euwa40_200mz
TRANSCRIPT
![Page 1: EUWA40_200MZ](https://reader038.vdocuments.mx/reader038/viewer/2022100506/55251e644a7959c2488b4ab0/html5/thumbnails/1.jpg)
EPLE03-26A
Air cooled chillers
EUWA*40-200MZHydronic systems
MOV81597_EPLE03-26A
Cyan Magenta Yellow Black
![Page 2: EUWA40_200MZ](https://reader038.vdocuments.mx/reader038/viewer/2022100506/55251e644a7959c2488b4ab0/html5/thumbnails/2.jpg)
• standard fitted with victaulic joints on evaporator and condenser pipes• victaulic joints absorb vibrations, reduce operating sound and thermal
deflection and simplify chiller piping and installation.• They can accommodate 8° angles and guarantee stress free, leak tight
water piping connection.
9 models are available with cooling capacities rangingfrom 111kW to 541kW. The units are ideal for use insevere weather conditions and over a wide operationrange. This major benefit results from the incorporationof an auto adaptive control system with built-infunctions that include:• head pressure control: fan control for low ambient
down to -15°C• head pressure setback for high ambient operation: on
hot days, when cooling is most needed, some chillerstend to trip out on high pressure protection. Daikinchillers will stay on line and prevent this situation byadjusting the capacity control.
FLEXIBLEAPPLICATION
EASY INSTALLATION
50
433940
30
20
10
0
-10
-20-15
-30-20 -10 0 10 20 30
-5 4 16 26
33
ambient temperature°C
***
leaving evaporator water temperature (°C)
Protect the water circuit against freezing by:• or heater tape (standard)• or filling up the system with a glycol solution
Pull-downarea
Continuousoperation
area
* Glycol (optional)** Water (standard)
Daikin’s unique position as a manufacturer ofair conditioning equipment, compressors andozone-friendly refrigerants has led to its close
involvement in environmental issues.For several years Daikin has had the intention to become aleader in the provision of environmental friendly products.This challenge demands the eco design and development ofa wide range of products and an energy management system;which involves energy conservation and reduction of waste.
MOV81597_EPLE03-26A
Cyan Magenta Yellow Black
![Page 3: EUWA40_200MZ](https://reader038.vdocuments.mx/reader038/viewer/2022100506/55251e644a7959c2488b4ab0/html5/thumbnails/3.jpg)
• condenser coils are constructed from specially designed header distribution pipes,combined with internally grooved Hi-X tubing and chromate coated waffle louvrepressed fins
• all condenser coils are standard anti-corrosion treated to withstand the effects fromsevere weather conditions
• condenser protection grilles are available throughout the whole range
SINGLE SCREWCOMPRESSOR
HEAT EXCHANGER
ELECTRONIC CONTROL
All chillers in this range arsemi hermetic single screw comprNEW: high efficiency motor, scrdesign of slide valves, gate r
BENEFIT:• overall COP increase of 5 to 10%
compared to the previous series• unequalled reliability for
increased long life operation• overhaul only necessary after
4.5 years of continuous operation
• advanced pco2 control• detailed information on and accurate control of all functional
parameters by easy menu scrolling: schedule timer, floating set point,free cooling, double evaporator pump, manual pump on, date andtime information, daily pump on
• chilled water temperatures down to -10°C on standard unit.(Parameter in the service menu of the DDC controller must be set by the installer)
• changeable digital input/output such as remote on/off, remote cooling/heating, dual setpoint andlimit capacity.
• self diagnostic and can be set up in several languages.• Lead lag function is standard• standard equipped with night setback and peak load limitation• DDC is removable and can be installed up to 1,000 m from the unit• thanks to the standard DICN, simultaneous operation of up to 4 chillers is allowed. This function
enables a Daikin 2MW chiller plant to be operated via a single controller.
MOV81597_EPLE03-26A
Cyan Magenta Yellow Black
![Page 4: EUWA40_200MZ](https://reader038.vdocuments.mx/reader038/viewer/2022100506/55251e644a7959c2488b4ab0/html5/thumbnails/4.jpg)
EUWA-MZEUWA*40MZ EUWA*50MZ EUWA*60MZ EUWA*80MZ EUWA*100MZ EUWA*120MZ EUWA*160MZ EUWA*180MZ EUWA*200MZ
111 144 164 199 285 349 395 468 541
42.8 52.8 65.2 78.9 109 142 158 192 226
2.59 2.73 2.52 2.52 2.61 2.46 2.5 2.44 2.39
100-74-48-0 100-87-74-61-48-24-0 100-89-74-63-48-27-0 100-87-74-61-48-24-0
brased plate heat exchanger, one per circuit
R-407C
27 39 42 58 84 84 128 129 130
thermostatic expansion valve
FVC68D
5.5 5.5 7.5 7.5 10 10 2x7.5 7.5+10 2x10
semi-hermetic single screw
1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2
cross fin coil / hi-X tubes and chromate coated waffle louvre fins
960 960 960 1,920 1,920 1,920 2,880 2,880 2,880
2,250x2,346x2,238 2,250 x 4,280 x 2,238 2,250 x 5,901 x 2,238
1,411 1,565 1,654 2,193 2,573 2,623 4,842 4,965 5,088
1,419 1,578 1,670 2,213 2,600 2,657 4,916 5,046 5,176
91 96 96 97 99 100 101 101 101
polyester painted galvanised steel plate
ivory white / Munsell code 5Y7.5/1
flexible coupling 3" flexible coupling 5"
field installation 1/4"G
compressor: 1"NPT compressor: 2x1"NPTcompressor: 1x(1"NPT) compressor:
+ 1x(2x1"NPT) 2x(2x1"NPT)
Double PED approved high pressure switches / Low pressure protection / Pressure relief valve on compressor / Compressor motor thermal protector / Compressor motor overcurrent relay /
Discharge temperature controller / Freeze-up protection / Recycling and guard timer / Reverse phase protector
-15°C ~ 43°C
-10°C ~ 26°C
3~/400V/50Hz
ISO14001 assures an effective environmentalmanagement system in order to help protect humanhealth and the environment from the potentialimpact of our activities, products and services and toassist in maintaining and improving the quality ofthe environment.
Daikin Europe N.V. is approved by LRQA for itsQuality Management System in accordance withthe ISO9001 standard. ISO9001 pertains to qualityassurance regarding design, development,manufacturing as well as to services related tothe product.
EPLE
03-2
6A /
800
/ 09/
03 /
La M
ovi
da
Prin
ted
on
no
n-c
hlo
rin
ated
pap
er /
Prin
ted
inB
elg
ium
Daikin units comply with the European regulationsthat guarantee the safety of the product.Specifications are subject to change without prior notice.
Daikin Europe N.V. is participating in the EUROVENTCertification Programme. Products are as listed inthe EUROVENT Directory of Certified Products.
Zandvoordestraat 300B-8400 Oostende, BelgiumInternet: http://www.daikineurope.com
Daikin products are distributed by:
Notes:Model type for PED approval (-)Model type for RLK approval (D)Model type for UDT approval (Q)Model type for SA approval (S)
To install EKBMSMBA, EKBMSBNA --> EKAC200A needs to be installed on the unito availablestd standard
Option Number Option description
Completely combinable optionsop03 dual pressure relief valve on condenser
op12 suction stop valve
op52 main isolator switch
op57 a-meter / V-meter
opln low noise operation
opcg condenser protection grilles
Available kitsEKCLWS leaving water control sensor for DICN
EKAC200A BMS card
EKBMSMBA BMS gateway modbus / j-bus protocol
EKBMSBNA BMS gateway bacnet protocol
Notes:1. Nominal cooling capacities are based on: evaporator 12°C/7°C • ambient 35°C2. Nominal cooling power input includes beside the power to the unit also an addition for the required pump power input
model-type unit sizeAvailability
- D Q S 40 50 60 80 100 120 160 180 200
o std o std o o o o o o o o o Factory mounted
o std o std o o o o o o o o o Factory mounted
o o o o o o o o o o o o o Factory mounted
o o o o o o o o o o o o o Factory mounted
o o o o o o o o o o o o o Factory mounted
o o o o o o o o o o o o o Factory mounted
o o o o o o o o o o o o o Kit
o o o o o o o o o o o o o Kit
o o o o o o o o o o o o o Kit
o o o o o o o o o o o o o Kit
Nominal capacity cooling kW
Nominal input cooling kW
EER
Capacity steps %
Water heat exchanger type
Refrigerant circuit type
charge kg
control
oil type
oil charge l
Compressor type
No. of circuits/compressors
Air heat exchanger type
air flow rate m3/min
Dimensions H x W x D mm
Machine weight kg
Operation weight kg
Sound power level dB(A)
Casing material
colour
Piping connections evaporator water in/outlet
evaporator water drain
relief device outlet
Safety and functional devices
Operation range air side °C
water side °C
Power supply Y1