exhibit ii - florida · exhibit ii equipment lists & sample service sheets site 1 - cbjtc post...

38
Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages Site 2- CBJTC CSMS Buildings: 13 pages Site 3 - CBJTC RTI Buildings: 15 pages Sample Service Sheet- 4 pages Note: Equipment specific service sheets will be provided/developed with the contract awarded vendor as part of the initial meeting referenced in the introduction of Section 5.

Upload: others

Post on 23-Jan-2020

30 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Exhibit II Equipment Lists & Sample Service Sheets

Site 1 - CBJTC Post Headquarters: 5 pages

Site 2- CBJTC CSMS Buildings: 13 pages

Site 3 - CBJTC RTI Buildings: 15 pages

Sample Service Sheet- 4 pages

Note: Equipment specific service sheets will be provided/developed with the contract awarded vendor as part of the initial meeting referenced in the introduction of Section 5.

Page 2: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

---------------------

AHU 1 SLP# 39MASTW04CKHWBXJGK S# 0708U05016 M# 39MN06C01 09NW22XGS S# 0708U05016 Manufacturer# 2V781897 M# 39MHSTW04CBKB8XGBV S# 0708V05015

Exhibit 11-Site 1 Post Headquarters

Johnson Controls Pressure & Temperature Sensor Weiss Instruments Temperature & Pressure Gauges in water lines. Johnson Controls M# 9220-GGA-3, 20nM(1771N-LB) Return Air Damper M# 9220-GGA-3, 20nM(1771N-LB) Make Up Air Damper M# VA9104-GGA-3S, 4nM(35 IN-LB) Chilled Water Line M# VA91 04-GGA-3S, 4nM(35 IN-LB) Hot Water Line Statitrol M3 501 K2 Air Duct Smoke Detector Supply & Return Cleveland Control M# AFS-460 Air Switch Johnson Controls lntellipass Integrated Drive Bypass System, VSD Series (2) filters

AHU2 Carrier M# 39MN12C0109NX22XGS S# 0708U05018 M# 39MCSTW04GBBXXCBGM S# 0708U05017 Manufacturer# 2V781897 Weiss Manufacturing Temperature & Pressure Gauges in Hot & Cold Water Lines Johnson Controls M# M9106-GGA-2 6nM(53in-lb) Chilled Water Line M# M9104-GGA-3S 4nM(35in-lb) Hot Water Line M# M9220-GGA-3 20nM(1771N-LB) MAKE UP AIR DAMPER M# M9220-GGA-3 20nM(1771N-LB) RETURN AIR DAMPER TEMPERATURE SENSOR Statitrol M# 501 K2 Air Duct Smoke Sensor in Supply & Return Ducts Cleveland Control M# AFS-460 Air Switch lntelipass Integrated Drive Bypass System, VSD Series 6 Filters

AHU3 Carrier Manufacturer# 2V781897 Catalog #1P39MN12C0109NY12XGS M# 39MN12C0109NY12XGS S# 0708U05019 M#39MCSTW04GBBXXCBCM S# 0708U05019 Weiss Temperature & Presure Gauge in Hot & Chilled Water Lines

------------

Page 1 of 5

Page 3: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Exhibit 11-Site 1 Post Headquarters

Statitrol Air Duct Smoke Detector M# 501 K2 in supply & return ducts Johnson Controls M# VA9104-GGA-3S 4nM(351N-LB) HOT WATER LINE M# M9106-GGA-2 6nM(531N-LB) CHILLED WATER LINE M# M9220-GGA-3 20nM(1771N-LB), RETURN AIR DAMPER M# M9220-GGA-3 20nM(1771N-LB), OUTSIDE AIR DAMPER lnnovair Air Temp System Sensor M#DH100ACDCLP Cleveland Control M# AFS-460 Air Switch 6 Filters

AHU4 Trane Unit Type CCBD06BNEC Basic Unit V3A5L02LLBG PRIMARY COILS 10CEQA2B100LOB2E ELECTRIC PRE HEAT 21000AOOOOOOOOOOO 00000 MARSHALL TOWN THERMOMETERS IN WATER LINES STATITROL AIR DUCT SMOKE DETECTORS M# 501K21N SUPPLY & RETURN DUCTS JOHNSON CONTROLS M# VA9104-GGA-3S 4nM(351N-LB) HOT WATER LINE M# VA9104-GGA-3S 4nM(351N-LB) CHILLED WATER LINE M# M9210-GGA-3 10nM(891N-LB) RETURN AIR DAMPER M# M9210-GGA-3 10nM(891N-LB) RETURN AIR DAMPER Johnson Controls, Penn Pressure Switch Johnson Controls Air Temperature Probe Cleveland Controls M# AFS-460 Air Switch 6 filters

AHU7 Carrier M# 39MHSTW04GHPXFXJBC S# 0708U05021 M# 39MHSTW04GHHXFGJBR S# 0708U05021 M# 39MN12C0109NZ11XGS S# 0708U05021 WEISS INSTRUCMENTS TEMPERATURE & PRESSURE GUAGES IN BOTH WATER LINES STATITROL AIR DUCT SMOKE DETECTOR M# 5011<2 IN SUPPLY & RETURN AIR DUCTS JOHNSON CONTROLS M# M9220-GGA-3 20nM(1771N-LB), RETURN AIR DAMPER M# M9109-GGA-2 6nM(531N-LB) CHILLED WATER LINE M# VA9104-GGA-3S 4nM(351N-LB) HOT WATER LINE 6 FILTERS

AHU8 Carrier M# 39MN12C0109P011XGS S# 0708U05022

Page 2 of 5

Page 4: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

-------~~- ----

M# 39MHSTW04GBPXFXJBC S# 0708U05022 M# 39MHSTW04GBHXFGJBR S# 0708U05022 M#39MCSTW04GBBXXCBGH S# 0708U05022

Exhibit 11-Site 1 Post Headquarters

WEISS TEMPERATURE & PRESSURE GAUGES IN EACH WATER LINE STATITROL AIR DUCT SMOKE DETECTOR M# 501 KS IN SUPPLY & RETURN AIR DUCTS JOHNSON CONTROLS M# M9220-GGA-3 20nM(1771N-LB) RETURN AIR DAMPER M# VA9104-GGA-3S 4nM(351N-LB) HOT WATER LINE M# M9109-GGA-2 6nM(531N-LB) CHILLED WATER LINE JOHNSON CONTROLS TEMPERATURE SENSOR JOHNSON CONTROLS PRESSURE SENSOR 6 FILTERS

AHU9 TRANE M# BWE060C400EO S# 172472 DATE X23 GE WATER COIL CATALOG# AY99X082 JOHNSON CONTROLS M# VA9104-GGA-3S 4nM(351N-LB) HOT WATER LINE M# R1BU1C TEMPERATURE SENSOR 1 FILTER

CU9 YORK M# YCJD4854343A S# WIG1207253

AHU10 TRANE M# BWE090C4000 S# Y04178453 DATE 01/1985 NO WATER COIL #'S JOHNSON CONTROLS M# VA9104-GGA-3SD 4nM(351N-LB) HOT WATER LINE 2 FILTERS

CU10 TRANE M# TT A090A300CC

Page 3 of 5

Page 5: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

0-----------

S# N234N33AH DATE 06/1998

AHU3 TRANE M# CCDB03ANEC BASIC UNIT# H3AIL02LLBF PRIMARY COIL#100EQA28100F5A2E S# K83F93716 JOHNSON CONTROLS

Exhibit 11-Site 1 Post Headquarters

M# VA9104-GGA-3S 4nM(351N-LB) HOT WATER LINE 2 FILTERS

MAIL ROOM CONDENSER GOODMAN M# CK49-1B S# 0004448698

AIR HANDLER GOODMAN M# A49-10 S# 0007542135

SPECIAL FORCES MITSUBISHI MINI SPLIT CONDENSORS #1 M# MUZ-A12-NA S# 6002250T #2 M# MUZ-A15-NA S# 6001232T #3 M# MUZ-A 17NA S#6003993T

Evapco COOLING TOWER M# AT-19-76L

CHEMICALS LMI CONTROLS LIQUITRON DC4500 M# P051-392S1 S# 20020613934

Monthly Service Required for Cooling Tower

Page 4 of 5

Page 6: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

M# A111-91T S# S82112100 M# P051-292S1 S# 20020613935

CHILLER CARRIER M# 30HXC106RYE561AA S# 0508008739 McDONALD FLOW SWITCH CHILLGAURD LE REFRIGERANT MONITOR

Exhibit 11-Site 1 Post Headquarters

WEISS INSTRUMENTS PRESSURE & TEMPERATURE GUAGES IN WATER LINES JOHNSON CONTROLS WATER TEMPERATURE SENSOR

BOILER BURNHAM BOILER M# PF-504 S# 7571160 BURNHAM GAS BLOWER M#R6.2-G-03 BURNER# T6976 GROUP6 NATURAL GAS

PUMPS BELL & GOSSETT PUMP #1 M#1-1/4BC 9-1/4BFW S31159196 45GPM 90FT 175 PSI Pump #2 SIZE 1510 BF 9.5 S# C057695-01A80 300 GPM 80FT 10 HP 1800 RPM 175 PSI PUMP#3 SIZE 1510 BF 10.5 S# C057694-01A80 230 GPM 100FT 10 HP 1800 RPM WEISS PRESSURE GAUGES IN ALL WATER LINES

Page 5 of 5

Page 7: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

BLD #4104 RM COM/NET EMI MINI SPLIT CONDENSER M# WHP12A030CAOOOC S# 104-M-4707-45 M# SCC09AAOOOOAAOB S# 1 04-M-4683-45

RM#220 YORK SPLIT SYSTEM AHU-1 M# N1AHC1606A S# XBN5051755 CU-1 M# H 1 RA048S06G S# WOM4255654

RM #212 CARPENTER SHOP UNIT# AT-MAU-1 MAKE UP AIR M# I G-1 09-H 1 0-HZ S# 05A04288 M# PVFH-0 S# 05A04288 M# PVF125H

HEATER M# SEM-11 0-CF S# SEL 11 OFD22CF

EXHAUST FAN EF-7 M# SBE-1 H20-5 S# 05A05254

RM # 209 MACHINE SHOP UNIT# AT-MAU-3 MAKE UP AIR M# IG-11 O-H20-HZ S# 05A026-36 M# PVFH S# 05A026-36 M# PVF200H

HEATER M# SEM-110-L-CF

Exhibit 11-Site 2 CSMS-AIIied Trades

1

Page 8: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

S# SEL 110FD22CF

EXHAST FAN M#SBE2W20-7 S# 05A05258

RM#205 SUPPORT BAY UNIT# AT-MAU4 M# IGX-118-H32-HZ S# 05A07686

HEATERS M# SEM-110-L-CF S# SEL 11 OFD22CF M# SEM-110-L-CF S# SEL 11 OFD22-F

EXHAUST FAN 4 M# ZDPZ-25-27-29

RM #203 PAINT SHOP UNIT#AT-MAU-7 M# IGX-118-H32-HZ S# 05A04292 UNIT# AT-MAU-8 M# IGX-118-H32-HZ S# 05A06067 UNIT# AT-MAU-9 M# IGX-118-H32-HZ S# 05A06068 UNIT# AT-MAU-10 M# IGX-118-H32-HZ S# 05A06069 UNIT# AT-MAU-11 M# IGX-118-H32-HZ S# 05A07685

HEATERS M# SEM-110-L-CF S# SEL 11 OFD22CF M# SEM-11 0-L-CF S# SEL 11 OFD22CF

AIR SYSTEMS UNIT#1 M# GAYS S# All500979 UNIT#2 M#GAYS

Exhibit 11-Site 2 CSMS-AIIied Trades

2

Page 9: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

S#AII500980 UNIT#3 M#GAYS S# All500981

HALLWAY UNIT# AT-SF-2 M# BSG-120-3 S# 05A07732 EXHAUST FAN UNIT# EX8 M# BSG-120-4 S# 05A07777

RM#214 SMALL ARMS REPAIR DEHUMIDIFIER UNIT# AT-DT-1 FRIEDRICH M# D-50-C

UNIT# AT-MAU2 M#IG-11 O-H20-HZ M# PFV200H

UNIT# AT-MAU-5 M# IG-109-H10-HZ S# 05A64285 M# PFV200H

UNIT# AT-MAU-6 M# IG-109-H12-H S# 05A04326 M# PFV175H

UNIT# AT-EF-1 M#20SN-51

UNIT# AT-EF-2 M# SBE-324

UNIT# AT-EF-3 M# SBE-3H-24

UNIT# AT-EF-5 M# SBE-1H20

UNIT# AT-EF-6 M# BSQ-160-3

UNIT# AT-EF-10

Exhibit 11-Site 2 CSMS-AIIied Trades

3

Page 10: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

M# SP-8110

UNIT# AT-EF-11 M# SP-8110

UNIT# AT-EF-12 M# SP-8110

UNIT# AT-EF-13 M# SP-8110

UNIT HEATERS UNIT# AT-EH-1 M#CWH120

UNIT# AT-EH-2 M# CWH-120

UNIT# AT-EH-3 M#CWH-120

GRAVITY INTAKE VENT UNIT# AT-GIV-1 M#GRS124

UNIT# AT-GIV-2 M# GRS-36

UNIT# AT-GIV-3 M# GRS-36

UNIT# AT-GIV-4 M# GRS48

UNIT# AT-GIV-5 M# GRSI-48

UNIT# AT-GIV-6 M# GRSI-48

UNIT# AT-GIV-7 M# GRSI-48

UNIT# AT-GIV-8 M# GRSI-48

Exhibit 11-Site 2 CSMS-AIIied Trades

4

Page 11: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

BUILDING# 4105 HEATERS M# SEM110-CF S# SEL-110FD22CF M# SEM110-CF S# SEL-110FD22CF M# SEM110-CF S# SEL-110FD22CF M# SEM110-CF S# SEL-110FD22CF M# SEM110-CF S# SEL-110FD22CF M# SEM110-CF S# SEL-110FD22CF

EXHAUST FANS #3 M# 3DP3-7-9-11 EXHAUST FANS #2 M# 850-180-15 S# 05A007786 EXHAUST FAN #11 M# SFB 2250

UNIT# EB-MAU 2 M# PVF-H S# 05G12839 M# IGX-118-H32-HZ S# 05042839 M# PVF400

RM #317 Service Room MITSUBISHI MINI SPLIT CONDENSER M# PKA-A24KA4 S# PKA-A24KA4.TH AIR HANLDER M# PUZ-A24NHA4 S# PUZ-A24NHA4.TH

RM #322 INSTRUMENT REPAIR MAGIC AIRE SPLIT SYSTEM CONDENSER M# 36BVW-C S# W041028091 AIR HANDLER OLSON TECHNOLOGY M# AC1048BBDVB

Exhibit 11-Site 2 CSMS-Eiectronics

5

Page 12: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

S# JR000151245X

RM # 319 COMMUNICATION NETWORK EMI MINI SPLIT CONDENSER M# WHP12A030CAOOL S# 1-04-M-4 708-45 AIR HANDLER M# SCC09AAOOOOAAOB S# 1-04-M-468-45

MECHANICAL ROOM AHU 1 M# XTI-084X075-FALA046A S# CAPMXT0122

Exhibit 11-Site 2 CSMS-Eiectronics

ROOM ELECTRICAL & FIRE ALARM SYSTEMS EMI PTAC UNIT NO#'S

RM# 301 SUPPORT BAY UNIT# 3DP2-2-4-6 M# PVFH S# 05912836

EXHAUST FAN UNIT# EB-EF-1 M# BSQ-180-15 S# 05A07705

RM#335 PRODUCTION CONTROL YORK UNIT# EB-BX-6 M#YH512 S#15653-4

RM#332 YORK UNIT# EB-BX-4 M# YH512 S# 15653-5

RM#333 YORK UNIT# EB-BX-5 M#YH506 S# 15653-5

6

Page 13: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

HALLWAY UNIT# EB-BX-1 YORK M#YHS-14 S# 15653-1

EXHAUST FANS ON TOP OF VAULT UNIT# EB-EF-4 M#BSQ-120-4 S# 05A07728 UNIT# EB-EF-4 M# BSQ-120-3 S# 05A07729

RM#305 COMMUNICATIONS/ELECTRICAL UNIT# EB-BX-3 YORK M#YH512 S# 15653-3 UNIT# EB-BX-2 YORK M#YH512 S# 15653-2

RM#315 POP VALVE TEST SUPPLY FAN#2 UNIT# EBSF2 M#BSQ120-3 EXHAUST FAN #5 UNIT# EB-EF-5 M# CP-258

RM#307 MISSLE REPAIR DEHUMIDIFIER M# D-50C

UNIT# EB-EF-6 M# SB-262

UNIT# EB-EF-8 M#SPB-150

UNIT# EB-EF-9 M#SBP-110

UNIT# EB-EF-10 M#SPB-110

Exhibit 11-Site 2 CSMS-Eiectronics

7

Page 14: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

UNIT# EB-EF-11 M# SFB-2250

UNIT# EB-EF-12 M# SP262

UNIT HEATERS UNIT# EB-EH-1 M# CW120DS

UNIT# EB-EH-2 M#CWH120DS

UNIT# EB-EH-3 M# CDF548REA

UNIT# EB-SF-1 M# BSQ-120-3

UNIT# EB-SF-3 M# BSQ-120-3

UNIT# EB-SF-4 M# BSQ-90

DUCT HEATER UNIT# EB-EDH-1

Exhibit 11-Site 2 CSMS-Eiectronics

8

Page 15: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

BLDG #4106 EXHAUST FANS OPEN BAYS FAN# AS-EF-2 M# BSQ-300-50 S# 05A07712 FAN# AS-EF-1 M# BSQ-300-50 S# 05A07711

UNIT# AS-MAU-2 M# IG112-H20-HZ S# 04L22128 M# PVF225 UNIT# AS-MAU-1 M# IG112-H20-HZ S# 04L21008 M# PVF225 UNIT# AS-MAU-4 M# IG112-H20-HZ S# 04L21007 M# PVF225 UNIT# AS-MAU-3 M# IG112-H20-HZ S# 04L22992 M# PVF225 UNIT# AS-MAU-6 M# IG112-H20-HZ S# 04L22991 M# PVF225 UNIT# AS-MAU-5 M# IG112-H20-HZ

M# PVF225

HEATERS UNIT# ASIRH-2 M# SEM-11 0-CF S# SEL-110FD22 M# SEM-110-CF S# SEL-11 OFD22 UNIT# ASIRH-3 M# SEM-110-CF S# SEL-11 OFD22 M#SEM-110-CF S# SEL-110FD22 UNIT# ASIRH-4 M# SEM-110-CF S# SEL-110FD22 M# SEM-110-CF

Exhibit 11-Site 2 CSMS-Auto Service

9

Page 16: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

S# SEL-110FD22 UNIT# ASIRH-5 M# SEM-11 0-CF S# SEL-11 OFD22 M# SEM-110-CF S# SEL-110FD22 UNIT# ASIRH-6 M#SEM-110-CF S# SEL-110FD22 M# SEM-110-CF S# SEL-110FD22 UNIT# ASIRH-7 M# SEM-110-CF S# SEL-110FD22 M# SEM-110-CF S# SEL-11 OFD22 UNIT# ASIRH-10 M# SEM-11 0-CF S# SEL-110FD22 M# SEM-11 0-CF S# SEL-110FD22 UNIT# ASIRH-11 M# SEM-110-CF S# SEL-110FD22 M# SEM-11 0-CF S# SEL-110FD22 UNIT# ASIRH-12 M# SEM-110-CF S# SEL-110FD22 M# SEM-110-CF S# SEL-110FD22

UNIT# AS-MAU-8 M#PFV250-H S#05A04281

EXHAUST FAN UNIT# AS-EF-4 M# BSQ-300-30 S# 05A07713

RM# 441 TRANS & POWER PACK REBUILD EXHAUST FAN UNIT #ASEF-6 M# SBE-2H20-5

HEATER M# SEM-110CF S# SEL-110FD22

Exhibit 11-Site 2 CSMS-Auto Service

10

Page 17: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

UNIT# AS-MAU-10 M# IG109-H10-HZ S# 05A06062 M# PFV260H

RM# 443 TRANS & POWER PACK TEST FAN# AS-EF-5 M# BSQ130-5

HEATER M# SEM-110CF S# SEM110FD22

UNIT# AS-MAU9 M# IG-110-H10-HZ S# 05A07674 M# PFV126H

RM# NOT MARKED NEW TRANE SPLIT SYSTEM AIR HANDLER M# 4TXCD061 B03HCBA S# 114 72XBA5G CONDENSER M# 4TTB4060 S# 103757612F

RM#422 COMMUNICATIONS & NETWORK AS-AHU-2 EMI MINI SPLIT AIR HANDLER M# SCC09AAOOOOAAOB S# 1-04-M-4686-35 CONDENSER M# NO#'S S# NO#'S

RM# 424 MECHANICAL & COMP. PAYNE SPLIT SYSTEM AIR HANDLER M# PFIMNC060 S# 1707A7322 CONDENSER M# PH13NR060C S# 1509X62349

RM# 430 TOOL BASIC NEW MITSUBISHI MINI SPLIT M# PUZ-A24NHA4 S# 1X002121A M# PKA-A24KA4

Exhibit 11-Site 2 CSMS-Auto Service

11

Page 18: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

S# 16M-0277

RM#403 AUTO SUPERVISOR AMANA PTAC M# PTH0735AXXXAB S# 1101555926

RM#436 FUEL & IGNITION REPAIR EXHAUST FAN UNIT# AS-EF-10 M# SBE-1 H24-3

SUPPLY FAN UNIT# AS-SF-1 M# SBS-1 H24-3

AIR SYSTEMS UNIT#1 UNIT# AS-ACP-1 M# GAYS FF S# API500502 UNIT#2 UNIT# AS-ACP-2 M# GAYS FF S# API500503

UNIT# AS-MAU-7 M# IG-110-H10-H2 S# 05A08672

UNIT# AS-MAU-11 M# IG-110-H10-H2 S# 05A07641

UNIT# AS-MAU-12 M# IG-114-H20-HZ

UNIT# AS-EF-3 M# BSQ-120

UNIT# AS-EF-7 M# SBE-2H-20

UNIT# AS-EF-8 M# BSQ-180-20

UNIT# AS-EF-9 M# SP-255

UNIT# AS-EF-11 M# SP-225

Exhibit 11-Site 2 CSMS-Auto Service

12

Page 19: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

UNIT# AS-EF-12 M# SP8150

UNIT# AS-EF-13 M# SP-8110

UNIT# AS-EF-14 M#SP-8110

UNIT# AS-EF-15 M# SP8-150

UNIT# AS-EF-16 M#SP8-110

UNIT# AS-EF-17 M#SP8-110

UNIT# AS-EF-18 M# SP-8150

UNIT HEATERS UNIT# AS-EH-1 M#CWH120

UNIT# AS-EH-2 M# CWH120DS

UNIT# AS-EH-3 M# CWH-120-DS

UNIT# AS-EH-4 M# CWH120

WATER TOWER MARLEY NC CLASS COOLING TOWER M# NC8302GG S# 806246-A 1

PUMP EMERSON CATALOG# UJ7S2APC 3 PHASE 7.5 HP

PUMP SCOT 10HP 3 PAHSE

Exhibit 11-Site 2 CSMS-Auto Service

---------------------

13

Page 20: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Building 3400

Exhibit 11-Site 3 Regional Training Institute

MAIN MECH ROOM INSIDE HALL WAY AHU9 York model#xti-051x078-faka017a Serial#cgsm-xt0334 Filter sizes 20x20x2 qty 2 20x20x12 qty 2 20x24x2 qty 4 20x24x12 qty 4 Belts #bx46 qty 2

AHU10 mod#xti-036x063-baja017a Ser#c gsmxt0089 Filters 12x24x2 qty 12x24x12 qty1 20x24x2 qty2 20x24x12 qty 2 Belt #bx44 qty 1

Danfoss Freq Drive Mod-VL T -6000 qty 2

OUTSIDE MECH ROOM AHU 11 mod#xti-04x069-baja017a Ser# cgsmxt0090 Filters 20x20x2 qty 3 20x20x12 qty 3 16x20x2 qty 3 16x20x12 qty 3 Belts 5vx51 0 qty 2

Danfoss Freq Drive Mod-VLT-6000 qty 1

Boiler #b5 lochivar copper fin 2 Mod#chl751 Ser#j07h00202148 2stage Filter 12xl2xl

Hot water pumps P II a Patterson pump Mod#v2a9a-cc Ser#hvac-c06603I-1 0 Gpm 60

Page 1 of 15

Page 21: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Pllb Mod#v2a9a-cc Ser#hvac-c066031-09 Gpm60 Cold water pumps

P10a Mod#v2c7a-cc Ser#hvac-c066031-08 Gpm 135

P10b Mod#v2c7a-cc Ser#hvac-c066031-07 Gpm 135

Danfoss Freq Drive Mod-VL T -6000 qty 4

BUILDING 3400 INTERIOR VAV mod-metalaire 500 Qty 22

Mitsubishi mini split system in audio visual room Mod#MSZ-GE18NA Ser#0005543

CHOW HALL BUILDING 3410 OUTSIDE MECH ROOM AHU12 Mod#xti-051x090-bala017a Ser#cgsmxt0335 Filters 20x20x2 qty 8 20x20x12 qty 8 Belts 5vx51 0 qty 2

Boiler #b6 Copperfin 2 2stage mod#chl50 1 Ser#j 07h00202077 Filter size 12x 12x 1

Hot water pump Patterson pump #p 12a Mod#vl.5a7a-cc Ser#hvac-c066031-12 Gpm50

pump#pl2b Mod#vl.5a7a-cc

Page 2 of 15

Page 22: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Ser#hvac-c066031-11 Gpm50

BUILDING 3410 PHASE 4 AHU23 York Mod#xti-05x090-bala017a Ser#cmvmxtO 129 Filters 20x20x2 qty 8 20x20x12 qty 8 belt size bx50 qty 3

Fulton boiler Mod#phw 500

Hot water pumps 19a/b Emerson mtrs mod-g29302 Frame-145jm Type-ute-4 Bell/gosset pumps Ser#c095145-02 k90

Danfoss freq Drives Mod-Vlt qty 6

VA V Mod-metalaire 500- qty 15

BUILDING 3402- EQUIPMENT LIST PHASE 3 AHU21 Mod#mccb030ua0a0ua Ser# ko8127415a Filters 24x12x2 qty 2 24x24x2 qty 6 24x12x12 qty 2 24x24x12 qty 6 20x20x2 qty 12 20x25x2 qty 4 Total 32 Filters Belt size 5vx860 qty 1

AHU20 Mod# B030UAOAOUB Ser #K08L27408A Filters 20x20x2 qty 12 20x25x2 qty 4 24x12x2 qty 2 24x24x2 qty 6 24x12x12 qty 2 24x24x12 qty 6 Total 32 Filters Belt size 5vx71 0 qty 2

Page 3 of 15

Page 23: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Cold water pumps 17alb Emerson Mtr mod# g29304

Frame 145jm type -ute-4 Bell/gosset pump 155 gpm ser#1af006 a80

Hot Water Pump p 18 alb mod# g29306 Frame 182jm type-ute-4 Bell/gosset pump 65-gpm ser 1 af002-b80

BOILER Fulton Mod#Phw750

Danfoss freq Drives Mod-Vlt qty 6

VAV Mod-metalaire 500- qty 37

LiebertChallenger AC Unit-Mod-3000 qty 1

BUILDING 3404 AHU14 Mod# mccb008ua0aoua Ser# k08127422a Filters 20x20x2 qty 4 24x20x2 qty 2 24x20x12 qty 2 Belt size ax59 qty 1

AHU17 Mod#mccb008ua0a0ua Ser#k08127429a Filters 20x20x2 qty 4

24x20x2 qty 2 24x20x12 qty 2 Belt size ax59 qty1

Boiler Fulton Phw750

Cold water pumps 13a/b Emerson Mtr 15hp mod 8046 Frame-254jp type ute-1

Bell-gosset pumps 420 gpm ser laf041-j80 size 80

Page 4 of 15

Page 24: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Hot water pumps 14alb Emerson Mtr Mod# g29306 Frame 182jm type ute-4

Bell-gosset pumps 65 gpm ser#laf002-b80

Fan Coil Units 14x24x1

EAST WING AHU15 York Mod#xti-030x048-daha017a Ser#cmvmxt0105 Filters 16x20x2 qty 1 16x20x12 qty 1 20x20x2 qty 1 20x20x12 qty 1 Belt size ax38 qty 1

Fulton boiler Mod#phw500

Hot water pumps 15alb Emerson mtrs mod#g29302 Frame 145jm Type ute-4

Bell-gosset pumps 44gpm ser#c095143-02 k90

Lochivar Potable Boiler Mod#ewl300pm Ser#lo9h00223122

WEST WING lSI FLR Lochivar Potable Boiler Mod#ewl3 OOpm ser#l09h00223123

Fulton Boiler Mod#phw1 000

Hot pumps 16alb Mod#g29306 Frame 182jm Type ute-4

Bell-gosset pumps 84 gpm ser#c095144-0 1 k90

AHU16

Page 5 of 15

Page 25: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

York Mod#xti-033x051-daha0 17a Ser#cmvmxtO 128

Filters 20x24x2 qty 2 20x24x12 qty 2 Belt size ax41 qty 1

2ND FLR AHU18 York Mod#xti-030x057 -dahaO 17a Ser#cnvmxto 120 Filters 20x24x2 qty 2

20x24x12 qty 2 Belt size ax41 qty 1

3R°FLR AHU19 York Mod#xti-030x045-daha017a Ser# cmvmxto 1 06 Filters 16x20x2 qty 1 16x20x12 qty 1 20x20x2 qty 2 20x20x12 qty 1 Belt size bx36 qty 1

Danfoss freq Drives Mod-Vlt qty 2

Fan Coil Units Trane 400cfm qty 52 Trane 300cfm qty 3 York 400cfm qty 1 06 York 2000cfm qty 1 Trane 1 OOOcfm qty 2 York 1 OOOcfm qty 4 York 3 OOcfm qty 5

BUILDING 3406- Billeting East Wing 2 Story AHU6 York Mod#xti-033x045-daha0 17a Ser#cgsmxt03 3 3 Filters 12x24x2 qty 1 12x24x12 qty 1 24x24x2 qty1 24x24x12 qty 1 Belt#bx34 qty 1

Boiler b4 Lochivar copperfin2 2stage Mod#chl50 1 Ser#j07h00202078

Page 6 of 15

Page 26: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Filter 12x12xl qty 1

Hot water pumps P9a mod#v1.5a7a-cc Ser#hvac-c066031-05 Gpm44 P9b Mod#v1.5a7a-cc Ser#hvac-c066031-06 Gpm 44

Danfoss freq drive Mod-vlt-6000 qty 2 Fan Coil Units York 400cfm qty 144 1000 cfm qty 15 300 cfm qty 5

BUILDING 3406 - Mid Section AHU 1 Mod#xti-036x048-faja017a Ser# cermxt0196 Filters 12x24x2 qty 1 12x24x12 qty 1 24x24x2 qty 1 24x24x 12 qty 1 Belt#6a149g qty 1

Cold water pumps P4a Mod#v5b9a-cc Ser#hvac-c067085-0 1 Gpm 420 P4b Mod#v5b9a-cc Ser#hvac-c060785 Gpm420

BUILDING 3406 - East Wing 2"d FLR AHU7 mod#xti-033x054-daha017a Ser#cgsmxt0093 Filters 20x24x2 qty1 20x24x12 qty 1 24x24x2 qtyl 24x24x12 qty1 Belt# bx3 8 qty 1

3rd Floor East Wing AHU8 Mod# xti-030x045-daha017a

Page 7 of 15

Page 27: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Ser#cgsmxt0094 Filters 16x20x2 qty 1 16x20xl2 qty 1 20x20x2 qty 1 20x20xl2 qty 1 Belt# bx36 qty 1

BUILDING 3414 Chiller Chi York Mod#yrtatbt0-46c Ser#sfrm-218070 Chill water pump 1 a Balder frame 213jm /7.5hp-400gpm s/n fD605183375 Patterson pump p 1 b cond us mtr Mod#g29316 20hp Frame 256jm Type-ute-4 Patterson pump mod# v5a11a-cc s/n hvac-co57477-10 600gpm

Ch2 York Mod#yrtatat0-46c Ser#sgsm-615460 Chill pump p2b Weg mtr mod#00718053e213jm 7.5 hp Frame 213jm Patterson pump P2b cond weg mtr Frame 256jm,20hp,mod#020 180s3e256jm Patterson pump mod#v5alla-cc 600gpm s/n hvac-2066031-02

Ch3 Trane Mod# rthd-uc 1 f-xhou-ad6a-2lal-e5a2-lala-xxqx-exab-bxy2-12dj-xa52-xxrx-xx Ser#u08m02753

Chill pump 3a us mtr mod#g74268 Frame 213jm Type-ute-4,7.5 hp big pump

Cond pump 3b b/g pump s/n laf043-h80 600 gpm

Max wp 175 Us mtr 20hp, mod#b050 Frame 256jp Type-ute-1

Flow meters incoming Onocon Mod#fl21 0 12in pipe,0-5 vdc, 0-2800gpm,mcu code 1428

Page 8 of 15

Page 28: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Type flow 320 gpm s/nl49624 freq mr output 2.459

Chiller flow mtr Onocon s/n 149623 12in pipe 0-5 vdc 0-2800 gpm

Mcu code 1425 Type flow 400 gpm Freq output mtr factor 2.454 ppg

Secondary Pumps Patterson pumps 800 gpm P3a/b Baldor mtrs 25hp Frame 284jm Cat#jmm41 03t 1760 rpm 230/460 volts

P3c weg mtr 25hp Frame 284jm 230/460 volts Mod#025180t3284jm

BUILDING 3406- Mid Section Boiler lochivar powerfin 1 stage Mod#pbl1 00 1-m9 Ser#j ObhOO 191721 Filter 11.5xll.5xl qtyl

Hot water pumps P5a Patterson Mod#v2c7a-cc Ser#hvac-cO 57 4 77-04 Gpm 65 P5b Mod# v2c7a-cc Ser#hvac-057477-05 Gpm65

Mid Section 2"d Floor Mech Room AHU2 Mod#xti-036x048-faja017a Ser#cerm-xt0197 Filters 12x24x2 qty 1 12x24x12 qty 1 24x24x2 qty 1

Page 9 of 15

Page 29: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

24x24x12 qty1 Belt#6al50g qty I

West Wing Mid Section 1st Floor AHU5 Mod#xti-033x051-daja017a Ser#cgsm xt0332 Filters 20x24x2 qty 2 20x24x12 qty 2 Belt#ax34 qty 1

Boiler b3 copperfin2 4 stage Mod#chl0991 Ser#i07h00202097 Filter 15.5xl5.5xl qtyl

Hot water pumps P8a mod#v2c7a-cc Ser#hvac-c066031-03 Gpm84 P8b mod#v2c7a-cc Ser#hvac-c066031-04 Gpm84

BUILDING 3408- Education Mech Room AHU3 Mod#xti-054x102-fama017a Ser#cermxtO 198 Filters 20x20x2 qty2 20x20x12 qty 2 20x24x2 qty 6 20x24x 12 qty 6 Belt# 6a128g qty2

AHU4 Mod#xti-054x090-fama017a Ser#cerm-xt0199 Filters 20x20x2 qty4 20x20xl2 qty 4 20x24x2 qty4 20x24xl2 qty4 Belt# la097g qty 2

Boiler b2 Lochivar powerfin 1 stage Mod#pbl0751-m9 Serial #j06h00191698 Filter 11.5xll.5xl qty 1

Page 10 of 15

Page 30: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Hot Water pumps P7a Mod#v2c7a-cc Ser#hvac-cO 57 4 77-09 Gpm65 p7b mod#v2c7a-cc Ser#hvac-c057 4 77-01 Gpm65 Cold water pumps P6a Mod#v2c7a-cc Ser#hvac-cO 57 4 77-06 Gpm 155 P6b Mod#v2c7a-cc Ser#hvac-c057 4 77-07 Gpm155

Danfoss Freq Drives Mod-Vlt-600 qty 6

BUILDING 3414- Chiller Plant

Chiller #4 York Screw Chiller Mod# yrtatbto-46c Ser# sawm-461920 R 134a freon 560lbs

Chill Water Pump Bell & Gossett 400 gpm Ser# co95141-02k90

Emerson Motor 7.5 Hp Mod# g74268 Frame-213jm Type ute-4 Id# N1 0-074268-M

Cooling Tower Pump Bell & Gossett 600 gpm Ser# co65142-010-290

Emerson Motor 20hp Mod# 08699397-100 Frame-256jp Type-ute-1 Id#P118699397-0001-M0002

Chiller #5 York Screw Chiller Mod# Yrtatbto-46c Ser#Sawm-461920 R134a Freon 560 Lbs

-------

Page 11 of 15

Page 31: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Chill Water Pump Bell & Gossett 400gpm Ser#C095141-0 I k90

Emerson Motor 7.5 Hp Mod#G74268 Frame-213jm Type-ute-4 ld#P0973818680063lm0006

Cooling Tower Pump Bell & Gossett 600gpm Ser#C095142-02190

Emerson Motor 20hp Mod#08699397-100 Frame256jp Type-ute-1

COOLING TOWER INFO

Tower#1 Evapco Model#at112-312 Ser#5-282998 Belt#6b-136

Tower#2 Evapco Model#at112-312 Ser#6-302338 Belt#6b-136

Tower#3 Evapco Mod#atl12-312 Ser#8-340132 Belt#6b-136

Danfoss Freq Drives qty 6

Mitsubishi Mini Split Units qty 2

BUILDING 3412 American Standard 5 ton Units qty 3

Mitsubishi mini split Unit in weapons Vault qty 1

AIR HANDLER UNIT BELT SIZES

AHUl AHU2 AHU3 AHU4 AHU5

6Al49G 6A150G 6A128G 1A097G AX34

qty 1 qty 1 qty 2 qty 2 qty 1

Page 12 of 15

Page 32: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

AHU6 AHU7 AHU8 AHU9 AHU10 AHU11 AHU12 AHU14 AHU15 AHU16 AHU17 AHU18 AHU19 AHU20 AHU21 AHU23

BX34 BX38 BX36 BX46 BX44 5VX510 5VX510 AX59 AX38 AX41 AX59 AX41 BX36 5VX710 5VX860 BX50

qty 1 qty I qty I qty 2 qty 1 qty 2 qty 2 qty I qty I qty I qty 1 qty 1 qty I qty 2 qty I qty 3

566 Filters Required for one (1) complete change- See Sizes and Quantities in Table Below:

Item Filter Size Quantity Item Filter Size Quantity No. No. 1 20x20x2 55 13 12xi2x1 3 2 20x24x2 27 14 15.5x15.5x1 I 3 I2x24x2 7 15 20x20xi 2 4 24x24x2 I6 16 20x2Ix1 1 5 16x20x2 6 17 IOx22xi 12 6 20x25x2 8 18 12.5x24.5x 1 250 7 20x20x6 55 19 20.5x29.5x1 I2 8 20x24x6 27 20 28.5x29.5x4 I 9 12x24x6 7 21 I6x25x1 2

10 24x24x6 I6 22 8x24x1 3 11 16x20x6 6 23 20x22x2 I 12 Il.5xi5.5xi 2 24 I3.5x24.5xi 52

Page 13 of 15

Page 33: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

SERVICE SHALL BE PROVIDED IN ACCORDANCE WITH THE MANUFACTURERS' RECOMMENDED SERVICE SCHEDULES TO INCLUDE THE FOLLOWING:

Evapco Cooling Towers Clean pan strainer, flush pan, check bleed valve operation, check/adjust float level, check drift eliminators, check water distribution system and spray pattern, check fan blades for cracks, vibration and missing balance weights, lubricate fan shaft bearings, fan motor bearings, adjust belt tension replace belt if necessary, pressure wash air inlet louvers and fill material on both sides clean scale throughout system inspect/grease sliding motor base, replace gear reducer oil, coupling /shaft inspect flex elements and hardware for tightness, proper torque & crack deterioration, inspect heater controller and clean probe ends, inspect junction box for loose wiring and moisture, inspect elements for scale buildup, inspect and clean protective finish.

Trane/Y ork Rotary Screw Chillers Meg and record motor winding resistance, check oil level in the compressor; adding oil as required, conduct an oil acidity test, conduct a refrigerant leak test correcting any leaks; add refrigerant as required, changing filter drier, tighten the power wiring and contactors in the motor terminal box, clean all contactors and recommend replacement if applicable, check all relays operating controls and safeties, unloader and external interlocks, check the suction and discharge compressor valves, brush condenser barrel tubes and starter heat exchanger tube, provide oil analysis, change solid state starter coolant, check flow switch operation, take and record water side pressure drops across vessels, check oil sump heater operation, check operation of electronic expansion valve, clean condenser water strainers, check head pressure control operation for tower fans or bypass valve, check minimum condenser water temperature operation, replace oil filter ,run Eddy current test, provide service report stating existing conditions and any repair modifications required wipe down chillers reinstall insulation jackets if removed during work.

Trane/Y ork Air Handler Units Inspect and clean the fan wheels and fan shaft, inspect and clean drain pipes, check damper linkage, set screws, and blade adjustment. Clean, but do not lubricate, the nylon damper rod bushings, clean damper operators, inspect electrical components and insulation, inspect wiring for damage, rotate the fan wheel and check for obstructions in the fan housing, lubricate motor bearings, check condition of gasketing and insulation around unit, door and dampers, examine flex connections for cracks or leaks. Repair or replace damaged material, clean inline strainer baskets and clean the coils replace primary air filters on a quarterly basis using pleated filters minimum merv 8 and secondary filters on an annual basis, check and adjust/replace belts

Fulton Pulse Boilers Change the spark plug, clean and replace flapper valve gaskets, verify proper combustion and adjust as necessary, lubricate the modulation motor arms, gas and exhaust butterfly valves. Ensure the motion of the valves is smooth, remove the low water cut off probe and clean. Replace the probe in the boiler, replace the flame rod, inspect the air intake and exhaust vent pipes for broken seals at the joints, inspect the screens on the air intake and exhaust vent terminal and make sure they are free of dirt or any foreign matter which may block the terminals, check the air intake and exhaust vent outlet for any blockage or restrictions, check for any leaks in exhaust piping.

Page 14 of 15

Page 34: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Lochivar Copper Fin/Power Fin Boilers Inspect the water pump and oil as necessary use SAE 30 non-detergent oil, replace igniter, remove burners and clean replace gaskets, remove heat exchanger and clean, inspect all electrical connections, inspect the intake and exhaust vent piping tighten if necessary, check and clean combustion fan, start u and check flame pattern.

York/Trane Fan Coil Units Clean coils, clean motor/blower assembly, clean drain line, inspect electrical connections and wiring for damage and tightness, inspect hot/cold water valves operation replace air filter on a quarterly basis using a pleated merv 7 filter

HV AC Controls 2 Monthly 8 hour visits go over system correct any problems found, calibrate sensors throughout system a minimum of one time annually or more if deemed necessary, supply all repair parts needed during the life of the contract.

HV AC System Water Treatment Monthly visits for open loop (cooling towers) and quarterly visits for both closed loop systems vendor to supply all chemicals and test kit for both loops for the customer as part of contract.

Page 15 of 15

Page 35: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

>- >-lo...

.1?: ...c Q) .j.J .j.J

lo... c: lo...

Sample ro 0 ro

Q) :::J >- ~ cJ

Comprehensives

Contact customer representative for performance issues X Check starter and contactor X X Check and tighten electrical connections X Inspect pilot and safeties (as applicable) X X Check flame quality X Check coil conditions X Check filter condition X

Check and clean condensate pan and drain If accessible X X Check safety control set points X Check damper operation and lubricate as required X X Change belt(s) X Check valve(s) X Check and lubricate fan and motor bearings X Check for proper fan rotation X Check condition of blower assembly X ll,;necK ror unusual no1ses, v1orat1on ana wear Keport recommendations X X Check overall condition of unit X Clean area around equipment X Complete any required maintenance checklists, report observations to

X X appropriate customer representative

Ope rationals Complete any required maintenance checklists, report observations to

X X appropriate customer representative

Clean area around equipment X Check overall condition of unit X X lvnecK ror unusual no1ses, v1oraoon ana wear Kepon: recommendations X Check fan operation X X Visually Inspect damper(s) X Check filter condition X

1 ~.;necK w1m appropnate customer represemar1ve ror operaoona1 deficiencies X

Exhibit II-Sample Service Sheet

Page 1 of 4

Page 36: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Check belt(s) (if applicable) X Check coil conditions X Secure and check all electrical connectors X X Inspect fan wheel for free movement, excessive play and debris X

Confirm that all mounting hardware is tight

Clean and Paint corroded areas as necessary

Check condensate pan and drain If accessible X Filters, Misc.

Dispose of dirty filter appropriately

Turn equipment on

Install new filters

Remove dirty filters

Turn equipment off

Lubricate & inspect fan bearings.

Replace air filters per agreement

1~.,;necK w1tn appropnate customer representative ror operational deficiencies

appropriate customer representative

Exhibit II-Sample Service Sheet

Page 2 of 4

Page 37: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

liljjQIJ Operation and Maintenance Instructions

MAINTENANCE CHECKLIST

PROCEDURE JAN FEB MAR APR

1. Clean pan strainer - monthly or as needed

2. Clean and flush pan** - quarterly or as needed

3. Check bleed-off valve to make sure it is operative - monthly

4. Check operating level in pan and adjust float valve if necessary - monthly

5. Check water distribution system and spray pattern - monthly

6. Check drift eliminators - quarterly

7. Check the fan blades for cracks, missing balancing weights, and vibrations - quarterly

8. Check sheaves and bushings for corrosion. Scrape and coat with ZRC • annually

9. Lubricate fan shaft bearings* -every 1000 hours of operation or every three months

10. Check belt tension and adjust - monthly

11. Sliding motor base - Inspect and grease -annually or as needed

12. Check fan screens, inlet louvers and fans. Remove any dirt or debris - monthly

13. Inspect and clean protective finish- annually - Galvanized: scrape and coat with ZRC - Stainless: clean and polish with a stainless steel cleaner.

14. Check water quality for biological contamination. Clean unit as needed and contact a water treatment company for recommended water treatment program** - regularly

OPTIONAL ACCESSORIES:

1. Gear Reducer- Check oil level with unit stopped - 24 hours after start-up & monthly

2. Gear Reducer/Piping - Do visual inspection for oil leaks, auditory inspection for unusual noises and vibrations - monthly

3. Gear Reducer • Replace oil - semi-annually

4. Oil Pump - Do visual inspection for leaks and proper wiring - monthly

5. Gear Reducer/Coupling - Check alignment of the system - 24 hours after start-up & monthly

6. Coupling/Shaft - Inspect flex elements and hardware for tightness, proper torque & crack/deterioration - monthly

7. Heater Controller - Inspect controller and clean probe ends - quarterly

• See maintenance manual for start-up instructions and lubrication recommendations.

MAY JUN JUL

" Cooling Towers must be cleaned on a regular basis to prevent the growth of bacteria including Legionella Pneumophila.

AUG SEP OCT NOV DEC

J

Exhibit II-Sample Service Sheet

Page 3 of 4

Page 38: Exhibit II - Florida · Exhibit II Equipment Lists & Sample Service Sheets Site 1 - CBJTC Post Headquarters: 5 pages ... Monthly Service Required for Cooling Tower 3DJH RI M# A111-91T

Operation and Maintenance Instructions ll!iii!i;lliiAf

MAINTENANCE CHECKLIST (continued)

OPTIONAL ACCESSORIES: JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC

8. Heater- Inspect junction box for loose wiring and moisture - one month after start-up and semi-annually

9. Heater - Inspect elements for scale build-up - quarterly

10. Electronic Water Level Controller - Inspect junction box for loose wiring and moisture -semi-annually

11. Electronic Water Level Controller - Clean probe ends of scale build-up - quarterly

12. Electronic Water Level Controller -Clean inside the standpipe - annually

13. Solenoid Make-up Valve - Inspect and clean valve of debris - as needed

14. Vibration Switch (mechanical)- Inspect enclosure for loose wiring and moisture -one month after start-up and monthly

15. Vibration Switch - Adjust the sensitivity -during start-up and annually

16. Sump Sweeper Piping - Inspect and clean piping of debris - semi-annually

17. Water Level Indicator -Inspect and clean-annually

, DURING IDLE PERIODS:

1. TWo or More Days: Energize motor space heaters -or run motors for 10 minutes twice dally

2. Few Weeks: Run gear reducer for 5 minutes -weekly

3. Several Weeks: Completely fill gear reducer with oil. Drain to normal level prior to running.

4. One Month or longer: Rotate motor shaMan 1 0 turns - bi-weekly

5. One Month or longer: Megger test motor windings - semi-annually

Seasonal Shut-Down Checklist When the system is to be shut down for an extended period of time, the following services should be performed.

1. The evaporative cooling unit cold water basin should be drained. 2. The cold water basin should be flushed and cleaned with the suction strainer screens in place. 3. The suction strainer screens should be cleaned and reinstalled. 4. The cold water basin drain should be left open. 5. The fan shaft bearings and motor base adjusting screws should be lubricated. This should also be performed if the unit is

going to sit idle prior to start up. 6. The water make up valve needs to be closed. All water make-up, overflow and drain piping needs to be drained, if not heat

traced and insulated. 7. The finish of the unit should be inspected. Clean and refinish as required. 8. The fan bearings and motor bearings need to be turned at least once a month by hand. This can be accomplished by

making sure the unit's disconnect is locked and tagged out, and grasping the fan assembly, rotating it several turns. 9. Energize motor space heaters.

See Fan & Pump Manufacturer Maintenance and long term storage Instructions for more detailed Instructions.

Exhibit II-Sample Service Sheet

Page 4 of 4