fan coil unit 50hz 2012 - midea nordic · fan coil unit 50hz commercial air conditioner business...

33
2012 MCAC-2012-16 Fan Coil Unit 50Hz Commercial Air Conditioner Business Units Midea Air Conditioning and Refrigeration Sector Add: West region of Midea commercial air conditioner department, Industry Avenue, Beijiao, Shunde, Foshan, Guangdong, P.R. China Postal code:528311 Tel+86-757-22394101 Fax: +86-757-26338003 http://www.midea.com http://www.mideaaircon.com

Upload: others

Post on 16-Mar-2020

26 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

2012

MCAC-2012-16

Fan Coil Unit 50Hz

Commercial Air Conditioner Business UnitsMidea Air Conditioning and Refrigeration SectorAdd: West region of Midea commercial air conditioner department, Industry Avenue, Beijiao, Shunde, Foshan, Guangdong, P.R. China Postal code:528311Tel:+86-757-22394101 Fax: +86-757-26338003http://www.midea.com http://www.mideaaircon.com

Page 2: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Corporate Introduction

Midea CAC (MCAC)As a key part of Midea Group, the Midea Central Air Conditioner (CAC) Business Unit is a professional CAC products supplier and commercial products solution expert. Since 1999 Midea central air-conditioner contributes to the commercial product R&D and technology innovation. By cooperating with the international enterprises plus the independent R&D, Midea CAC achieves big success in the commercial air-conditioner market and has established thousands of sample projects all over the world.

Right now Midea CAC is one of the most professional CAC products supplier as well as the professional project solution provider in marketing, sales, project design and after service etc.

MCAC Chongqing factory with 14 product lines concentrates on the water cooled centrifugal / screw/ scroll chillers, Air cooled screw/ scroll chillers, AHU/FCU etc.MCAC Shunde factory with 31 product lines concentrates on the VRF (DC inverter product/ Digital scroll product), split product, heat pump water heater, AHU/FCU etc.

From its humble beginnings in 1968, Midea has developed into a large corporation, covering HVAC, appliances, lighting, industrial components, logistics, and real estate. Its 40 years of relentless growth has brought its global turnover to $14 billion USD in 2009. Consequently, Midea has created over 150,000 jobs both within China and all over the world. In addition to providing affordable goods to consumers worldwide, Midea is a responsible corporate citizen, and has contributed to several social causes. Midea believes in creating value through rapid response to market demands, cost-efficient operations and consumer satisfaction. As a result, Midea wields vast production capacities to meet these demands, a fully integrated manufacturing process, and a comprehensive range of affordable, high-quality products to serve its global customers.

Today, Midea is a home appliance leader in China. The company continues to actively globalize its operation by opening plants in Vietnam, Belarus and Egypt. Additionally, Midea has several forthcoming plants in order to offer enhanced products and services closer to the market.

Midea Group

Page 3: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 04Fan Coil Unit03

Cassette (300-1500CFM) Duct (200-1200CFM)

Product Line Up2-pipe Fan Coil Units

Cassette (300–1500CFM)

Wall-mounted (250-600CFM)

Duct (200-2200CFM)

Floor-standing and Ceiling & Floor (150-900CFM)

4-pipe Fan Coil Units

4-way Cassette

Standard Static Pressure Duct High Static Pressure Duct District Cooling FCU

4-way Cassette (compact) 1-way Cassette

Ceiling & Floor

4-way Cassette 4-way Cassette (compact) duct

Wall-mounted

Floor-standing Floor-standing (new appearance)

Concealed Type

Page 4: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 06R410A DC Inverter VR4 Plus05

The Midea Chilled Water Fan Coil Unit is designed and manufactured on the base

of advanced technology, and utilize qualified galvanized iron as structure material.

Due to its supper-thin design, it has such advantages: beautiful outlook, space

saving, easy installation, etc. And the most obvious advantage is that it can

decrease the outlet air temperature difference as low as possible to make room

more comfortable, as well as don’t decrease cooling capacity output. For the large

air flow volume design, it can increase room ventilation frequency, supply more

flesh air, and balance room temperature distribution. Benefiting from adoption of

advanced material and technology, it can effectively reduce the running noise and

keep running smoothly. With the advantages above, it can be widely applied in

market, hospital, office building, hotel airport, etc..

The Midea Chilled Water Fan Coil Unit contains ceiling exposed type, ceiling

concealed type, wall-mounted type and floor-standing type. The air volume varies

from 150CFM~2,200CFM (255m3/h~3740m3/h). The standard power supply is

220-240V/1phase/50Hz.

Contents07

08

52

55

58

61

62

Nomenclature

Features and specifications

Fan performance

Controllers

Accessories

Application of network control & BMS control

Selection software

Dedicated to creat a comfortable,queit and high quality life for you

Introduction

Page 5: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 08Fan Coil Unit07

E

Features and specificationsM K HT3

Static PressureG12: 12Pa G30: 30Pa G50: 50PaG70: 70Pa G100: 100Pa

Function CodeR: Remote ControlRA: Remote Control with EAHE: With EAHF: 4-pipe 4-way CassetteS: 4-pipe 4-way Cassette(compact)N: Without PCBNF: 4-pipe FCU without PCB

Type Code*(Refer to below table)

Midea

Nominal Air Volume (CFM)

Static Pressure TypeH: High Static PressureOmit: 12Pa

Chilled Water Fan Coil Unit

*Meaning of the code

NomenclatureG1002200

A

C

D

F1

F2

F3

F4

F5

G

H1

H2

H3

T2

T3

T4

T5

T3H***G***

Q

4-way cassette

1-way cassette

4-way cassette (compact)

Exposed floor-standing (air return from side)

Exposed floor-standing (air return from bottom)

Concealed floor-standing

Exposed floor-standing (air return from side) of new appearance

Exposed floor-standing (air return from bottom) of new appearance

Wall-mounted

Exposed ceiling & floor (air return from side)

Exposed ceiling & floor (air return from bottom)

Concealed ceiling & floor

2-row duct

3-row duct

4-row duct

4-pipe duct

High static pressure duct

District cooling (High temp. difference)

Type Code Meanings

Page 6: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 10Fan Coil Unit09

Features

Capacity range: 600CFM to 1500CFM.Four color panels for choose: White, Gray, Blue, Black.4-way air supply panel is standard, 360°air supply panel is optional.Unique design of the centrifugal fan ensures extra-quiet operation and high efficiency.Wireless remote control with LED display, wired control is optional.Safety grill for safety maintenance.Built-in drain water pump with 750mm pumping head.Optional extended drainage pan for protecting your ceiling better.Four-speed motor with one reserved for more choice. Fresh air provision makes life healthier and more comfortable.

Features

4-way cassette

Current Panel Fresh air provision High water pump head

Four color panels360°panel Safety grill

Fresh air

Features and specifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB.

Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with A type unit.

Optional accessoriesSpecifications

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight (with EAH)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Panel

Indoor Unit

Pipe Connection

Model MKA- 600R(A) 750R(A) 850R(A) 950R(A) 1200R(A) 1500R

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

1,000

590

850

500

720

420

5,700

9,660

2,100

125

45/41/36

16.4

23.8

1,250

740

1,060

620

900

530

7,000

11,550

2,100

130

46/42/37

20

25.2

1,400

820

1,190

700

1,010

590

7,270

12,420

2,850

150

47/43/38

20.8

27

1,600

940

1,360

800

1,150

680

8,220

13,850

2,850

155

48/44/39

23.6

31.2

2,000

1,180

1,700

1,000

1,440

850

10,390

17,580

2,850

190

49/45/40

29.8

44

2,550

1,500

2,170

1,280

1,840

1,080

12,900

17,600

/

190

50/46/41

36.9

40

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

1.6

950×45×950

6

RC3/4"

RC3/4"

ODΦ32

840×230×840

25(27)

840×230×840

25(27)

840×300×840

30.5(33)

840×300×840

30.5(33)

840×300×840

30.5(33)

840×300×840

35

2 2 22 2 3

750mm

Page 7: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 12Fan Coil Unit11

Features

Capacity range: 750CFM to 1500CFM.

Various thermostats can be chosen by customer’s need.

Flexible wiring connection for non-PCB.

Four color panels for choose: White, Gray, Blue, Black.

4-way air supply panel is standard, 360°air supply panel is optional.

Unique design of the centrifugal fan ensures extra-quiet operation and high efficiency.

Safety grill for safety maintenance.

Built-in drain water pump with 750mm pumping head.

Optional extended drainage pan for protecting your ceiling better.

Fresh air provision makes life healthier and more comfortable.

Features

4-way cassette (without PCB)

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Optional accessoriesSpecifications

160

16.0kW

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Panel

Indoor Unit

Pipe Connection

Model MKA-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

1,250

740

1,060

620

900

530

6,100

8,100

130

46/42/37

17.5

25.2

840×230×840

29

1,600

940

1,360

800

1,150

680

6,650

8,600

190

48/44/39

19.1

31.2

840×300×840

35

1,920

1,130

1,630

960

1,380

810

9,900

16,500

180

49/45/40

28.4

44

840×300×840

35

Low noise 3-speed fan motor

Centrifugal, forward-curved Blades

1.6

950×45×950

6

750N 950N 1200N

1,900

1,120

1,620

950

1,370

800

11,400

19,000

228

50/46/41

32.7

40

840×300×840

35

1500N

2 2 2 3

RC3/4"

RC3/4"

ODΦ32

Page 8: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 14Fan Coil Unit13

Features

Capacity range: 300CFM to 500CFM.

Compact design, simple installation and easy maintenance.

Round blow air supply enables uniform air flow distribution.

Comfortable horizontal air discharge reduces draughts and ceiling soiling.

Wireless remote control with LED display, wired control is optional.

Built-in drain water pump with 500mm pumping head.

Optional extended drainage pan for protecting your ceiling better.

Four-speed motor with one reserved for more choice .

Fresh air provision makes life healthier and more comfortable.

Features

4-way cassette (compact)

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Optional accessoriesSpecifications

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Panel

Indoor Unit

Pipe Connection

Model MKD-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

510

300

440

260

360

210

3,000

4,000

50

36/33/28

8.7

14

680

400

580

340

480

280

3,700

5,100

70

42/39/32

10.7

15

850

500

730

430

600

350

4,500

6,000

95

45/42/34

12.9

16

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

647×50×647

3

575×261×575

17.5

G3/4"

G3/4"

ODΦ25

300 400 500

Round blow panel Compact body High water pump head

500mm

575mm575mm

261mm

Page 9: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 16Fan Coil Unit15

Features

Capacity range: 300CFM to 500CFM.

Various thermostats can be chosen by customer’s need.

Flexible wiring connection for non-PCB.

Compact design, simple installation and easy maintenance.

Round blow air supply enables uniform air flow distribution.

Comfortable horizontal air discharge reduces draughts and ceiling soiling.

Built-in drain water pump with 500mm pumping head.

Optional extended drainage pan for protecting your ceiling better.

Fresh air provision makes life healthier and more comfortable.

Features

4-way cassette (compact) (without PCB)

160

16.0kW

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Panel

Indoor Unit

Pipe Connection

Model MKD-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

510

300

440

260

360

210

2,930

4,000

50

36/33/28

8.7

14

680

400

580

340

480

280

3,700

5,100

70

42/39/32

10.7

15

850

500

730

430

600

350

4,500

6,000

87

45/42/34

12.9

16

Low noise 3-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

647×50×647

3

575×261×575

17.5

G3/4"

G3/4"

ODΦ25

300N 400N 500N

Optional accessoriesSpecifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Page 10: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 18Fan Coil Unit17

Features

Capacity range: 300CFM to 400CFM.

Smoother air flow with less turbulence.

One direction air flow guarantees quick cooling, flexible installation position.

Space saving, only 235mm in height.

Built-in drain water pump with 750mm pumping head.

Four-speed motor with one reserved for more choice .

Features

1-way cassette Optional accessoriesSpecifications

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight (with EAH)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Panel

Indoor Unit

Pipe Connection

Model MKC- 300R(A)

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

500

300

450

270

400

240

3,040

5,130

1,000

60

38/35/33

8.7

10.1

400R(A)

630

370

560

330

500

300

3,790

6,410

1,000

60

40/37/35

10.9

14.5

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

1,050×18×470

4

850×235×400

22.5(23)

RC3/4"

RC3/4"

ODΦ18

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with A type unit.

Space saving One direction air flow High water pump head

750mm

Single direction airflow,flexibly installed in various corners

235mmUItra Thin

Page 11: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 20Fan Coil Unit19

Features

Capacity range: 200CFM to 2000CFM.Two external static pressure (12Pa and 30Pa) settings for added flexibility.Space saving, only 242mm (200CFM to 1200CFM models) or 342mm (1500CFM to 2000CFM models) in height.Air return from the rear or below for increased installation flexibility.Standard extended drainage pan for protecting your ceiling better.Flexible control, no standard controller, remote controller and wired controller are optional.Pipe connection from left or right can be selected (in factory).Four-speed motor with one reserved for more choice .

Duct

2-Row Duct

12Pa ESP

30Pa ESP

12Pa ESP with EAH

30Pa ESP with EAH

MKT2-200

MKT2H-200

MKT2-200E

MKT2H-200E

MKT2-300

MKT2H-300

MKT2-300E

MKT2H-300E

MKT2-400

MKT2H-400

MKT2-400E

MKT2H-400E

MKT2-500

MKT2H-500

MKT2-500E

MKT2H-500E

MKT2-600

MKT2H-600

MKT2-600E

MKT2H-600E

MKT2-800

MKT2H-800

MKT2-800E

MKT2H-800E

MKT2-1000

MKT2H-1000

MKT2-1000E

MKT2H-1000E

MKT2-1200

MKT2H-1200

MKT2-1200E

MKT2H-1200E

MKT2-1400

MKT2H-1400

MKT2-1400E

MKT2H-1400E

3-Row Duct

12Pa ESP

30Pa ESP

MKT3-200

MKT3H-200

MKT3-300

MKT3H-300

MKT3-400

MKT3H-400

MKT3-500

MKT3H-500

MKT3-600

MKT3H-600

MKT3-800

MKT3H-800

MKT3-1000

MKT3H-1000

MKT3-1200

MKT3H-1200

4-Row Duct

30Pa ESP

30Pa ESP with EAH

50Pa ESP

MKT4H-200

MKT4H-200E

MKT4H-300

MKT4H-300E

MKT4H-400

MKT4H-400E

MKT4H-500

MKT4H-500E

MKT4H-600

MKT4H-600E

MKT4H-800

MKT4H-800E

MKT4H-1000

MKT4H-1000E

MKT4-1200

MKT4-1200E

MKT4-1500

MKT4-1500E

MKT4-2000

MKT4-2000E

MKT4H-1500G50 MKT4H-2000EG50

Features

Note:1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°CDB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with E type unit.

Optional accessoriesSpecifications (2-row)

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT2(H)- 200(E) 300(E) 400(E) 500(E) 600(E)

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

Pa

W

W

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

340

200

285

170

210

125

2,000

3,200

500

37

43.4

36/30/25

39/32/27

5.7

9.8

510

300

420

250

320

190

2,700

4,300

650

42.5

61.2

38/32/26

41/33/28

7.7

11

680

400

580

340

420

250

3,600

5,400

1,000

63.5

78.6

40/33/27

43/35/30

10.3

21

850

500

700

410

520

305

4,500

6,800

1,000

78

89.3

42/35/29

44/35/31

12.9

12.7

1,020

600

840

495

620

365

5,400

8,100

1,500

98

112

43/35/30

45/36/32

15.5

17.5

770×242×490

16(15.5)

770×242×534

18(18)

827×242×490

18.5(18)

827×242×534

19(19)

927×242×490

15(20.5)

927×242×534

25(25)

1,140×242×490

19(24)

1,140×242×534

28(28)

1,140×242×490

24(24.5)

1,140×242×534

28(28)

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight (12Pa/30Pa)

Net Dimension (W×H×D)

Net Weight (12Pa/30Pa)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Power Input

Noise(Hi/Med/Lo)

12Pa

30Pa

12Pa

30Pa

Fan Motor

Fan

Coil

Indoor Unit (without EAH)

Indoor Unit (with EAH)

Pipe Connection

12/30

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

RC3/4"

RC3/4"

ODΦ24

Page 12: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 22Fan Coil Unit21

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT2(H)- 800(E) 1000(E) 1200(E) 1400(E)

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

Pa

W

W

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

1,360

800

1,150

680

840

495

7,200

11,000

2,000

143

156

43/34/30

46/37/33

20.6

13.6

1,700

1,000

1,400

820

1,000

590

9,000

13,500

2,000

178

197

46/36/32

48/38/35

25.8

20

2,040

1,200

1,650

970

1,250

735

11,000

16,500

3,000

206

234

47/37/33

50/40/37

31.5

35

2,380

1,400

2,000

1,175

1,480

870

13,000

19,500

3,000

240

262

48/38/34

52/42/39

37.3

40

1,440×242×490

27(32)

1,440×242×534

34(32.4)

1,546×242×490

29(36)

1,546×242×534

37(37)

RC3/4"

RC3/4"

ODΦ24

1,835×242×490

33(33)

1,835×242×534

44(44)

1,835×242×490

34(34)

1,835×242×534

44(44)

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight (12Pa/30Pa)

Net Dimension (W×H×D)

Net Weight (12Pa/30Pa)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Power Input

Noise(Hi/Med/Lo)

12Pa

30Pa

12Pa

30Pa

Fan Motor

Fan

Coil

Indoor Unit (without EAH)

Indoor Unit (with EAH)

Pipe Connection

12/30

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

Note: 1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with E type unit.

Note:1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT3(H)- 200 300 400 500

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

340

200

255

150

170

100

2,100

3,500

34

40

36/33/27

39/34/28

6

9.8

510

300

385

225

255

150

3,300

5,300

46

60

38/32/28

40/35/29

9.5

11

680

400

510

300

340

200

4,200

6,800

65

80

40/34/30

43/35/28

12

20

850

500

640

375

425

250

4,800

7,900

68

110

42/36/31

45/38/30

13.8

12.7

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight (12Pa/30Pa)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Power Input

Noise(Hi/Med/Lo)

12Pa

30Pa

12Pa

30Pa

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

12/30

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

757×242×534

18(18)

812×242×534

19(19)

912×242×534

21.2(25)

912×242×534

21.5(25)

RC3/4"

RC3/4"

ODΦ24

Specifications (2-row) Specifications (3-row)

Page 13: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 24Fan Coil Unit23

Note: 1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with E type unit.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Standard External Static Pressure

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKT4(H)- 200(E) 300(E) 400(E) 500(E) 600(E) 800(E)

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

Pa

W

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

340

200

255

150

170

100

2,200

4,100

500

30

47

40/35/29

6.3

3.3

510

300

385

225

255

150

3,200

5,800

650

30

65

42/36/30

9.2

6.3

680

400

510

300

340

200

4,000

7,100

1,000

30

85

43/36/31

11.5

13

850

500

640

375

425

250

4,800

8,000

1,000

30

90

48/38/33

13.8

13

1,020

600

765

450

510

300

6,000

10,500

1,500

30

110

48/39/33

17.2

24.5

1,360

800

1,020

600

680

400

7,300

12,500

2,000

30

180

50/40/34

21

14.5

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight (With EAH)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

4

1.6

757×242×534

19(20)

812×242×534

21(22)

912×242×534

24(25)

RC3/4"

RC3/4"

ODΦ24

912×242×534

24(25)

1,125×242×534

30(32)

1,425×242×534

40(41)

Note: 1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT3(H)- 600 800 1000 1200

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

1,020

600

765

450

510

300

5,800

10,000

100

110

44/39/32

46/39/30

16.6

17.5

1,360

800

1,020

600

680

400

7,900

13,600

140

155

45/41/32

48/40/31

22.7

14.4

1,700

1,000

1,275

750

850

500

9,100

16,000

170

210

46/40/32

49/41/32

26.1

20.5

2,040

1,200

1,530

900

1,020

600

11,500

20,300

220

230

47/41/32

50/42/32

33

35

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight (12Pa/30Pa)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Power Input

Noise(Hi/Med/Lo)

12Pa

30Pa

12Pa

30Pa

Fan Motor

Fan

Coil

Indoor Unit

12/30

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

1,125×242×534

25(28)

1,425×242×534

34(34)

1,530×242×534

37(37)

1,820×242×534

44(44)

Pipe Connection

RC3/4"

RC3/4"

ODΦ24

Specifications (4-row)Specifications (3-row)

Page 14: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 26Fan Coil Unit25

Capacity range: 200~1400CFM.

Wider external static pressure supplying. Three external static pressure (12Pa/30Pa/50Pa) settings for added flexibility.

A patent design is able to prevent abnormal noise caused by blowing flins.

Higher efficient heat exchange for complete contranatant flow type.

Air inlet and air outlet both with flange.

Filter can be extracted in upward/downward/leftward/rightward way.

Accessary hook for extracting conveniently.

Standard extended drainage pan for protecting your celling better.

Features

New 2-row and 3-row duct

Filter be extracted in upward/downward/leftward/rightward way

Note: 1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with E type unit.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Standard External Static Pressure

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKT4(H)- 1000(E) 1200(E) 1500(E) 1500G50 2000(E) 2000G50

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

Pa

W

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

1,700

1,000

1,275

750

850

500

9,200

15,000

2,000

30

190

50/39/33

26.4

15

2,040

1,200

1,530

900

1,020

600

10,800

16,000

2,400

30

175

51/40/34

31

30

2,550

1,500

2,100

1,240

1,300

760

13,500

17,500

2,400

30

236

51/39/33

38.7

39

2,550

1,500

2,100

1,240

1,300

760

13,500

17,500

/

50

474

55/52/48

38.7

39

3,400

2,000

2,550

1,500

1,700

1,000

18,000

23,400

3,000

30

360

53/41/35

51.6

60

3,400

2,000

2,550

1,500

1,700

1,000

18,000

23,400

/

50

665

59/56/50

51.6

60

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight (With EAH)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

4

1.6

1,530×242×534

41(42)

1,369×342×612

45.5(49)

1,369×342×612

46(49)

1,369×342×612

46

1,500×342×612

57(58)

1,500×342×612

53.7

RC3/4"

RC3/4"

ODΦ24New 2-Row Duct

12Pa ESP

30Pa ESP

MKT2-200G12

MKT2-200G30

MKT2-300G12

MKT2-300G30

MKT2-400G12

MKT2-400G30

MKT2-500G12

MKT2-500G30

MKT2-600G12

MKT2-600G30

MKT2-800G12

MKT2-800G30

MKT2-1000G12

MKT2-1000G30

MKT2-1200G12

MKT2-1200G30

MKT2-1400G12

MKT2-1400G30

New 3-Row Duct

12Pa ESP

30Pa ESP

50Pa ESP

MKT3-200G12

MKT3-200G30

MKT3-200G50

MKT3-300G12

MKT3-300G30

MKT3-300G50

MKT3-400G12

MKT3-400G30

MKT3-400G50

MKT3-500G12

MKT3-500G30

MKT3-500G50

MKT3-600G12

MKT3-600G30

MKT3-600G50

MKT3-800G12

MKT3-800G30

MKT3-800G50

MKT3-1000G12

MKT3-1000G30

MKT3-1000G50

MKT3-1200G12

MKT3-1200G30

MKT3-1200G50

MKT3-1400G12

MKT3-1400G30

MKT3-1400G50

Specifications (4-row)

Page 15: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 28Fan Coil Unit27

Specifications

Note:1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT2-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

340

200

255

150

170

100

1,810

2,680

31

45

36/34/29

41/37/31

5.2

5

510

300

385

225

255

150

2,610

3,770

50

45

38/33/29

41/37/32

7.5

11

680

400

510

300

340

200

3,210

4,660

60

67

38/35/31

42/39/33

9.2

19

850

500

640

375

425

250

3,460

5,080

80

108

39/36/32

45/41/34

9.9

22

1020

600

765

450

510

300

4,530

6,770

97

110

40/36/33

46/41/35

13.0

14

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight(12Pa/30Pa)

Water-inlet pipe

Water-outlet pipe

Drain pipe

12

30

12

30

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

12/30

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

757×241×526

18/17

812×241×526

21/19

912×241×526

23/23

RC3/4"

RC3/4"

ODΦ24

912×241×526

23/23

1135×241×526

27/27

Power Input

Noise(Hi/Med/Lo)

200G12200G30

300G12300G30

400G12400G30

500G12500G30

600G12600G30

Specifications

Note:1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT2-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight(12Pa/30Pa)

Water-inlet pipe

Water-outlet pipe

Drain pipe

12

30

12

30

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

12/30

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

RC3/4

RC3/4

ODΦ24

Power Input

Noise(Hi/Med/Lo)

1360

800

1020

600

680

400

6,250

9,080

140

130

42/37/33

46/41/36

17.9

14

1435×241×526

36/36

800G12800G30

1700

1000

1275

750

850

500

7,510

10,880

172

171

44/39/34

47/43/37

21.5

22

1540×241×526

41.5/38

1000G121000G30

2040

1200

1530

900

1020

600

9,590

13,420

205

212

46/40/35

48/44/38

27.5

39

1830×241×526

47.5/44.2

1200G121200G30

2380

1400

1785

1050

1190

700

10,320

14,280

216

249

48/42/37

49/44/39

29.6

46

1992×241×526

49.5/49.5

1400G121400G30

Page 16: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 30Fan Coil Unit29

Specifications

Note:1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT3-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

W

dB(A)

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

340

200

255

150

170

100

2,200

3,500

33

49

51

35/32/26

41/37/31

45/40/35

6.3

14

510

300

385

225

255

150

3,100

5,300

53

64

76

36/33/27

42/38/32

47/42/37

8.9

26

680

400

510

300

340

200

4,000

6,800

66

75

89

37/34/28

43/39/33

48/43/38

11.5

18

850

500

640

375

425

250

4,600

7,900

87

93

111

40/36/30

44/40/34

49/44/39

13.2

24

1,020

600

765

450

510

300

5,800

9,800

100

114

128

42/38/32

45/41/35

49/44/40

16.7

36

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

12

30

50

12

30

50

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

12/30/50

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

757×241×526

17.5

812×241×526

21

912×241×526

23

RC3/4"

RC3/4"

ODΦ24

912×241×526

23

1,135×241×526

27

Power Input

Noise(Hi/Med/Lo)

200G12200G30200G50

300G12300G30300G50

400G12400G30400G50

500G12500G30500G50

600G12600G30600G50

Specifications

Note:1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Water Flow

Water Pressure Drop

Model MKT3-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

W

dB(A)

dB(A)

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

1,360

800

1,020

600

680

400

8,200

13,600

145

154

174

43/39/33

46/42/36

49/45/40

23.5

39

1,700

1,000

1,275

750

850

500

9,000

16,000

180

180

225

45/41/35

47/43/37

50/45/40

25.8

32

2,040

1,200

1,530

900

1,020

600

11,000

20,100

210

220

271

46/42/36

48/44/38

51/46/41

31.6

39

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

12

30

50

12

30

50

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

12/30/50

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

1,435x241x526

36

1,540x241x526

41.5

RC3/4"

RC3/4"

ODΦ24

1,830x241x526

47.5

1,992x241x526

49.5

Power Input

Noise(Hi/Med/Lo)

800G12800G30800G50

1000G121000G301000G50

1200G121200G301200G50

2,380

1,400

1,785

1,050

1,190

700

12,500

21,000

222

278

335

48/44/38

49/45/39

51/46/42

35.9

45

1400G121400G301400G50

Page 17: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 32Fan Coil Unit31

Features

High air volume, high static pressure, high capacity.

High-pressure centrifugal fans.

Easy to clean and change the air filter.

Auxiliary electrical heater is optional.

Flexible control, no standard controller, remote controller and wired controller are optional.

Standard extended drainage pan for protecting your ceiling better.

Four-speed motor with one reserved for more choice .

Pipe connection from left or right can be selected (in factory).

Features

High static pressure duct

High water pump head

Specifications

Note: 1. The data is the performance in high speed with 70Pa external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with E type unit.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Standard External Static Pressure

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKT3H- 800(E)G70 1000(E)G70 1200(E)G70 1400(E)G70

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

Pa

W

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

1,360

800

1,220

720

1,090

640

6,600

9,700

5,000

70

350

60/56/50

18.5

8

1,700

1,000

1,530

900

1,380

810

8,800

13,200

5,000

70

350

61/57/51

25.2

24

2,040

1,200

1,880

1,105

1,610

950

10,000

15,000

5,000

70

350

61/57/51

28.5

24

2,380

1,400

2,120

1,250

1,860

1,095

12,000

17,900

5,000

70

350

62/59/52

34.2

36

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

1.6

946×400×816 (946×400×876)

Type

Type

Row

Working Pressure

Net Dimension (with EAH) (W×H×D)

Net Weight (with EAH)

Water-inlet pipe

Water-outlet pipe

Drain pipe

50(53)

2 3 3 4

52(55) 52(55) 54(57)

RC3/4"

RC3/4"

ODΦ32

Page 18: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 34Fan Coil Unit33

Features

Different color of panels for choose.

Cross flow fan creates quiet and comfortable environment.

Wireless remote control with LED display, wired control is optional.

Multi-connection outlet pipe method: left\right\rear, satisfy the need of different rooms.

Built-in the 3-way electromagnetic valve.

Easy maintenance has been realized as the front panel can be removed for easy access.

Four-speed motor with one reserved for more choice.

Features

Wall-mountedOptional accessoriesSpecifications

Note: 1. The data is the performance in high speed with 100Pa external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room.4. The EAH capacity only available with E type unit.

Compact body High water pump head

Easy maintenance Multi-connection outlet pipe

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Electrical Auxiliary Heater (EAH)

Standard External Static Pressure

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKT3H- 1600(E)G100 1800(E)G100 2200(E)G100

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

Pa

W

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

2,720

1,600

2,450

1,440

2,170

1,280

14,100

21,200

9,500

100

550

62/58/53

40.4

52

3,060

1,800

2,750

1,620

2,450

1,440

15,800

23,800

9,500

100

800

63/60/55

45.4

90

3,740

2,200

3,360

1,980

2,990

1,760

19,900

30,000

9,500

100

950

66/63/58

57.2

130

Fan Motor

Fan

Coil

Indoor Unit

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

1,290×400×809 (1,290×400×874)

76(82)

RC3/4"

RC3/4"

ODΦ32

Type

Type

Row

Working Pressure

Net Dimension (with EAH) (W×H×D)

Net Weight (with EAH)

Water-inlet pipe

Water-outlet pipe

Drain pipe

Pipe Connection

Page 19: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 36Fan Coil Unit35

Alternative air return type Movable louver

Optional accessoriesSpecifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room

Flexible for installation, designed for horizontal/vertical, concealed/cabinet application.

Ultra-thin body, streamlined appearance.

Air return from the side or below for increased choice flexibility.

3-way electromagnetic valve can be built inside.

Movable louver makes wide angle air flow.

Pipe connection from left or right can be selected (in factory).

Features

Features

Floor-standing and Ceiling & FloorMKF1(2) MKF4(5) (New appearance)

MKH1(2) MKF3/MKH3 (Concealed type)

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKG- 250 300 400 500 600

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

425

250

360

210

320

190

2,200

3,020

28

30/24/20

6.3

12

510

300

430

250

380

220

2,640

3,690

40

35/29/24

7.6

18

680

400

580

340

510

300

3,080

4,340

44

37/31/26

8.8

22

850

500

720

420

640

380

4,070

5,690

50

39/33/28

11.7

26

1,020

600

870

510

770

450

4,450

6,300

60

40/34/29

12.8

29

Fan Motor

Fan

Coil

Indoor Unit

Low noise 4-speed fan motor

Cross flow fan

2

1.6

G3/4"

G3/4"

ODΦ20

Type

Type

Row

Working Pressure

Net Dimension (with EAH) (W×H×D)

Net Weight (with EAH)

Water-inlet pipe

Water-outlet pipe

Drain pipe

915×210×290

12

915×210×290

12

915×210×290

12

1,070×210×316

15

1,070×210×316

15

Pipe Connection

Page 20: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit37 Fan Coil Unit 38

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room

Optional accessoriesSpecifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room

Optional accessoriesSpecifications

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKF1(2,3,4,5)- 150 250 300 400 450

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

mm

kg

Inch

Inch

mm

255

150

215

125

190

110

1,150

2,540

27

32/29/26

3.3

18.3

425

250

360

210

320

190

1,870

4,170

29

35/32/30

5.4

10.1

510

300

430

250

380

220

2,530

5,640

40

37/34/32

7.3

14.2

680

400

580

340

510

300

3,270

7,220

46

39/36/34

9.4

9.5

765

450

650

380

570

335

3,970

8,850

39

41/38/36

11.4

10.3

Fan Motor

Fan

Coil

Indoor Unit

Indoor Unit

Indoor Unit

Low noise 3-speed fan motor

Centrifugal, forward-curved Blades

1.6

G3/4"

G3/4"

ODΦ16

Type

Type

Working Pressure

Row

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

3

800×626×220

22.8(22.5)

550×545×212

17

800×572×225

22.5(22.5)

3

800×626×220

22.6(24.5)

550×545×212

17

800×572×225

22.5(22.5)

2

1,000×626×220

23.4(29)

750×545×212

20

1,000×572×225

26(26)

2

1,000×626×220

26(26)

750×545×212

20

1,000×572×225

26(26)

3

1,200×626×220

32.5(32.5)

950×545×212

25

1,200×572×225

32.5(32.5)

MKF1(2)

MKF3

MKF4(5)

Pipe Connection

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKF1(2,3,4,5)- 500 600 800 900

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

mm

kg

Inch

Inch

mm

850

500

720

420

640

375

4,850

10,280

49

43/40/38

13.9

24.6

1,020

600

870

510

765

450

5,640

12,240

63

44/41/39

16.2

11.4

1,360

800

1,160

680

1,020

600

6,520

15,350

88

46/43/40

18.7

9.5

1,530

900

1,300

760

1,150

675

7,850

18,200

137

48/45/42

22.5

12.1

Fan Motor

Fan

Coil

Indoor Unit

Indoor Unit

Indoor Unit

Low noise 3-speed fan motor

Centrifugal, forward-curved Blades

1.6

G3/4"

G3/4"

ODΦ16

Type

Type

Working Pressure

Row

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

3

1,200×626×220

32.5(31.5)

950×545×212

25

1,200×572×225

32.5(35)

2

1,500×626×220

38(39)

1,250×545×212

32

1,500×572×225

39(36.6)

2

1,500×626×220

38(39)

1,250×545×212

32

1,500×572×225

39(39)

2

1,500×626×220

39(39)

1,250×545×212

32

1,500×572×225

39(39)

MKF1(2)

MKF3

MKF4(5)

Pipe Connection

Page 21: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 40Fan Coil Unit39

Note:1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room

Optional accessoriesSpecifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 50°C, enter air temperature 20°C, the same water flow as the cooling conditions.3. Noise level is tested in semi-anechoic room

Optional accessoriesSpecifications

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKH1(2,3)- 150 250 300 400 450

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

255

150

215

125

190

110

1,150

1,520

27

32/29/26

3.3

18.3

425

250

360

210

320

190

1,870

2,530

45

35/32/30

5.4

10.1

510

300

430

250

380

220

2,530

3,490

44

37/34/32

7.3

14.2

680

400

580

340

510

300

3,270

4,580

46

39/36/34

9.4

9.5

765

450

650

380

570

335

3,970

5,640

40

41/38/36

11.4

10.3

Fan Motor

Fan

Coil

Indoor Unit

Indoor Unit

Type

Type

Working Pressure

Row

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

3

800×626×220

22.5

550×545×212

17

3

800×626×220

22.5

550×545×212

17

2

1,000×626×220

26

750×545×212

20

2

1,000×626×220

26

750×545×212

20

3

1,200×626×220

32.5

950×545×212

25

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

1.6

G3/4"

G3/4"

ODΦ16

MKH1(2)

MKH3

Pipe Connection

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Model MKH1(2,3)- 500 600 800 900

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

850

500

720

420

640

375

4,850

6,980

49

43/40/38

13.9

24.6

1,020

600

870

510

765

450

5,640

8,230

77

44/41/39

16.2

11.4

1,360

800

1,160

680

1,020

600

6,520

9,580

118

46/43/40

18.7

9.5

1,530

900

1,300

760

1,150

675

7,850

11,690

137

48/45/42

22.5

12.1

Fan Motor

Fan

Coil

Indoor Unit

Indoor Unit

Type

Type

Working Pressure

Row

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

3

1,200×626×220

32.5

950×545×212

25

2

1,500×626×220

39

1,250×545×212

32

2

1,500×626×220

39

1,250×545×212

32

2

1,500×626×220

39

1,250×545×212

32

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

1.6

G3/4"

G3/4"

ODΦ16

MKH1(2)

MKH3

Pipe Connection

Page 22: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 42Fan Coil Unit41

Features

Capacity range: 200CFM to 1200CFM.

Space saving, only 242mm in height.

30Pa external static pressure for standard.

Need less water, little power of water pumps, save power cost for the high temp difference.

Standard extended drainage pan for protecting your ceiling better.

Air return from the rear or below for increased installation flexibility.

Pipe connection from left or right can be selected (in factory).

Four-Speed motor with one reserved for more choice.

Features

District cooling FCU

Note:1. The data is the performance in high speed with 30Pa external static pressure. 2. Cooling Conditions: 1*-Entering Water 7.2°C, Temperature Rise 8.4°C, Entering Air Temperature 26.7°C DB, 19.4°C WB. 2*-Entering Water 7.2°C, Temperature Rise 5.6°C, Entering Air Temperature 26.7°C DB, 19.4°C WB. 3. Noise level is tested in semi-anechoic room.

Specifications

Air Volume

High

Med

Low

Cooling Capacity (1*/2*)

Sensible Cooling Capacity (1*/2*)

Standard External Static Pressure

Power Input

Noise(Hi/Med/Lo)

Water Flow (1*/2*)

Water Pressure Drop (1*/2*)

Model MKQT3H- 200 300 400 500 600

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

340

200

290

170

200

120

2,000/2,480

1,600/1,640

30

45

36/33/27

3.2/6.4

3.9/8

510

300

430

250

310

180

2,900/3,600

2,320/2,370

30

62

38/32/28

4.7/9.2

5.6/11.2

680

400

580

340

410

240

3,200/3,970

2,560/2,620

30

72

40/34/30

5/10.2

6.2/12.5

850

500

720

420

510

300

3,700/4,590

2,960/3,030

30

92

42/36/31

5.9/11.8

7.2/14.6

1,020

600

870

510

610

360

5,100/6,320

4,080/4,170

30

112

44/39/32

8.2/16.2

9.9/20.2

Fan Motor

Fan

Coil

Indoor Unit

Pipe Connection

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

812×242×534

19.5

757×242×534

17

912×242×534

21.5

912×242×534

21.5

1,125×242×534

25

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

RC3/4"

RC3/4"

ODΦ24

Page 23: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 44Fan Coil Unit43

Features

High comfortable, cold and hot water can be supplied simultaneously.

Cooling and heating model can be exchanged conveniently.

High capacity of cooling and heating performance, high efficiency and energy-saving.

Optional extended drainage pan for protecting your ceiling better.

Four-speed motor with one reserved for more choice .

Features

4-pipe FCU

4-way cassette 4-way Cassette (compact) Duct type

4-way Cassette

duct

Hot water Cold water

4-way Cassette (compact)

Note:1. The data is the performance in high speed with 30Pa external static pressure. 2. Cooling Conditions: 1*-Entering Water 7.2°C, Temperature Rise 8.4°C, Entering Air Temperature 26.7°C DB, 19.4°C WB. 2*-Entering Water 7.2°C, Temperature Rise 5.6°C, Entering Air Temperature 26.7°C DB, 19.4°C WB. 3. Noise level is tested in semi-anechoic room.

Specifications

Air Volume

High

Med

Low

Cooling Capacity (1*/2*)

Sensible Cooling Capacity (1*/2*)

Standard External Static Pressure

Power Input

Noise(Hi/Med/Lo)

Water Flow (1*/2*)

Water Pressure Drop (1*/2*)

Model MKQT3H- 800 1000 1200 1500 2000

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

dB(A)

l/min

kPa

MPa

mm

kg

Inch

Inch

mm

1,360

800

1160

680

820

480

7,100/8,800

5,680/5,810

30

145

45/41/32

11.4/22.6

13.8/27.5

1,700

1,000

1,440

850

1020

600

7,500/9,300

6,000/6,140

30

170

46/40/32

11.9/23.9

14.6/29.2

2,040

1,200

1,730

1,020

1,220

720

9,600/11,900

7,680/7,860

30

220

47/41/32

15.2/30.5

18.7/37.6

2,550

1,500

2,170

1,280

1,530

900

11,250/13,950

9,000/9,210

30

280

49/43/34

18.1/35.8

23.5/47.1

3,400

2,000

2,890

1,700

2,040

1,200

15,000/18,600

12,000/12,280

30

350

52/46/37

24.1/47.7

28.7/57.2

Fan Motor

Fan

Coil

Indoor Unit

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

1,530×242×534

39.5

1,425×242×534

34

1,820×242×534

44.5

1,369×342×612

46

1,500×342×612

57

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

RC3/4"

RC3/4"

ODΦ24

Pipe Connection

Hot water Cold water Hot water Cold water

Page 24: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 46Fan Coil Unit45

Specifications

Note: 1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C, enter air temperature 20°C3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Fan Motor

Fan

Model MKD- 300S 500S

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

l/min

kPa

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

510

300

440

260

360

210

2,500

3,700

50

36/33/28

7.2

5.3

22

17

680

400

580

340

480

280

2,900

4,600

70

42/39/32

8.4

6.6

16

23

850

500

730

430

600

350

3,500

5,100

95

45/42/34

10

7.3

24

27

Cooling

Heating

Cooling

Heating

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Water Flow

Water Pressure Drop

Coil

Panel

Indoor Unit

400S

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

647×50×647

3

575×261×575

17.5

Cold water: G3/4" Hot water: G1/2"

Cold water: G3/4" Hot water: G1/2"

ODΦ25

Pipe Connection

Specifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C3. Noise level is tested in semi-anechoic room

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Fan Motor

Fan

Model MKA- 600F 750F 850F 950F 1200F 1500F

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

l/min

kPa

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

1,150

680

800

470

690

410

5,100

6,670

170

42/32/26

14.6

9.6

15

37

1,460

860

1,020

600

880

510

5,930

7,870

188

44/34/28

17

11.3

17

41

1,480

870

1,040

610

890

520

6,170

8,060

198

46/36/30

17.7

11.6

20

39

1,720

1,010

1,200

700

1,030

610

6,700

8,670

205

47/38/32

19.2

12.4

22

42

1,860

1,090

1,300

760

1,110

650

9,280

11,650

197

48/40/34

26.6

16.7

32

57

2,100

1,230

1,470

860

1,260

740

10,580

12,620

234

50/42/36

30.3

18.1

38

61

Cooling

Heating

Cooling

Heating

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Water Flow

Water Pressure Drop

Coil

Panel

Indoor Unit

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

1.6

950×45×950

6

840×300×840

Cold water: RC3/4" Hot water: RC1/2"

Cold water: RC3/4" Hot water: RC1/2"

ODΦ32

35 35 35 35 38 38

2 2 2 2 3 3

Pipe Connection

Page 25: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 48Fan Coil Unit47

Specifications

Note: 1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Model MKT5(H)- 600 800 1000 1200

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

dB(A)

dB(A)

l/min

l/min

kPa

kPa

MPa

mm

kg

Inch

Inch

mm

1,020

600

770

450

510

300

5,000

7,200

100

115

43/40/35

45/42/37

14.4

10.3

22

60

1,360

800

1,020

600

680

400

6,800

9,600

134

160

44/41/36

46/43/38

19.5

13.8

20

26

1,700

1,000

1,280

750

850

500

7,800

10,800

172

220

46/43/38

48/45/40

22.4

15.5

47

45

2,040

1,200

1,530

900

1,020

600

10,200

13,500

220

240

47/44/39

50/47/42

29.2

19.4

57

53

12Pa

30Pa

12Pa

30Pa

Cooling

Heating

Cooling

Heating

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Fan Motor

Fan

Coil

Indoor Unit

12/30

1,125×240×490

21

1,425×240×490

28

1,530×240×490

32

1,820×240×490

37

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

Cold water: G3/4" Hot water: G1/2"

Cold water: G3/4" Hot water: G1/2"

ODΦ24

Pipe Connection

Specifications

Note: 1. The data is the performance in high speed with relevant external static pressure.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C3. Noise level is tested in semi-anechoic room.

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Standard External Static Pressure

Model MKT5(H)- 200 300 400 500

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

Pa

W

W

dB(A)

dB(A)

l/min

l/min

kPa

kPa

MPa

mm

kg

Inch

Inch

mm

340

200

260

150

170

100

2,000

3,000

34

40

36/33/28

39/36/31

5.7

4.3

7.8

8.8

510

300

390

230

260

150

2,700

4,000

46

60

38/35/30

41/38/33

7.7

5.7

16

17

680

400

510

300

340

200

3,600

5,200

65

80

40/37/32

43/40/35

10.3

7.5

11

34

850

500

640

380

430

250

4,300

5,700

80

115

42/39/34

44/41/36

12.3

8.2

36

33

12Pa

30Pa

12Pa

30Pa

Cooling

Heating

Cooling

Heating

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Power Input

Noise(Hi/Med/Lo)

Water Flow

Water Pressure Drop

Fan Motor

Fan

Coil

Indoor Unit

12/30

757×240×490

14

812×240×490

16.5

912×240×490

18

912×240×490

18

Low noise 4-speed fan motor

Centrifugal, forward-curved Blades

3

1.6

Cold water: G3/4" Hot water: G1/2"

Cold water: G3/4" Hot water: G1/2"

ODΦ24

Pipe Connection

Page 26: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 50Fan Coil Unit49

High comfortable, cold and hot water can supply simultaneously.

Cooling and heating model can exchange conveniently.

Various thermostats can be chosen by customer’s need.

Flexible wiring connection for non-PCB.

High capacity of cooling and heating performance, high efficiency and energy-saving.

Built-in control valve helps to switch the supply of cold or hot water by remote controller.

Optional extended drainage pan for protecting your ceiling better.

Fresh air provision makes life healthier and more comfortable.

Features

4 -pipe cassette FCU (without PCB)

4-way Cassette 4-way Cassette (compact)

Specifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C3.Noise level is tested in semi-anechoic room

160

16.0kW

Air Volume

High

Med

Low

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Cooling

Heating

Cooling

Heating

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Fan Motor

Fan

Coil

Panel

Indoor Unit

Pipe Connection

35 35 38 38

Water Flow

Water Pressure Drop

Model MKA-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

l/min

kPa

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

1,460

860

1,020

600

880

520

5,930

7,870

188

44/34/28

17

11.3

17

41

1,720

1,010

1,200

700

1,030

610

6,650

8,600

190

47/38/32

19.1

12.3

22

42

1,860

1,090

1,300

760

1,110

650

9,100

11,650

197

48/40/34

26.1

17

32

57

Low noise 3-speed fan motor

Centrifugal, forward-curved Blades

1.6

950×45×950

6

840×300×840

Cold water: RC3/4" Hot water: RC1/2"

Cold water: RC3/4" Hot water: RC1/2"

ODΦ32

750NF 950NF 1200NF

2,050

1,210

1,470

860

1,260

740

10,000

12,600

234

50/42/36

28.7

18.1

38

61

1500NF

2 2 3 3

Page 27: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 52Fan Coil Unit51

Specifications

Note: 1. The data is the performance in high speed.2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°CWB. Heating Conditions: Entering Water 70°C, Entering/leaving temperature difference is 10°C,enter air temperature 20°C3.Noise level is tested in semi-anechoic room

Fan performance160

16.0kW

Air Volume

High

Med

Low

Model MKD-

m3/h

CFM

m3/h

CFM

m3/h

CFM

W

W

W

dB(A)

l/min

l/min

kPa

kPa

MPa

mm

kg

mm

kg

Inch

Inch

mm

510

300

440

260

360

210

2,360

3,700

50

36/33/28

6.8

5.3

22

17

680

400

580

340

480

280

2,900

4,600

70

42/39/32

8.3

6.6

16

23

850

500

730

430

600

350

3,500

4,830

87

45/42/34

10

6.9

24

27

Low noise 3-speed fan motor

Centrifugal, forward-curved Blades

2

1.6

647×50×647

3

575×261×575

17.5

Cold water: G3/4" Hot water: G1/2"

Cold water: G3/4" Hot water: G1/2"

ODΦ25

300NF 400NF 500NF

Cooling Capacity

Heating Capacity

Power Input

Noise(Hi/Med/Lo)

Fan Motor

Fan

Panel

Cooling

Heating

Cooling

Heating

Type

Type

Row

Working Pressure

Net Dimension (W×H×D)

Net Weight

Net Dimension (W×H×D)

Net Weight

Water-inlet pipe

Water-outlet pipe

Drain pipe

Water Flow

Water Pressure Drop

Coil

Indoor Unit

Pipe Connection

Page 28: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 54Fan Coil Unit53

Fan performance12Pa 30Pa 30Pa 50Pa

The units using the wide wheel of latest design and low speed forward-curved blades are most suitable for the motor through dynamic balance test.

The motor adopts durable capacitance, superior lubricant oil and rust-proof treatment for high reliability and low noise.

70/100Pa

0 84 12 16 20 24 28 32 36 40 44 48 52

10

20

30

50

40

60

Air Flow (m /min)

Ext

erna

l Sta

tic P

ress

ure

(Pa)

3

200 300 500 600 800 1000 1200 1400400

0 84 12 16 20 24 28 32 36 40 44 48 52

10

20

30

50

40

60

Air Flow (m /min)

Ext

erna

l Sta

tic P

ress

ure

(Pa)

3

200 300 500 600 800 1000 1200400

0 84 12 16 20 24 28 32 36 40 44 48 52

10

20

30

50

40

60

Air Flow (m /min)E

xter

nal S

tatic

Pre

ssur

e (P

a)3

80

70

90

200 300 500 600 800 1000 1200 1400400

10

20

30

50

40

60

Air Flow (m /min)

Ext

erna

l Sta

tic P

ress

ure

(Pa)

3

80

70

90

200 300 500 600 800 1000 1200400

MKT2-200~1400(E)

MKT3-200~1200

MKT2H-200~1400(E)

MKT3H-200~1200

0 84 12 16 20 24 28 32 36 40 44 48 52

10

20

30

50

40

60

Air Flow (m /min)

Ext

erna

l Sta

tic P

ress

ure

(Pa)

3

80

70

90

200 300 500 600 800 1000 1200 1400400

MKT3-200~1400G12

0 84 12 16 20 24 28 32 36 40 44 48 52

10

20

30

50

40

60

Air Flow (m /min)

Ext

erna

l Sta

tic P

ress

ure

(Pa)

3

80

70

90

200 300 500 600 800 1000 1200 1400400

MKT3-200~1400G30

0 12 6 18 24 30 36 42 48 54 60 66 72 78

20

40

60

100

80

120

Air Flow (m /min)E

xter

nal S

tatic

Pre

ssur

e (P

a)

3

160

140

180 800 1000 1400 1600 18001200

84 90

2200

MKT3H-800~1400G70MKT3H-1600~2200G100

0 105 15 20 25 30 35 40 45 50 55 60 65

10

20

30

50

40

60

Air Flow (m /min)

Ext

erna

l Sta

tic P

ress

ure

(Pa)

3

80

70

90 200 300 500 600 8001000 1200 1400400

70 75

2000G501500G50

MKT3-200~1400G50MKT4H-1500~2000G50

0 105 15 20 25 30 35 40 45 50 55 60 65

10

20

30

50

40

60

Air Flow (m /min)

Ext

erna

l Sta

tic P

ress

ure

(Pa)

3

80

70

90

200 300 500 600 8001000 1200 1500400

70 75

2000

MKT4H-200~2000(E)

Page 29: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 56Fan Coil Unit55

Controllers

ControllersFor cassette and wall-mountedStandard wireless remote controllers for cassette and wall-mounted

Optional wired controller for cassette and wall-mounted

Optional central controller for cassette and wall-mounted

Specification FunctionWorking Rated Voltage: DC3V.

Min vlotage for sending signal of CPU: DC2.4V.

Working Environment:Temperature: -5~60°C.

Effective receiving distance: 8~11m.

Temperature Controlling Range: 17~30°C.

Temperature Controlling Precision: ±1°C.

Applied Equipment: R05/BGE: cassette(standard), R51/E:

wall-mounted(standard).

LCD display screen.

Mode setting: auto/cool/heat/dry/fan.

Fan speed selection: auto/high/medium/low.

Time setting/temp. setting/ swing setting.R05/BGE R51/E

Specification FunctionWorking Voltage: DC5V.

Working Environment:

Temperature: -15~43°C

Relative Humidity: 40%~90%.

Temperature Controlling Range: 17~30°C.

Temperature Controlling Precision: ±1°C.

Applied Equipment: cassette and wall-mounted(optional).

Big LCD display screen.

Mode setting: auto/cool/heat/dry/fan.

Fan speed selection: auto/high/medium/low.

Economic operation mode/time setting/temp. setting.

ON/OFF mode setting.KJR-10B/DP(T)-EKJR-12B(DP)

Specification FunctionWorking Voltage: AC220±10%, 50/60Hz.

Working Environment:

Temperature: -15~43°C

Relative Humidity: 40%~90%.

Temperature Controlling Range: 17~30°C.

Temperature Controlling Precision: ±1°C.

Applied Equipment: cassette and wall-mounted(optional).

Centralized control:

the max. quality of indoor units is up to 64 by one CCM03.

Big LCD display screen.

Mode setting: cool/heat/ fan.

Fan speed selection: auto/high/medium/low.

Time setting/temp. setting/ swing setting.

CCM03

Page 30: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 58Fan Coil Unit57

Accessories

For floor-standing and ceiling & floorOptional wired controller for floor-standing and ceiling & floor

Specification FunctionWorking Voltage: AC220V~230V, 50/60Hz

Working Environment:

Temperature: -15~43°C

Relative Humidity: 40%~90%.

Temperature Controlling Range:17~30°C /62~86°F.

Temperature Controlling Precision: ±1°C.

Applied Equipment:

floor standing and ceiling & floor standing (optional).

LCD display screen.

Mode setting: cool/heat/fan.

Fan speed selection: high/medium/low.

Temperature display in °F or °C.

ON/OFF mode setting.

KJR-15B/E(P)

For Duct

Optional wired controller for duct units with EAH

Specification FunctionWorking Voltage: AC220V±10%, 50/60Hz.

Power Consumption: <2W.

Current Loae: <2A.

Temperature Controlling Range: 5~35°C.

Temperature Controlling Precision: ±1°C.

External Dimension: 86×86×13mm (W×H×D).

Installation hole pitch: 60mm (standard).

Applied Equipment: duct units with EAH(optional).

Blue backlight.

Clock display.

Temp. setting.

Mode setting: cool/heat/fan/electric heating on/off.

Fan speed selection: auto/high/medium/low.

Motorized valve control.

Electric heating control.

Remote control (optional).

KJR-21B/D

Optional wired controller for duct units without EAH

SpecificationWorking Voltage: AC220V±10%, 50/60Hz.

Working Environment:

Temperature: 0~45°C

Relative Humidity: 5%~90%.

Temperature Controlling Range:10~30°C.

Temperature Controlling Precision: ±1°C.

External Dimension: 85×130×43mm (W×H×D).

Installation hole pitch: 60mm (standard).

KJR-18B

FunctionApplied Equipment: duct units without EAH(optional).

Mode setting: cool/heat/off.

Fan speed selection: high/medium/low.

Temperature setting.

Model Applied Equipment Objects Controlled

3-speed fan

motorized valve and 3-speed fan

motorized valve and 3-speed fan

two motorized valve and 3-speed fan

KJB-18B-A

KJB-18B-B

KJB-18B-C

KJB-18B-D

2-pipe duct

2-pipe duct

2-pipe duct

4-pipe duct

Page 31: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 60Fan Coil Unit59

AccessoriesFeatures

Suitable for 2-pipe and 4-pipe ductable FCU without electric auxiliary heater.

Installation flexible ,it can be installed attaching on the unit, mounting on the wall or hanging under the ceiling.

Maintenance convenient for its external installed.

Three speeds adjustment: high/medium/low.

Operating status can be displayed from lamp indicator.

Network Interface Module standard, compatible with the CCM control and PC based software control.

Features

Specification

Extended drainage pan

PC board control kit for FCU

Valve kit

Optional accessoriesSpecificationsModel FCUKZ-01

2-pipe ductable FCU 4-pipe ductable FCU

FCUKZ-02

Operation range

Applicable appliance

Power supply

Room temperature

Inlet water temperature

Temperature controlling precision

Dimension (W×H×D)

Packing Size (W×H×D)

Selection for compatibility

220-240V-1Ph-50/60Hz

17°C-30°C

3°C-75°C

±1°C

310×76×290

384×174×359

Remote /Wired /Central /PC based network software control

Working Voltage: AC230±10%, 50/60Hz(24V can be customized).

Power Consumption: 4W(Only when you open and close the valve).

Nominal Pressure: 1.6Mpa.

Applied Medium: Cold or hot water, 50% glycol water liquor.

Medium Temperature: 2~75°C.

Environment Temperature: -5~50°C.

Specification

Working Voltage: AC230±10%, 50/60Hz(24V can be customized).

Power Consumption: 4W(AC230V) 6W(AC24V).

Nominal Pressure: 1.6Mpa.

Applied Medium: Cold or hot water, 50% glycol water liquor.

Protection Grade: IP54.

Working Journey: 2.5~3mm.

Medium Temperature: -20~70°C.

Environment Temperature: 0~50°C.

Security Class: Ⅱ(Double Insulation).

Running Time: ≤5 Minutes(25°C).

There is standard auxiliary drainage pan for ductable FCU with inlet plenum box, and optional auxiliary drainage pan for cassette FCU and ductable FCU without inlet plenum box.With extended drainage pan to receive the condensate water dripping from the water piping and valve connection.

DDSTF-01

DDSTF-04DDSTF-05

Page 32: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 62Fan Coil Unit61

Selection software

Application of network control & BMS control

KJR-90B/M-E

KJR-180A

CCM03

CCM09

Indoor unit central controller. Max. 64 indoor units can be controlled.Automatically record all setting information when lose power.Clear & bright LCD display screen, background light, more parameters display.Emergency ON/OFF control with simple dry contact input.

New design indoor unit central controller, similar function with CCM03. Max. 16 indoor units can be controlled.Easier for installation in the wall, complete cabinet at the rear.

New design indoor unit central controller, simple on/off function.Max. 16 indoor units can be controlled.Switch modes between cooling and heating .Overall/mono-control the indoor units.

Indoor unit weekly timer central controller.7 -days Weekly schedule setting (Maximum 128 weekly & daily schedules).Max. 64 indoor units group control or individual setting.Clear and bright screen with LCD backlight.Wireless remote control restriction.Sleep and Silent mode.Mode lock.Permanent schedule setting storage.

Optional for all the indoor units.Mode selection: Auto, Cool, Dry, Heat, Fan only.Temp. setting range: 17 ? to 30 ? Daily Timer setting.Fan speed control: H/M/L/Auto .Louver swing.

KJR-10B

KJR-12B

KJR-90A-E

Same function with KJR-10B.Add the follow me function.

KJR-90A1-E

All basic function as the same as KJR-10B.Small size and Easy for installation.Exquisite appearance and LCD display function.Optional for all the indoor units.

Designed for hotel or other similar place. 1) Only can select ON/OFF, Temp, Swing, and Timer2) Avoid mode conflict.Other functions are the same with KJR-90A-E.

Wall Mounted Compact 4-way Cassette

Softdog

RS485/RS232Converter

Network control software

UPS

Max.64

Max.64

CCM08BMS

Bacnet/IP Network

MAX. 16

Perfect system monitor/control functionIt can dynamically monitor indoor /outdoor units operation condition.Powerful schedule management, group management, uniform management.Accurately electricity distribution function.Adopt Microsoft Fire Bird Server database, It can output detailed data table.

TCP/IP Network PC in LAN

4-way Cassette

2-pipe concealed Ductable 4-pipe concealed Ductable

FCUKZ-01 FCUKZ-02

BACnet/Ethernet optional.Max. 4 Indoor/Outdoor CCMs (CCM02 or CCM03)Each CCM can connect Max. 64 indoor units or 32 outdoor units.No need to install the Network Control Software any more.By inputting IP address of CCM08,PC in LAN could accessCCM08 to realize simple setting and controlling of A/C.

Optional wired controller

Optional central controller

Network Control Software

BACnet Gateway - CCM08

Indoor CCM03

Indoor CCM03

Page 33: Fan Coil Unit 50Hz 2012 - Midea Nordic · Fan Coil Unit 50Hz Commercial Air Conditioner Business Units ... AHU/FCU etc. MCAC Shunde factory with 31 product lines concentrates on the

Fan Coil Unit 64Fan Coil Unit63

Selection softwareFeatures

Main interface

Selection interface

Selection Resule (Equipment List) Simple Report (Specifications)

Menu Project Operation Area Product Operation AreaSelection Button

Unit Settings

SELECTION SOFTWARE

The products of this selection software contain Fan Coil Unit, standard Air Handling Unit and Modular Air Handling Unit.

You can make selections under varies entering air conditions, entering water conditions and different fan speed settings.

The interface is very visualized, which makes the operation easy.

Powerful project management function.

All copyrights reserved by Midea. It should be authorized through Midea technical support engineer before using.