FIRE SAFETY INSPECTION REPORT Fakir Fashion Ltd. (Extension 2) ACCORD ID: 23771 Dohargaon, Baliapara, Rupgonj, Narayangonj 23.784037, 90.587276 Other Factories: None Inspected by: Md. Rakibul Alam & A.K.M. Monoarul Huda Date: 27 August 2019

Upload: others

Post on 01-Dec-2021

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fakir Fashion Ltd. (Extension 2)

FIRE SAFETY INSPECTION REPORT

Fakir Fashion Ltd. (Extension 2)

ACCORD ID: 23771

Dohargaon, Baliapara, Rupgonj, Narayangonj

23.784037, 90.587276

Other Factories: None

Inspected by: Md. Rakibul Alam & A.K.M. Monoarul Huda

Date: 27 August 2019

Page 2: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 2 Fakir Fashion Ltd. (Extension 2)

Fire Safety Inspection Report

Fakir Fashion Ltd. (Extension 2)

Introduction

Fakir Fashion Ltd. (Extension 2) was surveyed for fire safety on 27 August 2019 by The Accord

Inspection Team.

The purpose of the survey was to identify significant fire safety issues and to provide recommendations

for remediation based on applicable standards specified by the Accord. The scope of this initial fire

safety inspection was limited to the review and identification of major fire safety issues. The inspection

did not include identification of minor deficiencies, which will be further addressed as part of follow-up

inspections.

Limitations

The information in this fire safety inspection report was obtained during a visit to the facility and during

interviews with local factory management. It has not been possible to provide independent verification

for all the information and data collected, and, therefore, The Accord cannot accept general

responsibility for omissions or errors arising from inaccuracies in this report from the information

obtained.

The findings and recommendations in this report are not intended to imply, guarantee, ensure or

warrant compliance with any government regulations. Additionally, the results do not imply in any way

that compliance with the findings or recommendations as stated in this report will eliminate all hazards,

risks or exposures or that hazards, risks or exposures not referred to in this report do not exist.

Compliance with the findings and recommendations stated in this report does not relieve the factory

owner from obligation to comply with specific project requirements, industry standards, or the

provisions of any local government regulations.

Page 3: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 3 Fakir Fashion Ltd. (Extension 2)

General Factory Information

Factory Building Name(s):

Fakir Fashion Ltd. (Extension 2) – Building - 6

Fakir Fashion Ltd. (Extension 2) – Building - 7

Factory Address: Dohargaon, Baliapara, Rupgonj, Narayangonj

Points of Contact:

Shafiqul Islam

Sr. Manager-Compliance

Mobile: +88 01766670078

e-mail: [email protected]

Mohammad Ashiqur Rahman

AGM-Compliance

Mobile: +88 01766670036

e-mail: [email protected]

Page 4: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 4 Fakir Fashion Ltd. (Extension 2)

General Building Information – Fakir Fashion Ltd. (Extension 2) – Building - 6

Number of Stories Below / Above Grade 0 / 6

Highest Occupied Floor Level / Height 14 m

High Rise (Accord 3.2.1) No

Occupiable Roof (Accord 3.2.2) Yes

Occupiable Roof Provided with Adequate Parapets / Guards (Accord 6.12.2.4)

Yes

Occupancy Classifications F Business; H2 Storage

Floor Plans Available Yes

Typical Floor Plan Cross Section

Page 5: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 5 Fakir Fashion Ltd. (Extension 2)

Date of Construction Dec 2017 – Jul 2019

Major Renovations / Additions No

Comments 6 Storied Multi-Purpose Warehouse Building

Other Tenants In Building None

Floors Occupied By Factory All

Floor Use Occupant Load

Ground Floor Fabric Storage Area/Rack 15

1st Floor Fabric Storage 10

2nd Floor Fabric Inspection Machine 35

3rd Floor Fabric Storage 9

4th Floor Fabric Storage and Office 40

5th Floor Fabric Storage Racking 10

Construction Features

Non-Combustible Construction Yes

Fire-Resistive Construction Yes

Page 6: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 6 Fakir Fashion Ltd. (Extension 2)

Building Exposures

North Building-4

South Building-3

East Building-4

West Internal Road and Mosque

Vertical Openings

Exit Stairs Enclosed in Fire-Rated Construction (Accord 6.14)

No (Adjacent building stair)

Exit Stair Penetrations are Fire Rated (Accord 6.14)

Yes

Exit Stair Openings are Fire Rated (Accord 6.14)

No

Exterior Exit Stairs Separated From Building (Accord 6.3.1.3)

No

Shafts Enclosed in Fire Rated Construction (Accord 4.5.7)

No

Openings / Penetrations in Fire-Rated Floors are Protected (Accord 4.5.3)

Yes

Atrium Protected As Required (Accord 3.7) N/A

Page 7: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 7 Fakir Fashion Ltd. (Extension 2)

Egress Features

Single dedicated exit serves the building having additional shared exit from adjacent buildings at each floor level. All exits were remotely located and travel distance requirements were met. All exits discharged to the exterior of the building. Adjacent buildings exit stairs were not properly separated on all floors due to unprotected openings and penetrations. The exit doors are provided with 1.5-hr fire-rated doors. Certification documentation for the doors was not provided during the inspection. UL testing certification tags were provided on the doors. Collapsible gate, sliding gate and roll down shutter type doors were not used at any exits of the building. All doors were open and unlocked during the inspection. Handrails were present on both sides of the exit stairs on all floors. Emergency evacuation plans were not located at all the required location. Occupant load signs, floor level signs and stair designation signs were located at exits. No smoking signs were present in the factory at ground floor. Fire drills are conducted monthly; records were provided during the inspection.

Floor Use Number of exits Exit Capacity

Ground Floor Fabric Storage Area/Rack 3 1000

1st Floor Fabric Storage 3 438

2nd Floor Fabric Inspection Machine 3 438

3rd Floor Fabric Storage 3 438

4th Floor Fabric Storage and Office 2 342

5th Floor Fabric Storage Racking 2 342

Page 8: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 8 Fakir Fashion Ltd. (Extension 2)

General

Number of Exits Per Floor is Compliant (Accord 6.6)

Yes

Capacity of Exits Per Floor Is Compliant (Accord 6.5.3)

Yes

Exits Remotely Located (Accord 6.6.6) Yes

Exit Doors

Egress Doors are Side Hinged (Accord 6.8.1) Yes

Egress Doors Swing Correctly (Accord 6.8.1) Yes

Egress Doors Without Locking Hardware in Direction of Travel (Accord 6.8.2)

Yes

Exit Stairs

All Exit Stairs Discharge Directly to the Exterior (Accord 6.17)

Yes

Handrails Provided on Both Sides (Accord 6.9.2.4)

Yes

Exit Stairs Free of Storage and Obstructions (Accord 6.3.8, 6.3.9)

Yes

Electrical Panels Located Outside of Exit Stairs

Yes

Exit Stairs Serving More than 5 Stories Provided with Re-Entry (Accord 6.8.3)

Yes

Page 9: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 9 Fakir Fashion Ltd. (Extension 2)

Exit Access & Arrangement

Means of Egress Free of Storage & Obstructions (Accord 6.3.8, 6.3.9)

Yes

Means of Egress of Adequate Width (Accord 6.5)

No

Travel Distances, CPT, DE's Within Limits (Accord 6.13)

No

Exit Access Corridors Provided with Proper Fire Protection / Separation (Accord 6.3.1.1)

N/A

Daycare Within Limits (Accord 3.4.2.1.1) N/A

Egress Court Provided with Adequate Fire Rated Separation (Accord 6.17.2)

N/A

Utility / Storage Rooms Adequately Separated from Exit Enclosures (Accord 6.14.3)

No

Emergency Planning

Emergency Evacuation Plans Provided (Accord 13.3)

Not provided at required location and not reflected the exact floor and exit condition

Fire Drills Conducted & Records Maintained (Accord 13.2)

Yes

Smoking Prohibited (Accord 13.5) Yes

Page 10: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 10 Fakir Fashion Ltd. (Extension 2)

Evacuation Plan Fire Drill Document

Fire Protection Features

Sprinkler System

Sprinkler system was not available in the building. Based on the height of the highest occupiable floor,

automatic sprinkler protection is not required.

Standpipe System

Hose cabinet with 1.5 in hoses were provided inside the production floor and 2.5 in landing valves

were in stair enclosures. Based on the height of the highest occupiable floor, standpipe system is

required.

Standpipe System Required Yes

Type of System Installed Class-lll

Hose Connection Locations Inside the production floor and stair enclosures.

ITM Per NFPA 25 Yes

Comments Highest Occupied Floor Level was 35m.

Page 11: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 11 Fakir Fashion Ltd. (Extension 2)

Class-ll Hose Cabinet Class-1 Landing Valve

Fire Water Supply

The standpipe system was supplied by fire pumps fed from an underground cistern that is accessed from ground floor. The cistern had a reported capacity of 1,42,000 Gal. The fire pump system consisted of a diesel fire pump, an electric fire pump and a jockey pump. Fire department inlet and outlet connection was provided for the building.

Source, Location, & Capacity Underground cistern and fire pump.

Cistern tank/ underground/ 1,42,000 GAL

Fire Pump Provided Yes

Fire Department Inlet & Outlet Connections Provided (Accord 5.5.4)

Yes

Fire Pump Adequate (Accord 5.5.1) To be verified during functional test

Fire Pump Room Provided With Adequate Fire Rated Separation (NFPA 20)

No

Fire Pump ITM Per NFPA 25 Yes

Page 12: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 12 Fakir Fashion Ltd. (Extension 2)

Fire Alarm System

The building had an addressable fire alarm system built around a BOSCH FPA5000 alarm panel. The system supported smoke detectors, heat detectors, manual pull stations, horn and strobe units installed throughout the building. The activation switches on each floor trigger the fire alarm for the entire building. No functional test was conducted on the system during the inspection.

Type of System Addressable

Fire Panel Location Fire Control Room

Visible Notification Per NFPA 72 To be verified during functional test

Audible Notification Per NFPA 72 To be verified during functional test

Alarm Annunciation To be verified during functional test

ITM per NFPA 72 To be verified during design review and functional test

Functional Test Conducted No

Fire Alarm Switch Fire Alarm Siren

Page 13: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 13 Fakir Fashion Ltd. (Extension 2)

Fire Detection System

Interconnected smoke and heat detectors were located in various places throughout the factory. These detectors were tied into the fire alarm system. In the event they detect smoke and heat, they will send a signal to the fire alarm control panel to activate the fire alarm. No functional test was conducted on the system during the inspection.

Type of Detectors Smoke Detector & Heat Detectors Tied to Fire Alarm System

Smoke Detection Per NFPA 72 To be verified during design review and functional test

Smoke Detector

Portable Fire Extinguishers

Portable fire extinguishers, consisting of a mix of CO2 and dry chemical were provided throughout the

building. Inspection tags show recent and up-to-date inspections. Records of regular testing or

maintenance of the portable fire extinguishers were provided as per NFPA10.

Types Provided CO2 & dry chemical extinguishers.

Adequate Number/Spacing Yes

ITM Per NFPA 10 Yes

Page 14: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 14 Fakir Fashion Ltd. (Extension 2)

Extinguisher

Manual Fire Fighting Equipment

Ground floor had firefighting equipment staged inside the floor. Types of manual firefighting equipment

provided included: buckets, escape hoods, bolt/lock cutters, shovels, stretchers and personal

protection equipment.

Types Provided Buckets, escape hoods, bolt/lock cutters, shovels, stretchers and personal protection equipment.

Location of Equipment Only Ground Floor

Firefighting Equipment

Page 15: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 15 Fakir Fashion Ltd. (Extension 2)

Other Features

Emergency Lighting & Exit Signs

Emergency lighting appliances were located inside the production floor and exit stairs. There were

multiple CFL lights that had an alternate “Instant Power Supply” (IPS). Illuminated exit signs, located

at exits. The factory management reported that these are all serviced by normal electricity as well as

by multiple “Instant Power Supply” (IPS) units. They were keeping records or assertions of regular

testing or maintenance of the emergency lighting system in accordance with Accord standard.

Exits and Exit Access Properly Marked with Exit Signage

Yes

Emergency Power Battery IPS

Adequate Emergency Lighting for Exits & Exit Access

No

Adequate Inspection / Testing (Accord 10.12) Yes

Exit Signage Emergency Light

Page 16: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 16 Fakir Fashion Ltd. (Extension 2)

Elevator

There are two (2) elevators that serve the building. Signage stating “In Case of Fire Don't Use Lift” is provided outside the elevators on some floors.

Elevator Opens into Exit Enclosure Opens into Production Floor

Elevator Shaft / Doors Fire-Rated No

Elevator

Boiler, Generator & Furnace Equipment

Utilities were commonly used and covered by previous Accord inspection in the same complex.

Additional Information

None

Page 17: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 17 Fakir Fashion Ltd. (Extension 2)

General Building Information – Fakir Fashion Ltd. (Extension 2) – Building - 7

Number of Stories Below / Above Grade 0 / 2

Highest Occupied Floor Level / Height 3.5 m

High Rise (Accord 3.2.1) No

Occupiable Roof (Accord 3.2.2) No

Occupiable Roof Provided with Adequate Parapets / Guards (Accord 6.12.2.4)

N/A

Occupancy Classifications G2 Industrial; H2 Storage

Floor Plans Available Yes

Typical Floor Plan Cross Section

Page 18: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 18 Fakir Fashion Ltd. (Extension 2)

Date of Construction Dec 2017 – Jul 2019

Major Renovations / Additions No

Comments 2 Storied Composite Construction

Other Tenants In Building None

Floors Occupied By Factory All

Floor Use Occupant Load

Ground Floor Chemical Warehouse 20

1st Floor Sewing and Finishing 750

Construction Features

Non-Combustible Construction Yes

Fire-Resistive Construction No

Building Exposures

North Shed-10

South Mosque

East Shed-3

West Open Area

Page 19: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 19 Fakir Fashion Ltd. (Extension 2)

Vertical Openings

Exit Stairs Enclosed in Fire-Rated Construction (Accord 6.14)

Yes

Exit Stair Penetrations are Fire Rated (Accord 6.14)

Yes

Exit Stair Openings are Fire Rated (Accord 6.14)

Yes

Exterior Exit Stairs Separated From Building (Accord 6.3.1.3)

No

Shafts Enclosed in Fire Rated Construction (Accord 4.5.7)

No

Openings / Penetrations in Fire-Rated Floors are Protected (Accord 4.5.3)

No

Atrium Protected As Required (Accord 3.7) N/A

Egress Features

Three exit serves the building 1st floor and five exits at ground floor. All exits were remotely located and travel distance requirements were met. All exits discharged to the exterior of the building. The exit doors are provided with 1.5-hr fire-rated doors. Certification documentation for the doors was not provided during the inspection. UL testing certification tags were provided on the doors. Collapsible gate, sliding gate and roll down shutter type doors were not used at any exits of the building. All doors were open and unlocked during the inspection. Handrails were present on both sides of the exit stairs on all floors. Emergency evacuation plans were not located at all the required location. Occupant load signs, floor level signs and stair designation signs were located at exits. No smoking signs were present in the factory at ground floor. Fire drills are conducted monthly; records were provided during the inspection.

Page 20: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 20 Fakir Fashion Ltd. (Extension 2)

Floor Use Number of exits Exit Capacity

Ground Floor Chemical Warehouse 5 1370

1st Floor Sewing and Finishing 3 533

General

Number of Exits Per Floor is Compliant (Accord 6.6)

Yes

Capacity of Exits Per Floor Is Compliant (Accord 6.5.3)

No

Exits Remotely Located (Accord 6.6.6) Yes

Exit Doors

Egress Doors are Side Hinged (Accord 6.8.1) Yes

Egress Doors Swing Correctly (Accord 6.8.1) Yes

Egress Doors Without Locking Hardware in Direction of Travel (Accord 6.8.2)

Yes

Exit Stairs

All Exit Stairs Discharge Directly to the Exterior (Accord 6.17)

Yes

Handrails Provided on Both Sides (Accord 6.9.2.4)

Yes

Page 21: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 21 Fakir Fashion Ltd. (Extension 2)

Exit Stairs Free of Storage and Obstructions (Accord 6.3.8, 6.3.9)

Yes

Electrical Panels Located Outside of Exit Stairs

Yes

Exit Stairs Serving More than 5 Stories Provided with Re-Entry (Accord 6.8.3)

N/A

Exit Access & Arrangement

Means of Egress Free of Storage & Obstructions (Accord 6.3.8, 6.3.9)

Yes

Means of Egress of Adequate Width (Accord 6.5)

No

Travel Distances, CPT, DE's Within Limits (Accord 6.13)

Yes

Exit Access Corridors Provided with Proper Fire Protection / Separation (Accord 6.3.1.1)

N/A

Daycare Within Limits (Accord 3.4.2.1.1) N/A

Egress Court Provided with Adequate Fire Rated Separation (Accord 6.17.2)

No

Utility / Storage Rooms Adequately Separated from Exit Enclosures (Accord 6.14.3)

No

Emergency Planning

Emergency Evacuation Plans Provided (Accord 13.3)

Yes

Fire Drills Conducted & Records Maintained (Accord 13.2)

Yes

Smoking Prohibited (Accord 13.5) Yes

Page 22: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 22 Fakir Fashion Ltd. (Extension 2)

Evacuation Plan No Smoking Sign

Fire Protection Features

Sprinkler System

Sprinkler system was not available in the building. Based on the height of the highest occupiable floor,

automatic sprinkler protection is not required.

Standpipe System

Hose cabinet with 1.5 in hoses were provided inside the production floor and 2.5 in landing valves

were in stair enclosures. Based on the height of the highest occupiable floor, standpipe system is not

required.

Fire Water Supply

Refer to Building-6 report for fire water supply details.

Fire Alarm System

Refer to Building-6 report for fire alarm system details.

Page 23: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 23 Fakir Fashion Ltd. (Extension 2)

Fire Detection System

Refer to Building-6 report for fire detection system details.

Portable Fire Extinguishers

Refer to Building-6 report for portable fire extinguisher details.

Manual Fire Fighting Equipment

Refer to Building-6 report for fire water supply details.

Other Features

Emergency Lighting & Exit Signs

Emergency lighting appliances were located inside the production floor and exit stairs. There were

multiple CFL lights that had an alternate “Instant Power Supply” (IPS). Illuminated exit signs, located

at exits. The factory management reported that these are all serviced by normal electricity as well as

by multiple “Instant Power Supply” (IPS) units. They were keeping records or assertions of regular

testing or maintenance of the emergency lighting system in accordance with Accord standard.

Exits and Exit Access Properly Marked with Exit Signage

Yes

Emergency Power Battery IPS

Adequate Emergency Lighting for Exits & Exit Access

No

Adequate Inspection / Testing (Accord 10.12) Yes

Page 24: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 24 Fakir Fashion Ltd. (Extension 2)

Exit Signage Emergency Light

Elevator

One (1) elevators (cargo lift) that serve the building.

Elevator Opens into Exit Enclosure No, Opens into Production Floor

Elevator Shaft / Doors Fire-Rated No

Elevator

Page 25: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 25 Fakir Fashion Ltd. (Extension 2)

Boiler, Generator & Furnace Equipment

Utilities were commonly used and covered by previous Accord inspection buildings in the same

complex.

Additional Information

None

Page 26: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 26 Fakir Fashion Ltd. (Extension 2)

Findings & Recommendations

Table 1 summarizes the major fire safety issues identified during the inspection. Recommendations

have been provided to address each issue.

An implementation schedule shall be developed by the factory to remediate each of the findings. The

specific timing of improvements, including any requested extensions due to design / installation

constraints, shall be submitted to the Accord for approval.

Page 27: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 27 Fakir Fashion Ltd. (Extension 2)

Table 1. Findings And Recommendations

Remediation No. Category Finding Recommendation Timeframe

F-1 Fire Rated Exit stairs are not

Construction separated from work

areas & other spaces on

each floor by fire-rated

construction due to

unprotected openings

and penetrations.

(Shared stairs from

building 3 & 4 for

building 6 has several

unsealed openings

and penetrations

also some are not

enclosed by fire rated

construction).

Separate the exit stairs Within 3

from work areas and other months

building spaces on all floor

levels by minimum 2- hr

fire-rated construction.

Provide minimum 1.5- hr

fire rated doors and seal

all unprotected openings and

penetrations to maintain the

fire separation.

Ensure that all fire doors are

self-closing and positive

latching, and are provided

with fire exit (panic) hardware

where serving production

floors or assembly

occupancies. If fire doors are

required to be held open for

functional reasons, provide

automatic-closing devices

tied to the fire alarm system.

Once fire doors are installed, every door in a stair enclosure

serving more than 5 stories

shall be provided with re-entry

unless it meets ACCORD standard 6.8.3.1.

Page 28: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 28 Fakir Fashion Ltd. (Extension 2)

Provide minimum 1.5m Within 6 (59 in) unobstructed and months clear width of exit stairs as per Accord 6.5.6.2.1.

F-2 Egress Exit stairs widths were

less than 1.5m (59 in)

at building-7 and stairs

those were shared with

building-6.

Page 29: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 29 Fakir Fashion Ltd. (Extension 2)

F-3 Fire Rated Office on the 4th floor

Construction is not separated by a

minimum 2-hr fire-rated

construction.

Provide separated office Within 3

rooms separated by minimum months

2-hr fire-rated construction

having direct access to the

exit stair or outside of the

building.

Provide a minimum 2-hr fire- Within 3

rated shaft to separate the months

utility risers from each floor

level and seal all

penetrations in floor/ceiling

assemblies to maintain the

fire separation.

F-4 Fire Rated Unsealed electrical

Construction shaft is located in the

fire-rated floor/ceiling

assemblies.

(Building-6)

Page 30: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 30 Fakir Fashion Ltd. (Extension 2)

F-5 Fire Rated Storage rooms on all Openings from exit enclosure Within 3

Construction floor and both building to storage room, generator months

discharges directly into and hazard spaces shall

the exit stair discharge. be provided with a vestibule

with fire rated construction

and openings.

Provide a 1.5 hr. fire rated

door on the exit stair side and

a 1-hr. fire rated door on the

Store, generator, sub-station

room side. Ensure that the

fire rating of the vestibule

construction matches that of

the exit stair enclosure.

Page 31: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 31 Fakir Fashion Ltd. (Extension 2)

F-8 Fire The fire pump set Submit as-built drawings, Within 2

Protection installation requires testing records, equipment months

detailed review to certification and other

confirm compliance with relevant documentation to the

NFPA 20 and ACCORD ACCORD for review and

standard. approval/acceptance test.

F-6 Fire Rated The elevator does not

Construction have the proper fire

rating for the elevator

door at building-6 and

lift shaft and door at

building-7.

Provide the proper 2-hr Within 3

fire rating for the shafts months

and 1.5 hr fire rating

for the elevator doors.

F-7 Fire The fire alarm system Submit as-built drawings, Within 2

Protection installation requires testing records, equipment months

detailed review to certification and other

confirm compliance with relevant documentation to the

NFPA 72 and ACCORD ACCORD for review and

standard. approval/acceptance test.

Page 32: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 32 Fakir Fashion Ltd. (Extension 2)

F-9 Fire The standpipe system Submit as-built drawings, Within 2

Protection installation requires testing records, equipment months

detailed review to certification and other

confirm compliance with relevant documentation to the

NFPA 14 and ACCORD ACCORD for review and

standard. approval/acceptance test.

F-10 Egress Fire evacuation maps Fire evacuation maps shall Within 1

is not posted at the be posted at the entrance month

entrance of the exits to each exits and exit stairs

at most of the floors and actual floor shall be

and provided maps reflected on maps.

does not reflect the

actual factory floor

and evacuation route.

Page 33: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 33 Fakir Fashion Ltd. (Extension 2)

F-11 Egress Based on the number Test the emergency lighting Within 3

Lighting and location of system on each floor and months

emergency lights provide additional emergency

observed, adequate fixtures to supply adequate

illumination levels are illumination along the means

not anticipated along of egress. Provide a

egress routes. minimum illumination of 10

lux at the floor level within

exit stairs and along exit

discharge paths and a

minimum 2.5 lux along exit

access aisles.

F-12 Fire rated The newly constructed New construction shall be Within 4

Construction roof have steel trusses Type-1 or Type-2 construction months

and tin roof sheet. in accordance with Accord

(All building-7). standard 3.5.2.1 and BNBC

Part-2, Table-3.2.4.

Ensure fire-resistive rated

construction following

Section 4.4 and Table 4.4.1

of the Accord Standard or

Table 3.3.1 and Table 4.1.1

from BNBC Part 4.

Page 34: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 34 Fakir Fashion Ltd. (Extension 2)

F-13 Fire Rated The exit discharge path

Construction serving the [S-E exit]

is less than 10 ft wide

and is not separated

from the building-7

ground floor interior.

Seal all penetrations and Within 3

openings to the interior of the months

building along the discharge

path, up to a height of 10 ft,

to provide a minimum 1-hr

fire separation.

F-14 Fire Rated Exterior exit stair is not

Construction properly separated from

the buildings.

(Both building).

Exterior exit stairs shall be Within 6

separated from the building months

with a rating requirement of

1-hr fire rating for 3 or fewer

stories and 2-hr fire rating

for 4 or more stories. The

rating of the exterior wall

shall extend 3.05 m (10 ft)

beyond the ends of the

stair structure.

Page 35: Fakir Fashion Ltd. (Extension 2)

Accord - Bangladesh RMG Fire Safety Inspection Page 35 Fakir Fashion Ltd. (Extension 2)

F-15 Egress Exit capacity is not Reduce occupant load

Immediately

adequate for the immediately to not more than

occupant load at available exit capacity (533).

1st floor of building-7. Provide additional exits in the

future to increase exit

capacity.

F-16 Fire Rated Fire-rated floor/ceiling Seal all penetrations and Within 3

Construction assemblies have openings in floor/ceiling months

unprotected openings. assemblies to maintain

the fire separation.