Evaporative Cooling of Data Centers
![Page 2: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/2.jpg)
Evaporative Cooling of Data Centers
Why is this important? What does the industry say? How does the technology work? How does it address the problem? What do we offer? What are the alternatives? If you are not already doing this work where
do you find it?
![Page 3: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/3.jpg)
Evaporative Cooling of Data Centers
![Page 4: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/4.jpg)
Evaporative Cooling of Data Centers
Data Center Knowledge July, 2010 survey of 240 readers
26% operate more than 10 data centers 63% are expanding Top five interest areas
Data Center Design Green IT and Energy Efficiency Power and Cooling Data Center Management and Automation Solutions to Reduce Energy Cost
![Page 5: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/5.jpg)
Evaporative Cooling of Data Centers
Pike Research study Results released in August
$41B market by 2015 28% of all data center projects 46% of investments focused on reducing power
and cooling requirements
![Page 6: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/6.jpg)
Evaporative Cooling of Data Centers
42U rack 84 blades 250w/blade 19.32kw/rack 50 racks 1Mw of server demand Plus…1Mw of heat rejection
= 275 tons of cooling and 100,000 to 150,000 cfm
2Mw total demand
![Page 7: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/7.jpg)
Evaporative Cooling of Data Centers
![Page 8: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/8.jpg)
Evaporative Cooling of Data Centers
Convert expense to revenue
![Page 9: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/9.jpg)
Evaporative Cooling of Data Centers
“PUE” Previous slide PUE approximately 2.77 Target PUE approximately 1.0
![Page 10: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/10.jpg)
Evaporative Cooling of Data Centers
![Page 11: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/11.jpg)
Evaporative Cooling of Data Centers
![Page 12: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/12.jpg)
Evaporative Cooling of Data Centers
Microsoft’s latest promos
![Page 13: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/13.jpg)
Evaporative Cooling of Data Centers
![Page 14: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/14.jpg)
Evaporative Cooling of Data Centers
What is Direct Evaporative Cooling Cooling occurs because water changes
phase from a liquid to a vapor Water vapor is introduced directly into air
stream Constant wet bulb temp Saturation efficiency 80% DB & WB approach
![Page 15: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/15.jpg)
Evaporative Cooling of Data Centers
How much cooling can be achieved? Wet bulb depression
Difference between 100 DB and 70 WB System efficiency (aka “saturation efficiency”) of
80% 100-70 = 30 30 x 0.8 = 24 100-24 = 76
![Page 16: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/16.jpg)
Evaporative Cooling of Data Centers
-30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180
DRY BULB TEMPERATURE - °F
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
EN
TH
AL
PY
- B
TU
PE
R P
OU
ND
OF
DR
Y A
IR
-25 -20 -15 -10 -5 0 510
1520
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
HU
MID
ITY
RA
TIO
- G
RA
INS
OF
MO
IST
UR
E P
ER
PO
UN
D O
F D
RY
AIR
PSYCHROMETRIC CHARTSea LevelBAROMETRIC PRESSURE 29.921 inches of Mercury
Linric Company Psychrometric Chart, www.linric.com
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
VA
PO
R P
RE
SS
UR
E -
IN
CH
ES
OF
ME
RC
UR
Y
-40 0
10
20 25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
DE
W P
OIN
T -
°F
Added grains of moisture
![Page 17: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/17.jpg)
Evaporative Cooling of Data Centers
Cooling Effect Sensible cooling = 1.08 * cfm * delta-t 1.08 * 10,000 * 24 = 259,200 btuh or 21.6 tons
![Page 18: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/18.jpg)
Evaporative Cooling of Data Centers
What is Indirect Evaporative cooling Water never enters the supply air stream Indirect up to 75% system efficiency Straight sensible cooling Reduces wet bulb temperature
![Page 19: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/19.jpg)
Evaporative Cooling of Data Centers
How much cooling can be achieved? Wet bulb depression
Difference between 100 DB and 70 WB System efficiency of 75% 100-70 = 30 30 x 0.75 = 22.5 100-22.5 = 77.5
![Page 20: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/20.jpg)
Evaporative Cooling of Data Centers
Cooling Effect Sensible cooling = 1.08 * cfm * delta-t 1.08 * 10,000 * 22.5 = 243,000 btuh or 20.25
tons
![Page 21: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/21.jpg)
Evaporative Cooling of Data Centers
-30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180
DRY BULB TEMPERATURE - °F
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
EN
TH
AL
PY
- B
TU
PE
R P
OU
ND
OF
DR
Y A
IR
-25 -20 -15 -10 -5 0 510
1520
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
HU
MID
ITY
RA
TIO
- G
RA
INS
OF
MO
IST
UR
E P
ER
PO
UN
D O
F D
RY
AIR
PSYCHROMETRIC CHARTSea LevelBAROMETRIC PRESSURE 29.921 inches of Mercury
Linric Company Psychrometric Chart, www.linric.com
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
VA
PO
R P
RE
SS
UR
E -
IN
CH
ES
OF
ME
RC
UR
Y
-40 0
10
20 25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
DE
W P
OIN
T -
°F
![Page 22: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/22.jpg)
Evaporative Cooling of Data Centers
![Page 23: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/23.jpg)
Evaporative Cooling of Data Centers
What is Indirect/Direct Evaporative cooling Consider it a two-stage hybrid First stage lowers dry bulb and wet bulb Second stage further lowers the dry bulb using
the first stage results as the starting point
![Page 24: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/24.jpg)
Evaporative Cooling of Data Centers
How much cooling can be achieved (Stage One)? Wet bulb depression
Difference between 100 DB and 70 WB System efficiency of 75% 100-70 = 30 30 x 0.75 = 22.5 100-22.5 = 77.5
![Page 25: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/25.jpg)
Evaporative Cooling of Data Centers
How much cooling can be achieved (Stage Two)? Wet bulb depression
Difference between 77.5 DB and 63.5 WB System efficiency of 80% 77.5-63.5 = 14 14 x 0.8 = 11.2 77.5-11.2 = 66.3
Total temperature drop is 22.5 + 11.2 = 33.7 degrees
![Page 26: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/26.jpg)
Evaporative Cooling of Data Centers
Cooling Effect Sensible cooling = 1.08 * cfm * delta-t 1.08 * 10,000 * 33.7 = 363,960 btuh or 30.33
tons
![Page 27: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/27.jpg)
Evaporative Cooling of Data Centers
-30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180
DRY BULB TEMPERATURE - °F
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
EN
TH
AL
PY
- B
TU
PE
R P
OU
ND
OF
DR
Y A
IR
-25 -20 -15 -10 -5 0 510
1520
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
HU
MID
ITY
RA
TIO
- G
RA
INS
OF
MO
IST
UR
E P
ER
PO
UN
D O
F D
RY
AIR
PSYCHROMETRIC CHARTSea LevelBAROMETRIC PRESSURE 29.921 inches of Mercury
Linric Company Psychrometric Chart, www.linric.com
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
VA
PO
R P
RE
SS
UR
E -
IN
CH
ES
OF
ME
RC
UR
Y
-40 0
10
20 25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
DE
W P
OIN
T -
°F
Added grains of moisture
![Page 28: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/28.jpg)
Evaporative Cooling of Data Centers
Cooling Effect Summary Direct evap
Supply temp = 76 degrees Tonnage = 21.6
Indirect evap Supply temp = 77.5 degrees Tonnage = 20.25
Indirect/Direct evap Supply temp = 66.3 Tonnage = 30.33
![Page 29: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/29.jpg)
Evaporative Cooling of Data Centers
DALLAS
WICHITA
SACRAMENTO
![Page 30: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/30.jpg)
Evaporative Cooling of Data Centers
How does this address the problem? Remember the goal…shifting the kw required
for cooling over to the kw available for servers Evaporative cooling vs. chilled water vs. DX
![Page 31: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/31.jpg)
Evaporative Cooling of Data Centers
How does this address the problem? Aztec ASC ~ .25 kw/ton Air cooled rooftop ~ 1.15 kw/ton (10.5 EER)
Evaporative cooled chiller ~ .88 kw/ton
![Page 32: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/32.jpg)
Evaporative Cooling of Data Centers
How does this address the problem? For our 30 ton example unit:
Aztec ASC ~ 7.5 kw Air cooled rooftop ~ 34.5 kw Evaporative cooled chiller ~ 26.4 kw
![Page 33: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/33.jpg)
Evaporative Cooling of Data Centers
Potential applications Enterprise data centers Colocation data centers R&D labs Telecommunication equipment centers Server closets Container-based server centers Abandoned “big box” conversions
![Page 34: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/34.jpg)
Evaporative Cooling of Data Centers
Applications that probably will not work Tropical environments Marine environments
Potential corrosion due to salt air Heavily polluted environments
Potential corrosion due to VOCs and ozone “Traditional” design criteria is specified
![Page 35: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/35.jpg)
Evaporative Cooling of Data Centers
Issues to consider Hot aisle/Cold aisle separation Using the “worst case” scenario for design Be aware of the resulting dew point Remember the vapor barrier
![Page 36: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/36.jpg)
Evaporative Cooling of Data Centers
Equipment characteristics to consider Control the water
All welded floor of stainless steel or aluminum All welded drain pans at least 4” high Internal velocities Mist eliminators Conduit for electrical and control wiring
![Page 37: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/37.jpg)
Evaporative Cooling of Data Centers
Equipment characteristics to consider Know the water
Consider water quality Evaluate the use of automatic systems
Remember the end user
![Page 38: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/38.jpg)
Evaporative Cooling of Data Centers
Aztec ASC line Indirect or indirect/direct evap Cooling-only or Cooling-
Heating systems DDC controls with Internet
access available Stainless steel evap sections Fully welded floor pans Fiberdek UL900cl2 media Duradek edge coating Cleanable media pre-filters Internal seismic rated
fan/motor isolation VFD capable Automatic fill and drain system DHTD “digital high turndown”
burner heating technology 1,500 – 37,500 cfm range
![Page 39: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/39.jpg)
Evaporative Cooling of Data Centers
Alton HECD line Stainless steel evap sections Fully welded floor Fiberdek UL900cl2 media
optional Duradek edge coating optional Cleanable media pre-filters Automatic fill and drain system 5,000 – 64,000 cfm range
![Page 40: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/40.jpg)
Evaporative Cooling of Data Centers
What are the alternatives? In-rack In-room Conventional HVAC Hybrid DX or Chilled
Water/Evaporative HVAC
![Page 41: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/41.jpg)
Evaporative Cooling of Data Centers
What are the alternatives? In-rack
![Page 42: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/42.jpg)
Evaporative Cooling of Data Centers
What are the alternatives? In-room
![Page 43: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/43.jpg)
Evaporative Cooling of Data Centers
What are the alternatives? Conventional HVAC
![Page 44: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/44.jpg)
Evaporative Cooling of Data Centers
What are the alternatives? Hybrid Dx or chilled
water/Evaporative Cooling
![Page 45: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/45.jpg)
Evaporative Cooling of Data Centers
How to find the work Talk to electric utility folks Talk to local economic development folks Emphasize revenue vs. expense Emphasize easier repurposing of
abandoned retail space
![Page 46: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/46.jpg)
Evaporative Cooling of Data Centers
Summary Direct evaporative cooling is the least
expensive Indirect/direct evaporative cooling is the most
effective The goal is to convert expense to revenue for
the client And remember….computers don’t sweat…so
go as warm as you can
![Page 47: Evaporative Cooling of Data Centers. Why is this important? What does the industry say? How does the technology work? How does it address the problem?](https://reader036.vdocuments.mx/reader036/viewer/2022070305/5514428c550346414e8b4a20/html5/thumbnails/47.jpg)
Q & A
Evaporative Cooling of Data Centers