FIRE SAFETY INSPECTION REPORT
Fakir Fashion Ltd. (Extension 2)
ACCORD ID: 23771
Dohargaon, Baliapara, Rupgonj, Narayangonj
23.784037, 90.587276
Other Factories: None
Inspected by: Md. Rakibul Alam & A.K.M. Monoarul Huda
Date: 27 August 2019
Accord - Bangladesh RMG Fire Safety Inspection Page 2 Fakir Fashion Ltd. (Extension 2)
Fire Safety Inspection Report
Fakir Fashion Ltd. (Extension 2)
Introduction
Fakir Fashion Ltd. (Extension 2) was surveyed for fire safety on 27 August 2019 by The Accord
Inspection Team.
The purpose of the survey was to identify significant fire safety issues and to provide recommendations
for remediation based on applicable standards specified by the Accord. The scope of this initial fire
safety inspection was limited to the review and identification of major fire safety issues. The inspection
did not include identification of minor deficiencies, which will be further addressed as part of follow-up
inspections.
Limitations
The information in this fire safety inspection report was obtained during a visit to the facility and during
interviews with local factory management. It has not been possible to provide independent verification
for all the information and data collected, and, therefore, The Accord cannot accept general
responsibility for omissions or errors arising from inaccuracies in this report from the information
obtained.
The findings and recommendations in this report are not intended to imply, guarantee, ensure or
warrant compliance with any government regulations. Additionally, the results do not imply in any way
that compliance with the findings or recommendations as stated in this report will eliminate all hazards,
risks or exposures or that hazards, risks or exposures not referred to in this report do not exist.
Compliance with the findings and recommendations stated in this report does not relieve the factory
owner from obligation to comply with specific project requirements, industry standards, or the
provisions of any local government regulations.
Accord - Bangladesh RMG Fire Safety Inspection Page 3 Fakir Fashion Ltd. (Extension 2)
General Factory Information
Factory Building Name(s):
Fakir Fashion Ltd. (Extension 2) – Building - 6
Fakir Fashion Ltd. (Extension 2) – Building - 7
Factory Address: Dohargaon, Baliapara, Rupgonj, Narayangonj
Points of Contact:
Shafiqul Islam
Sr. Manager-Compliance
Mobile: +88 01766670078
e-mail: [email protected]
Mohammad Ashiqur Rahman
AGM-Compliance
Mobile: +88 01766670036
e-mail: [email protected]
Accord - Bangladesh RMG Fire Safety Inspection Page 4 Fakir Fashion Ltd. (Extension 2)
General Building Information – Fakir Fashion Ltd. (Extension 2) – Building - 6
Number of Stories Below / Above Grade 0 / 6
Highest Occupied Floor Level / Height 14 m
High Rise (Accord 3.2.1) No
Occupiable Roof (Accord 3.2.2) Yes
Occupiable Roof Provided with Adequate Parapets / Guards (Accord 6.12.2.4)
Yes
Occupancy Classifications F Business; H2 Storage
Floor Plans Available Yes
Typical Floor Plan Cross Section
Accord - Bangladesh RMG Fire Safety Inspection Page 5 Fakir Fashion Ltd. (Extension 2)
Date of Construction Dec 2017 – Jul 2019
Major Renovations / Additions No
Comments 6 Storied Multi-Purpose Warehouse Building
Other Tenants In Building None
Floors Occupied By Factory All
Floor Use Occupant Load
Ground Floor Fabric Storage Area/Rack 15
1st Floor Fabric Storage 10
2nd Floor Fabric Inspection Machine 35
3rd Floor Fabric Storage 9
4th Floor Fabric Storage and Office 40
5th Floor Fabric Storage Racking 10
Construction Features
Non-Combustible Construction Yes
Fire-Resistive Construction Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 6 Fakir Fashion Ltd. (Extension 2)
Building Exposures
North Building-4
South Building-3
East Building-4
West Internal Road and Mosque
Vertical Openings
Exit Stairs Enclosed in Fire-Rated Construction (Accord 6.14)
No (Adjacent building stair)
Exit Stair Penetrations are Fire Rated (Accord 6.14)
Yes
Exit Stair Openings are Fire Rated (Accord 6.14)
No
Exterior Exit Stairs Separated From Building (Accord 6.3.1.3)
No
Shafts Enclosed in Fire Rated Construction (Accord 4.5.7)
No
Openings / Penetrations in Fire-Rated Floors are Protected (Accord 4.5.3)
Yes
Atrium Protected As Required (Accord 3.7) N/A
Accord - Bangladesh RMG Fire Safety Inspection Page 7 Fakir Fashion Ltd. (Extension 2)
Egress Features
Single dedicated exit serves the building having additional shared exit from adjacent buildings at each floor level. All exits were remotely located and travel distance requirements were met. All exits discharged to the exterior of the building. Adjacent buildings exit stairs were not properly separated on all floors due to unprotected openings and penetrations. The exit doors are provided with 1.5-hr fire-rated doors. Certification documentation for the doors was not provided during the inspection. UL testing certification tags were provided on the doors. Collapsible gate, sliding gate and roll down shutter type doors were not used at any exits of the building. All doors were open and unlocked during the inspection. Handrails were present on both sides of the exit stairs on all floors. Emergency evacuation plans were not located at all the required location. Occupant load signs, floor level signs and stair designation signs were located at exits. No smoking signs were present in the factory at ground floor. Fire drills are conducted monthly; records were provided during the inspection.
Floor Use Number of exits Exit Capacity
Ground Floor Fabric Storage Area/Rack 3 1000
1st Floor Fabric Storage 3 438
2nd Floor Fabric Inspection Machine 3 438
3rd Floor Fabric Storage 3 438
4th Floor Fabric Storage and Office 2 342
5th Floor Fabric Storage Racking 2 342
Accord - Bangladesh RMG Fire Safety Inspection Page 8 Fakir Fashion Ltd. (Extension 2)
General
Number of Exits Per Floor is Compliant (Accord 6.6)
Yes
Capacity of Exits Per Floor Is Compliant (Accord 6.5.3)
Yes
Exits Remotely Located (Accord 6.6.6) Yes
Exit Doors
Egress Doors are Side Hinged (Accord 6.8.1) Yes
Egress Doors Swing Correctly (Accord 6.8.1) Yes
Egress Doors Without Locking Hardware in Direction of Travel (Accord 6.8.2)
Yes
Exit Stairs
All Exit Stairs Discharge Directly to the Exterior (Accord 6.17)
Yes
Handrails Provided on Both Sides (Accord 6.9.2.4)
Yes
Exit Stairs Free of Storage and Obstructions (Accord 6.3.8, 6.3.9)
Yes
Electrical Panels Located Outside of Exit Stairs
Yes
Exit Stairs Serving More than 5 Stories Provided with Re-Entry (Accord 6.8.3)
Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 9 Fakir Fashion Ltd. (Extension 2)
Exit Access & Arrangement
Means of Egress Free of Storage & Obstructions (Accord 6.3.8, 6.3.9)
Yes
Means of Egress of Adequate Width (Accord 6.5)
No
Travel Distances, CPT, DE's Within Limits (Accord 6.13)
No
Exit Access Corridors Provided with Proper Fire Protection / Separation (Accord 6.3.1.1)
N/A
Daycare Within Limits (Accord 3.4.2.1.1) N/A
Egress Court Provided with Adequate Fire Rated Separation (Accord 6.17.2)
N/A
Utility / Storage Rooms Adequately Separated from Exit Enclosures (Accord 6.14.3)
No
Emergency Planning
Emergency Evacuation Plans Provided (Accord 13.3)
Not provided at required location and not reflected the exact floor and exit condition
Fire Drills Conducted & Records Maintained (Accord 13.2)
Yes
Smoking Prohibited (Accord 13.5) Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 10 Fakir Fashion Ltd. (Extension 2)
Evacuation Plan Fire Drill Document
Fire Protection Features
Sprinkler System
Sprinkler system was not available in the building. Based on the height of the highest occupiable floor,
automatic sprinkler protection is not required.
Standpipe System
Hose cabinet with 1.5 in hoses were provided inside the production floor and 2.5 in landing valves
were in stair enclosures. Based on the height of the highest occupiable floor, standpipe system is
required.
Standpipe System Required Yes
Type of System Installed Class-lll
Hose Connection Locations Inside the production floor and stair enclosures.
ITM Per NFPA 25 Yes
Comments Highest Occupied Floor Level was 35m.
Accord - Bangladesh RMG Fire Safety Inspection Page 11 Fakir Fashion Ltd. (Extension 2)
Class-ll Hose Cabinet Class-1 Landing Valve
Fire Water Supply
The standpipe system was supplied by fire pumps fed from an underground cistern that is accessed from ground floor. The cistern had a reported capacity of 1,42,000 Gal. The fire pump system consisted of a diesel fire pump, an electric fire pump and a jockey pump. Fire department inlet and outlet connection was provided for the building.
Source, Location, & Capacity Underground cistern and fire pump.
Cistern tank/ underground/ 1,42,000 GAL
Fire Pump Provided Yes
Fire Department Inlet & Outlet Connections Provided (Accord 5.5.4)
Yes
Fire Pump Adequate (Accord 5.5.1) To be verified during functional test
Fire Pump Room Provided With Adequate Fire Rated Separation (NFPA 20)
No
Fire Pump ITM Per NFPA 25 Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 12 Fakir Fashion Ltd. (Extension 2)
Fire Alarm System
The building had an addressable fire alarm system built around a BOSCH FPA5000 alarm panel. The system supported smoke detectors, heat detectors, manual pull stations, horn and strobe units installed throughout the building. The activation switches on each floor trigger the fire alarm for the entire building. No functional test was conducted on the system during the inspection.
Type of System Addressable
Fire Panel Location Fire Control Room
Visible Notification Per NFPA 72 To be verified during functional test
Audible Notification Per NFPA 72 To be verified during functional test
Alarm Annunciation To be verified during functional test
ITM per NFPA 72 To be verified during design review and functional test
Functional Test Conducted No
Fire Alarm Switch Fire Alarm Siren
Accord - Bangladesh RMG Fire Safety Inspection Page 13 Fakir Fashion Ltd. (Extension 2)
Fire Detection System
Interconnected smoke and heat detectors were located in various places throughout the factory. These detectors were tied into the fire alarm system. In the event they detect smoke and heat, they will send a signal to the fire alarm control panel to activate the fire alarm. No functional test was conducted on the system during the inspection.
Type of Detectors Smoke Detector & Heat Detectors Tied to Fire Alarm System
Smoke Detection Per NFPA 72 To be verified during design review and functional test
Smoke Detector
Portable Fire Extinguishers
Portable fire extinguishers, consisting of a mix of CO2 and dry chemical were provided throughout the
building. Inspection tags show recent and up-to-date inspections. Records of regular testing or
maintenance of the portable fire extinguishers were provided as per NFPA10.
Types Provided CO2 & dry chemical extinguishers.
Adequate Number/Spacing Yes
ITM Per NFPA 10 Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 14 Fakir Fashion Ltd. (Extension 2)
Extinguisher
Manual Fire Fighting Equipment
Ground floor had firefighting equipment staged inside the floor. Types of manual firefighting equipment
provided included: buckets, escape hoods, bolt/lock cutters, shovels, stretchers and personal
protection equipment.
Types Provided Buckets, escape hoods, bolt/lock cutters, shovels, stretchers and personal protection equipment.
Location of Equipment Only Ground Floor
Firefighting Equipment
Accord - Bangladesh RMG Fire Safety Inspection Page 15 Fakir Fashion Ltd. (Extension 2)
Other Features
Emergency Lighting & Exit Signs
Emergency lighting appliances were located inside the production floor and exit stairs. There were
multiple CFL lights that had an alternate “Instant Power Supply” (IPS). Illuminated exit signs, located
at exits. The factory management reported that these are all serviced by normal electricity as well as
by multiple “Instant Power Supply” (IPS) units. They were keeping records or assertions of regular
testing or maintenance of the emergency lighting system in accordance with Accord standard.
Exits and Exit Access Properly Marked with Exit Signage
Yes
Emergency Power Battery IPS
Adequate Emergency Lighting for Exits & Exit Access
No
Adequate Inspection / Testing (Accord 10.12) Yes
Exit Signage Emergency Light
Accord - Bangladesh RMG Fire Safety Inspection Page 16 Fakir Fashion Ltd. (Extension 2)
Elevator
There are two (2) elevators that serve the building. Signage stating “In Case of Fire Don't Use Lift” is provided outside the elevators on some floors.
Elevator Opens into Exit Enclosure Opens into Production Floor
Elevator Shaft / Doors Fire-Rated No
Elevator
Boiler, Generator & Furnace Equipment
Utilities were commonly used and covered by previous Accord inspection in the same complex.
Additional Information
None
Accord - Bangladesh RMG Fire Safety Inspection Page 17 Fakir Fashion Ltd. (Extension 2)
General Building Information – Fakir Fashion Ltd. (Extension 2) – Building - 7
Number of Stories Below / Above Grade 0 / 2
Highest Occupied Floor Level / Height 3.5 m
High Rise (Accord 3.2.1) No
Occupiable Roof (Accord 3.2.2) No
Occupiable Roof Provided with Adequate Parapets / Guards (Accord 6.12.2.4)
N/A
Occupancy Classifications G2 Industrial; H2 Storage
Floor Plans Available Yes
Typical Floor Plan Cross Section
Accord - Bangladesh RMG Fire Safety Inspection Page 18 Fakir Fashion Ltd. (Extension 2)
Date of Construction Dec 2017 – Jul 2019
Major Renovations / Additions No
Comments 2 Storied Composite Construction
Other Tenants In Building None
Floors Occupied By Factory All
Floor Use Occupant Load
Ground Floor Chemical Warehouse 20
1st Floor Sewing and Finishing 750
Construction Features
Non-Combustible Construction Yes
Fire-Resistive Construction No
Building Exposures
North Shed-10
South Mosque
East Shed-3
West Open Area
Accord - Bangladesh RMG Fire Safety Inspection Page 19 Fakir Fashion Ltd. (Extension 2)
Vertical Openings
Exit Stairs Enclosed in Fire-Rated Construction (Accord 6.14)
Yes
Exit Stair Penetrations are Fire Rated (Accord 6.14)
Yes
Exit Stair Openings are Fire Rated (Accord 6.14)
Yes
Exterior Exit Stairs Separated From Building (Accord 6.3.1.3)
No
Shafts Enclosed in Fire Rated Construction (Accord 4.5.7)
No
Openings / Penetrations in Fire-Rated Floors are Protected (Accord 4.5.3)
No
Atrium Protected As Required (Accord 3.7) N/A
Egress Features
Three exit serves the building 1st floor and five exits at ground floor. All exits were remotely located and travel distance requirements were met. All exits discharged to the exterior of the building. The exit doors are provided with 1.5-hr fire-rated doors. Certification documentation for the doors was not provided during the inspection. UL testing certification tags were provided on the doors. Collapsible gate, sliding gate and roll down shutter type doors were not used at any exits of the building. All doors were open and unlocked during the inspection. Handrails were present on both sides of the exit stairs on all floors. Emergency evacuation plans were not located at all the required location. Occupant load signs, floor level signs and stair designation signs were located at exits. No smoking signs were present in the factory at ground floor. Fire drills are conducted monthly; records were provided during the inspection.
Accord - Bangladesh RMG Fire Safety Inspection Page 20 Fakir Fashion Ltd. (Extension 2)
Floor Use Number of exits Exit Capacity
Ground Floor Chemical Warehouse 5 1370
1st Floor Sewing and Finishing 3 533
General
Number of Exits Per Floor is Compliant (Accord 6.6)
Yes
Capacity of Exits Per Floor Is Compliant (Accord 6.5.3)
No
Exits Remotely Located (Accord 6.6.6) Yes
Exit Doors
Egress Doors are Side Hinged (Accord 6.8.1) Yes
Egress Doors Swing Correctly (Accord 6.8.1) Yes
Egress Doors Without Locking Hardware in Direction of Travel (Accord 6.8.2)
Yes
Exit Stairs
All Exit Stairs Discharge Directly to the Exterior (Accord 6.17)
Yes
Handrails Provided on Both Sides (Accord 6.9.2.4)
Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 21 Fakir Fashion Ltd. (Extension 2)
Exit Stairs Free of Storage and Obstructions (Accord 6.3.8, 6.3.9)
Yes
Electrical Panels Located Outside of Exit Stairs
Yes
Exit Stairs Serving More than 5 Stories Provided with Re-Entry (Accord 6.8.3)
N/A
Exit Access & Arrangement
Means of Egress Free of Storage & Obstructions (Accord 6.3.8, 6.3.9)
Yes
Means of Egress of Adequate Width (Accord 6.5)
No
Travel Distances, CPT, DE's Within Limits (Accord 6.13)
Yes
Exit Access Corridors Provided with Proper Fire Protection / Separation (Accord 6.3.1.1)
N/A
Daycare Within Limits (Accord 3.4.2.1.1) N/A
Egress Court Provided with Adequate Fire Rated Separation (Accord 6.17.2)
No
Utility / Storage Rooms Adequately Separated from Exit Enclosures (Accord 6.14.3)
No
Emergency Planning
Emergency Evacuation Plans Provided (Accord 13.3)
Yes
Fire Drills Conducted & Records Maintained (Accord 13.2)
Yes
Smoking Prohibited (Accord 13.5) Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 22 Fakir Fashion Ltd. (Extension 2)
Evacuation Plan No Smoking Sign
Fire Protection Features
Sprinkler System
Sprinkler system was not available in the building. Based on the height of the highest occupiable floor,
automatic sprinkler protection is not required.
Standpipe System
Hose cabinet with 1.5 in hoses were provided inside the production floor and 2.5 in landing valves
were in stair enclosures. Based on the height of the highest occupiable floor, standpipe system is not
required.
Fire Water Supply
Refer to Building-6 report for fire water supply details.
Fire Alarm System
Refer to Building-6 report for fire alarm system details.
Accord - Bangladesh RMG Fire Safety Inspection Page 23 Fakir Fashion Ltd. (Extension 2)
Fire Detection System
Refer to Building-6 report for fire detection system details.
Portable Fire Extinguishers
Refer to Building-6 report for portable fire extinguisher details.
Manual Fire Fighting Equipment
Refer to Building-6 report for fire water supply details.
Other Features
Emergency Lighting & Exit Signs
Emergency lighting appliances were located inside the production floor and exit stairs. There were
multiple CFL lights that had an alternate “Instant Power Supply” (IPS). Illuminated exit signs, located
at exits. The factory management reported that these are all serviced by normal electricity as well as
by multiple “Instant Power Supply” (IPS) units. They were keeping records or assertions of regular
testing or maintenance of the emergency lighting system in accordance with Accord standard.
Exits and Exit Access Properly Marked with Exit Signage
Yes
Emergency Power Battery IPS
Adequate Emergency Lighting for Exits & Exit Access
No
Adequate Inspection / Testing (Accord 10.12) Yes
Accord - Bangladesh RMG Fire Safety Inspection Page 24 Fakir Fashion Ltd. (Extension 2)
Exit Signage Emergency Light
Elevator
One (1) elevators (cargo lift) that serve the building.
Elevator Opens into Exit Enclosure No, Opens into Production Floor
Elevator Shaft / Doors Fire-Rated No
Elevator
Accord - Bangladesh RMG Fire Safety Inspection Page 25 Fakir Fashion Ltd. (Extension 2)
Boiler, Generator & Furnace Equipment
Utilities were commonly used and covered by previous Accord inspection buildings in the same
complex.
Additional Information
None
Accord - Bangladesh RMG Fire Safety Inspection Page 26 Fakir Fashion Ltd. (Extension 2)
Findings & Recommendations
Table 1 summarizes the major fire safety issues identified during the inspection. Recommendations
have been provided to address each issue.
An implementation schedule shall be developed by the factory to remediate each of the findings. The
specific timing of improvements, including any requested extensions due to design / installation
constraints, shall be submitted to the Accord for approval.
Accord - Bangladesh RMG Fire Safety Inspection Page 27 Fakir Fashion Ltd. (Extension 2)
Table 1. Findings And Recommendations
Remediation No. Category Finding Recommendation Timeframe
F-1 Fire Rated Exit stairs are not
Construction separated from work
areas & other spaces on
each floor by fire-rated
construction due to
unprotected openings
and penetrations.
(Shared stairs from
building 3 & 4 for
building 6 has several
unsealed openings
and penetrations
also some are not
enclosed by fire rated
construction).
Separate the exit stairs Within 3
from work areas and other months
building spaces on all floor
levels by minimum 2- hr
fire-rated construction.
Provide minimum 1.5- hr
fire rated doors and seal
all unprotected openings and
penetrations to maintain the
fire separation.
Ensure that all fire doors are
self-closing and positive
latching, and are provided
with fire exit (panic) hardware
where serving production
floors or assembly
occupancies. If fire doors are
required to be held open for
functional reasons, provide
automatic-closing devices
tied to the fire alarm system.
Once fire doors are installed, every door in a stair enclosure
serving more than 5 stories
shall be provided with re-entry
unless it meets ACCORD standard 6.8.3.1.
Accord - Bangladesh RMG Fire Safety Inspection Page 28 Fakir Fashion Ltd. (Extension 2)
Provide minimum 1.5m Within 6 (59 in) unobstructed and months clear width of exit stairs as per Accord 6.5.6.2.1.
F-2 Egress Exit stairs widths were
less than 1.5m (59 in)
at building-7 and stairs
those were shared with
building-6.
Accord - Bangladesh RMG Fire Safety Inspection Page 29 Fakir Fashion Ltd. (Extension 2)
F-3 Fire Rated Office on the 4th floor
Construction is not separated by a
minimum 2-hr fire-rated
construction.
Provide separated office Within 3
rooms separated by minimum months
2-hr fire-rated construction
having direct access to the
exit stair or outside of the
building.
Provide a minimum 2-hr fire- Within 3
rated shaft to separate the months
utility risers from each floor
level and seal all
penetrations in floor/ceiling
assemblies to maintain the
fire separation.
F-4 Fire Rated Unsealed electrical
Construction shaft is located in the
fire-rated floor/ceiling
assemblies.
(Building-6)
Accord - Bangladesh RMG Fire Safety Inspection Page 30 Fakir Fashion Ltd. (Extension 2)
F-5 Fire Rated Storage rooms on all Openings from exit enclosure Within 3
Construction floor and both building to storage room, generator months
discharges directly into and hazard spaces shall
the exit stair discharge. be provided with a vestibule
with fire rated construction
and openings.
Provide a 1.5 hr. fire rated
door on the exit stair side and
a 1-hr. fire rated door on the
Store, generator, sub-station
room side. Ensure that the
fire rating of the vestibule
construction matches that of
the exit stair enclosure.
Accord - Bangladesh RMG Fire Safety Inspection Page 31 Fakir Fashion Ltd. (Extension 2)
F-8 Fire The fire pump set Submit as-built drawings, Within 2
Protection installation requires testing records, equipment months
detailed review to certification and other
confirm compliance with relevant documentation to the
NFPA 20 and ACCORD ACCORD for review and
standard. approval/acceptance test.
F-6 Fire Rated The elevator does not
Construction have the proper fire
rating for the elevator
door at building-6 and
lift shaft and door at
building-7.
Provide the proper 2-hr Within 3
fire rating for the shafts months
and 1.5 hr fire rating
for the elevator doors.
F-7 Fire The fire alarm system Submit as-built drawings, Within 2
Protection installation requires testing records, equipment months
detailed review to certification and other
confirm compliance with relevant documentation to the
NFPA 72 and ACCORD ACCORD for review and
standard. approval/acceptance test.
Accord - Bangladesh RMG Fire Safety Inspection Page 32 Fakir Fashion Ltd. (Extension 2)
F-9 Fire The standpipe system Submit as-built drawings, Within 2
Protection installation requires testing records, equipment months
detailed review to certification and other
confirm compliance with relevant documentation to the
NFPA 14 and ACCORD ACCORD for review and
standard. approval/acceptance test.
F-10 Egress Fire evacuation maps Fire evacuation maps shall Within 1
is not posted at the be posted at the entrance month
entrance of the exits to each exits and exit stairs
at most of the floors and actual floor shall be
and provided maps reflected on maps.
does not reflect the
actual factory floor
and evacuation route.
Accord - Bangladesh RMG Fire Safety Inspection Page 33 Fakir Fashion Ltd. (Extension 2)
F-11 Egress Based on the number Test the emergency lighting Within 3
Lighting and location of system on each floor and months
emergency lights provide additional emergency
observed, adequate fixtures to supply adequate
illumination levels are illumination along the means
not anticipated along of egress. Provide a
egress routes. minimum illumination of 10
lux at the floor level within
exit stairs and along exit
discharge paths and a
minimum 2.5 lux along exit
access aisles.
F-12 Fire rated The newly constructed New construction shall be Within 4
Construction roof have steel trusses Type-1 or Type-2 construction months
and tin roof sheet. in accordance with Accord
(All building-7). standard 3.5.2.1 and BNBC
Part-2, Table-3.2.4.
Ensure fire-resistive rated
construction following
Section 4.4 and Table 4.4.1
of the Accord Standard or
Table 3.3.1 and Table 4.1.1
from BNBC Part 4.
Accord - Bangladesh RMG Fire Safety Inspection Page 34 Fakir Fashion Ltd. (Extension 2)
F-13 Fire Rated The exit discharge path
Construction serving the [S-E exit]
is less than 10 ft wide
and is not separated
from the building-7
ground floor interior.
Seal all penetrations and Within 3
openings to the interior of the months
building along the discharge
path, up to a height of 10 ft,
to provide a minimum 1-hr
fire separation.
F-14 Fire Rated Exterior exit stair is not
Construction properly separated from
the buildings.
(Both building).
Exterior exit stairs shall be Within 6
separated from the building months
with a rating requirement of
1-hr fire rating for 3 or fewer
stories and 2-hr fire rating
for 4 or more stories. The
rating of the exterior wall
shall extend 3.05 m (10 ft)
beyond the ends of the
stair structure.
Accord - Bangladesh RMG Fire Safety Inspection Page 35 Fakir Fashion Ltd. (Extension 2)
F-15 Egress Exit capacity is not Reduce occupant load
Immediately
adequate for the immediately to not more than
occupant load at available exit capacity (533).
1st floor of building-7. Provide additional exits in the
future to increase exit
capacity.
F-16 Fire Rated Fire-rated floor/ceiling Seal all penetrations and Within 3
Construction assemblies have openings in floor/ceiling months
unprotected openings. assemblies to maintain
the fire separation.