exergetic optimization of a solar photovoltaic thermal (pv/t) air collector
TRANSCRIPT
INTERNATIONAL JOURNAL OF ENERGY RESEARCH
Int. J. Energy Res. 2011; 35:813–827
Published online 16 June 2010 in Wiley Online Library (wileyonlinelibrary.com). DOI: 10.1002/er.1727
SHORT COMMUNICATION
Exergetic optimization of a solar photovoltaic thermal(PV/T) air collector
F. Sarhaddi�,y, S. Farahat, H. Ajam and A. Behzadmehr
Department of Mechanical Engineering, Shahid Nikbakht Faculty of Engineering, University of Sistan & Baluchestan, Zahedan
98164-161, Iran
SUMMARY
In this paper, an exergetic optimization has been developed to determine the optimal performance and designparameters of a solar photovoltaic thermal (PV/T) air collector. A detailed energy and exergy analysis has beencarried out to calculate the thermal and electrical parameters, exergy components, and exergy efficiency of a typicalPV/T air collector. The thermal and electrical parameters of a PV/T air collector include solar cell temperature,back surface temperature, outlet air temperature, open-circuit voltage, short-circuit current, maximum power pointvoltage, maximum power point current, etc. An improved electrical model has been used to estimate the electricalparameters of a PV/T air collector. Furthermore, a new equation for the exergy efficiency of a PV/T air collectorhas been derived in terms of design and climatic parameters. A computer simulation program has been alsodeveloped to calculate the thermal and electrical parameters of a PV/T air collector. The results of numericalsimulation are in good agreement with the experimental measurements noted in the previous literature. Moreover,the simulation results obtained in this paper are more precise than the one given by the previous literature, and thenew exergy efficiency obtained in this paper is in good agreement with the one given by the previous literature.Finally, exergetic optimization has been carried out under given climatic, operating, and design parameters. Theoptimized values of inlet air velocity, duct length, and the maximum exergy efficiency have been found. Parametricstudies have been also carried out. Copyright r 2010 John Wiley & Sons, Ltd.
KEY WORDS
exergy efficiency; exergetic optimization; solar photovoltaic thermal (PV/T) air collector
Correspondence
*F. Sarhaddi, Department of Mechanical Engineering, Shahid Nikbakht Faculty of Engineering, University of Sistan & Baluchestan,
Zahedan 98164-161, Iran.yE-mail: [email protected]
Received 30 September 2009; Revised 21 April 2010; Accepted 22 April 2010
1. INTRODUCTION
A solar photovoltaic thermal (PV/T) collector is a non-
adiabatic radiative heat exchanger. It receives solar
radiation energy and produces thermal and electrical
energy simultaneously. PV/T air collector systems can
be used for various applications, such as solar PV/T
dryers, PV/T greenhouses, building integrated photo-
voltaic thermal (BIPVT) systems, PV/T hybrid active
solar stills, PV/T solar water-heating systems, etc.
The energy payback time (EPBT) of a PV/T air
collector lies between 10 and 15 years depending on the
insulation and the performance of it. If the perfor-
mance of a PV/T air collector can be increased, the
energy payback time can be reduced. Therefore, the
optimized performance evaluation of a PV/T air
collector is important. The performance of a PV/T air
collector can be evaluated in terms of energy analysis
or exergy analysis.
Some deficiencies of energy analysis are mentioned
in References [1,2]. Exergy data are more practical
and realistic in comparison with the respective
energy values [1,2]. Thus, exergy analysis usually pro-
vides a more realistic view of process than energy
analysis.
A significant amount of theoretical as well as
experimental studies on the energy or exergy perfor-
mance evaluation of PV/T collector systems has been
carried out in the last 35 years.
Wolf [3] as early as in the 1970s has presented the
main concept of PV/T collector with the use of either
water or air as the coolant.
Copyright r 2010 John Wiley & Sons, Ltd.
Fujisawa and Tani [4] have compared the annual
performance of a flat-plate solar water-heating col-
lector, a PV module, a single-glazed PV/T collector
with mono-crystalline silicon solar cells, and an
unglazed one. The energetic evaluation of the
measured data showed that the single-glazed PV/T
collector is the best. In terms of exergy analysis,
unglazed PV/T collector gives the best performance.
The relations between energy and exergy, energy and
sustainable development, energy policy making, exergy
and the environment and exergy in detail have been
reported by Dincer [5].
Saitoh et al. [6] have compared the energy and
exergy efficiency of a brine-cooled PV/T collector with
a PV panel and a solar collector in Hokkaido (in
northern Japan) and given similar equations as taken
from Fujisawa and Tani [4].
Sahin et al. [7] have carried out the exergy analysis of
a PV array based on chemical potential components.
They have also obtained exergy components and PV
array exergy efficiency. Finally, they have compared
energy, electrical, exergy efficiencies under given cli-
matic and operating conditions.
Joshi and Tiwari [8] have carried out the energy and
exergy analysis of a PV/T parallel-plate air collector
for the cold climate region of India (in Srinagar). They
have reported that the instantaneous energy and
exergy efficiency of a PV/T air collector varies between
55–65% and 12–15%, respectively.
Badescu [9] has proposed an optimal operation
strategy for exergy gain maximization in open loop
thermal solar energy collection systems and
investigated the exergetic performance of an open loop
flat-plate solar collector. He has reported that the
maximum exergetic efficiency of the system is low
(usually less than 3%).
Aste et al. [10] have presented the experimental and
theoretical results of a research and development
(R&D) program on the design, development, and
performance monitoring of a PV/T air collector. They
have introduced an innovative technological system for
building integration of hybrid PVT air collectors and
reported the successful commercial application of their
system as a case study.
Nayak and Tiwari [11] have presented the perfor-
mance of a PV-integrated greenhouse system for
New Delhi climatic condition and reported that the
exergy efficiency of the system is 4%.
Raman and Tiwari [12] have compared the energy
and exergy performance of a hybrid photovoltaic
double-pass and single-pass air collector. They have
shown that electrical, thermal, and exergy efficiencies
of double-pass PV/T air collector are higher than sin-
gle-pass PV/T air collector.
Joshi et al. [13] have compared the thermal perfor-
mance of a glass-to-tedlar PV/T air collector and a
glass-to-glass PV/T air collector. Their results have
been shown; a glass-to-glass PV/T air collector has a
better thermal performance than a glass-to-tedlar
PV/T air collector.
Joshi et al. [14] have carried out the performance
analysis of both PV and PV/T system in terms of
exergy efficiency and reported that the thermal energy
due to solar radiation is actually a heat loss to the PV
system where as it is a useful heat for a PV/T system.
They have also shown that the electrical (exergy) effi-
ciency of a PV system can be improved if the heat can
be removed from the PV surface.
Dubey et al. [15] have evaluated the energetic and
exergetic performance of a PV/T air collector with air
duct above the absorber plate and the one with air duct
below the absorber plate. They have investigated the
effect of design and operating parameters and four
weather conditions on the performance of above-
mentioned PV/T air collectors for five different cities of
India and found that the latter one gives better results
in terms of thermal energy, electrical energy, and
exergy gain.
Tiwari et al. [16] have carried out the energy and
exergy analysis of an integrated photovoltaic thermal
solar (IPVTS) water heater. They have reported that
the overall exergy and thermal efficiency of an IPVTS
system are maximum at the hot water withdrawal flow
rate of 0.006 kg s�1.
Sarhaddi et al. [17] have optimized a PV array based
on exergy analysis and given useful results.
Sarhaddi et al. [18] have investigated the thermal
and electrical performance of a PV/T air collector
using an improved thermal and electrical model.
In the previous studies [3–18], the exergetic optimi-
zation of solar PV/T collector systems has not been
carried out.
In this paper, an exergetic optimization of a PV/T
air collector will be developed. A detailed energy and
exergy analysis will be carried out to calculate the
thermal and electrical parameters, exergy components,
and exergy efficiency of a typical PV/T air collector.
The thermal and electrical parameters of a PV/T air
collector include solar cell temperature, back surface
temperature, outlet air temperature, open-circuit vol-
tage, short-circuit current, maximum power point
voltage, maximum power point current, etc. Some
corrections will be carried out on heat loss coefficients.
An improved electrical model will be used to estimate
the electrical parameters of a PV/T air collector, such
as open-circuit voltage, short-circuit current, max-
imum power point voltage, maximum power point
current, etc. Furthermore, a new equation for the
exergy efficiency of a PV/T air collector will be derived
in terms of design and climatic parameters. A com-
puter simulation program will be developed to predict
the thermal and electrical parameters of a PV/T air
collector. Finally, the exergetic optimization of a PV/T
air collector will be carried out; also, the effect of cli-
matic, design, and operating parameters on exergy
efficiency will be studied.
Exergetic optimization of a solar PV/T air collectorF. Sarhaddi et al.
Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
814
The exergy efficiency of a PV/T air collector is
parametrically dependent on its energy analysis.
Hence, first, the energy analysis of a PV/T air collector
will be carried out. Then, the exergy components and
exergy efficiency of a PV/T air collector will be com-
puted and optimized.
2. ENERGY ANALYSIS
2.1. Thermal analysis
The proof of governing equations on PV/T air
collector thermal analysis is not included in order to
have a brief note. More details of governing equations
derivation are found in References [8,11–13,15,16,18].
Figure 1 shows the equivalent thermal resistant cir-
cuit of a PV/T air collector [18].
Writing the energy balance equation for each com-
ponent of a PV/T air collector gives the thermal
parameters and thermal efficiency of a PV/T air col-
lector as follows:
Tcell ¼ ½ðatÞeffG1UtTamb1UTTbs�=ðUt1UTÞ; ð1Þ
Tbs ¼ ½hp1ðatÞeffG1UtTTamb1hfTf ��ðUtT1hf Þ; ð2Þ
Tf ;out ¼ ðTamb þ hp1hp2ðatÞeffG=ULÞ
� ½1� expð�WULL= _mCpÞÞ�
1Tf ;in expð�WULL=ð _mCpÞÞ; ð3Þ
�Tf ¼1
L
Z L
x¼0Tf ðxÞdx
¼ ½Tamb1hp1hp2ðatÞeffG=UL�
� ½1�½1�expð�WULL=ð _mCpÞÞ�=ðWULL=ð _mCpÞÞ�
1Tf ;in½1�expð�WULL=ð _mCpÞÞ�=ðWULL=ð _mCpÞÞ;
ð4Þ
_Qu ¼ _mCpðTf ;out � Tf ;inÞ
¼ ð _mCp=ULÞ½hp1hp2ðatÞeffG�ULðTf ;in � TambÞ�
� ½1� expð�WULL=ð _mCpÞÞ�; ð5Þ
Zth ¼ _Qu=ðWLGÞ
¼ ð _mCp=WLULÞ½hp1hp2ðatÞeff �ULðTf ;in � TambÞ=G�
� ½1� expð�WULL=ð _mCpÞÞ�; ð6Þ
where Tcell, Tbs, Tamb, Tf,out, �Tf , _Qu, G, _m, Cp, L, W,
and Zth are solar cell temperature, back surface tem-
perature, ambient temperature, outlet air temperature,
average air temperature in flow duct, the rate of useful
thermal energy, solar radiation intensity, the mass flow
rate of flowing air, the heat capacity of flowing air, the
length of air duct, the width of air duct, and PV/T air
collector thermal efficiency, respectively. In the above
equations, the related heat transfer coefficients are
defined as follows [18]:
ðatÞeff ¼ tg½acbc1aTð1� bcÞ � bcZel�; ð7Þ
hp1 ¼ UT=ðUT1UtÞ; ð8Þ
hp2 ¼ hf=ðUtT1hf Þ; ð9Þ
UtT ¼ ½1=Ut11=UT��1 ¼ UtUT=ðUT1UtÞ: ð10Þ
Utf ¼ ½1=hf11=UtT��1 ¼ UtThf=ðUtT1hf Þ; ð11Þ
To increase the calculations precision of PV/T air
collector thermal parameters, some corrections have
been carried out on heat loss coefficients in a same
manner of Reference [18]. These corrections are not
mentioned to have a brief note [18].
2.2. Electrical analysis
As the presence of the electrical efficiency of PV
module Zel in Equation (7), the thermal parameters of
PV/T air collector and its electrical parameters are
dependent. The calculation precision of thermal
parameters of a PV/T air collector will be improved
if the electrical efficiency of PV module is calculated in
a precise way.
In the previous studies [3–17], the electrical efficiency
of a PV module has been calculated from the following
equation:
Zel ¼ Zel;ref ½1� 0:0045ðTcell � Tamb;ref Þ�: ð12ÞFigure 1. The equivalent thermal resistant circuit of a PV/T
air collector [18].
Exergetic optimization of a solar PV/T air collector F. Sarhaddi et al.
815Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
The subscript ‘ref’ indicates the value of parameters
at the reference conditions. Equation (12) has some
deficiencies. The deficiencies of Equation (12) are
mentioned in Reference [18].
In this research, the electrical efficiency of a PV
module and its electrical parameters are calculated
from the electrical simulation of a PV module. The
proof of governing equations on PV module electrical
analysis is not included to have a brief note. A PV
module is nonlinear device and can be represented by
its current–voltage (I–V) characteristic curve. Five-
parameter photovoltaic model for I–V characteristic
curve is defined as follows [19]:
I ¼ IL � Io½expððV1IRsÞ=aÞ � 1� � ðV1IRsÞ=Rsh;
ð13Þ
where I and V represent current and voltage at load, a,
IL, Io, Rs, and Rsh are ideality factor, light current,
diode reverse saturation current, series resistance, and
shunt resistance, respectively.
The calculation relations of five parameters a, IL, Io,
Rs, and Rsh at reference conditions (Tcell,ref 5 251C,
Gref 5 1000Wm�2 [20]) or at other climatic and oper-
ating conditions (Gnew, Tcell,new) have been mentioned
in Reference [18]. These relations are not included to
have a brief note.
The electrical efficiency of a PV module can be de-
fined as the ratio of actual electrical output power to
input the rate of solar energy incident on the PV sur-
face as follows [7,8,11–18]:
Zel ¼ VmpImp=S ¼ ðVocIscÞFF=S ¼ Eel=S; ð14Þ
where Voc, Vmp, Isc, Imp, FF, and Eel are open-circuit
voltage, maximum power point voltage, short-circuit
current, maximum power point current, fill factor, and
outlet electrical power, respectively. Furthermore, the
rate of solar energy incident on the PV surface (S) is
given by
S ¼ GNsNmAmod; ð15Þ
where Ns and Nm are the number of strings and the
number of modules in series per string, respectively.
PV module area (Amod) is given by
Amod ¼ L1L2; ð16Þ
where L1 and L2 are the length of PV module and the
width of PV module, respectively.
The overall energy efficiency of a PV/T air collector
can be calculated by adding the thermal efficiency
(Equation (6)) and thermal efficiency equivalent of
electrical efficiency as follows [13,18]:
Zen;ov ¼ Zth1Zel;th ¼ Zth1ðZel=0:36Þ: ð17Þ
In Equation (17), the coefficient 0.36 is the conver-
sion factor of the thermal power plant [13,18].
3. EXERGY ANALYSIS
Exergy analysis is a technique that uses the conserva-
tion of mass and conservation of energy principles
together with the second law of thermodynamics for
the analysis, design, and improvement of energy and
other systems. Exergy is defined as the maximum
amount of work that can be produced by a system or a
flow of mass or energy as it comes to equilibrium with
a reference environment [21].
The general form of exergy balance equation for a
control volume is written as [21,22]:XExinput;net �
XExoutput;net ¼
XExdestroyed; ð18Þ
whereP
Exoutput;net,P
Exinput;net, andP
Exdestroyed are
the net (desired) output exergy from control volume,
the net input exergy to control volume, and exergy
destructions in control volume, respectively.
The exergy efficiency of a PV/T air collector is de-
fined as the ratio of net output exergy to net input
exergy [21,22]:
Zex ¼P
Exoutput;netPExinput;net
¼ 1�P
ExdestroyedPExinput;net
: ð19Þ
According to Equation (19), the exergy efficiency of a
PV/T system can be calculated in terms of the net output
exergy of the system or exergy destructions in the system.
In this research, the exergy efficiency of PV/T system is
evaluated in terms of the net output exergy of the system.
3.1. The exergy destructions in controlvolume
According to the Gouy–Stodola theorem, the exergy
destructions in control volume are equal to the product
of reference environmental temperature to the entropy
generation in control volume [21,22]XExdestroyed ¼ T0
_Sgen; ð20Þ
where T0 and _Sgen are the reference environmental
temperature and the entropy generation in control
volume, respectively. Some relations for exergy
destruction components in solar collectors and PV
systems are reported in References [9,17,21,22]. These
relations are not mentioned to have a brief note.
3.2. The net input exergy of PV/T aircollector
The net input exergy of PV/T air collector includes
solar radiation intensity exergy (ExQ,sun). According to
the Petela theorem, it is given by [1,2]XExinput;net ¼ ExQ;sun
¼ S½1� 4ðTamb=TsunÞ=31ðTamb=TsunÞ4=3�;
ð21Þ
where Tsun is the sun’s temperature in Kelvin.
Exergetic optimization of a solar PV/T air collectorF. Sarhaddi et al.
Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
816
3.3. The net output exergy of PV/T aircollector
It includes thermal exergy and electrical exergy
[8,11,12,14–16]XExoutput;net ¼
XExthermal1
XExelectrical: ð22Þ
The thermal exergy includes the thermal exergy of
PV/T system and the thermal exergy of PV systemXExthermal ¼ Exthermal;PV=T1Exthermal;PV: ð23Þ
The thermal exergy of PV/T system includes the ex-
ergy changes of flowing air in air duct [21,22]
Exthermal;PV=T ¼ _mCp½Tf ;out � Tf ;in � Tamb
� lnðTf ;out=Tf ;inÞ�1 _mRTamb
� lnðPf ;out=Pf ;inÞ; ð24Þ
where R, Pamb, Pf,in, and Pf,out are gas constant,
ambient pressure, agent fluid pressure at entrance and
exit from PV/T air collector, respectively.
The thermal exergy of PV system includes the exergy
changes of initial and final mass in control volume. As
the inlet and outlet mass flow rate to control volume
are equal, there is no accumulation of mass in control
volume; therefore, initial and final mass in control
volume is constant and equal to PV module mass. The
exergy changes of the mass in control volume is defined
as [7,14,17,21,22]
Exthermal;PV ¼ ðmcellCp;cell=DtÞ
½Tcell � Tamb � Tamb lnðTcell=TambÞ�
� ðVocIsc � VmpImpÞTcell=Tsun:
ð25Þ
The first terms on the right hand side of the Equa-
tion (25) indicate physical exergy changes and the
second terms show exergy changes due to the varia-
tions of chemical potential in PV module [7,14], where
mcell and Dt are PV module mass and time interval,
respectively.
The electrical exergy includes only the outlet elec-
trical power of PV module [7,14,17]:XExelectrical ¼ VmpImp ¼ Eel: ð26Þ
3.4. The exergy efficiency of PV/T aircollector
Substituting Equations (21)–(26) into Equation (18)
and considering exergy efficiency definition (Equation
(19)), the exergy efficiency of a PV/T air collector is
obtained:
Zex ¼_mCp½Tf ;out � Tf ;in � Tamb lnðTf ;out=Tf ;inÞ�1 _mRTamb lnðPf ;out=Pf ;inÞ
S½1� 4ðTamb=TsunÞ=31ðTamb=TsunÞ4=3�
1ðmcellCp;cell=DtÞ½Tcell � Tamb � Tamb lnðTcell=TambÞ� � ðVocIsc � VmpImpÞTcell=Tsun1VmpImp
S½1� 4ðTamb=TsunÞ=31Tamb=TsunÞ4=3�
:
Equation (27) is a new equation for the exergy effi-
ciency of a PV/T air collector in terms of thermal, elec-
trical, design parameters, and climatic conditions.
It includes all of the exergy components of a PV/T air
collector. On the other hand, the electrical parameters
appear in this equation directly. In the previous studies
[4,6,8,11,12,15,16], the exergy efficiency of a PV/T air
collector has been calculated from the following equation:
Zex ¼ Zth½1� ðTamb=Tf ;outÞ�1Zel¼ _Qu½1� ðTamb=Tf ;outÞ�=ðWLGÞ
þ Zel;ref ½1� 0:0045ðTcell � Tamb;ref Þ�: ð28Þ
Equation (28) has some deficiencies; first, Equation (28)
does not include the pressure exergy terms of airflow and
the exergy components of chemical potential in PV
module. Second, Equation (28) has a significant error at
low solar radiation intensity. At low solar radiation in-
tensity, it gives PV/T exergy efficiency equal to the elec-
trical efficiency of the reference conditions (ZexEZel,ref50.12). The equivalence of the solar cell and ambient
temperature and the negligible amount of _Qu are the
reasons of this fact.
4. FORMULATION OFOPTIMIZATION PROBLEM
The energy and exergy models presented in the previous
sections have been inserted into a MATLAB computa-
tional program. In this program, most of the climatic,
operating, and design parameters of PV/T air collector
can be variables. The formulation of optimization
problem, considering the quantities Tamb, Tamb,ref, Tcell,ref,
Tf,inETamb, Tsun, G, Gref, Dt, Zel,ref, L1, L2, Amod, W,
Voc,ref, Vmp,ref, Isc,ref, Imp,ref, ac, bc, aT, tg, R, Pf,inEPamb,
Vw, and Nm as constant parameters is given by
Maximize Zex ¼ Equation ð27Þ;
subject to
Equations ð1Þ�ð11Þ; Equations ð13Þ�ð16Þ
and
0:001inp15ms�1;
L1pLp13L1m;
Tcell;Tf ;out;Tbs; �Tf ;Pf ;out; _m;mcell;Cp;Cp;cell; Io;
IL;Rs;Rsh; a; Isc;Voc; Imp;Vmp;S;UL;Ut;
ðatÞeff ; hp1; hp2; hfX0;
Ns;NcX1 and are integer: :
8>>>>>>>>>>>>>>>>>>>>>>>>>><>>>>>>>>>>>>>>>>>>>>>>>>>>:
(27)
Exergetic optimization of a solar PV/T air collector F. Sarhaddi et al.
817Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
where Vin and L are independent parameters and Tcell,
Tf,out, Tbs, �Tf , Pf,out, _m, mcell, Cp, Cp,cell, Io, IL, Rs, Rsh,
a, Isc, Voc, Imp, Vmp, S, UL, Ut, Ns, Nc, (at)eff, hp1, hp2,and hf are dependent parameters in optimization
procedure. The number of constraint equations,
independent optimization parameters, and dependent
optimization parameters are 16, 2, and 26, respectively.
The objective function and its constraint equations are
nonlinear. Therefore, a real-coded genetic algorithm
program has been developed to optimize the objective
function [23].
5. RESULTS AND DISCUSSION
5.1. Experimental validation
The experimental results of Joshi et al. [13] for a PV/T
air collector make it possible to verify the results
obtained by our computer simulation. The measured
data in Reference [13] include the solar radiation
intensity, ambient temperature, inlet and outlet air
temperature, solar cell temperature, back surface
temperature, inlet air velocity, open-circuit voltage,
short-circuit current, and outlet electrical power.
Additional information about the experiment method
and its conditions are found in Reference [13]. The
simulated values of outlet air temperature, solar cell
temperature, back surface temperature, open-circuit
voltage, short-circuit current, outlet electrical power,
thermal efficiency, electrical efficiency, and overall
energy efficiency in this work have been validated by
their corresponding experimental values in Reference
[13]. Further, a comparison between the simulated
values of outlet air temperature, solar cell temperature,
back surface temperature, outlet electrical power,
thermal efficiency, electrical efficiency, and overall
energy efficiency in this work and their corresponding
calculated values in Reference [13] have been carried
out. The experimental and calculated values of the
parameters described above have been obtained from
the figures and tables of Reference [13].
The climatic, operating, and design parameters of
the PV/T air collector during validation process are
described in Table I.
They correspond to the experimental system
described by Joshi et al. [13], except that they did not
report the wind speed observed over the course of their
tests. This affects the convective heat transfer coeffi-
cient between the PV/T air collector surface and the
ambient air.
In Table I, a wind speed of 1m s�1 is assumed to
have a comparison with the experimental data. On the
other hand, additionally performed calculations for
different wind speeds are also reported in the next
section.
To compare the simulated results with the experi-
mental measurements, a root mean square percentage
deviation (RMS) has been evaluated by following
equation [13,19]:
RMS ¼ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiX½100� ðXsim;i � Xexp;iÞ=Xsim;i�2=n;
qð29Þ
where n is the number of the experiments carried
out.
The variations of solar radiation intensity, ambient
temperature, inlet air temperature, and inlet air velo-
city during the test day are shown in Figure 2.
The simulated values of outlet air temperature, solar
cell temperature, back surface temperature and the
corresponding experimentally measured data during
the test day are shown in Figure 3.
The calculated values of these parameters presented
by Joshi et al. [13] are also shown in the same figure for
comparison. In this figure, the subscript ‘sim’ indicates
Table I. The values of climatic, operating, and design para-
meters during validation process, optimization procedure, and
parametric studies of PV/T air collector [13,18,20].
Solar PV/T air collector parameters Value
PV module type Siemens SP75,
monocrystalline silicon
The length of PV module, L1 1.2 m
The width of PV module, L2 0.527 m
The number of modules in
series per string, Nm
1
The number of strings, Ns 2
The short-circuit current at
the reference conditions, Isc,ref
Ns� 4.8 A
(for total PV array)
The open-circuit voltage at
the reference conditions, Voc,ref
Nm� 21.7 V
(for total PV array)
The maximum power point current
at the reference conditions, Imp,ref
Ns� 4.4 A
(for total PV array)
The maximum power point voltage
at the reference conditions, Vmp,ref
Nm� 17 V
(for total PV array)
The solar radiation intensity at
the reference conditions, Gref
1000 W m�2
The ambient temperature at
reference conditions, Tamb,ref
298.15 K
The solar cell temperature at
reference conditions, Tcell,ref
298.15 K
The electrical efficiency at
the reference conditions, Zel,ref
0.12
The sun temperature, Tsun 5760 K
The current temperature coefficient, a 2.06 mA 1C�1
The voltage temperature coefficient, b �0.077 V 1C�1
The transmitivity of glass cover tg 0.95
The absorptivity of solar cell, ac 0.85
The absorptivity of tedlar, aT 0.5
The length of air duct, L 1.2 m
The width of PV/T air collector, W 0.45 m
The packing factor of solar cell, bc 0.83
The wind speed, Vw 1 m s�1
The time interval, Dt 3600 s
The ambient pressure, Pamb 101 kPa
Exergetic optimization of a solar PV/T air collectorF. Sarhaddi et al.
Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
818
Figure 2. The variations of solar radiation intensity, ambient temperature, inlet air temperature, and inlet air velocity during the test day [13].
Figure 3. The simulated and calculated values of outlet air temperature, solar cell temperature, back surface temperature, and the
corresponding experimentally measured data during the test day.
Exergetic optimization of a solar PV/T air collector F. Sarhaddi et al.
819Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
the simulated values of parameters in this work and the
subscript ‘cal’ shows the calculated values of para-
meters by Joshi et al. [13]. According to this figure, it is
observed that there is a good agreement between the
experimental and simulated values of these parameters.
Further, the RMS percentage deviation of these
parameters are 2.37, 12.58, and 8.63%, respectively.
The RMS percentage deviation of these parameters
reported by Joshi et al. [13] are 4.75, 16.38, and
14.99%, respectively. It is observed from the figure that
our simulated results are more precise than the calcu-
lated results of Reference [13].
The simulated and experimental values of open-cir-
cuit voltage and short-circuit current during the test
day are shown in Figure 4.
The values of RMS percentage deviation are 2.24
and 13.25%, respectively. It is observed from the figure
that there is a good agreement between the simulated
and experimental values of these parameters. The
electrical model used in Reference [13] (Equation (12))
cannot estimate open-circuit voltage and short-circuit
current.
Figure 5 shows the simulated values of maximum
power point voltage, maximum power point current,
and the experimental and simulated values of electrical
power during the test day.
The experimental values of maximum power point
voltage and maximum power point current are not
mentioned in Reference [13]. Furthermore, the elec-
trical model used in Reference [13] (Equation (12))
cannot estimate the electrical parameters of PV/T air
collector. However, the electrical model used in this
work is able to predicate the electrical parameters.
The experimental and simulated values of outlet
electrical power and the calculated values of outlet
electrical power presented by Joshi et al. [13] during the
test day are shown in the same figure. The respective
values of RMS percentage deviation are 5.3 and
11.05%, respectively. It is observed that there is a good
agreement between the simulated and experimental
values of outlet electrical power. Further, it is observed
that the simulated values of outlet electrical power in
this work are more precise than the calculated values of
electrical power presented by Joshi et al. [13].
Figure 6 shows the experimental and simulated
values of overall energy efficiency, thermal efficiency,
and electrical efficiency during the test day.
The calculated values of these efficiencies presented
by Joshi et al. [13] are also shown in the same figure for
comparison. According to this figure, it is observed
that there is a good agreement between the experi-
mental and simulated values of these efficiencies.
Further, the RMS percentage deviations of these effi-
ciencies are 5.51, 24.42, and 5.32%, respectively. The
RMS percentage deviations of these efficiencies
reported by Joshi et al. [13] are 9.81, 28.56, and
11.02%, respectively. It is observed that our simulated
results are more precise than the calculated results of
Reference [13].
The simulated and experimental values of exergetic
efficiency described by Equations (27) and (28) during
the test day are shown in Figure 7.
Figure 4. The simulated and experimental values of open-circuit voltage and short-circuit current during the test day.
Exergetic optimization of a solar PV/T air collectorF. Sarhaddi et al.
Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
820
Figure 5. The simulated values of maximum power point voltage, maximum power point current, and the simulated and
experimental values of electrical power during the test day.
Figure 6. The experimental and simulated values of overall energy efficiency, thermal efficiency, and electrical efficiency during the test day.
Exergetic optimization of a solar PV/T air collector F. Sarhaddi et al.
821Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
The respective values of RMS percentage deviation
are 5.15 and 5.57%, respectively. It is observed from
the figure that there is a good agreement between the
simulated and experimental values of the exergetic
efficiency described by Equations (27) and (28).
A comparison between the experimental values of
exergetic efficiency given in Equation (27) and the
one given by Equation (28) is also carried out in
the same figure. It is clear from the figure that there
is a good agreement between these two exergy
efficiencies with a RMS of percentage deviation
(RMS)5 2.36%.
According to Figures 6 and 7, it is observed that the
behavior of exergy efficiency with respect to the var-
iations of climatic, operating, and design parameters is
so similar to the electrical efficiency of PV/T air col-
lector. The exergy shows the quality of energy. The
quality of thermal energy (thermal exergy) in a PV/T
air collector is low (Zex,thp2%); therefore, the exergy
efficiency value of a PV/T air collector is near to its
electrical efficiency value (ZexEZelE11%).
The good agreement between experiment and
simulation that are shown in the previous figures
(Figures 3–7) indicates that the assumption of a wind
speed as 1m s�1 in the calculations is reasonable.
The simulated parameters errors compared with
those obtained by the experimental measurement is
explained as follows:
� the temperature coefficients of current and voltage
have been assumed constant. In practical cases, they
have slight fluctuation due to the solar radiation
intensity and PV module temperature variations;
� the experimental and calculated results of
Reference [13] have been obtained from the
figures of Reference [13] by interpolation and
curve fitting methods. This subject decreases the
precision of measured data;
� wind speed is not constant and has a direct effect
on the overall heat loss coefficient that can
decrease the precision of calculated overall heat
loss coefficient in the computer simulation;
� the product of effective absorptivity and trans-
mittivity,(at)eff, has been assumed constant while
it is changing during the day with the change of
solar incidence angle on PV/T collector surface.
5.2. Optimization results
The type of PV/T air collector, its selected environmental,
design conditions, and constant parameters during the
optimization procedure are described in Table I. The
typical results of optimization procedure under the
sample conditions of Table I, Tf,in5Tamb5300K,
Figure 7. The simulated and experimental values of exergetic efficiency described by Equations (27) and (28) during the test day.
Exergetic optimization of a solar PV/T air collectorF. Sarhaddi et al.
Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
822
Pf,in5Pamb5101kPa, Vw51ms�1, G5700Wm�2,
Nm51, are been given in Table II.
5.3. Parametric studies
The values of climatic, operating, and design para-
meters in the parametric studies of PV/T air collector
are described in Table I. In order to plot the following
figures, some parameters are assumed that are men-
tioned above each figure. The rest of the parameters
needed to plot the following figures are used from
Table I.
Figure 8 shows the behavior of the exergy efficiency
as a function of inlet air velocity (Vin) and duct length
(L), it is presented to a range of operational and design
conditions where the exergy efficiency takes a global
maximum value.
The incremented quantities are inlet air velocity
from 0.001 to 15m s�1 and duct length from 1.2 to
15.6m. It is observed from this figure that there is a
global maximum point and the coordinate of this point
shows the values of optimized parameters. The calcu-
lated values of global maximum point are
Vin,opt 5 4.83m s�1, Lopt 5 6m, Zex,max 5 11.12%. In
the optimized value of duct length (Lopt 5 6m), the
exergy efficiency increases from �10 to �11.12%
initially and then after attaining the inlet air velocity of
Vin 5 4.83m s�1, it decreases to�8.3%. This indicates
the optimum value of inlet air velocity for given cli-
matic and design parameters (Table I). To illustrate the
behavior of exergy efficiency with respect to duct
length, Figure 9(a) has been plotted.
According to this figure, the exergy efficiency has a
slight variation (�11%) with respect to the changes of
duct length (1.2pLp15.6m) in the optimum value of
inlet air velocity (Vin,opt 5 4.83m s�1). However, there
Figure 8. The exergy efficiency as a function of inlet air velocity and duct length.
Table II. The typical results of optimization procedure under
the sample conditions of Table I, Tf,in 5 Tamb 5 300 K, Pf,in 5
Pamb 5 101 kPa, Vw 5 1 m s�1, G 5 700 W m�2, and Nm 5 1.
Optimization parameters Value
The maximum exergy efficiency, Zex,max 11.12%
The optimum inlet air velocity, Vin,opt 4.83 m s�1
The optimum length of air duct, Lopt 6 m
The thermal efficiency, Zth 28.15%
The electrical efficiency, Zel 10.12%
The overall energy efficiency, Zen,ov 56.7%
The outlet air temperature, Tf,out 315 K
The solar cell temperature, Tcell 323.5 K
The back surface temperature, Tbs 318.72 K
The average air temperature, �Tf 308.11 K
The rate of useful thermal energy, _Qu 532.16 W
The rate of solar energy incident
on the PV/T surface, S
2213.4 W
The open-circuit voltage, Voc 19.06 V
The short-circuit current, Isc 17 A
The maximum power point voltage, Vmp 14.81 V
The maximum power point current, Imp 15.13 A
The light current, IL 16.99 A
The diode reverse saturation current, Io 0.466 A
The series resistance, Rs 0.059OThe shunt resistance, Rsh 116.422OThe ideality factor, a 1.73 eV
The overall heat transfer coefficient, UL 6.86 W m�2 K�1
The heat capacity of flowing air, Cp 1 kJ kg�1 K�1
The number of strings, Ns 5
The product of effective absorptivity
and transmittivity, (at)eff
0.67
The penalty factor due to the presence
of solar cell material, glass, and EVA, hp1
0.79
The penalty factor due to the presence of
interface between tedlar and working fluid, hp2
0.68
Exergetic optimization of a solar PV/T air collector F. Sarhaddi et al.
823Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
Figure 9. (a) The variations of exergy efficiency with respect to duct length and (b) the variations of exergy efficiency with respect
to inlet air temperature.
Figure 10. (a) The effect of solar radiation intensity on the exergy efficiency and (b) the variations of exergy efficiency according
to the changes of wind speed.
Exergetic optimization of a solar PV/T air collectorF. Sarhaddi et al.
Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
824
is a optimized point for duct length that is equal with
Lopt 5 6m.
It is assumed that PV/T air collectors are connected
in series. For a number of PV/T air collectors con-
nected in series, the outlet temperature of the first
collector will be the inlet for second collector, the
outlet temperature of the second will be the inlet for
the third and so on.
The variations of exergy efficiency with respect to
inlet air temperature are plotted in Figure 9(b). The
exergy efficiency has a slight change with respect to
inlet air temperature variations (�11.2%). This sub-
ject allows the designer to optimize PV/T air collector
with respect to other conditions such as design lim-
itations and thermal applications.
Figure 10(a) shows the effect of solar radiation
intensity on the exergy efficiency.
It is observed that the exergy efficiency increases
from�3 to�11.43% initially and then it decreases to
�10.8% after the solar radiation intensity reaches
about 290Wm�2. This indicates the optimum value of
solar radiation intensity for given climatic and design
parameters (Table I).
Figure 10(b) shows the variations of exergy effi-
ciency according to the changes of wind speed. The
exergy efficiency increases from �11.09 to �11.4%
while wind speed is increasing from 0 to 10m s�1.
6. CONCLUSIONS
On the basis of this study, the following conclusions
have been drawn:
� The numerical simulation results of this study are
in good agreement with the experimental mea-
surements noted in the previous literature.
Furthermore, it is observed that the simulation
results obtained in this paper are more precise
than the one given by the previous literature.
� The new exergy efficiency obtained in this paper is
in good agreement with the one given by the
previous literature (for inlet air velocity less than
5m s�1).
� Increasing inlet air velocity or solar radiation
intensity, the exergy efficiency of a PV/T air
collector increases initially and then decreases
after attaining inlet air velocity or solar radiation
intensity of about a maximum point.
� The exergy efficiency of a PV/T air collector has a
slight change with respect to duct length or inlet
air temperature. This subject allows the designer
to optimize PV/T air collector with respect to
other conditions such as design limitations and
thermal applications.
� While increasing wind speed, the exergy efficiency
of a PV/T air collector increases.
NOMENCLATURE
a 5 ideality factor (V)
A 5 area (m2)
Cp 5 specific heat capacity of air
(J kg�1K�1)
Cp;cell 5 specific heat capacity of silicon
solar cell (J g�1K�1)
dx 5 elemental length of flow duct (m)
E 5 power (W)
EVA 5 ethyl vinyl acrelate
Ex 5 exergy (W)
FF 5 fill factor (dimensionlees)
G 5 solar radiation intensity (Wm�2)
h 5heat transfer coefficient (Wm�2K�1)
hp1 5penalty factor due to the presence
of solar cell material, glass, and EVA
hp2 5 penalty factor due to the presence of
interface between tedlar and
working fluid
I 5 circuit current (A)
I–V 5 current–voltage
L 5 dimensions of solar module, duct
length, the length of PV/T air
collector, thickness (m)
mcell 5mass of PV module (g)_m 5mass flow rate of air (kg s�1)
n 5 number of experiments
Nc 5 number of cells in PV module
Nm 5 number of modules in series per
string
Ns 5 number of string
P 5 pressure (Pa)
PV 5 photovoltaic
PV/T 5 photovoltaic/thermal collector_Q 5 heat transfer rate (W)
R 5 gas constant (kJ kg�1K�1),
resistance (O)RMS 5 root mean square percentage
deviation (%)
S 5 the rate of solar energy incident on
the PV surface (W)_Sgen 5 entropy generation (WK�1)
t 5 time interval (s)
T 5 temperature (K)
T0 5 reference environmental
temperature (K)
Ub 5 an overall back loss coefficient from
flowing air to ambient (Wm�2K�1)
UL 5 an overall heat loss coefficient from
the PV/T air collector to the
environment (Wm�2K�1)
Ut 5 an overall heat transfer coefficient
from solar cell to ambient through
glass cover (Wm�2K�1)
UT 5 a conductive heat transfer coefficient
from solar cell to flowing air through
tedlar (Wm�2K�1)
Exergetic optimization of a solar PV/T air collector F. Sarhaddi et al.
825Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
UtT 5 an overall heat transfer coefficient
from glass-to-tedlar through solar
cell (Wm�2K�1)
Utf 5 an overall heat transfer coefficient
from glass-to-air through solar cell
and tedlar (Wm�2K�1)
V 5 circuit voltage (V), wind speed
(m s�1)
W 5 the width of PV/T air collector (m)
X 5 experimental or simulated value of
parameter
Greek symbols
a 5 absorptivity, current temperature
coefficient (mA 1C�1)
(at)eff 5 the product of effective
absorptivity and transmittivity
b 5 packing factor, voltage
temperature coefficient (V 1C�1)
D 5 difference in current, temperature,
time, and voltage
Z 5 efficiency (%)
t 5 transmittivity
Subscripts
1 5 length
2 5width
amb 5 ambient
b 5 back
bs 5 back surface of tedlar
c 5 solar cell
cal 5 calculated
cell 5 cell, module
conv 5 convection
destroyed 5 destroyed
el 5 electrical
electrical 5 electrical
en 5 energy
ex 5 exergy
exp 5 experimental
f 5 fluid flow
g 5 glass
i 5 insulation, ith parameter
in 5 inlet
input 5 input
L 5 light current
max 5maximum
mod 5module
mp 5maximum power point
net 5 net
new 5 new
o 5 reverse saturation
oc 5 open-circuit
opt 5 optimum
out 5 outlet
output 5 output
Q 5 heat transfer
ov 5 overall
PV 5PV
PV/T 5PV/T
rad 5 radiative
ref 5 reference
s 5 series
sc 5 short-circuit
sh 5 shunt
sim 5 simulated
sun 5 sun
t 5 top
T 5 tedlar
th 5 thermal
thermal 5 thermal
u 5 useful
w 5wind
ACKNOWLEDGEMENTS
The authors acknowledge Prof. A. D. Sahin [7] forresponding to our inquiries.
REFERENCES
1. Petela R. An approach to the exergy analysis of
photosynthesis. Solar Energy 2008; 82:311–328.
2. Petela R. Exergy of undiluted thermal radiation.
Solar Energy 2003; 74:469–488.
3. Wolf M. Performance analysis of combined heating
and photovoltaic power systems for residences.
Energy Conversion and Management 1976; 16:79–90.
4. Fujisawa T, Tani T. Annual exergy evaluation on
photovoltaic–thermal hybrid collector. Solar Energy
Materials and Solar Cells 1997; 47:135–148.
5. Dincer I. The role of exergy in energy policy
making. Energy Policy 2002; 30(2):137–149.
6. Saitoh H, Hamada Y, Kubota H, Nakamura M,
Ochifuji K, Yokoyama S, Nagano K. Field experi-
ments and analyses on a hybrid solar collector.
Applied Thermal Engineering 2003; 23:2089–2105.
7. Sahin AD, Dincer I, Rosen MA. Thermodynamic
analysis of solar photovoltaic cell systems. Solar
Energy Materials and Solar Cells 2007; 91:
153–159.
8. Joshi AS, Tiwari A. Energy and exergy efficiencies
of a hybrid photovoltaic–thermal (PV/T) air collec-
tor. Renewable Energy 2007; 32(13):2223–2241.
9. Badescu V. Optimal control of flow in solar
collectors for maximum exergy extraction. Interna-
tional Journal of Heat and Mass Transfer 2007;
50:4311–4322.
Exergetic optimization of a solar PV/T air collectorF. Sarhaddi et al.
Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er
826
10. Aste N, Chiesa G, Verri F. Design, development
and performance monitoring of a photovoltaic-
thermal (PVT) air collector. Renewable Energy
2008; 33:914–927.
11. Nayak S, Tiwari GN. Energy and exergy analysis
of photovoltaic/thermal integrated with a solar
greenhouse. Energy and Buildings 2008; 40 (11):
2015–2021.
12. Raman V, Tiwari GN. A comparison study of
energy and exergy performance of a hybrid photo-
voltaic double-pass and single-pass air collector.
International Journal of Energy Research 2009;
33 (6):605–617.
13. Joshi AS, Tiwari A, Tiwari GN, Dincer I, Reddy
BV. Performance evaluation of a hybrid photovol-
taic thermal (PV/T) (glass-to-glass) system. Interna-
tional Journal of Thermal Sciences 2009; 48:154–164.
14. Joshi AS, Dincer I, Reddy BV. Thermodynamic
assessment of photovoltaic systems. Solar Energy
2009; 83(8):1139–1149.
15. Dubey S, Solanki SC, Tiwari A. Energy and exergy
analysis of PV/T air collectors connected in series.
Energy and Buildings 2009; 41(8):863–870.
16. Tiwari A, Dubey S, Sandhu GS, Sodha MS, Anwar
SI. Exergy analysis of integrated photovoltaic
thermal solar water heater under constant flow rate
and constant collection temperature modes. Applied
Energy 2009; 86 (12):2592–2597.
17. Sarhaddi F, Farahat S, Ajam H, Behzadmehr A.
Exergetic optimization of a solar photovoltaic (PV)
array. Journal of Thermodynamics 2009; DOI:
10.1155/2009/313561.
18. Sarhaddi F, Farahat S, Ajam H, Behzadmehr A,
Mahdavi Adeli M. An improved thermal and
electrical model for a solar photovoltaic thermal
(PV/T) air collector. Applied Energy 2010; 87:
2328–2339.
19. De Soto W. Improvement and validation of a model
for photovoltaic array performance. M.S. Thesis,
Chapter 2–3, 20–74, Solar Energy Laboratory,
University of Wisconsin-Madison, U.S.A., 2004.
20. Siemens Solar Industries. Siemens solar module
SP75, 2009. Available from: www.siemenssolar.com.
21. Kotas TJ. The Exergy Method of Thermal Plant
Analysis. Krieger Publish Company: Malabar, FL,
1995.
22. Wong KFV. Thermodynamics for Engineers.
University of Miami, CRC Press LLC: Boca Raton,
FL, 2000.
23. Osyczka A. Evolutionary Algorithms for Single and
Multicriteria Design Optimization (1st edn). Springer:
Heidelberg, 2001.
Exergetic optimization of a solar PV/T air collector F. Sarhaddi et al.
827Int. J. Energy Res. 2011; 35:813–827 r 2010 John Wiley & Sons, Ltd.
DOI: 10.1002/er