Integrity Home Inspections, Inc.

Report

Integrity Home Inspections, Inc.12042 SE Sunnyside RD. #562Clackamas , OR 97015

Alejandro & Dora Sandoval 4931 & 4941 Elkhorn Ct SE

Salem, OR

Page 2: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Table of Contents

General Information: 3

Report Summary: 4

Exterior Site Assesssment: 5

Exterior Structure Assessment: 5

Roof: 6

Attic: 4931 7

Attic: 4941 7

Porch, Patio, Deck, Garage: 4931 8

Porch, Patio, Deck, Garage: 4941 8

Exterior Utilities: 8

Interior Room Assessments: 4931 9

Interior Room Assessments: 4941 10

Interior Windows: 10

"Kitchen: " 4931 10

"Kitchen: " 4941 11

Interior Utilities: 4931 11

Interior Utilities: 4941 12

Bedrooms: 4931 12

Bedrooms: 4941 13

Bathrooms: 4931 13

Bathrooms: 4941 13

"Substructure: " 4931 14

"Substructure: " 4941 15

Wood Destroying Pest and Dry Rot Report 16

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 1 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 3: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Table of Contents (continued)

Pictures: 18

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 2 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 4: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

General Information:

Client Information

Client Name: Alejandro & Dora Sandoval

Property Address: 4931 & 4941 Elkhorn Ct SE

City: Salem State: Oregon

Inspection Conditions

People Present: Tenants, Seller Representative, Buyer

Property Occupied: Occupied

Approximate Year Built: 1975

Entrance Faces: South

Structure Type: Multi Family

Exterior Wall Type: Wood Frame

Weather: Dry

Soil Conditions Dry

Inspection Company Information:

Inspector Name Matt Sievers

Company Name Integrity Home Inspections, Inc.

Inspector License Number's: OCHI #022 WA #585

Address 12042 SE Sunnyside RD. #562

City: Clackamas State: OR Zip: 97015

Office Phone: (503)-246-5076

Office Fax: (503)-658-3711

Office E-Mail: [email protected]

Dept. of AG PCO Lic. OR #001451 WA #41309

State of Oregon General Contractors (CCB) Lic. #69324 WA #INTEGH1075RN

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 3 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 5: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Report Summary:

Inspector Comments/Recommendations: Two story duplex in mostly good overall shape, but various repairs needed, see report for details.

Scope of Inspection Survey: Integrity Home Inspections, Inc. strives to provide the most complete and comprehensive inspection survey available today. Our findings, however, are limited to only those areas readily accessible and visible to the inspector during the inspection survey. Integrity Home Inspections performs our inspections according to the State of Oregon Standards of Practice. It is the client's responsibility to read the entire Inspection Report and contact the inspector for clarification of any and all questions.

Limitations of Liability: INTEGRITY HOME INSPECTIONS, INC. LIMITS IT'S LIABILITY TO THE FEE PAID. The lack of mention of specific problems does not mean that such problems do not exist. It means that by using normal visual techniques, none was discovered at the time. This is not a code of compliance report. The inspection survey report does not include lifting carpet, moving furniture, or removal or dismantling of any systems throughout the structure. Only readily accessible and visible areas will be inspected. Integrity Home Inspections, Inc. makes no warranties either expressed or implied of the safety, condition, value serviceability, or any other aspect of the structure components inspected in this or any other report. We Recommend that re-inspections be performed after repairs have been completed; there is a nominal charge and the client is required to schedule re-inspections with integrity. This is not a home warranty - your real estate professional has information concerning quality home warranties which you can purchase. This report does no include environmental testing of hazardous material identification, such as but not limited to asbestos, lead, radon gas, heating oil tank leaks, etc. THIS REPORT IS INTENDED ONLY FOR THE USE OF THE PERSON PURCHASING THE HOME INSPECTION SERVICES. NO OTHER PERSON, INCLUDING A PURCHASER OF THE INSPECTED PROPERTY WHO DID NOT PURCHASE THE HOME INSPECTION SERVICES, MAY RELY UPON ANY REPRESENTATION MADE IN THE REPORT.

Inspector Signature:

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 4 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 6: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Exterior Site Assesssment:

Driveway: Concrete

*Repairs Recommended Comments: Cracking, lifting/settling and some trip hazards noted--repair as needed for best safety; otherwise, the driveway seems serviceable.

Sidewalks: Concrete

*Repairs Recommended Comments: Cracking, lifting/settling and trip hazard(s) noted--repair as needed for best safety; otherwise, the sidewalks seem serviceable, overall.

Grade & Slope: Flat, Sloped

*Appears Serviceable Comments: Note: Water problems/standing water can be seasonal and may not be detected. See owner for history of any previous water problems.

Exterior Structure Assessment:

Foundation: Concrete, Crawl Space

*Appears Serviceable Comments: Foundation looked fine. Keep the foundation vents open in all but the coldest weather as needed for best crawl space ventilation. Vent wells are recommended at all foundation vents at or below grade.

Siding: T-III Plywood All Sides Viewable, More Than One Story

*Repairs Recommended Comments: Some weathered siding noted in various areas, mainly just be aware of it. Some rot noted in the bottom of the T1 11 siding adjacent the front of unit 4931 and along the driveway side of unit 4931, and rot noted in the trim of the garage bay doors of 4931 & 4941, and some rot noted in the bottom trim of unit 4931 garage man door, consult a licensed contractor for full assessment and repairs needed. Some broken trim work and exposed fasteners noted above the entry door of unit 4941, repair as needed. There is some wood debris and planter boxes up against the siding in various places, this also limits access to the siding, so there is a potential for hidden damage, consult a licensed contractor for assessment and repairs needed. Also, see picture pages for those details. Otherwise, the siding still appears to be functioning as intended. Note: Siding is viewed from ground level.

Exterior Windows: Double Pane, Vinyl, Single Pane, Aluminum

*Repairs Needed Comments: Broken glass noted at the garage window of 4941, consult a licensed contractor for full evaluation and repairs needed. 1) Note: Due to weather and light conditions, Integrity makes no guarantees that thermal seals are in tact on windows. 2) Note: Although it is not required, Integrity recommends that all open-able windows have child proof safety locks installed to help prevent people (especially children) from falling out of windows. Consult a contractor to install as needed if not already installed.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 5 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 7: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Exterior Structure Assessment: (Continued)

Front Entry Doors: Metal

*Functioned Fine When Tested Comments: Unit 4931: Entry door seemed fine. Unit 4941: Unit not accessible, keys dont work; see owner or management company for access.

Patio Doors: Vinyl

*Functioned Fine When Tested Comments: Unit 4931: Slider door seemed to function as intended. Unit 4941: Unit not accessible, keys dont work; see owner or management company for access.

Doors(Other Exterior): Metal

*Repairs Needed Comments: Unut 4931: Weather stripping is missing or damaged, and the trimwork on the door frame is loose, repair as needed. Otherwise, the side garage entry door seemed functional. Unit 4941: Unit not accessible, keys dont work; see owner or management company for access.

Roof:

Gutters & Downspouts: Galvanized, Below Ground Drain

*Repairs Needed Comments: The galvanize gutters are quite dirty, and they are rusting through in different places, and some of the downspouts are damaged and dont extend into the drains properly, and some broken piping noted at the inground drain system for the gutters, the gutter system appears to need replacement, consult a licensed gutter contractor for full assessment and repairs needed. The inground drains appear to extend out to the street, but they most likely will need to be cleaned, and they are damaged in places, see plumber for full assessment and repairs needed. Note: Gutter drainage not tested for proper operation

Soffits/Eaves/Fascia: Wood, Open Rafter All Sides Viewable, More Than One Story

*Appears Serviceable Comments: The porch area overhangs were lower than typical standards of practice, just be aware of it, consult a licensed contractor for full assessment and options, as desired.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 6 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 8: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Roof: (Continued)

Roof:

Roof Material: Architectural Composition

Roof Viewed: Walked

Layers of Roof: 2

Approximate Life Expectancy: 8-10 Years

*Repairs Needed Comments: Treat and carefully remove moss as needed for best roof life and function - do not pressure wash, some exposed flashings noted at the sidewall to roofing transitions, caulk to seal, consult a licensed roofing contractor for full evaluation, repairs needed, and a more exact roof life estimate. Some tree limbs on roof, trim back. Also, see picture pages for those details. Otherwise, the roof still appears to be serviceable, at this time. Note: In determining the number of layers on a multiple layer roof, the inspector checks the roof at the roof eave or at the gable end. The roof is in no way defaced or partially removed to determine the number of layers. An Additional and undetected layer(s) may exist. INTEGRITY DOES NOT GUARANTEE AGAINST ROOF LEAKS.

Attic: 4931

Attic Viewed: From Access Opening

Roof Framing: Truss

Attic Type: Crawl Space

Sheathing: Plywood

Insulation: Fiberglass, Blown In

Value of Attic Insulation: R-38

*Appears Serviceable Comments: Attic viewed from the access opening due to the depth of the insulation. Attic appears to have adequate ventilation. Also, see picture pages for those details. Otherwise, the attic area looked in good overall shape, as viewed from the access opening. Note: Attic will be inspected from access opening if insulation is above framing.

Attic: 4941

Attic Viewed: (*)

Roof Framing: (*)

Attic Type: (*)

Sheathing: (*)

Insulation: (*)

Value of Attic Insulation: (*)

(*) Comments: (*)-Unit not accessible, keys dont work; see owner or management company for access. Note: Attic will be inspected from access opening if insulation is above framing.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 7 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 9: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Porch, Patio, Deck, Garage: 4931

Porch: Concrete

*Appears Serviceable Comments: Porch seemed fine.

Patio: Concrete

*Appears Serviceable Comments: Patio seemed fine.

Garage & Storage: Attached

*Repairs Needed Comments: Some inaccessible areas noted--due to various stored items. Typical slab cracks noted in the floor, but basic function is still OK. The garage bay door has been bumped into, so the roller is out of the track and the door pushed, and it wont open this way, consult a licensed bay door contractor for assessment and repairs needed, for proper function. Otherwise, the garage seemed serviceable, overall. Note: See roof and siding inspection for any comments pertaining to exterior of garage.

Porch, Patio, Deck, Garage: 4941

Porch: Concrete

*Appears Serviceable Comments: Porch seemed fine.

Patio: Concrete

*Appears Serviceable Comments: Patio areas seemed fine.

Garage & Storage: unit not accessed, unable to inspect

unit not accessed, unable to inspect Comments: unit not accessed, unable to inspect Note: See roof and siding inspection for any comments pertaining to exterior of garage.

Exterior Utilities:

Exterior Electrical Electrical Service: Underground

Service Ground: Water Pipes

Conductor Type: Aluminum

*Repairs Needed Comments: The weatherproof covers are broken or missing--replace as needed. The electrical service conduit for unit 4931 is broken and corroded at the ground level, which is a potential hazard, consult a licensed electrician for a full assessment and repairs needed.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 8 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 10: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Exterior Utilities: (Continued)

Exterior Plumbing Service Pipe Material: Copper

Main Water Shut Off Valve: At the Meter by the Street

*Repairs Needed Comments: See owner for all locations of main water shut off valves, and hose faucet shut off valves. Both the front and rear hose faucets leak when on, at unit 4941, repair as needed. Note: Exterior hose bibs should be frost-proof type or have supply shut off to protect against freezing during extreme cold. Lawn Sprinklers, spa's and swimming pools not tested.

Gas / Oil Gas or Oil: N/A

Main Shut Off Valve: N/A

N/A Comments: N/A Note: Integrity Home Inspections makes no guarantee that an undiscovered oil tank is not on the property. Integrity Home Inspections recommends soil samples on all buried oil tanks.

Interior Room Assessments: 4931

Entry -

*Appears Serviceable Comments:

Hallway -

*Appears Serviceable Comments:

Living Room -

*Appears Serviceable Comments: Room seemed fine.

Dining Room -

*Appears Serviceable Comments:

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 9 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 11: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Interior Room Assessments: 4931 (Continued)

Interior Room Assessments: 4941

unit not accessed, unable to inspect

unit not accessed, unable to inspect Comments: unit not accessed, unable to inspect

Interior Windows:

*Repairs Needed Comments: See individual rooms for details. 1) Note: Due to weather and light conditions, Integrity makes no guarantees that thermal seals are in tact on windows. 2) Note: Although it is not required, Integrity recommends that all open-able windows have child proof safety locks installed to help prevent people (especially children) from falling out of windows. Consult a contractor to install as needed if not already installed.

"Kitchen: " 4931

Sinks, Countertops, & Cabinets Countertops: Laminate

*Repairs Needed Comments: GFCI protection is recommended at kitchen outlets--consult a licensed electrician for repairs. Wiring to the disposal in the sink base cabinet should be installed inside conduit--consult a licensed electrician for repairs. Otherwise, the kitchen seemed serviceable, overall.

Flooring, Walls & Ceilings Floor Covering: Vinyl

*Appears Serviceable Comments:

Kitchen Appliances Appliances Present: Electric Cooktop, Electric Oven, Exhaust Diverter Hood, Dishwasher, Garbage Disposal, Refrigerator (Personal Property?)

*Appliances Functioned Fine When Tested Comments: Appliances checked out fine, when spot tested. Note: Appliances are only spot tested. Integrity Home Inspections, Inc. implies NO guarantee or warranty of their limited or continued use or operation.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 10 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 12: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

"Kitchen: " 4941

Sinks, Countertops, & Cabinets Countertops: (*)

(*) Comments: (*)-unit not accessed, unable to inspect

Flooring, Walls & Ceilings Floor Covering: (*)

(*) Comments: (*)-unit not accessed, unable to inspect

Kitchen Appliances Appliances Present: (*)

(*) Comments: (*)-unit not accessed, unable to inspect Note: Appliances are only spot tested. Integrity Home Inspections, Inc. implies NO guarantee or warranty of their limited or continued use or operation.

Interior Utilities: 4931

Water Heater -

Location: Garage

Gas or Electric: Electric

Capacity: 50 Gallons

*Repairs Needed Comments: Earthquake strapping is needed, consult a licensed plumber for assessment and repairs needed. Recommend extending the overflow pipe down to within 6 inches of the floor for best safety. Otherwise, the water heater functioned fine when tested--no leaks noted.

Electric Panel -

Location: Garage

Amperage: 125 Amps

Main Disconnect: Garage at the Panel

Visible Wire Type: Romex, Conduit

Lower Branch Wire Type: Copper

2 or 3 Pronged Outlets: 3 Pronged Outlets

*Appears to be Properly Wired Comments: Electric panel looked fine. Note: Electrical inspection is visual only and not intended to be all-inclusive. Receptacles throughout the structure have only been spot checked, and just those which were readily accessible to the inspector. This check does not imply a warranty or guarantee of condition or safety of any of the electrical system. An undiscovered condition may exist.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 11 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 13: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Interior Utilities: 4931 (Continued)Heating System -

Location: Zonal--individual areas

Type of System: Electric Wall Fan, Electric baseboard

*Functioned Fine When Tested Comments: Baseboard heaters seemed to heat fine, when checked. The wall fan heater in the living room is a King brand and it was functional. Note: Heating and cooling systems are checked only for basic functions; this is not an all-inclusive system check. Internal components are not inspected including heat exchangers.

Smoke Detectors -

Type: Battery, Hardwired

*Appear Serviceable Comments: Smoke detectors sounded off fine when tested. Note: Smoke & Carbon Monoxide detectors require regular testing and maintenance to ensure proper operation. This inspection report is not a guarantee of proper function.

Carbon Monoxide Detectors -

Type: Battery

Repairs Needed Comments: Carbon Monoxide (CO) detector upstairs sounded off fine when tested. The CO on the main floor has a missing battery, replace. Note: Smoke & Carbon Monoxide detectors require regular testing and maintenance to ensure proper operation. This inspection report is not a guarantee of proper function.

Interior Utilities: 4941

Bedrooms: 4931

NW Bedroom -

*Repairs Needed Comments: Broken thermal seal noted at the non-slider window--consult a licensed window contractor for full evaluation and repairs needed. Otherwise, the bedroom checked out fine, overall.

SW Bedroom -

*Repairs Needed Comments: Broken thermal seal noted at the non-slider window--consult a licensed window contractor for full evaluation and repairs needed. Otherwise, the bedroom checked out fine, overall.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 12 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 14: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Bedrooms: 4931 (Continued)NE Bedroom -

*Repairs Recommended Comments: Entry door does not latch--repair as needed. Otherwise, the bedroom checked out fine, overall.

Bedrooms: 4941

(*) Bedroom -

(*) Comments: (*)-Unit not accessible, keys dont work; see owner or management company for access.

Bathrooms: 4931

Main Floor Bathroom -

Half Bathroom

*Appears Serviceable Comments: Bathroom checked out fine.

Second Floor, Hallway Bathroom -

Full Bathroom

*Repairs Recommended Comments: The entry door does not latch well, repair. The glass shower door frame remains but the glass slider doors are missing, just be aware of it; there is a shower curtain installed in its place, though, FYI. The exhaust fan at the heat lamp fixture sounds very worn, and the secondary exhaust fan is not functional, consult a licensed contractor for assessment and repairs needed. Otherwise, the bathroom seemed serviceable, overall.

Bathrooms: 4941

(*) Bathroom -

(*)

(*) Comments: (*)-Unit not accessible, keys dont work; see owner or management company for access.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 13 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 15: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

"Substructure: " 4931

Crawl Space Structure: Post & Beam

Insulation: Sub-Floor

Vapor Barrier Type: Black Plastic

*Appears Serviceable Comments: The crawl space appears to have adequate ventilation. Sub floor not accessible due to floor insulation. Remove all wood debris inside crawl space as needed. Some stains from past puddling water noted, but no current water noted at this time, just be aware of it. Also, see picture pages for those details. Otherwise, the crawl space checked out fine, overall, no rot or wood destroying insects noted at the time of inspection.

Substructure Plumbing Supply Line: Copper

Waste Line: ABS Plastic

*Appears Serviceable Comments: Supply piping not visibly accessible due to insulation. No visible substructure leaks noted at this time.

Substructure Electrical

*Appears Serviceable Comments: - Looked fine.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 14 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 16: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

"Substructure: " 4941

Crawl Space Structure: (*)

Insulation: (*)

Vapor Barrier Type: (*)

(*) Comments: (*)-Unit not accessible, keys dont work; see owner or management company for access.

Substructure Plumbing Supply Line: (*)

Waste Line: (*)

(*) Comments: (*)-Unit not accessible, keys dont work; see owner or management company for access.

Substructure Electrical

(*) Comments: (*)-Unit not accessible, keys dont work; see owner or management company for access.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 15 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 17: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Wood Destroying Pest and Dry Rot ReportClient / Inspection Information -

Client - Alejandro & Dora Sandoval

Property Address - 4931 & 4941 Elkhorn Ct SE

City - Salem State - Oregon

House Faces - South

Structure Type - Multi Family

Exterior Wall Type - Wood Frame

Approximate Year Built - 1975

People Present - Tenants, Seller Representative, Buyer

Weather Conditions - Dry

Inspection Company Information -

Inspectors Name - Matt Sievers

Inspection Cert. Number - OR #022 WA #585

Dept. of AG PCO Lic. Number - OR #001451 WA #42309

State of Oregon General Contractors (CCB) Lic.- OR #69324

Inaccessible Area's:

Internal Structure: 1,3,4,6,7,8,9

External Structure: Attic: 5, attic viewed from access; No access into unit 4941

Garage: 1,3,6,7,9

Crawl Space: 5-subfloor, 4941 not accessible: see owner or management company for access.

Basement: Foundation: Porch: Deck: Roof:

Other: No access noted into unit 4941 so this duplex was not able to be fully inspected

Report Summary: 1) Some rot noted in the bottom of the T1 11 siding adjacent the front of unit 4931 and along the driveway side of unit 4931, and rot noted in the trim of the garage bay doors of 4931 & 4941, and some rot noted in the bottom trim of unit 4931 garage man door, consult a licensed contractor for full assessment and repairs needed. 2) There is some wood debris and planter boxes up against the siding in various places, this also limits access to the siding, so there is a potential for hidden damage, consult a licensed contractor for assessment and repairs needed. 3) No access into unit 4941, so the interior, attic, garage, crawl, were not able to be inspected, consult owner and or management company for access, than inspect as needed.

Scope of Inspection Survey - Integrity Home Inspections, Inc. agrees to inspect the readily accessible and visible area's for Wood Destroying organisms. Inaccessible area's will NOT be inspected, such as, but not limited to, insulated sub-floor framing, below carpet or floor coverings, behind owners belongings, furniture or appliances, wall voids or any other area that was obstructed or blocked in any way.

Limitations of Liability - INTEGRITY HOME INSPECTIONS, INC. LIMITS ITS LIABILITY TO THE FEE PAID. Due to the many inaccessible area's in a home, Integrity Home Inspections makes no guarantee or warrantee either expressed or implied, that Wood Destroying organisms were not present, only that using normal visual techniques, none were discovered at the time of the inspection.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 16 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 18: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Wood Destroying Pest and Dry Rot Report (Continued)

Inspectors Signature:

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 17 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 19: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Pictures: Picture 1 - Some minor rot noted in the bottoms of the garage bay door frame/trim work, in... ...various places, consult a licensed contractor for full assessment and repairs needed.

Picture 2 - Some rot noted in the driveway side of unit 4931 and... ...at the front entry area 4931, consult a licensed contractor for full assessment and repairs needed.

Picture 3 - Some rot noted in the bottom garage man door frame/trim work of unit 4931, consult a licensed contractor for full assessment and repairs needed. The wood debris and planters are not a good idea against the siding, since it could trap moisture against the siding which would cause rot, consult a licensed contractor for full assessment and repairs needed.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 18 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 20: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Pictures: (Continued)Picture 4 - The garage bay door of unit 4931 is badly damaged and... ... popped off the track, so it is not operational, consult a licensed garage bay door contractor for full assessment and repairs needed.

Picture 5 - The inground downspout drain piping system is broken and damaged in places, consult a licensed plumbing contractor for full assessment and repairs needed. The electrical service conduit for unit 4931 is broken and damaged at the ground level and it is a potential hazard, consult a licensed electrician for full assessment and repairs needed.

Picture 6 - Broken window pain noted at 4941 garage, consult a licensed contractor for full assessment and repairs needed. Missing chunk of trim noted on garage bay door frame for unit 4941, repair as needed.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 19 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 21: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Pictures: (Continued)Picture 6 - (continued)

Picture 7 - The gutters are rusting through in... ...various areas, consult a licensed gutter contractor for full assessment and repairs needed.

Picture 8 - Some atypical trim noted on the siding corner in this location, consult a licensed contractor for full assessment and repairs needed. Typically the siding should have a 1 inch clearance to the roofing, but it does not, consult a licensed contractor for full assessment and repairs needed.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 20 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 22: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Pictures: (Continued)Picture 9 - The gutters have extensive debris in them, consult a licensed gutter contractor for full assessment and repairs needed. The roof has extensive moss on it in places, and...

Picture 10 - ...the siding wall to roofing transitions have flashings that need the nail heads recaulked for proper seal, and... ...the tree needs to be trimmed away from the roofing, consult a licensed roofing contractor for full assessment and repairs needed.

Picture 11 - Otherwise, the roof still appears to be functioning as intended. The attic of unit 4931 has some drywall on the roof adjacent the neighbors unit apparently for some type of firewall protection, FYI.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 21 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 23: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Pictures: (Continued)Picture 11 - (continued)

Picture 12 - Some of the plywood roof sheathing seams have a little bit of a bow in them, just be aware of it. Otherwise, the attic appeared to be in good overall shape as viewed from the access opening.

Picture 13 - In the substructure crawlspace of 4931 there is some wood debris on the ground it should be removed when convenient. There are stains from past puddling water in unit 4931 crawl but no standing water anywhere in this crawl, at this time, it is possible that the failed and blocked gutters and inground drain system may have been the source of the aforementioned puddling water, just be aware of it; monitor.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 22 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.

Page 24: Exterior Utilities: 8 Exterior Structure Assessment: 5 …...Integrity Home Inspections, Inc. Report Integrity Home Inspections, Inc. 12042 SE Sunnyside RD. #562 Clackamas , OR 97015

Pictures: (Continued)Picture 14 - There was no access into unit 4941 crawl from this substructure, FYI; plus, no access into unit 4941, to check for a second crawl access, just be aware of it. Otherwise, this crawl of unit 4931 seemed fine, no rot or wood destroying insects noted, at this time.

Integrity Home Inspections, Inc.20:34 April 20, 2020

4931 & 4941 Elkhorn Ct SEPage 23 of 23

Palm-Tech Inspector, Copyright © 1998-2020, PDmB, Inc.