 30 1.35 40 - -48 T8 32 1.1 35 .97 3148 T12 34 1.18 40 .92 3160 T8 40 - - .90 3660 T12 50 1.26 63 .90 4572 T12 55 1.2 66 1.07 5996 T8 59 - - .94 5596 T12 60 1.15 70 .92 55

Other Nonincandescent LightingCompact Flour. HP Sodium Merc. Vapor Metal HalideRatedWatts

Actual(w/bal)

RatedWatts

Actual(w/bal)

RatedWatts

Actual(w/bal)

RatedWatts

Actual(w/bal)

13 17 50 66 50 74 50 7218 23 70 95 75 93 100 12822 24 100 138 100 125 175 215

Heat Gain Rates for Equipment – Watts(Latent heat values in Btu/hr)

Continuous AverageComputer – 15” Monitor 110 - - 17” Monitor 125 - - 19” Monitor 135 -Laser Printer - Desktop 130 100 - Small Office 320 160 - Large Office 550 275

Fax Machine 30Other Office Equipment 25% Nameplate

(Watts voltsamps)Coffee Maker – 10 cup 1050 +

1540 Btu/h LatentMicrowave Oven – 1 ft3 400

Refrigerator – 15 ft3 300Water Cooler – 8 gal/hr 350

¼ hp Motor 270¾ hp Motor 7501 hp motor 930

Cooling Load Factors - Lights (Start Time between 7 and 8 am)Zone Type A Zone Type B Zone Type C

Occupancy Hr = 10 Hr = 15 Hr = 2 Hr = 18 Hr = 10 Hr = 15 Hr = 2 Hr = 18 Hr = 10 Hr = 158 hrs/day 0.93 0.97 0.01 0.06 0.87 0.95 0.02 0.12 0.82 0.9

12 hrs/day 0.94 0.98 0.02 0.98 0.88 0.96 0.05 0.97 0.84 0.9216 hrs/day 0.95 0.98 0.08 0.99 0.9 0.97 0.15 0.98 0.97 0.93

Cooling Load Factors - Hooded Equipment (Occupancy begins between 7 and 8 am)Zone Type A Zone Type B Zone Type C

Occupancy Hr = 10 Hr = 15 Hr = 2 Hr = 18 Hr = 10 Hr = 15 Hr = 2 Hr = 18 Hr = 10 Hr = 158 hrs/day 0.9 0.98 0.01 0.11 0.78 0.94 0.03 0.22 0.72 0.89

12 hrs/day 0.9 0.98 0.02 0.99 0.78 0.94 0.08 0.97 0.73 0.8916 hrs/day 0.91 0.98 0.12 0.99 0.8 0.94 0.25 0.97 0.76 0.91

Cooling Load Factors - People and Unhooded Equipment (Occupancy begins between 7 and 8 am)Zone Type A Zone Type B Zone Type C

Occupancy Hr = 10 Hr = 15 Hr = 2 Hr = 18 Hr = 10 Hr = 15 Hr = 2 Hr = 18 Hr = 10 Hr = 158 hrs/day 0.86 0.97 0.01 0.16 0.68 0.91 0.04 0.31 0.6 0.82

12 hrs/day 0.86 0.97 0.03 0.99 0.69 0.92 0.11 0.96 0.6 0.8216 hrs/day 0.87 0.97 0.17 0.99 0.72 0.92 0.36 0.96 0.66 0.88

Note: To Determine Zone Type, Go To Wall & Roof Types Worksheet

Cooling Load Factors - Lights (Start Time between 7 and 8 am)Zone Type C Zone Type D

Hr = 2 Hr = 18 Hr = 10 Hr = 15 Hr = 2 Hr = 18 Occupancy0.05 0.15 0.74 0.85 0.08 0.2 8 hrs/day0.09 0.94 0.77 0.87 0.15 0.9 12 hrs/day0.2 0.95 0.81 0.89 0.28 0.92 16 hrs/day

Cooling Load Factors - Hooded Equipment (Occupancy begins between 7 and 8 am)Zone Type C Zone Type D

Hr = 2 Hr = 18 Hr = 10 Hr = 15 Hr = 2 Hr = 18 Occupancy0.04 0.26 0.71 0.85 0.07 0.24 8 hrs/day0.11 0.94 0.73 0.87 0.16 0.91 12 hrs/day0.25 0.95 0.78 0.89 0.31 0.93 16 hrs/day

Cooling Load Factors - People and Unhooded Equipment (Occupancy begins between 7 and 8 am)Zone Type C Zone Type D

Hr = 2 Hr = 18 Hr = 10 Hr = 15 Hr = 2 Hr = 18 Occupancy0.07 0.37 0.6 0.77 0.1 0.34 8 hrs/day0.19 0.91 0.62 0.82 0.23 0.87 12 hrs/day0.44 0.93 0.68 0.85 0.44 0.9 16 hrs/day

Note: To Determine Zone Type, Go To Wall & Roof Types Worksheet

ASHRAE 62.1-2004 Ventilation Rate Procedure Yellow CellsInput Req'd

Single Zone and Dedicated OA Systems (DOAS)Rp (cfm/person) No. of People Floor Area

10 25 0.12 800Multi-Zone Systems OnlyZone Description Zone Number Rp No. of People Rp*peopleOffice 1 5 1 5Reception 2 5 5 25Workroom 3 5 5 25Conference 4 5 20 100Office 5 5 3 15Break/Dining 6 7.5 8 60Office 7 5 2 10

89

10Totals 44 240

Max Building occupants 12 peopleDiversity 0.27Ez 1.00Vou 221 cfmEstimated Vp/A 1.00Ev 0.7Vo 316 cfm

People Factor Area factorcfm/person Lps/Person

Occupancy CategoryEducationDay Care 10 5 0.18 0.9Classroom (age 5-8) 10 5 0.12 0.6Classroom (age 9+) 10 5 0.12 0.6Lecture Classroom 7.5 3.8 0.06 0.3Food & BeverageRestaurant Dining 7.5 3.8 0.18 0.9Cafeteria/fast food 7.5 3.8 0.18 0.9Hotels, DormsBed/Living rooms 5 2.5 0.06 0.3Lobbies/pre-function 5 2.5 0.06 0.3Assembly 5 2.5 0.06 0.3Office BuildingsOffice space 5 2.5 0.06 0.3Reception area 5 2.5 0.06 0.3Telephone/data entry 5 2.5 0.06 0.3Public AssemblyConference 5 2.5 0.06 0.3Auditorium 5 2.5 0.06 0.3Library 5 2.5 0.12 0.6

Ra (cfm/ft2)

cfm/ft2

cfm/ft2 Lps/m2

Rp (IP Units) Rp (SI Units) Ra (IP Units) Ra (SI Units)

Museum 7.5 3.8 0.06 0.3RetailSales 7.5 3.8 0.12 0.6Mall - common area 7.5 3.8 0.06 0.3Supermarket 7.5 3.8 0.06 0.3SportsGym, playing areas - - 0.3 1.5Spectator areas 7.5 3.8 0.06 0.3Aerobics room 20 10 0.06 0.3Dance floor 20 10 0.06 0.3Game arcade 7.5 3.8 0.18 0.9

Blue Cells Green CellsOutput Input Optional

Ez1.00 Vo= 346 cfm

Ra Ra*Area Vbz Vp Vp Zp0.06 200 12 17 200 0.090.06 300 18 43 300 0.140.06 300 18 43 300 0.140.06 400 24 124 400 0.310.06 250 15 30 250 0.120.18 300 54 114 300 0.380.06 250 15 25 250 0.10

0 0.000 0.000 0.00

2000 156 Zpmax 0.38

Default Valuescfm/person Lps/person

25 17 8.625 15 7.435 13 6.765 8 4.3

70 10 5.1100 9 4.7

10 11 5.520 8 4

120 6 2.8

5 17 8.530 7 3.560 6 3

50 6 3.1150 5 2.7

10 17 8.5

A (ft2)

Peo./1000 ft2

(Peo./100 m2)

40 9 4.6

15 16 7.840 9 4.6

8 15 7.6

30 - -150 8 4

40 22 10.8100 21 10.3

20 17 8.3

Slab Insulation Unheated Slabs Heated SlabsInsulation Insulation Depth or Width (in.) Insulation Depth or Width (in.)

Position* Btu 0 12 24 36 48 0Horizontal 0.73 0.72 0.7 0.68 0.67 1.35

0.73 0.71 0.7 0.66 0.64 1.35Vertical 0.73 0.61 0.58 0.56 0.54 1.35

0.73 0.58 0.54 0.51 0.48 1.35Horz.+ Vert.(Fully Insul.)

Crawl Space or

Basement Heights

(ft.) (ft.) (ft.)

1 2 1.13 0.39 0.24 0.171 4 5 4.42 2.08 1.41 1.07

7 8 9 4.71 3.34 2.621 5 2.95 0.92 0.55 0.4

4 3 7 4.96 1.91 1.22 0.95 9 7.62 3.41 2.3 1.751 8 4.76 1.45 0.86 0.61

7 2 9 5.66 1.87 1.14 0.823 10 6.78 2.44 1.54 1.12

hr-°F-ft 2

RIns=5RIns =10RIns=5

RIns =10For RIns=5, For RIns=10, For RIns=5,

F=0.46 F=0.36

Fcsb (Btu/hr-ft-°F){qcsb=Fcsb×PBldg(ft)×[ti-to](°F)}

Lag Lbg Lcsb RIns.= 0 RIns.= 4 RIns.= 8 RIns.= 12hr-ft2-°F/Btu hr-ft2-°F/Btu hr-ft2-°F/Btu hr-ft2-°F/Btu

Table 7.5 Slab Perimeter Heat Transmission Coefficients (Fs) in Btu/hr-ft-°F

Table 7.6 Crawl Space and Basement Heat Transmission Coefficients (Fcsb) in Btu/hr-ft-°F

Heated SlabsInsulation Depth or Width (in.)

12 24 36 481.31 1.28 1.24 1.21.3 1.26 1.2 1.131.06 0.99 0.95 0.911 0.9 0.84 0.78

For RIns=5, For RIns=10,F=0.74 F=0.55

Table 7.5 Slab Perimeter Heat Transmission Coefficients (Fs) in Btu/hr-ft-°F

Table 7.6 Crawl Space and Basement Heat Transmission Coefficients (Fcsb) in Btu/hr-ft-°F

F o o tin g

F lo o rR In s* .

to

L b g

L c sb

t iL ag

W all

C ra w l S p ace o rB ase m e n t F lo o r

* In su la tio n can a lso b e lo ca ted o n in te rio r w a ll.

B lo c k (o r C o nc rete)

H o rizo ntal Ins ulatio n

V ertic alIns ulatio n

S la b -o n -G ra d e

*F ully Ins ulated = V ertic al and H o rizo ntal Ins ulatio n

W idth

B lo c k (o r C o nc rete)

H o rizo ntal Ins ulatio n

V ertic alIns ulatio n

S la b -o n -G ra d e

*F ully Ins ulated = V ertic al and H o rizo ntal Ins ulatio n

W idth

Filename: TuscTenClass .zonNote: Zone data file will be located in My Documents

Cooling Loads in kBtu/h Total Heat Loss in kBtu/h8am-Noon Noon-4pm 4pm-8pm 8pm-8am 8am Noon-4pm 4pm-8pm 8pm-8am

Zone 1 to 1 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!Zone 2 to 5 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!Zone 6 to 6 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!Zone 7 to 10 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!Zone 11 to 11 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!Zone to #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!Zone to #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!Zone to #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

`

Net Heat Requirement in kBtu/h8am Noon-4pm 4pm-8pm 8pm-8am BldgType NineMonthSchool

#VALUE! #VALUE! #VALUE! #VALUE! City Atlanta#VALUE! #VALUE! #VALUE! #VALUE! EFLHc = #VALUE!#VALUE! #VALUE! #VALUE! #VALUE! EFLHh = #VALUE!#VALUE! #VALUE! #VALUE! #VALUE!#VALUE! #VALUE! #VALUE! #VALUE!#VALUE! #VALUE! #VALUE! #VALUE!#VALUE! #VALUE! #VALUE! #VALUE!#VALUE! #VALUE! #VALUE! #VALUE!