![Page 1: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/1.jpg)
Exploring IEEE C37.246-2017 Guide for Protection Systems of Transmission-to-Generation
InterconnectionsPresented by Alla Deronja
System Protection EngineerAmerican Transmission Company
1
![Page 2: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/2.jpg)
AuthorsAlla Deronja, ATC (Chair)Keith Houser, Dominion Energy (Vice Chair)Abu Bapary, AEPJeffrey Barsch, AEPRandall Cunico, Power Grid EngineeringWill English, Consumers EnergyDominick Fontana, EversourceDale Fredrickson, We EnergiesNathan Gulczynski, ATCMike Jensen, PG&EGerald Johnson, Dominion Energy (CM)Yuan Liao, University of KentuckyHeather Malson, SynchroGrid
2
Rene Midence, ERLPhase Power Technologies (CM)Dean Miller, POI EngineeringJohn Miller, Georgia Transmission CorporationAdi Mulawarman, Xcel Energy (CM)Mukesh Nagpal, BC HydroJim O’Brien, Duke EnergyMahendra Patel, EPRIManish Patel, Southern CompanyNeftaly Torres, CenterPoint Energy (CM) Ian Tualla, Duke EnergyJoe Uchiyama, USBRJoseph Valenzuela, Kiewit Engineering & DesignSolveig Ward, Quanta TechnologyRichard Young, Electrical Consultants
![Page 3: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/3.jpg)
Objectives
• Need for industry document• Scope/purpose of new guide• Guide contents • Interconnection protection overview• Summary
3
![Page 4: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/4.jpg)
Need for industry document
• Past – vertically integrated utilities Individual electric utilities maintain their own
interconnection requirements
4
![Page 5: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/5.jpg)
Need for industry document (cont.)
• Present – power industry deregulation Independent power producers and transmission
companies Increasing penetration of inverter-
based generation Regulatory reliability standards
5
![Page 6: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/6.jpg)
Guide Scope and Purpose• Scope
Document accepted protection practices for transmission-to-generation interconnections
Cover protection system applications at transmission-to-generation interconnections greater than 10 MVA
Out of scope: distributed energy resources
• Purpose Provide guidance to those responsible for the protection of
electrical transmission-to-generation interconnections greater than 10 MVA
Not intended to supplant specific transmission or generator owner practices, procedures, requirements, or contractual agreements.
6
![Page 7: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/7.jpg)
Guide contentsEstablishing interconnection
• Technical data exchange between transmission and generator owners
Interconnection configurations • Straight bus• Dual-terminal bus• Tapped connections
System studies • Evaluate proposed transmission-to-generation interconnections • Power flow, transient stability, short-circuit, and relay
coordination
7
![Page 8: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/8.jpg)
Guide contents (cont.)Protection system settings for interconnections
• Specific protection system guidelines to be considered when designing new or upgrading existing interconnection substation.
• Interconnection substation protection and control functions • Issues of autoreclosing near generation and interconnection
communication-based transfer tripping • Tapped connections • Interconnections with renewable energy sources
8
![Page 9: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/9.jpg)
Establishing interconnectionRole of transmission owner
• Selects relays and protection schemes• Determines maximum and minimum fault current levels• Approves generator step-up (GSU) or interconnection
transformer winding configurations• Provides data on:
• Power system stability• Synchronizing practices• Autoreclosing practices• Grounding coordination
9
![Page 10: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/10.jpg)
Establishing interconnection Role of generator owner
• Proposes point of interconnection • Provides design drawings • Provides data on:
• Generator• Transformer• Ride-through capability• Reactive power, frequency control• Short circuit levels
10
![Page 11: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/11.jpg)
Establishing interconnectionSpecific considerations
• Various items to agree on: • Equipment• Protection • Testing
• Voltage transient effect
11
![Page 12: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/12.jpg)
Interconnection configurationsTie line
12
Transmission Station
Generating Unit
Transmission Station
Generating Unit
a) Double breaker arrangement
b) Single breaker arrangement
![Page 13: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/13.jpg)
Interconnection configurationsSwitching station
13
![Page 14: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/14.jpg)
Interconnection configurationsTapped connection
14
![Page 15: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/15.jpg)
System studies
• System impact study• Facilities study• Specific system studies
• AC power flow analysis• Transient stability analysis• Short circuit analysis• Relay coordination studies• Subsynchronous resonance (SSR) studies
15
![Page 16: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/16.jpg)
Interconnection protection functionsSynch Check (25)
16
25
TransmissionNetwork
52
![Page 17: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/17.jpg)
Interconnection protection functionsDegraded Grid Voltage (27)
• Generator auxiliary systems• Specified limits• Separation• Multiple elements• Coordination • See guide for further details
17
![Page 18: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/18.jpg)
Interconnection protection functionsReverse Power (32) – generator motoring
• Typically, part of generator protection• Applied with loss of prime mover energy• Trip 52G for power flow into the generator
18
32
TransmissionNetwork
52M52G
![Page 19: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/19.jpg)
Interconnection protection functionsReverse Power (32) – one-way power flow
• Generation for local load, no energy export Industrial plant with local generation
• Lost network source, power flowing into transmission system
• Trip 52M • Trip 52G
19
32
Transmissionsystem
52M52G
Load
![Page 20: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/20.jpg)
Interconnection protection functionsBreaker failure protection (50BF)
20
Transmission Line
Generating Unit
50BF
REM BU
![Page 21: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/21.jpg)
Interconnection protection functionsGSU Ground Overcurrent (51TG)
21
Example in the Guide!
Transmission Line
Generating Unit
51TG
67N
![Page 22: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/22.jpg)
Interconnection protection functionsFrequency protection (81)
• Typically applied at generation• Anti-islanding protection• Manufacturer recommendations• Regional requirements• Backup
22
![Page 23: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/23.jpg)
Interconnection protection functionsBus differential protection (87B)
• When is interconnection a bus?
• IEEE Std C37.234 - Protective Relay Applications to Power System Buses.
23
![Page 24: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/24.jpg)
Interconnection protection functionsTie line current differential protection (87L)
• When is interconnection a line?• Current differential scheme
• Not affected by weak infeed conditions• Only requires line currents• Setting simplicity
24
![Page 25: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/25.jpg)
Line autoreclosing
• Intermittent faults
• Consider possible damage to generation
• Mitigating options
25
![Page 26: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/26.jpg)
Tapped connectionsDesign issues
• Tap adds exposure for line faults to the existing circuit• Loss of the transmission line results in a loss of generator
26
TransmissionLine Tap
Generating Unit
Transmission Station A
Transmission Station B
![Page 27: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/27.jpg)
Tapped connectionsProtection issues
• More complex multi-terminal protection schemes • May require communication assisted schemes• Relay coordination issues• Zone 1 distance protection• Infeed effects
27
![Page 28: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/28.jpg)
Renewable energy resourcesWind plants
• Fault current contribution
• Varying fault currents
• Fast protection response needed
28
![Page 29: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/29.jpg)
Renewable energy resourcesSolar PV inverters
• Current controlled devices • Fault currents • Time-delayed protection issue• Filtering components of the inverter • Fast protection response required
29
![Page 30: Exploring IEEE C37.246-2017 Guide for Protection Systems ...ccaps.umn.edu/...PowerPoints/.../ExploringIEEEC37.pdfExploring IEEE C37.246-2017 Guide for Protection Systems ... • Provides](https://reader033.vdocuments.mx/reader033/viewer/2022041910/5e66ed55c090ac66650cdff6/html5/thumbnails/30.jpg)
Summary
30
• Engineering transmission-to-generation interconnection • Design reliable interconnection for dependable
system operation during normal or abnormal system conditions.
• Collaborate between transmission and generator owners during interconnection design
• Role of IEEE C37.246 guide • Aid protection engineers in interconnection design • Document and explain protection principles and best
practices • Expound on practical application issues