fieldvue dlc3000 series digital level...

42
Using This Guide Installation Basic Setup and Calibration Specifications and Related Documents Loop Schematics and Nameplates D103214X012 DLC3000 Series Quick-Start Guide Form 5797 September 2005 FIELDVUE r DLC3000 Series Digital Level Controllers Note This guide provides installation and initial setup and calibration for the DLC3000 Series digital level controllers. See the FIELDVUE R DLC3000 Series Digital Level Controller Instruction Manual - Form 5631, available from your Fisher R sales office or from our website at www.FIELDVUE.com, for additional information. Note:. This guide applies to: Type DLC3010 Model 375 Field Communicator Device Revision Firmware Revision Hardware Revision Device Description Revision 1 8 1 2 For details see page 1-1 www.Fisher.com 1 2 3 4 5

Upload: dinhxuyen

Post on 05-Jun-2018

249 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Using This Guide

Installation

Basic Setup and Calibration

Specifications and Related Documents

Loop Schematics and Nameplates

D10

3214

X01

2

DLC3000 SeriesQuick-Start GuideForm 5797September 2005

FIELDVUE DLC3000 SeriesDigital Level Controllers

NoteThis guide provides installation and initialsetup and calibration for the DLC3000Series digital level controllers. See theFIELDVUE DLC3000 Series Digital LevelController Instruction Manual - Form 5631,available from your Fisher sales office orfrom our website at www.FIELDVUE.com,for additional information.

Note: This guide applies to:

Type DLC3010Model 375 FieldCommunicator

DeviceRevision

FirmwareRevision

HardwareRevision

Device DescriptionRevision

1 8 1 2

For details see page 1-1

www.Fisher.com

12345

Page 2: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

i

Unfold This Sheet to See theModel 375 Field Communicator

Menu Tree

Page 3: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Process Variables1 < PV > Value2 Process Temp3 Elect Temp4 PV Range

Serial Numbers1 Instrument S/N2 Displacer S/N3 Final Asmbly Num

Display Type1 PV Only2 PV/Proc Temp3 % Range Only4 PV/% Range

Process Var1 PV Hi Alrm2 PV Hi-Hi Alrm3 PV Lo Alrm4 PV Lo-Lo Alrm5 PV Alrm Deadband

Online1 Process Variables2 Diag/Service3 Basic Setup4 Detailed Setup5 Review

Version Info1 Device Rev2 Firmware Rev3 Hardware Rev4 HART Univ Rev5 275 DD Rev

Temperature1 Proc. Temp Hi Alrm2 Proc. Temp Lo Alrm3 Elec. Temp Hi Alrm4 Elec. Temp Lo Alrm5 Temp Alrm Deadband

Output Condition1 Analog Output2 LCD Meter3 Configure Alarms4 Display Alarms

PV Setup1 PV & Temp Units2 PV Range3 Level Offset4 PV Damp5 Specific Gravity6 PV is

Sensor Calibrate1 Mark Dry Coupling2 Two Point3 Wet/Dry Cal4 Single Point5 Trim PV Zero6 Weight-based Cal

Diag/ Service1 Test Device2 Loop Test3 Hardware Alarms4 Calibration5 Write Lock Displacer

1 Displacer Info2 Inst Mounting3 Sensor Calibrate

Device Information1 HART2 Version Info3 Serial Numbers4 Device ID

Sensors1 Displacer2 Torque Tube3 Process Temp4 Measure Spec Gr

Displacer Info1 Displacer Units2 Length3 Volume4 Weight5 Disp Rod

Torque Tube1 Material2 Change Material

Basic Setup1 Setup Wizard2 Sensor Calibrate3 PV Setup

Trending1 Trend Var2 Trend Interval3 Read Trend

LCD Meter1 Meter Installed2 Display Type3 Decimal Places

Calibration1 Sensor Calibrate2 Temp. Calibration3 Scaled D/A Trim

Field Communicator1 Offline2 Online3 Frequency Device4 Utility

Hardware Alarms1 Alarm Jumper2 NVM3 Free Time4 Level Snsr Drive5 A/D TT Input

Detailed Setup1 Sensors2 Output Condition3 Device Information4 Trending

NOTES:THIS MENU IS AVAILABLE BY PRESSING THE LEFT ARROW KEY FROM THE

PREVIOUS MENU.APPEARS ONLY IF LCD METER IS INSTALLED.< PV > APPEARS AS “LEVEL”, “INTERFACE”, OR “DENSITY”, DEPENDING ON

WHAT IS SELECTED FOR PV IS UNDER PV SETUPAPPEARS ONLY IF PV IS NOT DENSITY. IF PV IS DENSITY,PV RANGE BECOMES 3-3, AND PV IS BECOMES 3-3-4.APPEARS ONLY IF RTD IS INSTALLED. IF THE CONFIGURATION DOES NOT

HAVE AN RTD INSTALLED, PV RANGE BECOMES 1-3 AND ELECT TEMP BECOMES 1-2.SEE MENU 3-2.

1 2 3 4 5

A

B

C

D

E

F

G

H

I

2-32

2-4

3-3

4

4-1

4-1-1

1

3

Configure Alarms1 Process Var2 Alarm Enable3 Temperature4 Temp Alarm Enable

Test Device1 Status2 Meter

2-1

1

PV Range1 URV2 LRV3 USL4 LSL5 Set Zero & Span

3-3-2

6

Process Temp1 Process Temp RTD2 Digital Proc Temp

HART1 HART Tag2 Polling Address3 Message4 Descriptor5 Date6 Burst Mode7 Burst Option

Analog Output1 PV Value2 AO3 % Range4 Alarm Jumper

Review1 Device Params2 Device Info3 Device Troubleshoo4 Factory Settings

1

5

4-2

4-3

4-4

4-1-2

4-1-3

3-2

4-2-2

4-3-1

4-3-2

4-3-3

4-2-3-1

1-4 PV Range1 URV2 LRV

2

2

Factory Settings1 TTube Rate2 TTube Rate Units3 TTube Temp Coeff.4 Input Filter

PV & Temp Units1 < PV > Units2 Temp Units

Set Zero & Span1 Set Zero (4 mA)2 Set Span (20 mA)

Displacer Units1 Length Units2 Volume Units3 Weight Units

4-2-3

4-2-1

4-2-3-3

3

3

3

4

4

4

3

3-3-1

5-4

4-2-2-2

3-3-2-5

5

6

4-1-1-1

4-1-1-1-1

5

6

6

Hot Key1 Range Values2 PV Setup3 Write Lock

Temp. Calibration1 Process Temp2 Proc Temp Offset3 Elect Temp4 Elect Temp Offset

2-4-2

Model 375 Field Communicator Menu Tree for FIELDVUE DLC3000

2

2

2

DLC3000 Series

ii

Menu Tree CompatibilityDLC3010 Model 375

Device Rev Firmware Rev DD Rev

1 8 2

Page 4: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

iii

Hot Key1 Range Values2 PV Setup3 Write Lock

1 Range Values1 LRV2 URV3 LSL4 USL

PV Setup1 PV & Temp Units2 PV Range3 Level Offset4 PV Damp5 Specific Gravity6 PV is

2

PV & Temp Units1 < PV > Units2 Temp Units

2-1

PV Range1 URV2 LRV3 USL4 LSL5 Set Zero & Span

2-2

1

1

NOTES:APPEARS ONLY IF PV IS IS NOT DENSITY. IF PV IS DENSITY,

PV RANGE BECOMES 2-3 AND PV IS BECOMES 2-4< PV > APPEARS AS LEVEL, INTERFACE, OR DENSITY,

DEPENDING ON WHAT IS SELECTED FOR PV IS UNDER PV SETUP

2

1

2

Set Zero & Span1 Set Zero2 Set Span

2-2-5

Model 375 Field Communicator Fast-Key Sequence. The Sequence Describes the Steps to go to a Menu Item(1)

Function Condition Fast KeySequence

Coordi-nates(1) Function Condition Fast Key

SequenceCoordi-nates(1)

Analog Output 4-2-1 5-E Percent Range 4-2-1-3 5-EAlarms, Display 4-2-4 4-F Polling Address 4-3-1-2 5-GAlarm Jumper 4-2-1-4 5-E RTD installed 1-2

Basic Setup 3 2-C Process Temperature RTD NOTinstalled N/A 2-B

Burst Mode 4-3-1-6 5-H Process Variable Alarm Enable 4-2-3-2 5-GBurst Option 4-3-1-7 5-H Process Variable Alarm Limits 4-2-3-1 6-F

Calibration 2-4 3-CPV is

Level orInterface 3-3-6

2-E

Damping, PVPV is NOT

Density 3-3-42-E

PV isDensity 3-3-4

2-E

Damping, PVPV is Density 3-3-3

2-E

RDT Installed 1-4Date 4-3-1-5 5-H

Process Variable RangeRDT Installed 1-4

3-ADescriptor 4-3-1-4 5-H

Process Variable RangeRTD NOTInstalled 1-3

3-A

Detailed Setup 4 2-F Process Variable Units 3-3-1-1 3-DDevice Info 4-3 4-G PV Setup Hot Key-2 See menuDiagnostic and Service 2 2-B Range Values Hot Key-1

See menuabove

Displacer Info 4-1-1-1 6-B Review 5 2-GDisplacer Serial Number 4-3-3-2 5-I RTD, Process Temperature 4-1-3-1 5-D

RTD Installed 1-3 Scaled D/A Trim 2-4-3 3-CElectronics Temperature RTD Not

Installed 1-2 2-B Sensor Calibrate 3-2 3-D

Filter, Input 5-4-4 3-H Set Zero & Span 3-3-2-5 4-EFirmware Rev 4-3-2-2 5-H Setup Wizard 3-1 2-C

Hardware Alarms 2-3 3-BSpecific Gravity

PV is NOTDensity 3-3-5

2-EHART Tag 4-3-1-1 5-G

Specific GravityPV is Density N/A

2-E

Instrument Mounting 4-1-1-2 5-C Status 2-1-1 3-BInstrument Serial Number 4-3-3-1 5-I Temperature Alarm Enable 4-2-3-4 5-GLCD Meter 4-2-2 5-F Temperature Alarm Limits 4-2-3-3 6-G

LCD Meter Test

LCD MeterInstalled 2-1-2

3-BTemperature Units 3-3-1-2 3-D

LCD Meter TestLCD Meter

NOT Installed N/A3-B

Test Device 2-1 3-B

Level OffsetPV is NOT

Density 3-3-32-E

Torque Tube Rate 5-4-1 3-HLevel Offset

PV is Density N/A2-E

Torque Tube Material 4-1-2-1 5-DLoop Test 2-2 2-B Trending 4-4 4-HLRV (Lower Range Value) 3-3-2-2 3-E URV (Upper Range Value) 3-3-2-1 3-ELSL (Lower Sensor Limit) 3-3-2-4 3-E USL (Upper Sensor Limit) 3-3-2-3 3-EMessage 4-3-1-3 5-H Weight Based Calibration 3-2-6 3-D

Output Condition 4-2 4-F Write Lock Hot Key-3 See menuabove

1. Coordinates are to help locate the item on the menu structure on the previous page.N/A = “Not available”

Page 5: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

v

Installation and Basic Setup Check List

Instrument correctly configured and mounted on the sensor. See theappropriate mounting procedure or installation instructions provided with themounting kit.

Conduit or I.S. barrier, if necessary, properly installed. Refer to local andnational electrical codes.

Mounting

Wiring and Electrical Connections

Loop wiring properly connected to the LOOP + and − terminals in the terminal box.Connect loop wiring as described on page 2-8.

Basic Setup and Calibration

Basic Setup complete. Perform Basic Setup procedure, using theSetup Wizard on page 3-2.

Calibration complete. Perform the Quick Calibration procedure on page 3-5.

Transmitter correctly responds to an input change and is stable.

Installation

Transmitter is ready to be placed on line.

HART Impedance requirements met, as described on page 2-7.

Configuration check. Confirm all final process data is correctly entered.

Page 6: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

vi

Page 7: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Using This Guide

September 2005 1-1

1-1 1

Figure 1-1. Type DLC3000 Digital Level Controller

W7977 / IL

NoteNo person may install, operate, ormaintain a DLC3000 Series digitalvalve controller without first beingfully trained and qualified in valve,actuator and accessory installation,operation and maintenance, and carefully reading and understandingthe contents of this manual. If youhave any questions regarding theseinstructions, contact your Fisher salesoffice before proceeding.

Product DescriptionType DLC3010 digital level controllers (figure 1-1) areused with level sensors to measure liquid level, thelevel of interface between two liquids, or liquid specificgravity (density). They are communicating,microprocessor-based sensing instruments. In additionto the normal function of providing a 4 to 20milliampere current signal, Type DLC3010 digital levelcontrollers, using the HARTcommunicationsprotocol, give easy access to information critical toprocess operation.

These digital level controllers are designed to directlyreplace standard pneumatic and electronic leveltransmitters, and mount on a wide variety of Fisher249 Series cageless and caged level sensors. TypeDLC3010 digital level controllers mount on othermanufacturers’ displacer type level sensors with rotaryshaft outputs through the use of mounting adaptors.

Use of this GuideThis guide describes how to install, setup, andcalibrate DLC3000 Series digital level controllers.Additional information for installing, operating, andmaintaining the DLC3000 Series digital levelcontrollers can be found in the related documentslisted on page 4-8.

This guide describes instrument setup and calibrationusing a Model 375 Field Communicator. Forinformation on using the Model 375 FieldCommunicator, see the Product Manual for the FieldCommunicator, available from Emerson PerformanceTechnologies. An abbreviated description of FieldCommunicator operation is also contained in theDLC3000 instruction manual.

Procedures that can be accomplished with the use ofthe Model 375 Field Communicator have the Field

Communicator symbol in the heading.

Procedures that are accessible with the Hot Key onthe Field Communicator will also have the Hot Keysymbol in the heading.

Most procedures also contain the sequence ofnumeric keys required to display the desired FieldCommunicator menu. For example, to access theTemp. Calibration menu, from the Online menu, press2 (selects Diag/Service) followed by a 4 (selectsCalibration) followed by a 2 (selects Temp.Calibration) (2-4-2). The path required to accomplishvarious tasks, the sequence of steps through the FieldCommunicator menus, is also presented in textualformat. Menu selections are shown in italics, e.g.,Calibrate. An overview of the Model 375 FieldCommunicator menu structures are shown at thebeginning of this quick start guide.

You can also setup and calibrate the instrument usinga personal computer and AMS Suite: IntelligentDevice Manager. For information on using AMSDevice Manager with a FIELDVUE instrument, refer tothe appropriate documentation or online help.

1

Page 8: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20051-2

Displaying the Field CommunicatorDevice Description Revision NumberDevice Description (DD) Revision is the revisionnumber of the Fisher Device Description that residesin the Field Communicator. It defines how the FieldCommunicator is to interact with the user andinstrument.

Field Communicators with device description revision2 are used with DLC3000 Series instruments. You candisplay the device description revision when the FieldCommunicator is Offline or Online: to see the FieldCommunicator device description revision numberfrom the Offline menu, select Utility, Simulation, FisherControls, and DLC3000. From the Online menu, selectDetailed Setup, Device Information, Version Info, andDevice Description (4-3-2-5).

NoteNeither Emerson, Emerson ProcessManagement, Fisher, nor any of theiraffiliated entities assumesresponsibility for the selection, use,and maintenance of any product.Responsibility for the selection, use,and maintenance of any productremains with the purchaser andend-user.

1

Page 9: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Installation

September 2005 2-1

1-1 22-2This section contains digital level controller installationinformation, including an installation flowchart (figure2-1), mounting and electrical installation information,and a discussion of failure mode jumpers.

Configuration: On the Bench or inthe LoopConfigure the digital level controller before or afterinstallation. It may be useful to configure theinstrument on the bench before installation to ensureproper operation, and to familiarize yourself with itsfunctionality.

Protecting the Coupling andFlexures

CAUTION

Damage to flexures and other parts cancause measurement errors. Observethe following steps before moving thesensor and controller.

Lever LockThe lever lock is built in to the coupling access door.When the door is open, it positions the lever in theneutral travel position for coupling. In some cases, thisfunction is used to protect the lever assembly fromviolent motion during shipment.A DLC3010 controller will have one of the followingmechanical configurations when received:1. A fully assembled and coupled caged-displacersystem is shipped with the displacer or driver rodblocked within the operating range by mechanicalmeans. In this case, the access handle (figure 2-5) will

be in the unlocked position. Remove thedisplacer-blocking hardware before calibration. (Seethe appropriate sensor instruction manual). Thecoupling should be intact.

CAUTION

When shipping an instrument mountedon a sensor, if the lever assembly iscoupled to the linkage, and the linkageis constrained by the displacer blocks,use of the lever lock may result indamage to bellows joints or flexure.

2. If the displacer cannot be blocked because of cageconfiguration or other concerns, the transmitter isuncoupled from the torque tube by loosening thecoupling nut, and the access handle will be in thelocked position. Before placing such a configurationinto service, perform the Coupling procedure.

3. For a cageless system where the displacer is notconnected to the torque tube during shipping, thetorque tube itself stabilizes the coupled lever positionby resting against a physical stop in the sensor. Theaccess handle will be in the unlocked position. Mountthe sensor and hang the displacer. The couplingshould be intact.

4. If the controller was shipped alone, the accesshandle will be in the locked position. All of theMounting, Coupling and Calibration procedures mustbe performed.

The access handle includes a retaining set screw, asshown in figures 2-5 and 2-7. The screw is driven in tocontact the spring plate in the handle assembly beforeshipping. It secures the handle in the desired positionduring shipping and operation. To open or close theaccess door, this set screw must be backed out so thatits top is flush with the handle surface.

2

Page 10: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20052-2

STARTHERE

Factorymounted on249 sensor?

Use Setup Wizardto enter sensor

data and calibrationcondition

Check AlarmJumper Position

Mount and WireDigital levelController

PowerDigital levelController

No

Yes

Install heatinsulatorassembly

Extremetemperatureapplication?

Yes

No

Set LevelOffset to Zero

Calibratesensor

WireDigital LevelController

PowerDigital LevelController

Enter Tag,Messages, Date, andcheck or set target

application data

DensityMeasurement?

SetRange Values

UsingTemperatureCorrection?

SetTemperature

Units

Setup specificgravity tablesSet

Specific Gravity

Yes

No

Yes

No

Using RTD?Yes Setup and

Calibrate RTD

Enter ProcessTemperature

No

1

1

1

DONE

Disable Writes

NOTES:IF USING RTD FOR TEMPERATURE CORRECTION,

ALSO WIRE RTD TO DIGITAL LEVEL CONTROLLER2

2

DISABLING WRITES IS EFFECTIVE ONLY IF THEDLC3000 REMAINS POWERED-UP

Figure 2-1. Installation Flowchart

2

Page 11: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Installation

September 2005 2-3

STYLE 1TOP AND BOTTOM CONNECTIONS,SCREWED (S-1) OR FLANGED (F-1)

STYLE 2TOP AND LOWER SIDE CONNECTIONS,

SCREWED (S-2) OR FLANGED (F-2)

STYLE 3UPPER AND LOWER SIDE CONNECTIONS,

SCREWED (S-3) OR FLANGED (F-3)

STYLE 4UPPER SIDE AND BOTTOM CONNECTIONS,

SCREWED (S-4) OR FLANGED (F-4)28B5536-1B1820-2 / IL

Figure 2-2. Style Number of Equalizing Connections

Mounting

WARNING

To avoid personal injury, always wearprotective gloves, clothing, andeyewear when performing anyinstallation operations.Personal injury or property damagedue to sudden release of pressure,contact with hazardous fluid, fire, orexplosion can be caused bypuncturing, heating, or repairing adisplacer that is retaining processpressure or fluid. This danger may notbe readily apparent whendisassembling the sensor or removingthe displacer. Before disassemblingthe sensor or removing the displacer,observe the appropriate warningsprovided in the sensor instructionmanual.Check with your process or safetyengineer for any additional measuresthat must be taken to protect againstprocess media.

Mounting the 249 Series Sensor

The 249 Series sensor is mounted using one of twomethods, depending on the specific type of sensor. Ifthe sensor has a caged displacer, it typically mountson the side of the vessel as shown in figure 2-3. If thesensor has a cageless displacer, the sensor mountson the side or top of the vessel as shown in figure 2-4.

The Type DLC3000 digital level controller is typicallyshipped attached to the sensor. If ordered separately,it may be convenient to mount the digital levelcontroller to the sensor and perform the initial setupand calibration before installing the sensor on thevessel.

NoteCaged sensors have a rod and blockinstalled on each end of the displacerto protect the displacer in shipping.Remove these parts before installingthe sensor to allow the displacer tofunction properly.

2

Page 12: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20052-4

Figure 2-3. Typical Caged Sensor Mounting

A3789-1 / IL

Figure 2-4. Typical Cageless Sensor Mounting

A3788-1 / IL

Digital Level Controller Orientation

Mount the digital level controller with the torque tubeshaft clamp access hole (see figure 2-5) pointingdownward to allow accumulated moisture drainage.

Figure 2-5. Sensor Connection Compartment(Adapter Ring Removed for Clarity)

PRESS HERE TOMOVE ACCESSHANDLE

SLIDE ACCESS HANDLETOWARD FRONT OF UNIT TOEXPOSE ACCESS HOLE

ACCESSHOLE

MOUNTINGSTUDS

SHAFTCLAMP

SETSCREW

NoteIf alternate drainage is provided by theuser, and a small performance loss isacceptable, the instrument could bemounted in 90 degree rotationalincrements around the pilot shaft axis.The LCD meter may be rotated in 90degree increments to accommodatethis.

The digital level controller and torque tube arm areattached to the sensor either to the left or right of thedisplacer, as shown in figure 2-6. This can be changedin the field on the 249 Series sensors (refer to theappropriate sensor instruction manual). Changing themounting also changes the effective action, becausethe torque tube rotation for increasing level, (looking atthe protruding shaft), is clockwise when the unit ismounted to the right of the displacer and counter-clockwise when the unit is mounted to the left of thedisplacer.

2

Page 13: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Installation

September 2005 2-5

8

24

6

3

7

1

5

SENSOR

CAGED

CAGELESS

RIGHT-OF-DISPLACERLEFT-OF-DISPLACER

1 1

1 POSITION 5 NOT AVAILABLE FOR 2-INCH CLASS 300 AND 600 TYPE 249C.

19B2787 Rev. D19B6600 Rev. CB1407-2/IL

8

24

6

1

3

7

5

Figure 2-6. Typical Mounting Positions for Type DLC3010 Digital Level Controller on 249 Series Sensor

Figure 2-7. Close-up of Set-Screw

SET-SCREW

All caged 249 Series sensors have a rotatable head.That is, the digital level controller can be positioned atany of eight alternate positions around the cage asindicated by the position numbers 1 through 8 in figure2-6. To rotate the head, remove the head flange boltsand nuts and position the head as desired.

Mounting the Digital Level Controller ona 249 Series Sensor Refer to figure 2-5 unless otherwise indicated.

1. If the set-screw in the access handle, (see figure2-7) is driven against the spring plate, back it out untilthe head is flush with the outer surface of the handle,using a 2 mm hex key. Slide the access handle to thelocked position to expose the access hole. Press onthe back of the handle as shown in figure 2-5 thenslide the handle toward the front of the unit. Be surethe locking handle drops into the detent.

2. Using a 10 mm deep well socket inserted throughthe access hole, loosen the shaft clamp (figure 2-5).This clamp will be re-tightened in the Coupling portionof the Initial Setup section.

3. Remove the hex nuts from the mounting studs. Donot remove the adapter ring.

2

Page 14: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20052-6

MN2880020A7423-CB2707 / IL

Figure 2-8. Digital Level Controller Mounting on Sensor in High Temperature Applications

SENSOR DIGITAL LEVEL CONTROLLER

SHAFTEXTENSION(KEY 58)

SHAFT COUPLING(KEY 59)

SET SCREWS(KEY 60)

INSULATOR(KEY 57)

CAP SCREWS(KEY 63) MOUNTING STUDS

(KEY 33)

HEX NUTS(KEY 34)

CAUTION

Measurement errors can occur if thetorque tube assembly is bent ormisaligned during installation.

4. Position the digital level controller so the accesshole is on the bottom of the instrument.

5. Carefully slide the mounting studs into the sensormounting holes until the digital level controller is snugagainst the sensor.

6. Reinstall the hex nuts on the mounting studs andtighten the hex nuts to 10 Nm (88.5 lbfin).

Mounting the Digital Level Controller forExtreme Temperature Applications

Refer to figure 2-8 for parts identification except whereotherwise indicated.

The digital level controller requires an insulatorassembly when temperatures exceed the limits shownin figure 2-9.

A torque tube shaft extension is required for a 249Series sensor when using an insulator assembly.

HEAT INSULATORREQUIRED

Figure 2-9. Guidelines for Use of OptionalHeat Insulator Assembly

70

0 20 40 60 80 100 120 140 160

0 10 20 20 10 30 40 50 60400300200100

00

400

800

325

AMBIENT TEMPERATURE (C)

STANDARD TRANSMITTERAMBIENT TEMPERATURE (F)

HEAT INSULATORREQUIRED

TOOHOT

NOTES: FOR PROCESS TEMPERATURES BELOW 29 C ( 20 F) ANDABOVE 204C (400F) SENSOR MATERIALS MUST BE APPROPRIATE FOR THE PROCESS — SEE TABLE 4-6.

PRO

CES

S TE

MPE

RAT

UR

E (

C)

PRO

CES

S TE

MPE

RAT

UR

E (

F)

39A4070-BA5494-1/IL

42580

100

200

176 20 40

40 30

TOOCOLD

1

1

2. IF AMBIENT DEW POINT IS ABOVE PROCESS TEMPERATURE, ICEFORMATION MIGHT CAUSE INSTRUMENT MALFUNCTION AND RE-DUCE INSULATOR EFFECTIVENESS.

NO HEAT INSULATOR NECESSARY

CAUTION

Measurement errors can occur if thetorque tube assembly is bent ormisaligned during installation.

1. For mounting a digital level controller on a 249Series sensor, secure the shaft extension to thesensor torque tube shaft via the shaft coupling and setscrews, with the coupling centered as shown in figure 2-8.

2

Page 15: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Installation

September 2005 2-7

230 Ω ≤ RL ≤ 1100 Ω

POWERSUPPLY

Signal loop may be grounded atany point or left ungrounded.A HART-based communicator

may be connected at any termination point in the signalloop. Signal loop must havebetween 250 and 1100 ohmsload for communication.

Figure 2-10. Connecting a Communicator to the Digital Level Controller Loop

Reference meterfor calibration ormonitoring operation. Maybe a voltmeteracross 250 ohmresistor or a current meter.

E0363 / IL

1

NOTE:THIS REPRESENTS THE TOTAL SERIES LOOP RESISTANCE.1

2. Slide the access handle to the locked position toexpose the access hole. Press on the back of thehandle as shown in figure 2-5 then slide the handletoward the front of the unit. Be sure the locking handledrops into the detent.

3. Remove the hex nuts from the mounting studs.

4. Position the insulator on the digital level controller,sliding the insulator straight over the mounting studs.

5. Re-install the four hex nuts on the mounting studsand tighten the nuts.

6. Carefully slide the digital level controller with theattached insulator over the shaft coupling so that theaccess hole is on the bottom of the digital levelcontroller.

7. Secure the digital level controller and insulator tothe torque tube arm with four cap screws.

8. Tighten the cap screws to 10 Nm (88.5 lbfin).

Electrical ConnectionsProper electrical installation is necessary to preventerrors due to electrical noise. A resistance between230 and 1100 ohms must be present in the loop forcommunication with a HART-based communicator.Refer to figure 2-10 for current loop connections.

Power Supply To communicate with the digital level controller, youneed a 17.75 volt dc minimum power supply. Thepower supplied to the transmitter terminals isdetermined by the available supply voltage minus theproduct of the total loop resistance and the loopcurrent. The available supply voltage should not dropbelow the lift-off voltage. (The lift-off voltage is theminimum “available supply voltage” required for agiven total loop resistance). Refer to figure 2-11 todetermine the required lift-off voltage. If you know yourtotal loop resistance you can determine the lift-offvoltage. If you know the available supply voltage, youcan determine the maximum allowable loopresistance.If the power supply voltage drops below the lift-offvoltage while the transmitter is being configured, thetransmitter may output incorrect information.The dc power supply should provide power with lessthan 2% ripple. The total resistance load is the sum ofthe resistance of the signal leads and the loadresistance of any controller, indicator, or related piecesof equipment in the loop. Note that the resistance ofintrinsic safety barriers, if used, must be included.

2

Page 16: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20052-8

Maximum Load = 43.5 X (Available Supply Voltage 12.0)

12 30

LIFT-OFF SUPPLY VOLTAGE (VDC)

Load

(Ohm

s)

0

10 20 2515

783

250

OperatingRegion

Figure 2-11. Power Supply Requirements and LoadResistance

E0284 / IL

Field Wiring

NoteFor intrinsically safe applications,refer to the instructions suppliedby the barrier manufacturer.

WARNING

To avoid personal injury or propertydamage caused by fire or explosion,remove power to the instrumentbefore removing the digital levelcontroller cover in an area whichcontains a potentially explosiveatmosphere or has been classified ashazardous.

All power to the digital level controller is supplied overthe signal wiring. Signal wiring need not be shielded,but use twisted pairs for best results. Do not rununshielded signal wiring in conduit or open trays withpower wiring, or near heavy electrical equipment. If thedigital controller is in an explosive atmosphere, do notremove the digital level controller covers when thecircuit is alive, unless in an intrinsically safeinstallation. Avoid contact with leads and terminals. Topower the digital level controller, connect the positivepower lead to the + terminal and the negative powerlead to the terminal as shown in figure 2-12 .

Figure 2-12. Digital Level Controller Terminal Box

4 TO 20 MA LOOPCONNECTIONSTEST CONNECTIONS

INTERNALGROUNDCONNECTION

1/2-INCH NPT CONDUIT CONNECTION

EXTERNALGROUNDCONNECTION

FRONT VIEW

REAR VIEW

RTDCONNECTIONS

W8041 / IL

CAUTION

Do not apply loop power across the Tand + terminals. This can destroy the 1 Ohm sense resistor in the terminalbox. Do not apply loop power acrossthe Rs and — terminals. This candestroy the 50 Ohm sense resistor inthe electronics module.

When wiring to screw terminals, the use of crimpedlugs is recommended. Tighten the terminal screws toensure that good contact is made. No additional powerwiring is required. All digital level controller coversmust be fully engaged to meet explosion proofrequirements. For ATEX approved units, the terminalbox cover set screw must engage one of the recessesin the terminal box beneath the terminal box cover.

2

Page 17: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Installation

September 2005 2-9

Grounding

WARNING

Personal injury or property damagecan result from fire or explosioncaused by the discharge of staticelectricity when flammable orhazardous gases are present. Connecta 14 AWG (2.1 mm2) ground strapbetween the digital level controllerand earth ground when flammable orhazardous gases are present. Refer tonational and local codes andstandards for groundingrequirements.

The digital level controller will operate with the currentsignal loop either floating or grounded. However, theextra noise in floating systems affects many types ofreadout devices. If the signal appears noisy or erratic,grounding the current signal loop at a single point maysolve the problem. The best place to ground the loopis at the negative terminal of the power supply. As analternative, ground either side of the readout device.Do not ground the current signal loop at more than onepoint.

Shielded Wire

Recommended grounding techniques for shielded wireusually call for a single grounding point for the shield.You can either connect the shield at the power supplyor to the grounding terminals, either internal orexternal, at the instrument terminal box shown in figure2-12.

Power/Current Loop Connections

Use ordinary copper wire of sufficient size to ensurethat the voltage across the digital level controllerterminals does not go below 12.0 volts dc. Connect thecurrent signal leads as shown in figure 2-10. Aftermaking connections, recheck the polarity andcorrectness of connections, then turn the power on.

RTD ConnectionsAn RTD that senses process temperatures may beconnected to the digital level controller. This permitsthe instrument to automatically make specific gravitycorrections for temperature changes. For best results,

locate the RTD as close to the displacer as practical.For optimum EMC performance, use shielded wire nolonger than 3 meters (9.8 feet) to connect the RTD.Connect only one end of the shield. Connect the shieldto either the internal ground connection in theinstrument terminal box or to the RTD thermowell.Wire the RTD to the digital level controller as follows(refer to figure 2-12):

Two-Wire RTD Connections

1. Connect a jumper wire between the RS and R1terminals in the terminal box.

2. Connect the RTD to the R1 and R2 terminals.

Three-Wire RTD Connections

1. Connect the 2 wires which are connected to thesame end of the RTD to the RS and R1 terminals inthe terminal box. Usually these wires are the samecolor.

2. Connect the third wire to terminal R2. (Theresistance measured between this wire and either wireconnected to terminal RS or R1 should read anequivalent resistance for the existing ambienttemperature. Refer to the RTD manufacturer’stemperature to resistance conversion table.) Usuallythis wire is a different color from the wires connectedto the RS and R1 terminals.

Communication Connections

WARNING

Personal injury or property damagecaused by fire or explosion may occurif this connection is attempted in anarea which contains a potentiallyexplosive atmosphere or has beenclassified as hazardous. Confirm thatarea classification and atmosphereconditions permit the safe removal ofthe terminal box cap beforeproceeding.

The 375 Field Communicator interfaces with the TypeDLC3000 digital level controller from any wiringtermination point in the 4–20 mA loop (except acrossthe power supply). If you choose to connect the HARTcommunicating device directly to the instrument,attach the device to the loop + and terminals insidethe terminal box to provide local communications withthe instrument.

2

Page 18: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20052-10

Test Connections

WARNING

Personal injury or property damagecaused by fire or explosion may occurif the following procedure is attemptedin an area which contains a potentiallyexplosive atmosphere or has beenclassified as hazardous. Confirm thatarea classification and atmosphereconditions permit the safe removal ofthe terminal box cap beforeproceeding.

Test connections inside the terminal box can be usedto measure loop current across an internal 1 ohmresistor.

1. Remove the terminal box cap.

2. Adjust the test meter to measure a range of 0.001to 0.1 volts.

3. Connect the positive lead of the test meter to the +connection and the negative lead to the T connectioninside the terminal box.

4. Measure Loop current as:

Voltage (on test meter) 1000 = milliamps

example:

Test meter Voltage X 1000 = Loop Milliamps

0.004 X1000 = 4.0 milliamperes

0.020 X 1000 = 20.0 milliamperes

5. Remove test leads and replace the terminal boxcover.

Alarm Jumper Each digital level controller continuously monitors itsown performance during normal operation. Thisautomatic diagnostic routine is a timed series ofchecks repeated continuously. If diagnostics detect afailure in the electronics, the instrument drives itsoutput to either below 3.70 mA or above 22.5 mA,depending on the position (HI/LO) of the alarm jumper.

An alarm condition occurs when the digital levelcontroller self-diagnostics detect an error that wouldrender the process variable measurement inaccurate,incorrect, or undefined, or a user defined threshold is

violated. At this point the analog output of the unit isdriven to a defined level either above or below thenominal 4 20 mA range, based on the position of thealarm jumper.

On encapsulated electronics 14B5483X042 andearlier, if the jumper is missing, the alarm isindeterminate, but usually behaves as a FAIL LOWselection. On encapsulated electronics 14B5483X052and later, the behavior will default to FAIL HIGH whenthe jumper is missing.

Alarm Jumper Locations

Without a meter installed:

The alarm jumper is located on the front side of theelectronics module on the electronics side of the digitallevel controller housing, and is labeled FAIL MODE.

With a meter installed:

The alarm jumper is located on the LCD faceplate onthe electronics module side of the digital levelcontroller housing, and is labeled FAIL MODE.

Changing Jumper Position

WARNING

Personal injury or property damagecaused by fire or explosion may occurif the following procedure is attemptedin an area which contains a potentiallyexplosive atmosphere or has beenclassified as hazardous. Confirm thatarea classification and atmosphereconditions permit the safe removal ofthe instrument cover beforeproceeding.

Use the following procedure to change the position ofthe alarm jumper:

1. If the digital level controller is installed, set the loopto manual.

2. Remove the housing cover on the electronics side.Do not remove the cover in explosive atmosphereswhen the circuit is alive.

3. Set the jumper to the desired position.

4. Replace the cover. All covers must be fullyengaged to meet explosion proof requirements. ForATEX approved units, the set screw on the transducerhousing must engage one of the recesses in the cover.

2

Page 19: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Installation

September 2005 2-11

Loop Test (2 2) (optional)Loop test can be used to verify the controller output,the integrity of the loop, and the operations of anyrecorders or similar devices installed in the loop. Toinitiate a loop test, perform the following procedure:1. Connect a reference meter to the controller. To doso, either connect the meter to the test connectionsinside the terminal box (see the Test Connectionsprocedure) or connect the meter in the loop as shownin figure 2-10.2. From the Online menu, select Diag/Services, andLoop Test, to prepare to perform a loop test.

3. Select OK after you set the control loop to manual.

The Field Communicator displays the loop test menu.

4. Select a discreet milliamp level for the controller tooutput. At the “Choose analog output” prompt, select 4 mA, 20 mA, or Other to manually input a valuebetween 4 and 20 milliamps.

5. Check the reference meter to verify that it reads thevalue you commanded the controller to output. If thereadings do not match, either the controller requires anoutput trim, or the meter is malfunctioning.

After completing the test procedure, the display returnsto the loop test screen and allows you to chooseanother output value or end the test.

2

Page 20: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20052-12

Installation Check List

Is the sensor correctly mounted on the actuator? If not, refer to appropriatemounting procedure and see installation instructions provided with themounting kit.

Is the conduit or I.S. barrier, if necessary, properly installed? If not, refer tolocal and national electrical codes.

Mounting

Wiring and Electrical Connections

Is the loop wiring properly connected to the LOOP + and terminals in the terminalbox? If not, connect loop wiring as described on page 2-8.

You are ready to perform Basic Setup and Calibration in the next section.

Are the HART impedance requirements met? Can you communicate with the instrument? If not, refer to Electrical Connections on page 2-7.

2

Page 21: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Basic Setup and Calibration

September 2005 3-1

3-3 3Initial Setup If a Type DLC3010 digital level controller ships fromthe factory mounted on a 249 Series sensor, initialsetup and calibration is not necessary. The factoryenters the sensor data, couples the instrument to thesensor, and calibrates the instrument and sensorcombination.

NoteIf you received the digital levelcontroller mounted on the sensor withthe displacer blocked, or if thedisplacer is not connected, theinstrument will be coupled to thesensor and the lever assemblyunlocked. To place the unit in service,if the displacer is blocked, remove therod and block at each end of thedisplacer and check the instrumentcalibration. (If the “factory cal” optionwas ordered, the instrument will beprecompensated to the processconditions provided on the requisition,and may not appear to be calibrated ifchecked against room temperature 0and 100% water level inputs).If the displacer is not connected, hangthe displacer on the torque tube, andre-zero the instrument by performingthe Mark Dry Coupling procedure.If you received the digital levelcontroller mounted on the sensor andthe displacer is not blocked (such asin skid mounted systems), theinstrument will not be coupled to thesensor, and the lever assembly will belocked. To place the unit in service,unlock the lever assembly and couplethe instrument to the sensor. Thenperform the Mark Dry Couplingprocedure.

To review the configuration data entered by thefactory, connect the instrument to a 24 volt dc powersupply as shown in figure 2-10. Connect the 375 Field

Communicator to the instrument and turn it on. Fromthe Online menu select Review, then select DeviceParams (Device Parameters). You can then pagethrough the configuration data using the NEXT andPREV keys. If your application data has changedsince the instrument was factory-configured, refer tothe menu tree at the beginning of this quick start guidefor paths to the appropriate parameters.For instruments not mounted on a level sensor orwhen replacing an instrument, initial setup consists ofentering sensor information. The next step is couplingthe sensor to the digital level controller. When thedigital level controller and sensor are coupled, thecombination may be calibrated.Sensor information includes displacer and torque tubeinformation, such as:

Length units (meters, inches, or centimeters)

Volume units (cubic inches, cubic millimeters, ormilliliters)

Weight units (kilograms, pounds, or ounce)

Displacer Length

Displacer Volume

Displacer Weight

Displacer Driver Rod Length (moment arm) (seetable 3-1)

Torque Tube Material

Instrument mounting (right or left of displacer)

Measurement Application (level, interface, ordensity)

NoteA sensor with a K-Monel torque tubemay have NiCu on the nameplate asthe torque tube material.

3

Page 22: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20053-2

Figure 3-1. Example Sensor Nameplate

(DISPLACER PRESSURE RATING)

1500 PSI

103 CU-IN

316 SST

249B

76543210

PSI

2 x 32 INCHES

4 3/4 LBS

K MONEL/STD

285/100 F

WCB STL

MONEL

(DISPLACER MATERIAL)

DISPLACER VOLUME

DISPLACER SIZE(DIAMETER X LENGTH)

TORQUE TUBE MATERIAL

SENSOR TYPE DISPLACER WEIGHT

(ASSEMBLY PRESSURE RATING)

(ASSEMBLY MATERIAL)

(TRIM MATERIAL)

23A1725-E sht 1E0366 / IL

NOTE: ITEMS IN PARENTHESIS NOT NEEDED FOR SETUP

Preliminary Considerations

Write LockTo setup and calibrate the instrument, write lock mustbe set to Writes Enabled with the Field Communicator.(Write Lock is reset by a power cycle. If you have justpowered up the instrument Writes will be enabled bydefault.) To change the write lock, press the Hot Key

on the Field Communicator. Select Write Lock thenselect Writes Enabled.

Level Offset (3-3-3)The Level Offset parameter should be cleared to zerobefore running Setup Wizard. To clear Level Offset,select Basic Setup, PV Setup then select Level Offset.Enter the value 0.0 and press Enter and Send.

Setup Wizard (3-1)

NotePlace the loop into manual operationbefore making any changes in setup orcalibration.

Table 3-1. Moment Arm (Driver Rod) Length(1)

Sensor Type(2)Moment Arm

Sensor Type(2)mm Inch

249 203 8.01249B 203 8.01

249BF 203 8.01249BP 203 8.01249C 169 6.64

249CP 169 6.64249K 267 10.5249L 229 9.01249N 267 10.5249P

(CL 125 600) 203 8.01

249P(CL 900 2500) 229 9.01

249V (Special)(1) See serial card See serial card249V (Std) 343 13.5

249W 203 8.011. Moment arm (driver rod) length is the perpendicular distance between the verticalcenterline of the displacer and the horizontal centerline of the torque tube. See figure3-2. If you cannot determine the driver rod length, contact your Fisher sales officeand provide the serial number of the sensor.2. This table applies to sensors with vertical displacers only. For sensor types notlisted, or sensors with horizontal displacers, contact your Fisher sales office for thedriver rod length. For other manufacturers’ sensors, see the installation instructionsfor that mounting.

Figure 3-2. Method of Determining Moment Arm fromExternal Measurements

E0283 / IL HORIZONTAL CLOF TORQUE TUBE

VERTICAL CL OF DISPLACER

MOMENT ARMLENGTH

A Setup Wizard is available to aid initial setup. To usethe Setup Wizard, from the Online Menu select BasicSetup then Setup Wizard. Follow the prompts on theField Communicator display to enter information forthe displacer, torque tube, and digital measurementunits. Most of the information is available from thesensor nameplate, shown in figure 3-1. The momentarm is the effective length of the displacer (driver) rodlength, and depends upon the sensor type. For a 249Series sensor, refer to table 3-1 to determine displacerrod length. For a special sensor, refer to figure 3-2.1. You are prompted for displacer length, weight, andvolume units and values, and for moment arm length(in the same units chosen for displacer length).2. You are asked to choose Instrument Mounting (leftor right of displacer, refer to figure 2-6).

3

Page 23: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Basic Setup and Calibration

September 2005 3-3

3. You are asked to select the measurementapplication (level, interface, or density).

NoteFor interface applications, if the 249 isnot installed on a vessel, or if the cagecan be isolated, calibrate theinstrument with weights, water, orother standard test fluid, in levelmode. After calibrating in level mode,the instrument can be switched tointerface mode. Then, enter the actualprocess fluid specific gravity(s) andrange values.If the 249 sensor is installed and mustbe calibrated in the actual processfluid(s) at operating conditions, enterthe final measurement mode andactual process fluid data now.

a. If you choose “Level” or “Interface,” the defaultprocess variable units are set to the same unitschosen for displacer length. The default upperrange value is set to equal the displacer length andthe default lower range value is set to zero.

b. If you choose “Density,” the default processvariable units are set to “SGU” (Specific GravityUnits). The default upper range value is set to “1.0”and the default lower range value is set to “0.1”.

4. You are asked, “Do you wish to make theinstrument direct or reverse acting?”Choosing “reverse acting” will swap the default valuesof the upper and lower range values (the processvariable values at 20 mA and 4 mA). In a reverseacting instrument, the loop current will decrease as thefluid level increases.5. You are given the opportunity to modify the defaultvalue for the process variable engineering units.6. You are now given the opportunity to edit thedefault values that were entered for the upper rangevalue (PV Value at 20 mA) and lower range value (PVValue at 4 mA).

NoteIf Setup Wizard aborts on step 6, clearthe Level Offset parameter beforerestarting Setup Wizard.

7. The default values of the alarm variables will be setas follows:

Direct-Acting Instrument (Span = Upper Range Value LowerRange Value

Alarm Variable Default Alarm ValueHi-Hi Alarm Upper Range ValueHi Alarm 95% span + Lower Range ValueLo Alarm 5% span + Lower Range ValueLo-Lo Alarm Lower Range Value

Reverse-Acting Instrument (Span = Lower Range Value UpperRange Value

Alarm Variable Default Alarm ValueHi-Hi Alarm Lower Range ValueHi Alarm 95% span + Upper Range ValueLo Alarm 5% span + Upper Range ValueLo-Lo Alarm Upper Range Value

The PV alarm deadband is set to zero.The process variable alarms are all disabled.8. You are asked if temperature compensation is tobe used.

a. If you select “No Temperature Compensation”

If Density mode was chosen, the Setup Wizard iscomplete.

If specific gravity temperature compensationtables exist in the instrument, you will be asked if it’sok to overwrite them with single values.

You are prompted to enter the specific gravity ofthe process fluid (if interface mode, the specificgravities of the upper and lower process fluids).

NoteIf you are using water or weights forcalibration, enter a specific gravity of1.0 SGU. For other test fluids, enter thespecific gravity of the fluid used.

b. If you select “Temperature Compensation”

Two data specific gravity tables are available that maybe entered in the instrument to provide specific gravitycorrection for temperature (refer to the Detailed Setupsection of the instruction manual). For interface levelapplications, both tables are used. For levelmeasurement applications, only the lower specificgravity table is used. Neither table is used for densityapplications. Both tables may be edited during detailed

3

Page 24: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20053-4

setup. The Setup Wizard asks if the tables should beused. If not, then you must supply a “single point”specific gravity value (two “single point” values for aninterface application).

NoteThe existing tables may need to beedited to reflect the characteristics ofthe actual process fluid.

If Density mode was NOT chosen, you will bepresented with the current specific gravity temperaturecompensation table (or lower fluid specific gravitytemperature compensation table if interfaceapplication) for editing. You can accept the currenttable(s), modify an individual entry, or enter a newtable manually. For an interface application, you canswitch between the upper and lower fluid tables.

You are prompted to choose a torque tubematerial. The instrument loads the default torque tubetemperature compensation table for the materialchosen. If you choose “Unknown” for the material, theK Monel temperature compensation table is loaded. Ifyou choose “Special” the current table in theinstrument will be left unchanged, but the label for thematerial is changed to “Special”. This feature allows aspecial user table to be retained without overwriting,but does not allow it to be copied to a storedconfiguration.

You are presented with the torque-tubetemperature compensation table for edit. You canaccept the table, edit an individual table entry, load atemperature compensation table for a different torquetube material, or enter a new table manually. If atemperature compensation table for a differentmaterial is chosen, the torque tube material will beupdated to reflect the new material chosen. If a newtable is entered manually, or an individual entry ismodified, then the torque tube material will bechanged to “Special.”

NoteIn firmware version 07 and 08, the datatables for torque-tube correction aresimply stored without implementation.You may use the information topre-compensate the measuredtorque-tube rate manually.

Coupling After entering the sensor information, the SetupWizard prompts you to couple the digital levelcontroller to the sensor. If not already coupled,perform the following procedure to couple the digitallevel controller to the sensor.1. Slide the access handle to the locked position toexpose the access hole. Press on the back of thehandle as shown in figure 2-5 then slide the handletoward the front of the unit. Be sure the locking handledrops into the detent.2. Set the displacer to the lowest possible processcondition, (i.e. lowest water level or minimum specificgravity) or replace the displacer by the heaviestcalibration weight.

NoteInterface or density applications withdisplacer/torque tube sized for a smalltotal change in specific gravity aredesigned to be operated with thedisplacer always submerged. In theseapplications, the torque rod issometimes resting on a stop while thedisplacer is dry. The torque tube doesnot begin to move until a considerableamount of liquid has covered thedisplacer. In this case, couple with thedisplacer submerged in the fluid withthe lowest density and the highestprocess temperature condition, or withan equivalent condition simulated withthe calculated weights.If the sizing of the sensor results in aproportional band greater than 100%(total expected rotational span greaterthan 4.4 degrees), couple thetransmitter to the pilot shaft while atthe 50% process condition to makemaximum use of available transmittertravel (6). The Mark Dry Couplingprocedure is still performed at the zerobuoyancy (or zero differentialbuoyancy) condition.

3. Insert a 10 mm deep well socket through theaccess hole and onto the torque tube shaft clamp nut.Tighten the clamp nut to a maximum torque of 2.1 Nm(18 lbfin).4. Slide the access handle to the unlocked position.(Press on the back of the handle as shown in figure2-5 then slide the handle toward the rear of the unit.)Be sure the locking handle drops into the detent.

3

Page 25: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Basic Setup and Calibration

September 2005 3-5

Calibration

Quick Calibration

The following procedure may be used to calibrate theinstrument as an analog transmitter replacement. Theoutput 4 and 20 mA conditions will be related to agiven pair of mechanical input conditions only, the PVin engineering units will not be calibrated. Thisapproach will give satisfactory results for many of thesimple level measurement applications encountered.

NoteThis procedure assumes that you areusing the instrument in LevelMeasurement Mode, even if theprocess is interface or density.The SG value used for Level is theactual fluid SG. The SG value used forInterface is the difference between theSG of the upper and lower fluids. TheSG value entered for Density would bethe difference between the minimumand maximum density range of theapplication.

1. Connect a 24 V dc supply and make sure there isbetween 230 and 1100 Ohms series resistance in theloop. Hook up a 375 Field Communicator (or otherHART master) across the instrument terminals oracross the series resistor and establishcommunications with the transmitter.

2. Enter the mounting sense (4-1-1-1-2), then SEND.

3. Set Level Offset (3-3-3) to zero; then SEND.

4. Set PV is (3-3-6) to LEVEL, then SEND.

5. Set Specific Gravity (3-3-5) to the differencebetween SGs of the upper and lower fluids.

6. Set up the lowest process condition (or hang aweight equal to the displacer weight minus theminimum buoyancy).

7. Couple to the 249 Series transmitter sensor andclose the access door (this unlocks the leverassembly).

8. Mark Dry-Coupling (3-2-1) point (this marks zerodifferential buoyancy).

9. Set Zero (3-3-2-5-1).

10. Set up the highest process condition (or hang aweight equal to the displacer weight minus themaximum buoyancy).11. Set Span (3-3-2-5-2).12. Set Meter Type to % Range Only (4-2-2-2-3).13. The instrument is calibrated stop here. Do notproceed to Detailed Calibration.

Detailed Calibration

PV Sensor CalibrationIf the advanced capabilities of the transmitter are to beused, it is necessary to calibrate the PV sensorinstead of using the Quick Calibration (“zero andspan”) approach.

Sensor Calibration Using LiquidsLevel Application—with standard displacer andtorque tube, using a single test fluid

Standard practice is to initially calibrate the system atfull design span to determine the sensitivity of thesensor/transmitter combination. (This practice hastraditionally been called “matching”). The data isrecorded in the transmitter non-volatile memory. Theinstrument may then be set up for a target fluid with agiven specific gravity by changing the value of SG inmemory. The value of SG in the instrument memoryduring the calibration process should match the SG ofthe test fluid being used in the calibration.1. From the Online menu select: Basic Setup, PVSetup, Level Offset (3-3-3). Set Level Offset to 0.00,press ENTER and SEND.

2. Run through Setup Wizard (3-3-1) and verify thatall sensor data is correct.

Select Application = Level, Direct Action. Use No temperature compensation.Enter SG = 1.0 (for water) or actual SG of of test

fluid if different than 1.03. After completing the Setup Wizard, raise the testfluid level to the process zero point (e.g.: up to thecenterline of the lower side equalizing connection, halfthe displacer length below the center-of-float mark,etc.) From the Online menu select: Basic Setup,Sensor Calibrate, Mark Dry Coupling (3-2-1). Followall prompts.4. Fill the cage with test liquid almost to the top of thedisplacer. From the Online menu select: Basic Setup,Sensor Calibration, Single Point (3-2-4). Follow theprompts and enter the actual test liquid level in thecurrently selected engineering units.5. Adjust the test fluid level and check the instrumentdisplay and current output against external level at

3

Page 26: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20053-6

several points to verify the level calibration. If thedisplay is slightly inaccurate:

a. For bias errors, try re-marking the coupling pointat the zero level condition.

b. For gain errors, try using the two-point sensorcalibration to trim the torque tube rate. Use twoseparate fluid levels on the displacer, separated byat least 10 inches.

After the calibration, edit the SG parameter (3-3-5) toconfigure the instrument for the target process fluid.The sensor is calibrated.

Interface Application—with standard displacerand torque tube

This procedure assumes that process temperature isnear ambient temperature and that the displacer is notoverweight for the torque tube. If these assumptionsare not correct for your installation, refer to theoverweight displacer procedures in this section or theTemperature Compensation information in theinstruction manual. First, use the standard sensorcalibration procedure under the previous heading,Level Application—with standard displacer and torquetube using a single test fluid. Proceed with step 6.

6. When the single liquid level is as accurate as youcan get it, set up or simulate the zero interface levelcondition. E.g.: Bring the actual lower process fluid tothe zero interface level position and fill the rest of thecage with the actual lighter upper process fluid. Anequivalent weight or computed water level can beused as an alternative.

The output in % should now be approximately:

100 * SGupperfluid / SGlowerfluid

From the Online menu, select: Basic Setup, PV Setup,PV is, (3-3-6). (Note: if the PV is parameter has beenset to density, the menu selection for PV is will be3-3-4.) Select Interface, press ENTER and SEND.

7. From the PV Setup menu (where you should beafter finishing the PV is selection), select the SpecificGravity menu. Use the single point entry method, andenter the SG of the lower fluid and the SG of theupper fluid, respectively, at the prompts.

8. If you are using the actual upper fluid, make surethe displacer is completely covered.

If you are simulating the upper fluid with water, you willneed to fill the cage to SGupperfluid times displacerlength (plus a little extra to account for the amount thatthe displacer rises because of the increase inbuoyancy).

NoteInformation on computing precisesimulation of this effect is available inthe Supplement to 249 Series SensorsInstruction Manual Form 5767 (partnumber D103066X012). Contact yourFisher sales office for information onobtaining this manual supplement.

From the Online menu, select: Basic Setup, SensorCalibrate, Trim PV Zero (3-2-5).

Enter 0.0 inches. This will trim out the displacer risecorrection at the minimum buoyancy condition. (Checkthe Level Offset variable, to see how much correctionwas made. If the Level Offset exceeds 20% ofdisplacer length, there may be problems when usingDeltaV [see the notes on pages 3-8 and 3-9regarding DeltaV interaction]. However, the fraction ofan inch that is trimmed out here will not hurt.) Thisstep is taken to make sure that a 4 mA output will beproduced at the lowest measurable process condition.Since the output will not change any more for interfacelevels dropping below the bottom of the displacer, wearbitrarily re-label that point as zero. An alternativeapproach is to adjust the range values slightly to get 4mA out at the lowest possible computed PV.9. The sensor is calibrated. Check output againstinput to validate reconfiguration to Interface mode.

Interface Application—with an overweightdisplacer

An interface application can be mathematicallyrepresented as a level application with a single fluidwhose density is equal to the difference between theactual fluid densities. We take advantage of this factwhen the sensor sizing prevents the transmitter frombeing able to observe the actual zero buoyancycondition (i.e., the linkage is lying on a travel stop atthe dry displacer condition).1. From the Online menu, select; Basic Setup, PVSetup (3-3).

2. Set Level Offset (3-3-3) to zero.3. Set the range values (3-3-2) to: LRV = 0.0, URV =displacer length.4. Mark the coupling point at lowest process condition(displacer completely submerged in the upperfluid NOT dry).5. Set PV is (3-3-6) to Level6. Set Specific Gravity (3-3-5) to the differencebetween the 2 fluid SGs. (For example, if SG upper =

3

Page 27: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Basic Setup and Calibration

September 2005 3-7

0.87 and SG lower = 1.0, the specific gravity to enteris 0.13).

7. Use any of the sensor calibration methods tocalibrate torque tube rate, but use actual processfluids, or use a single test fluid to set up buoyancyconditions simulating the process conditions you arereporting to the instrument. From the Online menuselect: Basic Setup, Sensor Calibrate (3-2).

NoteInformation on simulating processconditions is available in theSupplement to 249 Series SensorsInstruction Manual Form 5767 (partnumber D103066X012). Contact yourFisher sales office for information onobtaining this manual supplement.

8. If the zero is off, set up the zero condition againand repeat the Mark Dry Coupling procedure. Do notuse Trim PV Zero.

Following are some guidelines on the use of thevarious sensor calibration methods when theapplication uses an overweight displacer:

Weight-based: Use two accurately known weightsbetween minimum and maximum buoyancyconditions. The full displacer weight is invalid becauseit will put the unit on a stop.

Wet/dry: “Dry” now means submerged in lightest fluidand “wet” means submerged in the heaviest fluid.

Single-point: Set up any valid process condition thatyou can independently measure, (other than thecondition that matches the coupling point). The higherthe data point is, the better the resolution will be.

Two-point: Use any two interface levels that actuallyfall on the displacer. Accuracy is better if the levels arefarther apart. The result should be close if you canmove the level even 10%.

Density Applications with standard displacerand torque tube.

NoteYou will need to select PV Units whenchanging from level or interface todensity. After sending the info, it isnecessary to back out of the handheldmenu that shows SG SP and LevelOffset, and then re-enter that menuand select Range Values. The rangevalues will need to be edited toprovide reasonable magnitudes in thenew unit system.

If the displacer is overweight, there is no way to getthe output numerically correct in density mode,because the Level Offset is not available. Therefore,density calibration normally has to begin with theassumption that the displacer is free moving at zerobuoyancy (dry) conditions. “Mark” the coupling pointaccurately at the dry displacer condition. Then any ofthe four sensor calibration methods (weight-based,wet/dry, single-point, or two-point) can be used indensity mode. However, the terminology can beconfusing, because it usually refers to a “level” as theprocess condition to set up. When using one of thesemethods, remember that you are in the density modeand enter observed PV in current units of SGU, g/L,lb/in3, kg/m3, etc.Weight Based: The weight based method asks youfor the lowest and highest density you want to use forthe calibration points, and computes weight values foryou. If you can’t come up with the exact values it asksfor, you are allowed to edit the values to tell it whatweights you actually used.Wet/dry: The wet/dry method essentially reverts tolevel mode during the calibration process. It asks forthe SG of your test fluid first. Then, it has you set upfirst a dry and then a completely submerged displacercondition.Single-point: When using the single-point calibration,you must report the density condition in current PVunits when it asks you for the “level” in current PVunits. The precondition for single-point calibration towork is that the coupling point was previously“marked” at the zero buoyancy state.Two-point: The two-point calibration method requiresyou to set up two different process conditions, with asmuch difference as possible. You could use twostandard fluids with well-known density and alternatelysubmerge the displacer in one or the other. If you are

3

Page 28: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20053-8

going to try to simulate a fluid by using a certainamount of water, you have to remember that theamount of displacer covered by the water is whatcounts, not the amount in the cage. The amount in thecage will always need to be slightly more because ofthe displacer motion. Because of this inconvenience,and the extra work of draining and flooding with twofluids, the two-point calibration method is probably theleast attractive in density mode.

Note: These calibration methods advise you to trim PVzero for better accuracy. That command is notavailable in density mode.

Sensor Calibration at Process Conditions (HotCut-Over) when input cannot be varied

If the input to the sensor cannot be varied forcalibration, you can configure the instrument gainusing theoretical information and trim the output offsetto the current process condition. This allows you tomake the controller operational and to control a levelaround a setpoint. You can then use comparisons ofinput changes to output changes over time to refinethe gain estimate. A new offset trim will be requiredafter each gain adjustment. This approach is notrecommended for a safety-related application, whereexact knowledge of the level is important to prevent anoverflow or dry sump condition. However, it should bemore than adequate for the average level-controlapplication that can tolerate large excursions from amidspan set point.

There are a number of calibration methods available inthe DLC3000 Device Description. Two-point calibrationallows you to calibrate the torque tube using two inputconditions that put the measured interface anywhereon the displacer. The accuracy of the methodincreases as the two points are moved farther apart,but if the level can be adjusted up or down even a fewinches, it is enough to make a calculation. Most levelprocesses can accept a small, manual adjustment ofthis nature. If your process cannot, then the theoreticalapproach is the only method available.

NoteThis approach is not recommended foruse with DeltaV. It results in a largevalue being entered in the Level Offsetparameter, which can trigger arecursive attempt to write range valuesto the digital level controller after acommunications glitch. Thenon-volatile memory write-cycle life inthe instrument will be exhaustedrapidly.

1. Determine all the information you can about the249 hardware: 249 type, mounting sense (controller tothe right or left of displacer), torque tube material andwall thickness, displacer volume, weight, length, anddriver rod length. (Driver rod length is called “DispRod” in the DD menus. It is not the suspension rodlength, but the horizontal distance between thecenterline of the displacer and the centerline of thetorque tube). Also obtain process information: fluiddensities, process temperature, and pressure. (Thepressure is used as a reminder to consider the densityof an upper vapor phase, which can becomesignificant at higher pressures.)2. Run the Setup Wizard and enter the various datathat is requested as accurately as possible. Set theRange Values (LRV, URV) to the PV values whereyou will want to see 4 mA and 20 mA output,respectively. These might be 0 and 14 inches on a 14inch displacer.3. Mount and couple at the current process condition.It is not necessary to run the Mark Dry Couplingprocedure, because it stores the current torque tubeangle as the zero buoyancy condition, and willtherefore not be accurate.4. With the torque tube type and material information,find a theoretical value for the composite or effectivetorque tube rate, (Refer to the Entering TheoreticalTorque Tube (TT) Rates procedure in this section),and enter it in the instrument memory. The value can

3

Page 29: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Basic Setup and Calibration

September 2005 3-9

be accessed in the Review Menu under FactorySettings.

5. If the process temperature departs significantlyfrom room temperature, use a correction factorinterpolated from tables of theoretical normalizedmodulus of rigidity. Multiply the theoretical rate by thecorrection factor before entering the data. You shouldnow have the gain correct to within perhaps 10%, atleast for the standard wall, short length torque tubes.(For the longer torque tubes (249K, L, N) with thin-walland a heat insulator extension, the theoretical valuesare much less accurate, as the mechanical pathdeparts considerably from the linear theory.)

NoteTables containing information ontemperature effects on torque tubescan be found in the Supplement to 249Series Sensors Instruction Manual Form 5767 (part number D103066X012).Contact your Fisher sales office forinformation on obtaining this manualsupplement.

6. Now using a sight glass or sampling ports, obtainan estimate of the current process condition. Run theTrim PV Zero procedure and report the value of theactual process in the PV engineering units. (forexample, sight glass reads 11 inches.) The instrumentwill compute an offset to trim out the differencebetween your value and it’s calculation, and store it inthe Level Offset parameter.

7. You should now be able to go to automatic control.If observations over time show the instrument outputexhibits, for example,1.2 times as much excursion asthe sight glass input, you could divide the storedtorque tube rate by 1.2 and send the new value to theinstrument. Then run another Trim PV Zero procedureto correct the offset, and observe results for anotherextended period to see if further iteration is required.

Entering Theoretical Torque Tube (TT) Rates

The Supplement to 249 Series Sensors InstructionManual, Form 5767, provides the theoreticalcomposite torque tube (TT) rate for 249 Seriessensors with Type DLC3010 controllers. Thesenumbers are nominal values. They should be within10% of the values that the instrument would computewhen you perform a sensor calibration. They will beless accurate for the long torque tubes (Type 249K, L,N, V, and P), especially with thin-wall constructions.If you are unable to perform a sensor calibrationduring installation, you may enter the values into theinstrument at the following menu item in the handheld:Review, Factory Settings, TT rate (5-4-1)Then, manually set the LRV and URV to the PVvalues at which you desire 4 and 20 mA output,respectively.Basic Setup, PV Setup, PV Range, URV LRV(3-3-2-2)Next, perform a Trim PV Zero operation to align theinstrument output with the sight glass reading.Basic Setup, Sensor Calibrate, Trim PV Zero (3-2-5)These steps will provide an approximate PVcalibration to get a system operational. Furtherrefinements can then be made when it is possible tomanipulate and observe the level and instrumentoutput.

NoteThis approach is not advised whenusing the HART interface in a DeltaVinstallation, because the computedLevel Offset can exceed 20% ofdisplacer length, making one of therange values appear invalid during theDeltaV initialization process. This canlead to repetitive re-initializationattempts, using up the write-cycle lifeof the instrument NVM.

See the instruction manual for information on accuracyconsiderations and temperature compensation.

3

Page 30: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20053-10

Basic Setup and Calibration Check ListIs basic setup complete? If not, perform Basic Setup procedure,using the Setup Wizard, on page 3-2.

Is calibration complete? If not, perform the Quick Calibration procedureon page 3-5.

Does the transmitter correctly respond to an input change and is itstable? If not, refer to the Troubleshooting section of the instructionmanual.

Transmitter is ready to be placed on line.

3

Page 31: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Specifications and Related Documents

September 2005 4-1

4-4 4

Table 4-1. Type DLC3000 Digital Level Controller Specifications

Available ConfigurationsType DLC3010 Digital Level Controller:Mounts on Fisher 249 Series caged and cagelesssensors. See tables 4-8 and 4-9 and sensordescription.Function: TransmitterCommunications Protocol: HART

Input Signal(1)

Level, Interface, or Density: Rotary motion oftorque tube shaft proportional to changes in liquidlevel, interface level, or density that change thebuoyancy of a displacer.Process Temperature: Interface for 2- or 3-wire100 ohm platinum RTD for sensing processtemperature, or optional user-entered targettemperature to permit compensating for changes inspecific gravity

Output Signal(1)

Analog: 4 to 20 milliamperes dc ( directaction—increasing level, interface, or densityincreases output; or reverse action—increasinglevel, interface, or density decreases output)High saturation: 20.5 mALow saturation: 3.8 mAHigh alarm: 22.5 mALow Alarm: 3.7 mAOnly one of the above high/low alarm definitions isavailable in a given configuration. NAMUR NE 43compliant when high alarm level is selected.Digital: HART 1200 Baud FSK (frequency shiftkeyed)HART impedance requirements must be met toenable communication. Total shunt impedanceacross the master device connections (excludingthe master and transmitter impedance) must bebetween 230 and 1100 ohms. For purposes ofdetermining the allowable wiring capacitance, theHART “receive impedance” of the transmitter: Atcontrol frequencies may be modeled as— Rx: 42Kohms and Cx: 14 nFIn the HART normal frequency band of 950−2500Hz and above— Rx: 21K ohms and Cx: 12 nF is abetter fit.Note that in point-to-point configuration, analog anddigital signalling are available. The instrument maybe queried digitally for information, or placed inBurst mode to regularly transmit unsolicited process

information digitally. In multi-drop mode, the outputcurrent is fixed at 4 mA, and only digitalcommunication is available.

Performance

PERFORMANCECRITERIA

DLC3000Digital LevelController(1)

w/ 3-Inch249W, Using

a 14-inchDisplacer

w/ AllOther 249

Series

IndependentLinearity

0.25% ofoutput span

0.8% ofoutput span

0.5% ofoutput span

Hysteresis <0.2% ofoutput span

Repeatability 0.1% of fullscale output

0.5% ofoutput span

0.3% ofoutput span

Dead Band <0.05% ofinput span

Hysteresis plusDeadband <1.0% of

output span<1.0% of

output spanNOTE: At full design span, reference conditions.1. To lever assembly rotation inputs.

At effective proportional band (PB)<100%, linearity,dead band, and repeatability are derated by thefactor (100%/PB)

Operating InfluencesPower Supply Effect: Output changes <±0.2% offull scale when supply varies between min. and maxvoltage specifications. Transient Voltage Protection: The loop terminalsare protected by a transient voltage suppressor.The specifications are as follows:

Pulse Waveform Max VCL Max IPPRise Time

s)Decay to50% s)

Max VCL(Clamping Voltage) (V)

Max IPP(Pulse Peak

@ Current) (A)10 1000 93.6 168 20 121 83

Note: µs = microsecond

Ambient Temperature: The combined temperatureeffect on zero and span without the 249 sensor isless than 0.03% of full scale per degree Kelvin overthe operating range 40 to 80 C ( 40 to 176 F)Process Temperature: The torque rate is affectedby the process temperature (see figure 4-1). Theprocess density may also be affected by theprocess temperature.Process Density: The sensitivity to error inknowledge of process density is proportional to thedifferential density of the calibration. If thedifferential specific gravity is 0.2, an error of 0.02specific gravity units in knowledge of a process fluiddensity represents 10% of span.

4

Page 32: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20054-2

Table 4-1. Type DLC3000 Digital Level Controller Specifications (continued)

Electromagnetic Interference (EMI): Tested perIEC 61326-1 (Edition 1.1). Complies with EuropeanEMC Directive. Meets emission limits for class Aequipment (industrial locations) and class Bequipment (domestic locations). Meets immunityrequirements for industrial locations (Table A.1 inthe IEC specification document). Immunityperformance is shown in table 4-2.

Supply Requirements (See figure 2-11)12 to 30 volts dc; instrument has reverse polarityprotection.A minimum compliance voltage of 17.75 is requiredto guarantee HART communication.

CompensationTransducer compensation: for ambienttemperature.Density parameter compensation: for processtemperature (requires user-supplied tables).Manual compensation: for torque tube rate attarget process temperature is possible.

Digital MonitorsLinked to jumper-selected Hi (factory default) orLo analog alarm signal:Torque tube position transducer: Drive monitor andsignal reasonableness monitorUser-configurable alarms: Hi-Hi and Lo-Lo Limitprocess alarmsHART-readable only:RTD signal reasonableness monitor: When RTDinstalledProcessor free-time monitor.Writes-remaining in Non Volatile Memory monitor.User-configurable alarms: Hi and Lo limit processalarms, Hi and Lo limit process temperature alarms,and Hi and Lo limit electronics temperature alarms

DiagnosticsOutput loop current diagnostic.LCD meter diagnostic.Spot specific gravity measurement in level mode:used to update specific gravity parameter toimprove process measurementDigital signal-tracing capability: by review of“troubleshooting variables”, andBasic trending capability for PV, TV and SV.

LCD Meter IndicationsLCD meter indicates analog output on a percentscale bar graph. The meter also can be configuredto display:Process variable in engineering units only.Percent range only.Percent range alternating with process variable orProcess variable, alternating with processtemperature (and degrees of pilot shaft rotation).

Electrical ClassificationHazardous Area:

Explosion proof, Intrinsically Safe Dust-Ignition proof Explosion proof, Non-incendive, Dust-Ignition proof, Intrinsically Safe Intrinsically Safe, Type n, Flameproof

FlameproofRefer to the Hazardous Area Classification bulletins9.2:001 and 9.2:002, tables 4-3 and 4-4 and figures 5-1, 5-2, 5-3 and 5-4 for additional approvalsinformation.Electrical Housing: NEMA 4X, CSA EnclosureType 4X, and IP66

Minimum Differential Specific GravityWith a nominal 4.4 degrees torque tube shaftrotation for a 0 to 100 percent change in liquid level(specific gravity=1), the digital level controller canbe adjusted to provide full output for an input rangeof 5% of nominal input span. This equates to aminimum differential specific gravity of 0.05 withstandard volume displacers.See 249 Series sensor specifications for standarddisplacer volumes and standard wall torque tubes.Standard volume for 249C and 249CP series is∼980 cm3 (60 in3), most others have standardvolume of ∼1640 cm3 (100 in3).Operating at 5% proportional band will degradeaccuracy by a factor of 20. Using a thin wall torquetube, or doubling the displacer volume will eachroughly double the effective proportional band.When proportional band of the system drops below50%, changing displacer or torque tube should beconsidered if high accuracy is a requirement.

continued

4

APPROVED

ATEX

SAA

Page 33: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Specifications and Related Documents

September 2005 4-3

Table 4-1. Type DLC3000 Digital Level Controller Specifications (continued)

Mounting PositionsDigital level controllers can be mounted right- orleft-of-displacer, as shown in figure 2-6.Instrument orientation is normally with the couplingaccess door at the bottom, to provide properdrainage of lever chamber and terminalcompartment, and to limit gravitational effect on thelever assembly. If alternate drainage is provided byuser, and a small performance loss is acceptable,the instrument could be mounted in 90 degreerotational increments around the pilot shaft axis.The LCD meter may be rotated in 90 degreeincrements to accommodate this.

Construction MaterialsDLC3000 Series Digital Level Controller:Case and Cover: Low-copper aluminum alloyInternal: Plated steel, aluminum, and stainlesssteel; encapsulated printed wiring boards;Neodymium Iron Boron Magnets

Electrical ConnectionsTwo 1/2-14 NPT female conduit connections; oneon bottom and one on back of terminal box. M20adapters available.

Options Heat insulator. See description under OrderingInformation. Mountings for Masoneilan,

Yamatake and Foxboro/Eckhardt displacersavailable. Level Signature Series Test(Performance Validation Report) available (EMAonly) for instruments factory-mounted on 249sensor. Factory Calibration: available forinstruments factory-mounted on 249 sensor, whenapplication, process temperature and density(s) aresupplied. Device is compatible withuser-specified remote indicator.

Operating Limits

Process Temperature: See table 4-6 and figure 2-9.Ambient Temperature and Humidity: See below

Conditions NormalLimits(1,2, 3)

Transport andStorageLimits(1)

NominalReference(1)

AmbientTemperature

40 to 80 C( 40 to 176 F)

40 to 85 C( 40 to 185 F)

25C(77F)

AmbientRelativeHumidity

0 to 95%,(non-condensing)

0 to 95%,(non-condensing) 40%

Weight

Less than 2.7 Kg (6 lbs)1. Defined in ISA Standard S51.12. LCD meter may not be readable below 20 C ( 4 F)3. Contact your Fisher sales office or application engineer if temperatures exceeding these limits are required.

Table 4-2. Immunity PerformancePort Phenomenon Basic Standard Performance Criteria(1)

Electrostatic discharge (ESD) IEC 61000-4-2 B

Enclosure EM field IEC 61000-4-3 AEnclosureRated power frequency magnetic field IEC 61000-4-8 ABurst IEC 61000-4-4 B

I/O signal/control Surge IEC 61000-4-5 BI/O signal/controlConducted RF IEC 61000-4-6 A

Note: RTD wiring must be shorter than 3 meters (9.8 feet).1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering. Specification Limit = +/ 1% of span.

4

Page 34: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20054-4

Table 4-3. Hazardous Area Classifications for North AmericaCertification

Body Certification Obtained Entity Rating Temperature Code Enclosure Rating

(Intrinsic Safety)Class/DivisionClass I,II,III Division 1 GP A,B,C,D,E,F,Gper drawing 28B5744

Vmax = 30 VdcImax = 226 mACi = 5.5 nFLi = 0.4 mH

T6 (Tamb < 80°C) 4X

CSA(Explosion Proof)Class/DivisionClass I, Division 1 GP B,C,D

T6 (Tamb < 80C) 4X

Class I Division 2 GP A,B,C,DClass II Division 1 GP E,F,GClass III

T6 (Tamb < 80°C) 4X

(Intrinsic Safety)Class/DivisionClass I,II,III Division 1 GP A,B,C,D,E,F,Gper drawing 28B5745

Vmax = 30 VdcImax = 226 mAPi = 1.4 WCi = 5.5 nFLi = 0.4 mH

T6 (Tamb < 80°C) 4X

FM (Explosion Proof)Class/DivisionClass I, Division 1 GP A,B,C,D

T6 (Tamb < 80C)

Class I Division 2 GP A,B,C,DClass II Division 1 GP E,F,GClass II Division 2 GP F,G

T6 (Tamb < 80°C)

Table 4-4. Hazardous Area Classifications for Europe and Asia PacificCertificate(Agency) Certification Obtained Entity Rating Temperature Code Enclosure Rating

(Intrinsic Safety)

II 1 G DGasEEx ia IIC T6DustT85C (Tamb < 80C)

Ui = 30 VdcIi = 226 mAPi = 1.4 WCi = 5.5 nFLi = 0.4 mH

T6 (Tamb < 80C) IP66

ATEX(LCIE)

(Flameproof)

II 2 G DGasEEx d IIC T6DustT85C (Tamb < 80C)

T6 (Tamb < 80C) IP66

(Type n)

II 3 G DGasEEx nCL IIC T4DustT85C (Tamb < 80C)

T4 (Tamb < 80C) IP66

SAA(Flameproof)GasEx d IIC T6

T6 (Tamb < 80C) IP66

4

Page 35: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Specifications and Related Documents

September 2005 4-5

TORQUE RATE REDUCTION(NORMALIZED MODULUS OF RIGIDITY)

Gno

rm

TEMPERATURE (C)

N05500N06600

N10276

S3160020 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420

1.00

0.96

0.92

0.88

0.84

0.82

0.80

0.90

0.86

0.98

0.94

TORQUE RATE REDUCTION(NORMALIZED MODULUS OF RIGIDITY)

TEMPERATURE (F)

N05500N06600

N10276

S3160050 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800

1.00

0.96

0.92

0.88

0.84

0.82

0.80

0.90

0.86

0.98

0.94

Gno

rm

NOTE: DUE TO THE PERMANENT DRIFT THAT OCCURS NEAR AND ABOVE 260C (500F), K-MONELIS NOT RECOMMENDED FOR TEMPERATURES ABOVE 232C (450F).

1

1

1

Figure 4-1. Theoretical Reversible Temperature Effect on Common Torque Tube Materials

4

Page 36: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20054-6

Table 4-5. 249 Series Sensor Specifications

Input SignalLiquid Level or Liquid-to-Liquid InterfaceLevel: From 0 to 100 percent of displacer lengthLiquid Density: From 0 to 100 percent ofdisplacement force change obtained with givendisplacer volume—standard volumes are 980cm3 (60 inches3) for Types 249C and 249CPsensors or 1640 cm3 (100 inches3) for mostother sensors; other volumes available dependingupon sensor construction

Sensor Displacer LengthsSee tables 4-8 and 4-9 footnotes

Sensor Working PressuresConsistent with applicable ANSIpressure/temperature ratings for the specific sensorconstructions shown in tables 4-8 and 4-9

Caged Sensor Connection StylesCages can be furnished in a variety of endconnection styles to facilitate mounting on vessels;

the equalizing connection styles are numbered andare shown in figure 2-2.

Mounting PositionsMost level sensors with cage displacers have arotatable head. The head may be rotated through360 degrees to any of eight different positions, asshown in figure 2-6.

Construction MaterialsSee tables 4-7, 4-8, and 4-9

Operative Ambient TemperatureSee table 4-6For ambient temperature ranges, guidelines, anduse of optional heat insulator, see figure 2-9.

Options Heat insulator, see description under OrderingInformation Gauge glass for pressures to 29 barat 232C (420 psig at 450F), and Reflex gaugesfor high temperature and pressure applications

Table 4-6. Allowable Process Temperatures for Common 249Sensor Pressure Boundary Materials

MaterialProcess Temperature

Material Min. Max.Cast Iron 29 C ( 20 F) 232C (450F)Steel 29 C ( 20 F) 427C (800F)Stainless Steel 198 C ( 325 F) 427C (800F)N04400 Monel 198 C ( 325 F) 427C (800F)GraphiteLaminate/SSTGaskets

198 C ( 325 F) 427C (800F)

Monel/PTFEGaskets 73 C ( 100 F) 204C (400F)

Table 4-7. Displacer and Torque Tube MaterialsPart Standard Material Other Materials

Displacer 304 Stainless Steel

316 Stainless Steel,Hastelloy B, Monel,Plastic, and SpecialAlloys

Displacer Rod,Driver Bearing,Displacer Rod Driver

316 Stainless Steel

Hastelloy B and C,Monel, Nickel, otherAustenitic StainlessSteels, and SpecialAlloys

Torque Tube N05500 (K Monel)(1)316 and 304LStainless Steels,Inconel, Hastelloy C

1. K-Monel is not recommended for spring applications above 232C(450F). Contact your Fisher sales office or application engineer iftemperatures exceeding this limit are required.

4

Page 37: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Specifications and Related Documents

September 2005 4-7

Table 4-8. Caged Displacer Sensors(1)

TORQUETUBE TYPE

NUMBERSTANDARD CAGE, HEAD,AND TORQUE TUBE ARM

EQUALIZING CONNECTIONANSI CLASS(2)TUBE

ORIENTATION

TYPENUMBER AND TORQUE TUBE ARM

MATERIAL Style Size (Inch)ANSI CLASS(2)

249(3) Cast ironScrewed 1-1/2 or 2

125 or 250249(3) Cast iron Flanged 2 125 or 250

Screwed or optional socket weld 1-1/2 or 2 600

Torque tube 249B, 249BF(4) Steel Raised face or optional 1-1/2 150, 300, or 600Torque tubearm rotatable

249B, 249BF Steel Raised face or optionalring type joint flanged 2 150, 300, or 600arm rotatable

with respect toequalizing

Screwed 1-1/2 or 2 600with respect toequalizingconnections

249C(3) 316 stainless steelRaised face flanged

1-1/2 150, 300, or 600connections

249C 316 stainless steelRaised face flanged 2 150, 300, or 600

249K Steel Raised face or optional ring typejoint flanged 1-1/2 or 2 900 or 1500

249L Steel Ring-type joint flanged 2(5) 25001. Standard displacer lengths for all styles (except Type 249) are 14, 32, 48, 60, 72, 84, 96, 108 and 120 inches. Type 249 uses a displacer with a length of either 14 or 32 inches.2. DIN flange connections available in EMA (Europe, Middle East and Africa).3. Not available in EMA.4. Type 249BF available in EMA only. Also available in DIN size DN40 with PN10 to PN100 flanges and size DN50 with PN10 to PN63 flanges.5. Top connection is 1-inch ring-type joint flanged for connection styles F1 and F2.

Table 4-9. Cageless Displacer Sensors(1)

Mounting TypeNumber

Standard Head(2), WaferBody(6) and TorqueTube Arm Material

Flange Connection ANSI Class(3)

249BP(4) Steel4-inch raised face or optional ring type joint 150, 300, or 600

249BP(4) Steel 6-inch or 8 inch raised face 150 or 300

Mounts on 249CP 316 Stainless Steel 3-inch raised face 150, 300, or 600Mounts ontop of vessel

249P(5) Steel or stainless steel4-inch raised face or optional ring-type joint 900 or 1500

(DIN PN10 to PN250)249P(5) Steel or stainless steel

6- or 8-inch raised face 150, 300, 600, 900, 1500, or2500

Cast Iron 4-inch 125 or 2504-inch raised face or flat face 150

Mounts on side of vessel 249V

Cast Steel 4-inch raised face or optional ring type joint 300, 600, 900, or 1500(DIN PN10 to PN160)

side of vessel 249V4-inch ring-type joint 2500

316 Stainless Steel4-inch raised face or flat face 150

316 Stainless Steel 4-inch raised face or optional ring type joint 300, 600, or 900

Mounts on top ofvessel or oncustomer 249W

WCC (steel) or CF8M(316 stainless steel) 3-inch raised face 150, 300, or 600

vessel or oncustomersupplied cage

249WLCC (steel) or CF8M(316 Stainless Steel 4-inch raised face 150, 300, or 600

1. Standard displacer lengths are 14, 32, 48, 60, 72, 84, 96, 108, and 120 inches.2. Not used with side-mounted sensors.3. DIN flange connections available in EMA (Europe, Middle East and Africa).4. Not available in EMA.5. Type 249P available in EMA only.6. Wafer Body only applicable to Type 249W.

4

Page 38: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20054-8

Related Documents Other documents containing information related to theType DLC3000 digital level controllers and 249 Seriessensors include:

FIELDVUE Type DLC3010 Digital LevelControllers (Bulletin 11.2:DLC3000)

Proportional Control Loop with FIELDVUE

Instruments (PS Sheet 62.1:FIELDVUE(E))

Audio Monitor for HART Communications (PSSheet 62.1:FIELDVUE (G))

Using FIELDVUE Instruments with the SmartHART Loop Interface and Monitor (HIM) (PS Sheet62.1:FIELDVUE(L))

Caged 249 Series Displacer Sensors InstructionManual - Form 1802

Cageless 249 Series Displacer SensorsInstruction Manual - Form 1803

Type 249W Cageless Wafer Style Level SensorInstruction Manual - Form 5729

Supplement to 249 Series Sensors InstructionManual: Simulation of Process Conditions forCalibration of Level-Trols - Form 5767

Technical Monograph 7: The Dynamics of Leveland Pressure Control

Technical Monograph 18: Level-Trol DensityTransmitter

Technical Monograph 26: Guidelines forSelection of Liquid Level Control Equipment

Educational Services For information on available courses for the DLC3000Series digital level controller, as well as a variety ofother products, contact:Emerson Process ManagementEducational Services, RegistrationP.O. Box 190; 301 S. 1st Ave.Marshalltown, IA 50158 2823Phone: 800 338 8158 orPhone: 641 754 3771 FAX: 641 754 3431e-mail: [email protected]

NoteNeither Emerson, Emerson ProcessManagement, Fisher, nor any of theiraffiliated entities assumesresponsibility for the selection, use,and maintenance of any product.Responsibility for the selection, use,and maintenance of any productremains with the purchaser andend-user.

4

Page 39: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Loop Schematics and Nameplates

September 2005 5-1

5-5 5

This section includes loop schematics required forwiring of intrinsically safe installations and theapprovals nameplates. If you have any questions,contact your Fisher sales office.

28B5744 / DOC

Figure 5-1. CSA Schematic and Nameplate

5

Page 40: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

DLC3000 Series

September 20055-2

28B5745 / DOC

Figure 5-2. FM Schematic and Nameplate

CONDITIONS OF CERTIFICATION:

1. IT IS A CONDITION OF SAFE USE THAT ON INSTALLATIONS UTILIZINGGLAND ENTRIES, THE GLAND USED MUST BE STANDARDS AUSTRALIACERTIFIED AND MUST BE CAPABLE OF MAINTAINING THE NOMINATEDIP RATING.

2. IT IS A CONDITION OF SAFE USE THAT THE UNUSED CONDUIT ENTRYIS FITTED WITH THE ORIGINAL CONDUIT PLUG PROVIDED WITH THEEQUIPMENT CERTIFIED AS PART OF THIS CERTIFICATION OR OTHERAPPROPRIATELY CERTIFIED CONDUIT PLUG.

Figure 5-3. SAA Approval Nameplate

5

Page 41: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

Loop Schematics and Nameplates

September 2005 5-3

TYPE n AND DUST

FLAMEPROOF AND DUST

INTRINSICALLY SAFE AND DUST

SPECIAL CONDITIONS FOR SAFE USE:

THE APPARATUS TYPE DLC3010 IS AN INTRINSICALLYSAFE APPARATUS; IT CAN BE MOUNTED IN A HAZARDOUSAREA.THE APPARATUS CAN BE ONLY CONNECTED TO AN INTRINSICALLY SAFE CERTIFIED EQUIPMENT AND THISCOMBINATION MUST BE COMPATIBLE AS REGARDS THEINTRINSICALLY SAFE RULES.

OPERATING AMBIENT TEMPERATURE: 40 C TO +80C.

SPECIAL CONDITIONS FOR SAFE USE: OPERATING AMBIENT TEMPERATURE: 40 C TO +80C.THE APPARATUS MUST BE FITTED WITH A CERTIFIEDEEx d IIC CABLE ENTRY.

SPECIAL CONDITIONS FOR SAFE USE:

THIS EQUIPMENT SHAFT BE USED WITH A CABLEENTRY ENSURING AN IP66 MINIMUM AND BEING IN COM-PLIANCE WITH THE RELEVANT EUROPEAN STANDARDS OPERATING AMBIENT TEMPERATURE: 40 C TO +80C.

Figure 5-4. ATEX / LCIE Approval Nameplates

5

Page 42: FIELDVUE DLC3000 Series Digital Level Controllerseuedocs.emersonprocess.co.uk/groups/public/documents/quick_start... · calibrate DLC3000 Series digital level controllers. Additional

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, theyare not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.

Fisher Controls International, LLC 2005; All Rights Reserved Printed in USA

FIELDVUE, ValveLink and Fisher are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of Emerson Electric Co. AMS Suite and DeltaV are marks owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. Emerson and the Emerson logo are trademarks and service marks of Emerson ElectricCo. HART is a mark owned by the HART Communications Foundation. All other marks are the property of their respective owners.

Emerson Process Management

www.Fisher.com

Fisher Marshalltown, Iowa 50158 USACernay 68700 France Sao Paulo 05424 BrazilSingapore 128461