  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    1/43

    0

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4 Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    2/43

    External alarms termination methodologies, 1

    1

    Scenario 1: Cabin/T5 installed

    2G and/or 3G

    3G 2G

    Alarm Crone Block

    Alarms termination in 3G

    Scenario 2: 2 Cabins/T5s. 1 cabin installed 2G and/or 3G and

    another cabin is just installed TX

    3G 2G

    Alarm Crone Block

    Alarms termination in 3G

    Just TX equipment only

    Alarm Crone Block

    Alarms termination in 2G

    Scenario 3: 2 Cabins/T5s. 1 cabin installed 3G and another

    cabin installed 2G

    3G 2G

    Alarm Crone Block

    Alarms termination in 3G

    Alarm Crone Block

    Alarms termination in 2G

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    3/43

    External alarms termination methodologies, 2

    2

    Scenario 4: T5 with APM30

    installed 3G

    3G

    2GAlarm Crone Block

    Alarms termination in 3G

    APM30

    Scenario 5: existing T5 installed 2G x 2 units with APM30

    installed 3G

    3G

    2GAlarm Crone Block

    Alarms termination in 3G

    APM30

    TX

    TXAlarm Crone Block

    Alarms termination in 2G

    Scenario 6: Install inside 2G BBU unit

    1. Huawei 3G equipment with DBS3806.

    2. Huawei 3G equipment not exist

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    4/43

    Please inform Huawei and Maxis for further rectification

    External alarms termination methodologies, 3

    3

    Existing T5 x 2 units with APM30 installed 3G

    3G

    2GAlarm Crone Block

    Alarms termination in 3G

    APM30

    TX

    TX

    Alarm cable loop from other T5

    Alarm Crone Block

    The External Alarm CANNOT be loop

    from one T5 cabinet to another

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    5/43

    4

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4 Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    6/43

    Alarm Crone Block Termination Information, 1

    5

    Before external alarm cables terminated

    Just remove the existing alarm cables in this column.

    After external alarm cables terminated

    Alarm Cable from BBUEXT-ALM 0

    Alarm Cable from BBUEXT-ALM 1

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    7/43

    Alarm Crone Block Termination Information, 2

    6

    NO MORE! Loop cable happen at crone box external alarm cable

    termination

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    8/43

    Alarm Cable Information

    7

    Top with

    clipper

    Bottom with

    metal pin

    PIN Start 1 PIN end 8

    Alarm Cable Definition

    (Follow LAN Cable Standard)

    PIN Cable Color Alarm #

    1

    White

    Orange 1

    2 Orange

    3 White Green2

    6 Green

    5 White Blue3

    4 Blue

    7 White Brown4

    8 Browm

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    9/438

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    10/43

    Eltek SMPS 1000W Rectifier Overview

    9

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    11/43

    Eltek SMPS 1000W Rectifier Alarm Termination Information, 1

    10

    Eltek SMPS 1000W Rectifier

    OPTO

    Type OPTO Description

    RectifierRelay

    Test

    RectifierAlarm Board

    Ports

    Alarm

    Level Remark

    1 Intruder Alarm High (NC)

    2 Over Temperature High (NC)

    3 AC Main Failure High (NC)

    4 DC High Voltage 2 17, 18 High (NC)

    5 DC Low Voltage 3 1, 2 High (NC)

    6 Rectifier PSU Failure 5 9, 10 High (NC)7 Battery Disconnect 4 5, 6 High (NC)

    8 Tower Light Low (NO)

    Ignore when not

    tower

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    12/43

    Eltek SMPS 1000W Rectifier Alarm Termination Information, 2

    11

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    13/43

    How to test alarm OPTO 1Intruder Alarm?

    12

    Step 1: Ensure the door close and intruder alarm is seizing status

    Step 2: Open the door to test intruder alarm. Intruder alarm will

    activated. Check with BSC integrator the intruder alarm activated

    in M2000 and can use LED lit to test.

    Step 3: Close the door again. Intruder alarm will seizing. Check

    with BSC integrator the intruder alarm will deactivated in M2000.

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    14/43

    How to test alarm OPTO 2Over Temperature Alarm?

    13

    Step 1: Usually MaxissTemperature Sensor Honeywell will set as 28 C

    or more than 28 C.

    Step 2: To activate Over Temperature alarm, turn the Honeywell sensor

    to 10 C and listen click sound. Check with BSC integrator the OverTemperature is activated in M2000. Can use LED lit to test.

    Step 3: To deactivate Over Temperature alarm, turn the Honeywell

    sensor to 28 C and listen click sound. Check with BSC integrator the

    Over Temperature is deactivated in M2000.

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    15/43

    How to test alarm OPTO 3AC Main Failure?

    14

    Step 1: Check the delay units are installed

    inside the ACPDB (usually installed on left top

    of ACPDB).

    Step 2: To activate AC Main Failure alarm, take out one unit of the delay

    units. Check with BSC integrator the AC Main Failure is activated in

    M2000. Can use LED lit to test.

    Step 3: To deactivate AC Main Failure alarm, install the delay unit whichis already take out previously. Check with BSC integrator the AC Main

    Failure is deactivated in M2000.

    f S S f

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    16/43

    How to perform the Eltek SMPS 1000W Rectifier Alarm Test?

    For OPTO 4, 5, 6 and 7

    15

    1. Press and then see User Option

    2. Press and then see Service Option

    3. Press and then see Password 0000

    4. Press and then see Volt. Adjustment

    5. Press and then see Calibration

    6. Press and then see Change Password

    7. Press and then see Set Boost Time

    8. Press and then see Start/Stop Boost

    9. Press and then see Output Control

    10. Press and then see Relay Test

    11. Press and then see Relay 1

    12. Press and then see Relay 2

    13. PressRelay 2 alarm Trigger,

    check with BSC integrator

    14. Press and then see Relay 3

    15. PressRelay 3 alarm Trigger,

    check with BSC integrator

    16. Press and then see Relay 4

    17. PressRelay 4 alarm Trigger,

    check with BSC integrator

    18. Press and then see Relay 5

    19. PressRelay 5 alarm Trigger,

    check with BSC integrator

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    17/4316

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    18/43

    Eltek Flatpack 1800W Rectifier Overview

    17

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    19/43

    Eltek Flatpack 1800W Rectifier Alarm Termination Information, 1

    18

    Eltek Flatpack 1800W Rectifier

    OPTO

    Type OPTO Description

    Rectifier

    Relay

    Test

    Rectifier

    Alarm Board

    Ports

    Alarm

    Level Remark

    1 Intruder Alarm High (NC)

    2 Over Temperature High (NC)

    3 AC Main Failure High (NC)

    4 DC High Voltage 2 14, 15 High (NC)

    5 DC Low Voltage 3 11, 12 High (NC)

    6 Rectifier PSU Failure 5 5, 6 High (NC)

    7 Battery Disconnect 4 8, 9 High (NC)

    8 Tower Light Low (NO)

    Ignore when not

    tower

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    20/43

    Eltek Flatpack 1800W Rectifier Alarm Termination Information, 2

    19

    H t t t l f Fl t k 1800W R tifi

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    21/43

    How to test alarm for Flatpack 1800W Rectifier

    OPTO 1, 2, 3, 4, 5, 6 and 7?

    20

    Entire external alarms test are as

    same as alarm testing for Eltek SMPS

    1000W rectifier

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    22/4321

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    23/43

    EXSEL Rectifier Overview

    22

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    24/43

    How to test alarm for Exsel Rectfier - OPTO 1, 2, 3, 4 and 5?

    23

    OPTO 3AC Main Failure

    Step 1: Ensure the AC 2A fuses are installed properly manner and

    no OPTO 3 alarm occur at BSC

    Step 2: To activate AC Main Failure alarm, take

    out one unit of AC 2A fuse. Check with BSC

    integrator the AC Main Failure is activated in

    M2000. Can use LED lit to test.

    Step 3: To deactivate AC Main Failure alarm, install the AC 2A fuse

    which is already take out previously. Check with BSC integrator the AC

    Main Failure is deactivated in M2000.

    OPTO 1 and 2 just follow the slides as Eltek SMPS 1000W Rectifier

    OPTO 4 and 5, no any test require for DC High Voltage and DC Low Voltage

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    25/43

    How to test alarm for Exsel Rectfier - OPTO 6?

    24

    Step 1: Ensure entire Rectifier Circuit breaker units are switch ON , if

    any reporting to BSC integrator is required. Make sure no OPTO 6alarm occur at BSC

    Step 2: To activate OPTO 6

    Rectifier PSU Failure alarm,

    Switch OFF one of the PSUunit circuit breaker. Check with

    BSC integrator the Rectifier

    PSU Failure is activated in

    M2000. Can use LED lit to test.

    Step 3: To deactivate Rectifier PSU Failure alarm,Switch ON circuit breaker which is switch OFF

    previously. Check with BSC integrator the Rectifier

    PSU Failure is deactivated in M2000.

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    26/43

    How to test alarm for Exsel Rectfier - OPTO 7?

    25

    Step 1: Ensure the Battery DC 2A Fuse is installed

    in properly manner , Make sure no OPTO 7 alarmoccur at BSC

    Step 2: To activate Battery Disconnect Alarm, take

    out DC 2A fuse. Check with BSC integrator the

    Battery Disconnect is activated in M2000. Can useLED lit to test.

    Step 3: To deactivate Battery Disconnect Alarm,

    install the DC 2A fuse which is already take out

    previously. Check with BSC integrator the Battery

    Disconnect is deactivated in M2000.

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    27/43

    26

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4

    Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    28/43

    T5 Cabinet with Emerson Rectifier Overview

    27

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    29/43

    How to test alarm OPTO 1 - T5 Cabinet with Emerson Rectifier?

    28

    Step 1: Ensure the door sensor is in good condition and intruder

    alarm is seizing status

    Step 2: Open the door to test intruder alarm. Intruder alarm will

    activated. Check with BSC integrator the intruder alarm activatedin M2000 and can use LED lit to test.

    Step 3: Close the door sensor or press the door spring button.

    Intruder alarm will seizing. Check with BSC integrator the intruder

    alarm will deactivated in M2000.

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    30/43

    How to test alarm OPTO 2 - T5 Cabinet with Emerson Rectifier?

    29

    Step 1: Usually MaxissT5 cabinet for FAN circuit breaker units are at

    the right hand of DC panel. But same cases the FAN CB units are inbetween the DC panel, please check on site accordingly

    Step 2: To activate Over Temperature alarm, switch OFF the FAN unit

    circuit breaker and the FAN unit will not operation. Check with BSC

    integrator the Over Temperature is activated in M2000. Can use LED litto test.

    Step 3: To deactivate Over Temperature alarm, switch ON the FAN

    unit circuit breaker and FAN unit will operation in normal condition.Check with BSC integrator the Over Temperature is deactivated in

    M2000.

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    31/43

    How to test alarm OPTO 3AC Main Failure?

    30

    Step 1: Check the AC fuse units are installed

    properly inside T5 Emerson Rectifier cabinet.

    Step 2: To activate AC Main Failure

    alarm, take out one AC fuse unit.

    Check with BSC integrator the AC

    Main Failure is activated in M2000.

    Can use LED lit to test.

    Step 3: To deactivate AC Main Failure alarm,

    press or install back the fuse unit which is

    already take out previously. Check with BSCintegrator the AC Main Failure is deactivated in

    M2000.

    How to test alarm OPTO 4 and 5 DC High Voltage and DC Low

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    32/43

    How to test alarm OPTO 4 and 5DC High Voltage and DC Low

    Voltage?

    31

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    33/43

    How to test alarm OPTO 4?DC High Voltage

    32

    1. Press x 2 times and see Setting

    2. Press

    3. Press x 4 times and see DC Setting

    4. Press

    5. See

    6. Move the cursor to DC Hi# 1: 55.7V by press

    x 1 time

    7. Press until value of 53.4V and below

    8. Presswait 3 second, DC High Voltage

    will activate

    9. Pressuntil the voltage value become

    55.7V (back to original)

    11. DC High Voltage will deactivate

    10. Press

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    34/43

    How to test alarm OPTO 5?DC Low Voltage

    33

    1. Continue from OPTO 4 alarms test

    2. See

    5. Presswait 3 second, DC Low Voltage

    will activate

    6. Pressuntil the voltage value become

    48.0V (back to original)

    8. DC Low Voltage will deactivate

    7. Press

    3. Move the cursor to DC Lo# 1: 48.0V by press

    x 1 time

    4. Press until value of 53.6V and above

    9. Press until exit from alarm testing

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    35/43

    How to test alarm OPTO 6?Rectifier PSU Failure

    34

    Step 1: Ensure entire Rectifier PSU units are

    working in normal condition and Rectifier Circuit

    breaker units are switch ON , if any reporting to

    BSC integrator is required. Make sure no OPTO 6alarm occur at BSC

    Step 2: To activate OPTO 6Rectifier PSU Failure

    alarm, Switch OFF one of the PSU unit circuit

    breaker. Check with BSC integrator the RectifierPSU Failure is activated in M2000. Can use LED lit

    to test.

    Step 3: To deactivate Rectifier PSU Failure alarm,

    Switch ON circuit breaker which is switch OFFpreviously. Check with BSC integrator the Rectifier

    PSU Failure is deactivated in M2000.

    H l OPTO 7? B Di

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    36/43

    How to test alarm OPTO 7?Battery Disconnect

    35

    Step 1: Ensure entire Baterries Circuit

    Breaker units are in switch ON condition, if

    any reporting to BSC integrator is required.

    Make sure no OPTO 7 alarm occur at BSC

    Step 2: To activate OPTO 7Battery Disconnect alarm, Switch

    OFF one of the battery unit circuit breaker. Check with BSC

    integrator the Rectifier PSU Failure is activated in M2000. Can

    use LED lit to test.

    Step 3: To deactivate Battery Disconnect alarm, Switch ON

    circuit breaker which is switch OFF previously. Check with

    BSC integrator the Battery Disconnect alarm is deactivated in

    M2000.

    T5 Cabinet with Emerson Rectifier Guide Book

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    37/43

    T5 Cabinet with Emerson Rectifier Guide Book

    for alarm testing and overview.

    36

    T5 Cabinet System OverviewT5 Cabinet with Emerson Rectifier

    Alarm Testing Guide Book

    Contents

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    38/43

    37

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4

    Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

    How to test alarm OPTO 1 for T5 Cabinet with

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    39/43

    o to test a a O O o 5 Cab et t

    Eltek Smartpack Rectifier? Coming Soon!!

    38

    Coming Soon!!!

    Contents

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    40/43

    39

    Contents

    2 Alarm Crone Box and Cable Information

    3 Eltek SMPS 1000W Rectifier

    4 Eltek Flatpack 1800W Rectifier

    5 Exsel Rectifier

    1 External Alarm Termination Methodologies

    6 T5 Cabinet with Emerson Rectifier

    7 T5 Cabinet with Eltek Smartpack Rectifier

    8 Troubleshooting Knowledge Sharing

    C 1 T t S F lt

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    41/43

    Case 1Temperature Sensor Faulty

    40

    During OPTO 2 alarm testThe temperature sensor cant trigger

    the OPTO 2 alarm to BSC. The problem is may caused by both

    screw units as shown were loose or the alarm cables were wrongconnected ports or loose connection.

    Loose the screw on

    top of Temperature

    Sensor

    Remove the cover of

    Temperature Sensor

    Make sure the alarm cable

    connect into right position.

    Must in screw 1 and 3. 2 is

    not connect anything.

    Make sure the both screw as

    shown above are not loose. If

    loose, please install and

    screw until tighten.

    If everything in place,

    just close the cover and

    tighten up the screw.

    Test again the OPTO 2

    alarm with turn the

    temperature sensor

    If alarm OPTO 2 trigger

    as normal.

    Troubleshooting closed

    If alarm OPTO 2 cant

    trigger or no any

    occurrence happen after

    repair action. Please inform

    Huawei or Maxis.

    Case 2 Rectifier PSU Module Faulty

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    42/43

    Case 2Rectifier PSU Module Faulty

    41

    If have any alarm occur on

    PSU unit, please remove the

    faulty PSU unit and continue

    the alarm test. If not, the

    OPTO 6 alarm will always

    occur during the alarmtesting. At the same time

    inform Huawei or Maxis

    Personnel.

    Ensure entire PSU modules

    are working in normal

    conditionwith green LED

    lit ON

    Case 3Batteries Unit Not Exist at Site or Faulty or

  • 5/22/2018 External Alarm Termination Guideline_20130109_Rev0 1

    43/43

    y

    Circuit Breaker units were switched OFF

    Make sure the batteries unit are exist at site for cabin,

    T5 cabinet or others related equipment location.

    Check the circuit breaker for batteries unit are switch

    ON condition. After that, just perform OPTO 7 Battery Disconnect Alarm Test. If above occurrence

    happen at site, please inform Huawei or Maxis.

    No Batteries unit exist on

    site or batteries were

    vandalized.

    Batteries unit circuit breaker

    were switched OFF